Valtek Position Pac GENERAL INFORMATION INSTALLATION INSTRUCTIONS OPERATION. Valtek Linear Actuators

Similar documents
Valtek Spring Cylinder Linear Actuators

Flowserve Spring Diaphragm Rotary Actuators

Valtek VL-HC Spring Cylinder Linear Actuators

USER INSTRUCTIONS. Spring Diaphragm Rotary Actuators. Installation Operation Maintenance. Experience In Motion FCD VLAIM /12

Valtek Flow Boosters

Valtek MaxFlo 3 Control Valves

USER INSTRUCTIONS. Valtek Control Products Spring Cylinder Linear Actuators. Installation Operation Maintenance. Experience In Motion

Valtek Valdisk 150. Valtek Valdisk 150. Control Valves. Flowserve Corporation, Valtek Control Products, Tel. USA

Valtek MaxFlo Control Valves

Valtek XL Series High Performance Positioner. for Control Valves

Valtek Survivor Control Valves

Valtek Tek-Check. Check Valves

Valtek Beta Positioner. Valtek Beta Positioners. for Control Valves

OpTK. Product Instruction Manual. Spring Cylinder Rotary Actuators INTRODUCTION SAFETY INFORMATION INSTALLATION. Leading Technologies For Control

Kämmer Series Low Flow Valve

Vogt Valves The Connection Bulletin for Forged Steel Globe Valves for Water-Free Chlorine Service Class 300, 600 & 800 CB 07

Series 72 Electri-SAFE On/Off Operation Including CLC Option Installation, Operation and Maintenance Instructions

Valtek Auxiliary Handwheels and Limit Stops

Kämmer Series Split Body Valves

Vogt Valves The Connection Bulletin for Y Pattern Globe & Check Valves Class 1690 & Class 2680 CB 18

Kämmer Series Low Flow Valves

Experience In Motion. Flowserve Control Valve Products North American Quick Response Centers

Valtek Beta Positioners for Control Valves

Rotary Valve Maxflo + 60 and 80 Opening type NT

Figure 1 Figure 2 Double Acting Actuator Spring Return Actuator

McCANNA Actuation Systems B

Desuperheater FCD VLENTB /11. Experience In Motion

USER INSTRUCTIONS. Installation Operation Maintenance. NAF Setball SF Ball Sector Valves. Experience In Motion FCD NFENIM A4 09/16

Installation and Operating Manual

Valtek Tek-Check Control Valves Valtek Tek-Check

Solenoid Block Kit for Series 90 Modular Accessory System Installation, Operation and Maintenance Instructions

XL90 Series High-Performance Positioner

USER INSTRUCTIONS. Valtek Valdisk TX3 Triple Offset Butterfly Control Valve. Installation Operation Maintenance. Experience In Motion

Kämmer Multi-Z Severe Service Valves

Installation Operation Maintenance

USER INSTRUCTIONS. Limitorque TM V Series. Installation Operation Maintenance. Experience In Motion FCD LMENIM AQ 02/15

SUREPOWR TM SERIES -SURE 49 FIELD INSTALLATION INSTRUCTIONS

Installation Instructions

Valtek Valdisk 150. Valtek Valdisk 150. Control Valves

Mark 100. Technical Bulletin F C D F C A T B

USER INSTRUCTIONS. Installation Operation Maintenance. Valtek ShearStream HP Control Valves Segmented V-Port Ball Valves. Experience In Motion

Valtek ShearStream Control Valves

flowserve.com Kämmer Multi-Z Kämmer Multi-Z Severe Service Valves

INSTRUCTION MANUAL. Anchor Darling 1878 Swing Check Valves. Installation Operation Maintenance. Sizes 1/2 through 2 FCD ADENIM

Mounting: The following instructions apply to rotary actuators only. Linear applications require special mounting and coupling (consult factory).

USER INSTRUCTIONS. Limitorque HBC Series. Installation Operation Maintenance. Experience In Motion FCD LMENIM A4 (10/14)

Accord DS/DM Series UltraSwitch Switch box

Installation Instructions

Limitorque Actuation Systems PT Series Worm Gear Operator

Surepowr Series 100 Installation Manual

Product Specification

Limitorque Actuation Systems B320 Series. Rugged and dependable bevel gear operators for manual or motorized valve control applications

Installation Instructions

flowserve.com Flowserve Solenoid Valves Namur, Remote and Banjo Mounted Designs for Precision Control

USER INSTRUCTIONS. NAF Trunnball DL Ball Valves. Installation Operation Maintenance. Experience In Motion FCD NFENIM A4 01/15

SUREPOWR TM SERIES -SURE 24/25 FIELD INSTALLATION INSTRUCTIONS

XL90 Series High-Performance Positioner

Limitorque Accutronic MX/WTR Performance and Dimensions. Limitorque Actuation Systems

THD-SERIES S11DA280 THRU S27DA1020 & S11SR280 THRU S27SR1020 DOUBLE ACTING & SPRING RETURN SCOTCH YOKE ACTUATORS

Moniteur INSTALLATION & OPERATING INSTRUCTIONS. SERIES 40 Positioners. Installation and Operating Instructions Series 40 Positioners.

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

Limitorque HBC Series Worm Gear Operators

Installation, Operation and Maintenance Instructions Series 608 Ball Valve

CENTAC Inlet and Bypass Valve Positioners

Instruction Manual for Barber-Colman Series EA Electric High Torque Actuators

SY-SERIES S04DA75 THRU S06DA180 & S04SR75 THRU S06SR180 DOUBLE ACTING & SPRING RETURN SCOTCH YOKE ACTUATORS

Quarter Master Series 94 Actuator

Surepowr Series Sure 150

Spring Cylinder Rotary Actuators

Installation Instructions

K10 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual

Flowserve Anchor Darling Isolation Valve Application

TECHNICAL BULLETIN. Audco Ball Valve. Reduced Bore Fire safe Flanged Ball Valves 51/52 Series. Experience In Motion

Installation Instructions

OIL FIELD ELECTRIC ACTUATOR INSTRUCTION MANUAL SPECIAL APPLICATIONS ACTUATORS Q 6.0.1

Edward. Equiwedge Forged Gate Valvee. Experience In Motion

Installation Instructions

Product Description. Product Numbers. Warning/Caution Notations. Required Tools. Wiring. Prerequisites

Quarter Master Chief Series 92 Actuator

flowserve.com Limitorque LRP Limitorque Rack & Pinion Pneumatic Actuator

MERIDIAN, 2 or 3 PIECE, TRUNNION MOUNTED BALL VALVES

MARPAC K SERIES. Full Bore Fire Safe Flanged Ball Valves

Installation Instructions

Worcester Controls Directional Ball Valves

Installation and Operating Instructions Electro-Pneumatic Rotary Positioner SP-21. Description of Device. Part Number System

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

Series 10 Actuator. Installation, Operation and Maintenance Manual

VG7000 Valve Linkage for M100 Series Motor Actuators

Powers TM Controls EA 338 Electronic Actuator

Heavy Duty Miniature Quick-Change Applicator (Side-Feed Type) with Mechanical or Air Feed Systems

M9216 Series Electric Spring Return Actuators

ANDCO Eagle Actuator Instruction Manual

USER INSTRUCTIONs. Installation Operation Maintenance. Valtek MaxFlo 3 Control Valves. User instructions - MaxFlo 3 - VLENIM

NAF Duball DL Pocket Ball Valves TECHNICAL BULLETIN FCD NFENTB A4 11/17

Limitorque. HBC Series Worm gear operators proven in the most demanding situations

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

MC-351, 421, 431, MC-4311

Mark 100. Installation, Operation and Maintenance Instructions F C D F C A I M

Damper Actuator Installation

TECHNICAL BULLETIN. NAF Setball SF Ball Sector Valves. Experience In Motion. flowserve.com. NAF Setball FCD NFENTB A4 02/16

Transcription:

Valtek Position Pac GENERAL INFORMATION The following instructions are designed to assist with installing, calibrating and troubleshooting the Valtek Position Pac valve position indicator. Product users and maintenance personnel should thoroughly review this bulletin in conjunction with the maintenance bulletin for the appropriate valve body and actuator being used. To avoid possible injury to personnel or damage to valve parts, WARNING and CAUTION notes must be strictly adhered to. Modifying this product, substituting non-factory or inferior parts, or using maintenance procedures other than outlined could drastically affect performance, be hazardous to personnel and equipment, and may void existing warranties. OPERATION Position Pac is a package unit containing a potentiometer and transmitter, two or four limit switches, or a combination of a transmitter and two limit switches. The position transmitter utilizes a potentiometer to measure the valve s position and a transmitter circuit that sends a 4 to 20 ma electrical signal to a remote monitoring device. Position Pac will continuously transmit the position of a control valve as it modulates between the open and closed positions. The limit switches in Position Pac can be independently set to indicate open, closed or any intermediate valve position. Position Pac s sealed construction provides protection from the entry of water, dust and oil as defined by the National Electrical Manufacturers Association (NEMA) 1, 3, 3R, 4, 12 and 13. Position Pac is also explosionproof, providing protection from flammable hydrocarbon atmospheres, metal dust, coal dust, and grain dust. It is and CSA listed for Class I, Division 1, Groups B, C, D; Class II, Division 1, Groups E, F, G (See Table I). All electrical wiring should be installed per NEC articles 501-4 and 501-5. WARNING: Keep hands, hair, clothing, etc. away from moving parts when operating the valve. Failure to do so can cause serious injury. INSTALLATION INSTRUCTIONS The following instructions are designed to assist in the field installation of Position Pac units. Valtek Linear Actuators To install Position Pac on Valtek linear actuators, refer to Figures 1 and 2, and proceed as follows: 1. Remove the name plate from the yoke leg opposite from the stroke indicator plate. 2. Using the two tapped holes, attach the Position Pac mounting bracket to the yoke leg using two mounting bolts. When facing this yoke leg, the bracket will jog in towards the valve center and protrude to the left. 3. Remove the nut from the stem clamp bolting. Place the tripper bracket on the bolt so the S shape extends down. Replace the nut and tighten it firmly. Valtek Flowserve. Corporation, 62152 Valtek Control Products, Flowserve Tel. Corporation, USA 801 489 Valtek 8611Control Products, Tel. USA 801 489 8611 29-1

Figure 1: Linear Application Front View (cover removed) Figure 2: Linear Application Rear View (cover removed) Table I: Model Configuration Model TH2 H2TS Description Analog Transmitter with two her- metically sealed SPDT switches Two hermetically sealed SPDT switches with terminal switch NEMA 4 Electrical Area Explosion Proof Class I Division Class II Division 1 & 2 (Group) 1 & 2 (Group) A B C D E F G CENELEC Approval Rating Sealed Switches Yes Yes Housing Size TX TA2 A2 A4 A2TS Analog transmitter Analog transmitter SPDT switches with two Two SPDT switches Four SPDT switches Two SPDT switches with terminal strip Pending /CSA Short Short Table II: Linear Mounting Information Actuator Valve Spud Kit Hole Size Stroke Size.* Set (sq. in.) (inch) (inch) (Mounting) 25 0.5-1.0 2.00 37434 bottom of slot 1.5 2.00 37434 top of slot 50 0.5-2.5 2.62 37345 bottom holes 3.0 2.62 37345 top holes 100 1.0-3.5 2.62/2.88 37436 bottom holes & larger 4.0 3.38 37630 top holes 4.0 4.75 71636 top holes *Kit includes: bracket, arm, trip lever or stem clamp with trip lever nuts and bolts. 4. Mount Position Pac to the bracket using the mounting holes as specified in Table II: Insert the lever onto the switch shaft. On larger actuators (size 50 and larger) that use the adjustable lever arm, adjust the length so that the center of the roller rests on the center of the tripper bracket. To preload the Position Pac s restoring spring, be certain the control valve is in its minimum signal position. Loosen the lever arm clamp screw with a 0.14-inch ( 9 /64) hex wrench, allowing the arm to turn on the shaft. While holding the arm in contact with the bottom of the tripper bracket and using a slotted screwdriver to rotate the switch shaft perform the following (all rotation direction instructions are as viewed from the lever arm side of the Position Pac): 29-2 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611

Figure 3: Rotary Application Rear View (cover removed; air-to-close valve) Figure 4: Rotary Application Front View (cover removed; air-to-close valve) For direct-acting, air-to-open actuators, rotate the shaft counter clockwise as far as it will go, then back off approximately 5 to 10 degrees. For direct-acting, air-to- close actuators, rotate the shaft counter clockwise approximately 5 to 10 degrees. For reverse-acting, air-to-open actuators, rotate the shaft counter clockwise approximately 5 to 10 degrees. For reverse-acting, air-to-close actuators, rotate the shaft counter clockwise as far as possible, then back off approximately 5 to 10 degrees. With the slot in this position, tighten lever arm clamp screw tightly (until the teller tab will not move). With this procedure completed, stroke valve to ensure spring is preloaded throughout the entire valve travel. 5. To make electrical connections, remove the housing cover. (Refer to the specifications in Table IV for component electrical ratings.) Attach transmitter signal wiring to the transmitter terminal block, using caution to attach the positive and negative wires to the appropriate terminal. CAUTION: Do not apply a voltage greater than 40 volts to the transmitter terminals or the circuit will be damaged. Attach limit switch wiring to the COMM (common) and either NC (normally closed) or NO (normally open) terminals according to the needed signal. 6. To adjust the limit switches and/or position transmitter, remove the housing cover and refer to the Calibration section in this document. 7. Replace the housing cover. 8. Reinstall the name plate to the mounting bracket. NOTE: Name plate reinstallation is important for valve identification/servicing purposes. Valtek Rotary Actuators To install Position Pac on Valtek rotary actuators, refer to Figures 3 and 4, and proceed as follows: 1. Mount the bracket to the mounting pad on the backside of the actuator using two 0.31-inch ( 5 /16) mounting bolts. 2. Mount the Position Pac to the bracket using four 0.31-inch ( 5 /16) mounting bolts and nuts. 3. Loosely mount the trip lever to the valve shaft within the yoke. 4. Attach the switch lever to the Position Pac shaft. 5. Connect the linkage assembly to both levers as shown in Figure 3. 6. Measure the approximate radius of the trip lever from the center of the valve shaft to the linkage assembly connection (not the end of the lever). Next, adjust the switch lever to approximately the same radius and tighten. Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611 29-3

Table III: Rotary Mounting Kits Actuator Valve Shaft Size Diameter Kit.* (sq. in.) (inches) 25 0.62 97556 25 0.75 97557 25 0.88 97558 50 0.62 97559 50 0.75 97560 50 0.88 97561 50 1.12 97562 100 0.88 97563 100 1.12 97564 100 1.50 97565 100 1.75 97566 *Kit includes: bracket, trip lever, switch lever, linkage assembly, nuts and bolts. 7. With the actuator at its minimum signal position, slide the trip lever along the shaft until the linkage assembly is parallel to the mounting bracket. At the same time, rotate the trip lever until it is at a 45- degree angle to the mounting bracket and pointing toward the top yoke bolt closest to the Position Pac. Tighten the trip lever on the shaft in this position. 8. Adjust the linkage assembly until the switch lever is approximately the same angle as the trip lever and the linkage assembly is horizontal. To preload the Position Pac's restoring spring (used to remove backlash in the linkage), be certain the actuator is in its minimum signal position and perform the following using a slotted screw driver to rotate the switch shaft (all rotation direction instructions are as viewed from the lever arm side of the Position Pac): For direct-acting, air-to-open actuators, rotate the shaft counter clockwise as far as it will go, then back off approximately 5 to 10 degrees. For direct-acting, air-to-close actuators, rotate the shaft clockwise approximately 5 degrees. For reverse-acting, air-to-open actuators, rotate the shaft clockwise approximately 5 degrees. For reverse-acting, air-to-close actuators, rotate the shaft counter clockwise as far as possible, then back off approximately 5 to 10 degrees. With the slot in this position, tighten the lever arm clamp screw tightly (until the teller tab will not move). 9. If possible, stroke the valve; the linkage assembly should travel back and forth remaining horizontal. 10. To make electrical connections, remove the housing cover. (Refer to the specifications in Table IV for the component electrical ratings.) Attach the transmitter signal wiring to the transmitter terminal block, using caution to attach the positive and negative wires to the appropriate terminal. Attach the limit switch signal wiring to COMM (common) and either NC (normally closed) or NO (normally open) terminals according to the needed signal. 11. To adjust the limit switches and/or the position transmitter, remove the housing cover and refer to the Calibration section in this document. 12. Replace the housing cover. CALIBRATION When a Position Pac is installed in the field or a factory installed unit needs to have output signal adjustments made, refer to Figure 5 and proceed as follows: Limit Switch Position Pac limit switches are adjusted at the factory before shipment and should not require on-site adjustment. However, if the mechanical lever has shifted position, the unit may need readjustment. To readjust the limit switch, proceed as follows: CAUTION: If the valve cannot be stroked without disturbing the process fluid, bypassing or removing the valve from the line may be necessary before calibrating the Position Pac. WARNING: Prior to removing the valve from the line, depressurize the line to atmospheric pressure, drain all process fluid and, if caustic or hazardous material are present, decontaminate the valve. Failure to do so can cause serious injury. 1. Stroke the valve to the closed position. WARNING: Keep hands, hair, clothing, etc. away from moving parts when operating the valve. Failure to do so can cause serious injury. 2. Remove the housing cover from the Position Pac. 3. Lift the appropriate cam follower lever. Move the cam wheel axially to disengage the teeth on the wheel from the teeth on the shaft disc. 4. Turn the cam wheel to the desired position. Each notch on the cam wheel represents an operating point change of 7 0 20'. 5. When the cam wheel has been rotated to the desired location, slide the cam wheel to engage with the mating shaft disc. (For finer adjustment, use the setscrew in the cam follower.) 6. Release the cam follower lever. 7. Cycle the valve and check for proper adjustment. Readjust if necessary. 8. Replace the housing cover. 29-4 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611

Transmitter terms block Limit switch adjustment cams (not shown) Transmitter span adjusting screw (pot) Limit switch wiring terminal Transmitter zero Adjusting Screw (pot) Clockwise/counterclockwise switch Figure 5: Calibration Points Position Transmitter 1. Remove the housing cover from the Position Pac. 2. Wire the Position Pac transmitter in series with a 12.5-40 VDC power supply and a milliamp meter. NOTE: Instructions within parenthesis ( ) refer to older Position Pac models characterized by a white label. CAUTION: Do not apply a voltage greater than 40 volts to transmitter terminals or the circuit will be damaged. 3. Be certain the CW/CCW Switch located next to the potentiometer (Direct/Reverse Switch located next to the wire terminal block) is set to provide the desired output signal action. In the CW (DIR) position, a clockwise rotation of the Position Pac shaft will cause the output signal to increase. In the CCW (REV) position, a counterclockwise stem rotation causes the signal to increase. 4. Stroke the valve to the closed position. WARNING: Keep hands, hair, clothing, etc. away from moving parts when operating the valve. Failure to do so can cause serious injury. 5. Referring to Figure 5, adjust the ZERO adjusting screw with a small, straight end screw driver, until the meter reads 4 ma DC. 6. Stroke the valve to the open position. 7. Adjust the SPAN adjusting screw until the meter reads 20 ma DC. 8. Stroke valve to the closed position and recheck the meter for 4 ma DC. Some readjusting of the calibration may be required. Repeat steps 4-8 until satisfied. 9. If calibration is unsuccessful after following this procedure, one of two problems may exist: (a) The orientation of the Position Pac stem may need to be adjusted. (b) The ZERO and SPAN potentiometers may be adjusted out of range. NOTE: The electrical travel of the potentiometer is 340 (150) degrees. To operate properly, the potentiometer wiper must stay within the center 185 degrees of its 340 degree electrical range during the full stroke of the valve. 9a. To adjust, stroke the valve to its middle position. Loosen the potentiometer collar nut. While measuring the voltage between pins 1 and 2 on the back of the potentiometer, rotate the potentiometer until the voltage is between 0.55 and 0.65 volts. Retighten the potentiometer being careful to keep the potentiometer oriented in the same position. Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611 29-5

9b. Set the ZERO and SPAN potentiometers to their approximate middle position. This is accomplished by first turning each potentiometer clockwise 25 turns or until a click is either felt or heard. Then turn each potentiometer counterclockwise approximately 12 complete turns. Repeat steps 2 through 8 to complete calibration. 10. Replace the housing cover. REVERSING POSITION TRANSMITTER SIGNAL The following instructions should be used when the signal being transmitted from the position transmitter is either incorrect or needs to be reversed. Refer to Figure 5. NOTE: Instructions within parenthesis ( ) refer to older Position Pac models characterized by a white label. 1. Remove the housing cover. 2. Locate the switch next to the position transmitter s wiring terminal. Move switch to the opposite position, CCW or CW (DIR or REV). Repeat steps 3-9 in the Calibration section for the position transmitter. NOTE: The SPAN potentiometer will generally not need readjustment. 3. Replace the housing cover. Max. Load Resistance, R L (Ω) 1500 1250 1000 750 Figure 6: Wiring Diagram R L max = V PS - 12.5V 20 ma 500 250 Operating Region 0 0 10 20 30 40 50 60 Power Supply Voltage, V PS (volts) Figure 7: Power Supply Requirements Table IV: Specifications Analog Output Power Supply Range 12.5 to 40 VDC (24V DC typical) Maximum Load Maximum Resistance (ohms) = Resistance Supply Voltage - 12.5 (see Figure 3) 0.02 Current Signal Output 4-20 ma Span Adjustable from 5 to 100 of angular rotation Null 4 ma position may be set at any angular position Linearity ±1.0% full-scale* Repeatability ±0.25% full-scale Hysteresis ±1.0% full-scale Operating -40 O to 185 O F (-40 O to 85 O C) Temperature Range Ambient Temperature For a 100 O F (38 O C) change in ambient Range temperature, maximum zero shift is ±0.4% full scale, maximum span shift is ±0.7% full scale Power Supply Output signal changes less than 0.05% when supply voltage is varied between 12.5 and 40 volts dc Limit Switches (SPDT) 20 amps, 125, 250, 480 VAC, ind. and /CSA Rating (L23) res. 1 Hp. 125 VAC; 2 Hp, 250 VAC, 0.5 amp. 125 VDC; 0.25 amp, 250 VDC res. Mechanical Input motion ±105 O from the center; spring loaded to return to the center * Linearity is ±1.0% for 90 O rotary shaft input. When mounted to linear travel valves, linearity is dependent on linkage design and stroke length. Typical linearity is ±1.5% full-scale on Valtek Mark One control valves. 29-6 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611

Rotary Short Housing Housing 1.26 dia. max. 32 0.88 22 4.09 max. 104 0.88 22 5.71 max. 145 0.72 18 1.57 40 0.37 9 3.78 max. 96 0.37 9 3.78 max. 133 4.00 102 3.15 80 2.00 51 2.38 typ 60 3.86 dia. 98 0.29 dia. 7 3.82 dia. 97 0.33 dia. thru (4) 8 0.80 20 1.00 25 0.75-14 NPT (5 full threads min.) (2) Eight side mounting holes can be tapped 5/16-18-inch 0.80 20 1.00 25 0.75-14 NPT (5 full threads min.) (2) 0.50 13 0.57 14 0.25 6 Front Mounting 0.49 12 0.75 19 1.50 38 Lever Actuators 4.04 103 Adjust 1.50-3.70 38-94 1.00 25 0.27 7 0.16 4 0.83 21 0.39 10 0.74 19 0.72 18 0.16 4 0.09 2 0.31 8 Figure 8: Dimensions Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611 29-7

Troubleshooting Failure Probable Cause Corrective Action Operation erratic 1. Loose bracket bolting 1. Tighten bolting bracket to yoke leg or transfer and inconsistent case: readjust position transmitter and switches 2. Loose Position Pac mounting 2. Tighten mounting screws, readjust position screws transmitter and switches 3. Loose tripper bracket 3. Tighten tripper bracket or extended spline (linear actuator) or extended connector spline connector (rotary actuator) 4. Internal or electrical 4a. Ensure that terminal block connections are malfunction tight 4b. Check for foreign material in contact with printed circuit board or components 4c. Check for components or wires broken loose from printed circuit board 4d. Check that the switch is fully set in desired position Indicating 1. Incorrect adjustment 1. Refer to Calibration section, step 9 incorrect position 2. Internal or electrical 2a. Ensure that terminal block connections are tight 2b. Check for foreign material in contact with printed circuit board or components 2c. Check for components or wires broken loose from printed circuit board 2d. Check that the switch is fully set in desired position Flowserve Corporation has established industry leadership in the design and manufacture of its products. When properly selected, this Flowserve product is designed to perform its intended function safely during its useful life. However, the purchaser or user of Flowserve products should be aware that Flowserve products might be used in numerous applications under a wide variety of industrial service conditions. Although Flowserve can (and often does) provide general guidelines, it cannot provide specific data and warnings for all possible applications. The purchaser/user must therefore assume the ultimate responsibility for the proper sizing and selection, installation, operation and maintenance of Flowserve products. The purchaser/user should read and understand the Installation Operation Maintenance (IOM) instructions included with the product, and train its employees and contractors in the safe use of Flowserve products in connection with the specific application. While the information and specifications presented in this literature are believed to be accurate, they are supplied for informative purposes only and should not be considered certified or as a guarantee of satisfactory results by reliance thereon. thing contained herein is to be construed as a warranty or guarantee, express or implied, regarding any matter with respect to this product. Because Flowserve is continually improving and upgrading its product design, the specifications, dimensions and information contained herein are subject to change without notice. Should any question arise concerning these provisions, the purchaser/user should contact Flowserve Corporation at any of its worldwide operations or offices. For more information, contact: For more information about Flowserve, contact www.flowserve.com or call USA 972 443 6500 Flowserve and Valtek are registered trademarks of Flowserve Corporation. Regional Headquarters 1350 N. Mt. Springs Prkwy. Springville, UT 84663 Phone 801 489 8611 Facsimile 801 489 3719 12 Tuas Avenue 20 Republic of Signapore 638824 Phone (65) 862 3332 Facsimile (65) 862 4940 12, av. du Québec, B.P. 645 91965, Courtaboeuf Cedex, France Phone (33 1) 60 92 32 51 Facsimile (33 1) 60 92 32 99 Quick Response Centers 5114 Railroad Street Deer Park, TX 77536 USA Phone 281 479 9500 Facsimile 281 479 8511 104 Chelsea Parkway Boothwyn, PA 19061 USA Phone 610 497 8600 Facsimile 610 497 6680 1300 Parkway View Drive Pittsburgh, PA 15205 USA Phone 412 787 8803 Facsimile 412 787 1944 29-8 FCD VLAIM029-04 2000 Flowserve Corporation. Flowserve Corporation, Flowserve Corporation, Valtek Control Valtek Products, Control Tel. Products, USA 801 Tel. 489 USA 8611 801 489 8611