Product Specifications for Phase Over Phase GOABS(r)

Similar documents
Product Specifications for Aluminum Vertical Break Switches

CENTER BREAK GROUP OPERATED AIR BREAK SWITCHES RATED 15.5kV THROUGH 170kV EFFECTIVE DATE: 10/25/16 REV B

TYPE V CENTER BREAK SWITCH

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

34-SDMS-01 SPECIFICATIONS FOR

100 / 110 DRYWELL FUSE SPECIFICATION

SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

Three-Phase Pole Mounted Recloser

Copper Double Break Switch

Transmission Switching

Underground Distribution Switchgear

Catalog 14A January 2013

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

Publication No.: PSG

Operators/Accessories. Type V2-CA Aluminum. Vertical Break Switch. Ordering Information Furnish: Available Accessories. Standard Operator Features

Aluminum Vertical Break Switch kv A.

M-Force three-phase switch

A. Submit manufacturer's literature and technical data before starting work.

Type EB, EBB, EBF and VEB DOUBLE SIDE BREAK SWITCHES 38 kv through 362 kv 600 to 3000 Ampere

Typical Specification

Copper Vertical Break Switch kv A.

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

Disconnect & ByPass Switches

M-Force three-phase switch

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Aluminum Vertical Break Switch 345 kv, 1300 kv BIL 2000 A A.

Horizontal Circuit Switchers

3.0OVERHEAD TRANSMISSION SWITCHES

43-SDMS-01 SPECIFICATIONS FOR

25 kv Apparatus Bushings

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

Horizontal Circuit Switchers

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

SECTION PANELBOARDS

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Technical Specification for Pole Mounted Capacitor Rack

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Technical Specification For Outdoor Substation Harmonic Filter Banks

OVERHEAD DISTRIBUTION SWITCHES

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

Underground Distribution Switchgear

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

CLEAVELAND / PRICE INC. Type RL-C Side Break Switch kv A. Bulletin DB-104E12

AVX. Operation and Maintenance Manual AVX 1200A A 15kV to 362kV. ALUMINIUM VERTICAL BREAK DISCONNECT SWITCH 15kV to 362kV 1200A A

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Specifications. S&C Omni-Rupter Switches Outdoor Distribution (14.4 kv and 25 kv) Conditions of Sale

35-kV Safefront 200 Amp SuperWell Primary Metering Station Pad-Mounted Outdoor

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

S&C Loadbuster Disconnects

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv)

WESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO. GUARANTEED TECHNICAL PARTICULARS 1 of 2

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Design Standard. Purpose: Design Standard:

INSTRUCTIONS For Field Assembly and Installation

Power Fuses. > Power Fuses > BPA & HPA kv AMPs

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

TYPE EE and EEB CENTER- SIDE-BREAK SWITCH TYPE VEE and CBV CENTER BREAK V SWITCH 1200, 1600, 2000 & 3000 Amperes 7.

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

Submersible Vacuum Fault Interrupters

Figure 1. HX cutout fuseholders.

www. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE

Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

Figure 1. HX cutout fuseholders. Positive Interruption

35-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current-Limiting Fuses

DO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc.

PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT

AIRBREAK SWITCHES East Ginter Rd. Tucson, Arizona USA (520) Fax (520)

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

Installation Instruction for Phase-Over-Phase GOABS(r)

TYPE BLT DISCONNECT SWITCHES

C1000 Series Automatic Cap Bank

Horizontal center break disconnector Type SDF, up to 550 kv Maximum reliability and minimal maintenance

SUGGESTED SPECIFICATIONS

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

SPECIFICATION BULLETIN

34-SDMS-02 SPECIFICATIONS FOR

SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed.

Unitized Quick Install Switches for Transmission Applications

15-kV Safefront 200 Amp Primary Capacitor Station Pad-Mounted Outdoor

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

IB-FAS3 Mar Type FAS THRU 115Kv Amp 61 KA Momentary. Vertical-Break, Gang-Operated Outdoor Air Disconnect Switch.

Chapter 6 Generator-Voltage System

Instructions for Installation and Operation

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

15 kv and 25 kv Thru-Bushings

Type MOST oil switch

Transcription:

1. General a) This specification covers the design, manufacture, and shipment of phase-over-phase, 1-way, 2-way, 3-way, and 4-way, gang-operated disconnecting switches, both air-break and load-break, for transmission switching applications b) All switches furnished shall conform to all applicable IEEE, NEMA, and ANSI standards c) The switch manufacturer shall furnish all parts required to install a complete operating switch, including switch frames, operating mechanism, and equipment mounting hardware; insulators, if required, will be specified separately d) The pole structure, dead-end assemblies, guying and grounding materials, through bolts and miscellaneous pole line hardware will be provided by Others e) This equipment will be field assembled and installed by Others 2. Applicable Standards and Specifications a) The following standards shall form a part of this specification unless otherwise stated: ANSI C29.9 ANSI C37.32 ANSI C37.34 ASTM 123 NEMA SG6 Wet-Process Porcelain Insulators Schedules of Preferred Ratings, Manufacturing Specifications, and Application Guide for High Voltage Air Switches Test Code for High-Voltage Air Switches Zinc Coating (Hot Dip) on Iron and Steel Hardware Power Switching Equipment b) All switches furnished shall be in accordance with the latest versions of the appropriate specifications. c) The switch shall be a SEECO type G or GL, or approved equivalent. 3. Materials and Workmanship a) The equipment shall be new and of standard commercial, first-grade quality as to materials, workmanship, and design, in accordance with the best engineering practice, and shall be such as has been proven to be suitable for the intended purpose. b) All welding shall be done by welders experienced in the process to be used and in a manner evidencing good workmanship. 4. Environmental Conditions a) Temperature - Equipment supplied shall be adequate for an operating range of -40 degrees C to +55 degrees C b) Humidity - Equipment supplied shall be operated under humidity of up to 95% at a temperature of 40 degrees C c) Environment - Equipment supplied shall provide reliable performance in environments with high exposure to salt, minerals, chemicals, or windborne particulate d) Ice - Equipment supplied shall operate adequate with a build-up of 3/4 clear ice Page 1

5. Ratings and Type a) Type - Switches shall be group operated side-break switches with an integral design (2-way and 3-way switches), mounted horizontal upright on aluminum support structures, in a phase-over-phase configuration b) Ratings - Switches shall meet or exceed the following ratings Rated Voltage Rated Maximum Voltage Rated Frequency Rated Continuous Current Rated Momentary Current Rated Withstand Voltage (BIL) 15 kv through 230 kv 15.5 kv through 242 kv 60 Hz 600 Amp through 3,000 Amp 40 ka through 100 ka 110 kv through 1050 kv 6. Switch Design and Construction a) Jaw Contacts i) All jaw contacts shall be silver to copper and designed so that wiping action is provided with a minimum of roughening or wear on the silver spherical contacts ii) The design of the jaw contacts shall be such that the resultant magnetic forces during short circuit will tend to hold the blade in the closed position and maintain contact pressure; blade locks or other latching devices are not permitted iii) Switch contacts shall be the high pressure line contact type with a minimum of 100 lbs pressure on each silver contact iv) Contact pressure shall be maintained by separate back-up spring members independent of the main current path. Contact members shall be independently adjustable for proper contact deflection v) Wear of contacts shall not result in diminished contact performance due to reduction of contact pressure. The number and size of contact fingers shall be sufficient to ensure adequate transfer of rated current from the blade to the jaw vi) All contacts shall be self-aligning and self-adjusting and designed to ensure firm positive contact b) Switch Blade i) Each switch blade shall form one solid piece and shall be so assembled that no part of the blade can move relative to another ii) Ends of switch blades shall be completely closed except for drain holes iii) Rotating-blade switches which require blade locks or latching devices are not permitted Page 2

c) Terminal Pads i) Terminal pads on each end of the switch shall be located at the same height above the insulator ii) Terminal pads shall have flat, machined surfaces iii) Terminal pads shall have NEMA standard 2-hole arrangement for 600 ampere switches and NEMA standard 4-hole arrangement for switches rated 1200 to 2000 amperes d) Switch Assembly i) Switches of the same rating and design shall have interchangeable parts ii) The switch shall be so designed that when installed, its operation will not be prevented by accumulated water, sleet, ice, snow, dirt, or other atmospheric contamination. iii) Metal live parts shall be non-rusting and corrosion resistant. All current carrying parts shall be non-ferrous. v) Live parts shall be designed to use at least three of the four mounting holes in the insulator or insulator adapter. vi) Bolts, screws, and pins shall be provided with lock washers, keys, or equivalent locking facilities vii) No part of the switch blade or jaw assembly, except arcing horns, shall project lengthwise beyond the terminal pads e) Switch Mechanism i) The mechanism shall be so designed that all three phases are in positive continuous control throughout the entire operating cycle ii) Each rotating insulator stack shall have double roller or double ball bearings in the base bearing assembly. Bearing housings shall be weatherproof. Open type bearing assemblies must be rustproof and non-corroding, and they shall be designed to completely drain water and moisture accumulation. iii) All roller or ball bearings shall be greaseless or maintenance free type iv) Rotating insulator stacks with 5 bolt circles (115 kv and greater) shall have leveling provisions at the base of each stack; rotating insulator stacks with 3 bolt circles (69 kv and below) may employ shims for alignment v) All operating pipes shall be sufficiently rigid to maintain positive control under the most adverse conditions, including a heavily iced switch and operating mechanism. vi) It shall be impossible, after proper and final adjustment has been made, for any part of the mechanism to be displaced sufficiently, at any point in the travel, to allow improper functioning of the switch when the switch is opened or closed at any operating speed vii) All ferrous parts, except springs, shall be hot-dip galvanized in accordance with ASTM A153, latest revision Page 3

f) Operating Mechanism i) The operating mechanism shall be positively toggled when the switch is closed to ensure correct, complete switch operation and to provide operating personnel with visual confirmation ii) All vertical operating shafts shall be supported on ball or roller thrust bearings. Guides shall be provided on the vertical shaft at regular intervals to ensure proper operation. iii) Switches rated 230 kv and below shall be furnished with a horizontal swing handle. Geared mechanisms shall be acceptable, if required, to ensure proper operation. iv) Provision shall be made for padlocking the mechanism in the open or closed position. v) A flexible copper braid shunt shall be provided on the operating mechanism for ground connections by Others g) Switch Frames (Support Structures) i) The switch frames shall be an all aluminum design with welded or welded and bolted construction ii) The frame material shall be structural grade aluminum, 6061-T6 iii) The frame tension rating shall be 10,000 lbs working load, and 16,500 lbs ultimate iv) Angled pull-offs at the tap are permitted with de-rated tensions. Consult the manufacturer for a schedule of angles and tensions h) Arcing Horns i) Switches will be supplied complete with high-speed, snap-out arcing horns for the interruption of limited amounts of line charging and transforming magnetizing currents ii) Horns to be constructed from beryllium or stainless steel with appropriate mechanical and electrical attributes to maintain function throughout the life of the switch without degradation of spring characteristics iii) iv) Horn shall be of a tapered design to provide maximum tip speed Arcing horn assembly shall include a mechanical stop (snubber) to prevent return/rebound of the horn and possible re-strike 7. Insulators a) Switches will be supplied without insulators unless specified otherwise on customer s RFQ or manufacturer s proposal b) Insulators will be wet-process porcelain and conform to ANSI C29.8 and C29.9. Polymer style insulators can also be supplied at customer request; consult the manufacturer for guidance on appropriate applications c) Insulators supplied will be standard strength, ANSI 70 sky-tone gray unless specified otherwise on customer s RFQ or manufacturer s proposal Page 4

8. Interrupters a) Switches requiring load interruption capability shall utilize a vacuum interrupter to interrupt current and to provide a confined arc when switching load, line charging or transformer magnetizing currents b) The interrupter unit shall be designed to ensure high speed interruption regardless of the operational speed of the switch c) When not being operated, the interrupter unit shall be out of the current path so that it is not subject to fault currents d) When the interrupter employs a dielectric to enhance the interrupting rating of the enclosed vacuum bottle, accidental loss or disposal of the dielectric shall not pose a risk to the health of utility personnel or the environment; SF6 is not acceptable as a dielectric 9. Pole Structures a) Switches may be mounted on pole structures of various types, including wood, laminated wood, concrete, or steel b) Switch pole structures must be adequate for the intended purpose, and designed for the specific loads and line tensions of the switching application; tangent type line structures are generally discouraged. Consult the switch manufacturer for general guidance, if in doubt c) Wooden poles, class H1 minimum recommended, are appropriate for switches 69 kv and below d) Engineered structures of steel, concrete, or laminated wood, designed for the anticipated load and line tensions, are recommended for switches rated 115 kv and up e) For engineered structures, the maximum resultant deflection with worse case ice and wind loads applied is 2% of the structure height above grade f) Pole structures must be sized for height to insure adequate clearance for grade to phase, phase to phase, and phase to shield dimensions. These dimensions vary with the voltage of the equipment. Consult the manufacturer for a schedule of voltages and dimensions. 10. Nameplates a) All switches shall be equipped with a non-corrosive nameplate in accordance with ANSI C37.30, permanently attached with stainless steel screws or rivets b) Nameplate shall include the appropriate catalog number, electrical ratings, and manufacturer s sales order number for proper and complete identification of the switch 11. Shipping a) Switches shall be shipped knocked-down to minimize transportation costs and facilitate handling and storage b) Switch live parts shall be completely assembled, and then broken down for shipment. For switches rated 69 kv and below, base bearings and sub-bases will be assembled and bolted into position on switch frames c) Operating pipe will be shipped unassembled and banded together d) All other switch components shall be shipped in a wooden crate e) All shipping units will carry a detailed packing slip with part number identification, associated drawing number and call out, and quantity count; packing slip will also provide the manufacturer s sales order number and customer purchase order number f) All switches and accessories shall be shipped FOB factory, freight prepaid and add unless otherwise noted Page 5