The IAQ50 Air Damper/Monitor Installation and Maintenance Manual

Similar documents
Air Quality Solutions

Document number AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions

Installation, Operation and Maintenance Manual

Installation, Operation, and Maintenance Instructions

FOR USE IN SOLUTION AIR HANDLING UNITS

Installation, Operation and Maintenance Manual

3900 Dr. Greaves Rd. Kansas City, MO (816) FAX (816) ABD-SEA-E

MANUAL INSTALLATION. Venturi FX. VFX Series. v100 Issue Date: 11/22/ Price Industries Limited. All rights reserved.

Installation, Operation and Maintenance Manual

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.

Introduction to Johnson Controls Dampers

TED50XT EXTREME TEMPERATURE THERMALLY EFFICIENT, INSULATED BLADE DAMPER

AD-1251 Probe with Differential Pressure Transducer

Air Quality Solutions

MODEL 8682 SUREFLOW ADAPTIVE OFFSET CONTROLLER

AD-1250 Airflow Measuring Station

Air Measuring Products AMD AMS IAQ

MR Modulo. Adjustable Constant Airflow Regulator

RUS-L24-MOD Electric 24 Volt Modulating Control Damper Actuator

Air Quality Solutions

GE Measurement & Control

AMD-42V Air Measuring Station with VCD-42V Control Damper

AMD-42 Air Measuring Station with VCD-42 Control Damper

SD-1250 and SD-1600 Series Smoke Dampers

Laboratory Exhaust Air Terminal

COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES /2014 Supersedes 8/2012

RUS-L24-MOD Electric 24 Volt Modulating Control Damper & Louver Actuator

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS

FSD60, FSD60LP CoMBINAtIoN FIRe AND SMoKe DAMPeR

FSD36, FSD36LP COMBINATION FIRE AND SMOKE DAMPER 1 1 /2 HOUR UL555 RATED, UL555S LEAKAGE CLASS 2

Installation, Operation and Maintenance Manual

SECTION CONTROL DAMPERS

Safety & Installation Instructions

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS

FAN POWERED HEPA FILTER UNIT

100% OUTSIDE AIR MAKE-UP UNITS WITH DISCHARGE TEMPERATURE CONTROL & c.pco DIRECT DIGITAL CONTROL MODULE

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT

CCS Zone/Bypass Damper Assembly

Installation Instructions

Fan Powered Low Profile Variable Volume Terminal Units

X4 Installation and Operation Manual - POWER FLAME INCORPORATED

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas

AMD-33. Air Measuring Station with VCD-33 Control Damper. Application and Design. Features & Control Options

NJK Precision Product NJK-02 Sensor Installation Guide


D-4070 Two Stage Pneumatic Actuator

AMD-33 Air Measuring Station with VCD-33 Control Damper

Laboratory Exhaust Air Terminal

PC-125x Counter-Balanced Backdraft Damper

Blank-off. HVAC unit screws. Spacer for 1" filter ILL. 3. Screw

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma

CRECOMZR054B00 CRECOMZR055B00. VERTICAL AND HORIZONTAL ECONOMI$ER2 ACCESSORY MEDIUM ROOFTOP UNITS 15 to 27 1/2 TONS WARNING TABLE OF CONTENTS

VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD

INSTALLATION, OPERATION & MAINTENANCE MANUAL BYPASS ECONOMIZER OPTION

AMD-42-TD. Thermal Dispersion Air Measuring Station with VCD-42 Control Damper. Application and Design. Ratings. Features and Control Options

INSTALLATION, OPERATION & MAINTENANCE MANUAL

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:

Patient Care Facility

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:

Drug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions

Air Measuring Products. AMS Thermal Dispersion Pressure Differential

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

ACCUVALVE MODEL AVT6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVT6000 AVT6 - - DWG. NO: REVISION: REV. DATE:

AK Application. Features. Applicable Literature. Positive Positioner Pneumatic Relay General Instructions

Screw. (Note 4) Spacer for 1" filter ILL. 3. Screw

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST. For Use with Bard CH Series 3, 4, & 5 Ton Wall Mount Heat Pumps

LDV / LDVQ 5000 AIR VOLUME CONTROL VALVE INSTALLATION MANUAL. Date: 02 / 10 Reference # : F-36. w w w. p r i c e - h v a c. c o m

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction.

VOLU-probe. Pitot Airflow Traverse Probes. amca. Accurate airflow measurement for demanding applications. CERTIFIED RATInGS

Metasys Zoning Package Installation

NMQB24-MFT, NMQX24-MFT Quick Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

MP-5400 Series. Application. Features. Applicable Literature. Electronic Positive Positioning Hydraulic Actuator General Instructions

Air Actuated Hydraulic Bottle Jack on Wheels

Patient Care Facility

Drug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions

Model 8144NC Fresh Air Ventilator

INSTALLATION INSTRUCTION

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN. Rev.

YCCS Zone/Bypass Damper Assembly

Polaris 1000 User s Manual

Installation Instructions

Model VCD-40. Extruded Airfoil Blade Control Damper Narrowline Frame Construction. Application. Ratings. Flange Options.

AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application. Ratings. Features and Options

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST

Model VCD-20. Control Damper. Application. 3V Blade. Ratings. Flange Options. Size Limitations. Blade Operation. Features and Options

YCCS Zone/Bypass Damper Assembly

Installation Instructions

Motorized Fire Dampers

FBV-43. Vertical Face & Bypass Control Damper Ultra Low Leakage Aluminum Frame Construction. Application and Design. Size Limitations.

Screw. (Note 4) Spacer for 1" filter ILL. 3. Screw

LMCB24-SR LMCB24-SR-T. applications. Dimensions (All numbers in brackets are in millimeters.) 1/4 to 3/4 [6 to 20] 5/16 to 3/4 [8 to 26] 1.

Baked Enamel, Epoxy, Hi Pro Polyester, Industrial Epoxy, Kynar/Hylar (70%) Permatector. Single or Reverse Flange 8 x 6 (203 x 178)

ECONOMIZERS. 5/2012 Supersedes

ATP-2040 Electric Damper Actuator/Transmitter

Dimensions [All numbers in brackets are in millimeters.] K4-2 US (supplied) 1/2" Centered (Default) 3/4" Centered (Field Selectable)

ACCUSTATION SUBMITTAL MATERIALS

Minimum 90 in-lb Torque. Applications. NFB, NFX Series At A Glance. NFB and NFX Series Spring Return Direct Coupled Actuator

Installation Instructions

Transcription:

The IAQ50 Air Damper/Monitor Installation and Maintenance Manual RUSKIN MANUFACTURING 3900 Dr. Greaves Road Kansas City, Missouri 64030-1183 U.S.A.

! WARNING DO NOT TAMPER WITH (REMOVE, REPLACE, RELOCATE OR ADJUST) THE ACTUATOR ON ANY IAQ50 DAMPER PRODUCT WITHOUT FIRST CONTACTING RUSKIN AIR AND SOUND CONTROL. THE ACTUATOR IS CALIBRATED WITH THE CONTROLS TO MATCH JOB SPECIFIC SET POINTS. MANIPULATING THE ACTUATOR IN ANY WAY WILL VOID THE WARRANTY OF THE DAMPER AND RESULT IN IMPROPER CFM READINGS.! WARNING THIS ACCESSORY IS TO BE INSTALLED BY A QUALIFIED SERVICE PERSON. TO AVOID UNSATISFACTORY OPERATION OR DAMAGE TO THE PRODUCT AND POSSIBLE UNSAFE CONDITIONS. THE INSTALLATION INSTRUCTIONS PROVIDED WITH THIS ACCESSORY MUST BE STRICTLY FOLLOWED AND THE PARTS SUPPLIED USED WITHOUT SUBSTITUTION. DAMAGE TO THE PRODUCT RESULTING FROM NOT FOLLOWING THE INSTRUCTIONS OR USING UNAUTHO- RIZED PARTS MAY BE EXCLUDED FROM THE MANUFACTURER'S WARRANTY COVERAGE.! WARNING DISCONNECT ELECTRICAL POWER TO THE UNIT. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH. The IAQ50 Air Damper/Monitor unit and digital controller panel may ship in separate containers. Please verify the receipt of both prior to installation. On projects with multiple units, it is necessary to match the specific controller with the specific IAQ50 damper. Match the control numbers to insure the controller is the correct match for the damper/monitor. 5.1 IAQ50 Air Damper/Monitor Installation Instructions 1. Remove the IAQ50 Air Damper/Monitor from its shipping container and inspect for damage, rust or corrosion. Care must be taken in handling the unit. Always handle the IAQ50 Air Damper/Monitor by its frame. Do not lift it by the blade, linkage, axle, motor or jackshaft. Do not drop, drag, step on, or apply excessive bending, twisting or racking loads to the IAQ50. Improper handling of the unit will have adverse affects on the calibration and could result in cancellation of the warranty. 2. Inspect the ductwork and/or opening where the IAQ50 Air Damper/Monitor assembly will be installed for any obstruction or irregularities that might interfere with blade or linkage rotation, or actuator mounting. If it is to be installed in ductwork, the ductwork should be supported in the area of the IAQ50 to prevent sagging due to the unit s weight. 3. The IAQ50 Air Damper/Monitor must be installed with the frames square and without twisting or bending. Unless specifically designed for a vertical blade application, the unit must be mounted with its blade axis horizontal. The damper blades, axles, and linkage must be able to operate without binding. 4. The best location for the extended shaft or jackshaft must be determined before installing the damper. The damper may be rotated to get the extended shaft on the correct side of the ductwork. After the damper is installed the shaft location cannot be changed without removing the damper. The jackshaft, if installed, will always be in the leaving air stream. Unlike other control dampers, which have no airflow orientation, the IAQ50 has a specified inlet and outlet. The outside air (or other controlled air stream) enters the unit through the air straightener section and exits the unit from the damper frame side. 5. Use appropriate shims between damper frame and duct opening to prevent distortion of the frame by fasteners holding it in place. If creating a multi-section assembly, be sure that all of the sections are fastened together on both sides. 6. The IAQ50 Air Damper/Monitor is factory calibrated and tested in order to perform correctly in its application immediately following installation. The electric actuator should not be moved, adjusted, or altered in any way to facilitate installation. Such modifications affect the factory calibration of the unit. If the actuator, linkage, or shafting present a problem for installation, please consult your local Ruskin representative or the Ruskin factory. The IAQ50 should be cycled after installation to assure proper operation. Page 1 of 5

5.2 Digital Controller Panel Installation 1. The controller enclosure should be mounted securely on an adjacent wall, attached to the air handling unit, or placed within some other suitable control panel. The panel should be mounted within 120 feet of the IAQ50 Air Damper/Monitor to prevent pressure signal variations from the IAQ50 to the control panel. If the enclosure must be mounted more than 120 feet from the IAQ50 damper frame, please consult your local Ruskin representative or the Ruskin factory. 2. Loosen the enclosure s cover screws and remove the cover. 3. Remove the appropriate knockouts for connection of the field wires to the enclosure s terminal blocks. 4. Fasten the enclosure to the wall or flat surface using the (4) 1/4 dia. holes at the four corners. 5.3 IAQ50 Wiring & Piping Connections (refer to control panel wiring diagram) IAQ50 Wiring Connections 1. Connect the 115VAC power supply to IAQ50 control panel terminals L1 and L2. 2. Connect 24VAC power wires from the Ruskin or Honeywell actuator terminal block to the control panel terminal block. Do not wire actuator terminals 1 & 2 directly into the IAQ50 plant controller. Wire from actuator terminal 1 "T" to terminal block 47. Wire from actuator terminal 2 "C to terminal block 46. Wire from actuator terminal 3 "+" directly to the IAQ50 plant controller terminal 50 "A01." Wire from actuator terminal 5 "F" directly to the IAQ50 plant controller terminal 19 "A12." Actuator terminal 4 "-" is not wired. 3. Connect the motor actuator (0-10V control signal) wire 3 to panel terminal 50. 4. Connect the motor actuator (2-10V position feedback signal) wire 5 to panel terminal 19. 5. (Optional) Connect the 0-10VDC remote setpoint adjustment signal (by others) to control panel terminals 26 and 27 (terminal 26 is the positive terminal). If used, remove the 2K resistor. 6. (Optional) Connect the wires to receive 0-20mA actual CFM signal from the IAQ50 panel to terminals 51 and 52 (terminal 52 is the positive terminal). 7. (Optional) If BMS contacts are wired to the IAQ50 plant controller terminals 1, 2 & 3, contact sequence is as shown in the table below. SEQUENCE 1 & 2 Closed 2 & 3 Open 1 & 2 Closed 2 & 3 Closed 1 & 2 Open 2 & 3 Closed 1 & 2 Open 2 & 3 Open CONTROL FUNCTION Close Damper Open Damper Open Damper IAQ Control Mode 8. (Optional) Connect the 0-10VDC remote outside air cooling demand signal (by others) to control panel terminals 28 and 29 (terminal 28 is the positive terminal). If this signal calls for more outside air than the minimum ventilation setpoint, the IAQ50 will modulate open beyond minimum position in response to this signal (0-20mA scaled to 0-100% damper open). At no time will the IAQ50 digital controller allow an airflow below the minimum CFM setpoint. If used, remove the 2K resistor. IAQ50 Piping Connections 1. Connect the total pressure signal tubing (from upstream side of damper) labeled H to barbed fitting on the side of the IAQ50 control panel labeled H. 2. Connect the static pressure signal tubing (from downstream side of damper) labeled L to barbed fitting on the side of the IAQ50 control panel labeled L. Page 2 of 5

5.4 IAQ50 Inspection and Troubleshooting Instructions IAQ50 Symptom Possible Cause Inspection Action IAQ50 remains closed and does not modulate. Power failure (fail closed setup). 1. Check terminals LI and L2 for 120VAC power supply. 2. Check terminals 46 and 47 for 24VAC power. 1. Restore power. 2. Replace transformer. Close mode in effect. 1. Check wiring connections to terminals 1 and 2 (Sl switch) for a closed circuit. 1. Remove jumper wire or open external controls. Power failure (fail open setup). 1. Check terminals LI and L2 for 120VAC power supply. 2. Check terminals 46 and 47 for 24VAC power. 1. Restore power. 2. Replace transformer. Economizer mode in effect. 1. Check wiring connections to terminals 2 and 3 (S2 switch) for a closed circuit. 1. Remove jumper wire or open external controls. IAQ50 remains open and does not modulate. Insufficient airflow. 1. IAQ50 is responding properly to system conditions. Check for obstructions and fan problems. 1. Insure proper system operation. 2. Check CFM on terminals 51-52. Pressure signal loss. 1. Check tubing/piping connection from IAQ50 frame to panel. Ports could be swapped. Tubes may be leaking. 2. Check terminals - and O on pressure transducer for 0-10VDC signal (10V at 1"w.c.) 1. Repair piping connections. 2. Call Ruskin. Actuator feedback failure. 1. Check DC voltage at terminals 46 and 19 for 0-10VDC range. 1. Call Ruskin. CFM Indication remains below setpoint with open damper. Insufficient airflow. Poor air sensing. 1. Check supply fan and HVAC system operation. 1. Check the straightener section and sensing blades for excessive dirt and dust. 1. Return HVAC system to normal operation. 1. Follow maintenance procedures recommended by Ruskin. Page 3 of 5

5.5 IAQ50 Maintenance Instructions 1. Semi-annually the tiebar linkage and the jackshaft or extended shaft bearings should be lubricated with a silicone lubricant. 2. Blade axle bearings do not normally require lubrication. 3. When dampers are installed where they will be exposed to heavy dust-laden air, discretional flushing of the axle bearings with water is recommended for extended bearing life. 4. The air straightener section and the damper blades should be annually inspected for particulate build-up. Use a damp cloth to wipe clean the damper blades. One can use water to clean and flush the air straightener section and the damper blades if deemed necessary. The air straightener section can be unbolted from the damper for ease of cleaning. Ruskin recommends using pressurized air to clear the sensing ports of water. See step 5. 5. Disconnect the piping connections between the IAQ50 Air Damper/Monitor frame and the control panel. Apply a clean, pressurized air source (35psi max.) to the air piping connections on the IAQ50 damper frame in order to flush out the sensing ports on the fixed monitoring blade(s) of the IAQ50. DO NOT connect this air source to the control panel as this will damage the IAQ instrumentation. RECOMMENDED SPARE PARTS LIST IAQ50 Air Damper/Monitor DESCRIPTION Roto Clip Blade Edge Seal - Opposed Digital Controller Differential Pressure Sensor 120V/24V Transformer 85VA Wire Terminal Electric Actuator PART NO. E-25 80-020045-00B W7760C2025** RU-274-R2-VDC** T-202 (2) 324-HDS/3 MS7106K2004** **Requires factory calibration. Consult Ruskin. Contact Ruskin Manufacturing, Commercial Damper Sales, 3900 Dr. Greaves Road, Grandview, MO 64030 for information. Telephone: 816-761-7476 Copyright 2005 Ruskin Manufacturing The information provided in this manual is believed to be complete and accurate. Ruskin Manufacturing is a manufacturer and supplier of equipment and, as such, is not responsible for the manner in which its equipment is used nor for infringement of rights of third parties resulting from such use. System design is the prerogative and responsibility of the system designer. All Rights Reserved. A U.S. patent protects the product detailed in this manual. Illustrations and product descriptions published are not binding in detail. In keeping with its policy of continuous improvement, Ruskin reserves the right to change or modify designs or specifications of products without notice or obligation. Page 4 of 5