LV Bushing Oil to Air Dry Insulation PTAB-SLV832

Similar documents
Low voltage bushings for pad-mounted distribution transformers Technical information guide

High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide

Dry Well Cannister Type CLT, OIL Immersed PTAP-AFH926. Technical Guide Load-break, Dead-break

Load Break Switch Type LBOR-II, Oil Immersed PTAT-LIR975 IZUA Technical Guide Nut Mount Weld Mount

Eaton s Cooper Power Systems

ABB Power T&D Company Inc. General Information: DT-100 DT-150 DV-100 DV-150. De-energized Switches TPL , July 1999, Page 1 of 4

DO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc.

Product Description: Objective and Certification: Test Samples and Test Cable:

Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:

A 1.2 kv class externally removable secondary bushing

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

CERTIFIED TEST REPORT. Cooper Power Systems. 25 kv Class 200 Amp 15.2/26.3 kv SEPARABLE CONNECTOR SYSTEM

INSTALLATION PRODUCTION TESTS

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

Transformer bushings, type GOH. Technical guide

25 kv Apparatus Bushings

GROUP C. Apparatus Bushing.

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Surge Arresters. UltraSIL Polymer-Housed Evolution (10 ka) Surge Arresters. General. Construction. features

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

Test report. Type VRLTC load tap changer VRLTC 1500A Type test summary report

TABLE OF CONTENTS Page

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

SERIES TAP-CHANGER

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

IEC Separable Connectors 17.5 kv/24 kv, 630A

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION

IEC Separable Connectors 36 kv and 42 kv, 630A and 1250A Front T-Body / Coupling (Rear) T-Body Connector

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

200 A and 600 A, 15, 25, and 35 kv junction bars for separable connectors

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

15 kv and 25 kv Thru-Bushings

Surge Arresters. UltraSIL Polymer-Housed VariSTAR Surge Arresters: Normal-Duty (5 ka), Heavy-Duty (10 ka), and Heavy-Duty Riser Pole (10 ka)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

Bushings for High Voltage AC Applications

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number:

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

CERTIFIED TEST REPORT

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

Transformer Components & Accessories

CAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION

Substation Equipment (Bushings)

Loadbreak Apparatus Connectors

Molded Current-Limiting Fuse

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

600 A 15 kv class T-OP II deadbreak connector

600 A 35 kv class BT-TAP deadbreak connector

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Kuhlman Electric Corporation Volt Instrument Transformers

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

Surge arresters. UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters. General. COnSTrUCTIOn

tests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.

FEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation

600 A 25 kv class BT-TAP deadbreak connector

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology

SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

I Surge Arresters. UltraSIL Polymer-Housed VariSTAR Type U3 Surge Arrester for Systems through 275 kv IEC 10 ka; Line Discharge Class 3 GENERAL

Power/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers

Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer

PSC Terminations. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables.

Review Section: 3. Definitions..the surrounding air in contact with the apparatus onto which the bushing is mounted, not inside bus duct or enclosure.

Distribution transformers Efficiency over life-cycle

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

Micafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB

PABS. AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS ANSI STANDARDS AN ALSTOM COMPANY

B kv T&D GAS INSULATED SWITCHGEAR

www. ElectricalPartManuals. com Substation Transformers Primary or Secondary Unit

ABB PTTR SPAIN. Zaragoza. The product: Cast coil transformers

ELASTIMOLD UNDERGROUND CABLE ACCESSORIES

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

CSP Circuit Breaker Three Phase

Transcription:

LV Bushing Oil to Air Dry Insulation PTAB-SLV832 Technical Guide 600 V, 30 kv BIL, 600-2500 A 5/8" Integral Flange Bushing 1.0" Integral Flange Bushing 1.25" Bushing

General Description The ABB low voltage bushings are designed for use on pad or surface mounted distribution transformers. They serve to terminate the transformer s internal low voltage leads at the tank wall and to provide a standard threaded connection for the external low voltage circuit. The bushings consist of a thermoset body which is molded around a copper conductor stud. The conductor stud is terminated with an internal connection spade and an external mounting thread. 600 A 1200 A Features and Advantages Test Proven Quality and Reliability The ABB low voltage bushings have passed a series of design tests which were designed to verify ratings, suitability for use on pad mounted distribution transformers, and long term reliability. 1. Seal Integrity Test 2. Full Wave Impulse Test 3. Low Frequency Voltage Withstand Test 4. Conductor Stud Torque Test 5. Flange compression Strength Test 6. Cantilever Load Test 7. Flange Torque Test 8. Thermal Cycle Test 9. Temperature Rise Test In addition to the design testing, the following routine production tests are done on an audit basis: 1. Dimension Check 2. Visual Inspection 3. Leak test Interchangeable The ABB low voltage bushings have been designed to be dimensionally interchangeable with the majority of low voltage bushings presently on the market. Included in these interchangeable dimensions are: the bolt circle for the integral mounting flange; the tank wall hole size; the conductor stud diameter; and the external thread size. Integral Flange on 5/8" & 1.0" Conductors The mounting flange on the 5/8" and 1.0" conductor bushings is molded as an integral part of the bushing. This eliminates the need for a separate mounting flange, and in the case of a metal mounting flange, the associated electrical losses through induced current in the flange. Compression Limited Gasket Designs The integral flange assembly of the 5/8" and 1.0" conductor bushing has a molded-in gasket seat to ensure proper gasket location and compression during mounting. The 1.25" conductor bushing uses a compression ring to properly locate the gasket and limit gasket compression. Conductor Variety Most ABB low voltage bushings are available in a standard or extended length thread design. Proven Thermoset Material Because of the critical nature of the low voltage bushing application, high strength, molded, thermoset materials are used. These materials have proven their ability to withstand the stresses of the transformer environment through their many years of field service and rigorous aging tests. Certification of 5/8" and 1.0" Bushings To Certify the product ratings, production samples of the 5/8" and 1.0" diameter low voltage bushing rated through 600 volt were tested. The tests were conducted at the ABB Engineering Laboratories in Alamo, TN and Raleigh, NC. The tests were conducted in accordance with ANSI/ IEEE. Design Tests The design tests were divided into (3) three parts: 1. Dielectric Tests Impulse test Low Frequency 60 Hz Withstand test 2. Mechanical Strength Tests Leak test Stud Interface Strength test Stud Torque Strength test Cantilever test Flange Torque test 2 ABB

3. Environmental Tests Thermal Cycle test Oil Compatibility test 1. Dielectric Tests Impulse Test The purpose of this test is to verify the impulse withstand of the bushing. Sample bushings were subjected to two positive and two negative full wave impulses. The voltage impulse used was a standard 1.2 x 50 µs wave having the crest value of the specified voltage. The voltage level attained was well above the BIL rating of 30 kv. Samples successfully passed 36 kv impulse test levels. Samples successfully passed chopped wave tests well above the rating of 36 kv. Low Frequency 60 Hz Withstand Test The purpose of the low frequency withstand test is to verify the integrity of the insulation structure of the bushing at operating frequency. The samples were tested at 12 kv for one minute and then allowed to rest for one minute. They were then retested for another minute. All samples passed this test. 2. Mechanical Strength Tests Leak Test The purpose of the leak test is to ensure that, over the life of the bushing, no leak will occur between the copper stud and the polyester resin. The bushings were tested using two methods. For the first method, sample bushings were tested by mounting them in a tank pressurized to 30 psi and submerging the tank in water for 1 minute. For the second method, the bushings were attached to a leak test fixture which mates the bushing to a Helium detector (Veeco Instruments). A vacuum is created around the internal surfaces of the bushing. Any leak will be detected if Helium passes into the detector through the bushing. All bushings passed with no indication of leaking air when submerged in water or leaks faster than 1 x 10-9 atm cc/sec using the Helium detector. Stud Interface Strength Test The purpose of this test is to verify that no damage will result when bushing terminals are connected or removed. With the bushings attached to simulate transformer mounting, a nut is threaded onto the threaded copper stud and torqued to 50 ft-lb twenty times. The bushings are then leak tested to verify that the seal between the copper stud and the polyester resin remained intact. are screwed onto the threaded portion of the bushing simulating the attachment of a standard H-spade. The nut is tightened until failure. The average torque value was 92 ft-lb for the 5/8" stud and 199 ft-lb for the 1" stud. In all cases either the threads stripped or the stud broke. Cantilever Test This test demonstrates the ability of the bushing to withstand the stresses generated when attaching line leads to the conductor. With the bushings attached to simulate transformer mounting, an extension is threaded onto the bushing stud and a load applied until failure. With a configuration of one hole down on the integral flange, the average failure occurred at 172 ft-lb for the 5/8" stud, and 421 ft-lb for the 1" stud bushing. Flange Torque Test The purpose of the flange torque test is to demonstrate the ability of the integral flange to withstand the stresses generated while being mounted to a transformer tank. The bushing is mounted to the test fixture with the mounting bolts tightened to the standard 90 in-lb. The bolts are sequentially tightened in increments of 25 in-lb until failure. The pads crushed at an average torque of 516 in-lb. 3. Environmental Test Thermal Cycle Test The purpose of the thermal cycle test is to verify the integrity of materials used in the bushing over the expected service life of the bushing. The sample bushings previously leak tested were subjected to 20 thermal cycles in air. One cycle consists of: a 2 hour transition to 135 C, 2 hours at 135 C, a 4 hour transition from 135 C to -40 C, then 2 hours at -40 C. After the thermal cycle test, the bushings were tested again with no bushing showing any indication of leaking. Oil Compatibility Test The purpose of this test is to verify that the bushing will not degrade the transformer's oil as it ages. Samples of bushings are aged under controlled conditions in a test vessel containing tansformer oil. At the conclusion of the test, the molding material is tested for degradation. The material passed the standard oil compatibility test. In addition, this bushing is molded from a thermoset polyester resin system which has essentially the same chemistry as that which has been used for insulators in other oil filled apparatus for over 30 years. Stud Torque Strength Test The purpose of this test is to verify the strength of the copper stud. Two brass nuts separated by a steel washer ABB 3

ABB Inc. 1128 S. Cavalier Drive Alamo, TN 38001, USA Telephone: 731-696-5561 Fax: 731-696-5362 www.abb.com IZUA 2761-600en Replaces TPL 44-841 February 98. Printed in USA by Tennessee Industrial Printing Services, Inc.