Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers

Similar documents
COOPER POWER CA280012EN

Types VSA12, VSA12B, VSA16, VSA20, and VSA20A; three-phase; air-insulated; electronically controlled recloser

Effective October 2017 Supersedes July 2014 (280-40)

NOVA three-phase, microprocessorcontrolled

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

Figure 1. Kyle Type KFME recloser. TABLE 1 Summary of Ratings

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Typical Specification

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!

Single-Phase Step Voltage Regulators

Solid Dielectric, Single Phase Recloser

Single-phase step voltage regulators

Horizontal Circuit Switchers

SWITCHGEAR DIVISION PRODUCT PROFILES

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

Cobra-S. Catalog Cobra-S

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Effective August 2017 Supersedes January 1990 (285-71) Types PWE and PWVE Three-Phase Reclosers

Three-Phase Pole Mounted Recloser

Horizontal Circuit Switchers

Solid Dielectric, Three Phase Reclosers Catalog O-vs18

Molded Vacuum Reclosers The recloser you want, all in one package. Single- and Three-Phase Molded Vacuum Reclosers, 15 38kV

Single-phase pad-mounted step voltage regulator

Underground Distribution Switchgear

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

Solid Dielectric, Single Phase Reclosers

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Solid Dielectric, Independent Pole Operated Reclosers Catalog O-vst16

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013

600 A 15 kv class Cleer loadbreak connector system

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C

COOPER POWER SERIES. Type VSA12, VSA12B, VSA16, VSA20, and VSA20A operation and installation instructions. Reclosers MN280063EN

Joslyn Hi-Voltage. Overhead Reclosers & Switches. In this section...

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

M-Force three-phase switch

X-Limiter full-range current-limiting fuse

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout

Two-position sidewall (horizontal) and cover (vertical) mounted loadbreak switches

Solid Dielectric, Triple Option Reclosers Catalog O-vst14

solutions RUS accepted

PRODUCT SELECTION GUIDE

Underground Distribution Switchgear

Medium Voltage Metal-Enclosed Switches

600 A 35 kv class BT-TAP deadbreak connector

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

600 A 28 kv class Cleer loadbreak connector system

Technical Specification for Pole Mounted Capacitor Rack

A 1.2 kv class externally removable secondary bushing

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Medium Voltage Metal-Enclosed Switches

NOVA NX-T Triple-Single, Microprocessor-Controlled Recloser

600 A 15 and 25 kv class Cleer grounding elbow

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION

CATALOG. Joslyn Hi-Voltage Overhead reclosers & switches

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Underground Distribution Switchgear

Surge arresters. UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters. General. COnSTrUCTIOn

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

Transfer switch OTEC open or delayed transition

RUS accepted Catalog O-vst18

Product Group Brochure. PS Range Capacitor Vacuum Switches

600 A 15 kv class T-OP II deadbreak connector

Eaton s Cooper Power Systems

C1000 Series Automatic Cap Bank

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

GROUP D. Switch & Protective device.

Disconnect & ByPass Switches

Figure 1. Single-phase pad-mounted voltage regulator. STANDARD FEATURES

VacClad-W type VCP-W 5 and 15 kv, 36-inch-wide switchgear components

M-Force three-phase switch

VersaRupter 5-38 kv Load Interrupter Switch. Technical Guide

200 A and 600 A, 15, 25, and 35 kv junction bars for separable connectors

Underground Distribution Switchgear

Edison modular fuse, vault application products

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment

CMU medium voltage power fuses

UltraSIL polymer-housed VariSTAR station-class surge arresters

K-Limiter high ampere Companion II fuse

COOPER POWER SERIES. Types VWE, VWVE27, VWVE38X, WE, WVE27, and WVE38X; threephase electronically controlled; installation and operation instructions

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

Fusetron FRN-R Class RK5 250Vac/125Vdc A, dual element, time-delay fuses

Power Break II Switchboard

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General

Submersible Vacuum Fault Interrupters

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

SDV7. Outdoor distribution circuit breaker family 15.5 kv to 38.0 kv. usa.siemens.com/sdv7

Chapter 6 Generator-Voltage System

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Transcription:

Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers Medium-voltage vacuum circuit breakers Catalog information

Medium-voltage vacuum circuit breakers catalog Technical Data Effective August 2014 Medium-voltage vacuum circuit breakers catalog contents Contents Description Page Type VSA20B air-insulated; vacuum; electronically controlled power circuit breaker (290-25).... 3

Technical Data 290-25 Supersedes June 1995 Type VSA20B air-insulated; vacuum; electronically controlled power circuit breaker Description The Type VSA20B electronically controlled, vacuum circuit breaker provides reliable and economical overcurrent protection for 15 kv distribution systems. The VSA20B circuit breaker has been full-power tested in accordance with ANSI and NEMA standards for power circuit breakers. Detailed ratings and related capabilities on a symmetrical current basis, using maximum design voltage and a K factor of 1.0, are shown in Table 1. The VSA20B circuit breaker has a rated interrupting time of 2.5 cycles in accordance with ANSI standards. The fast interrupting time minimizes fault damage and provides fast coordination capability. A choice of electronic controls enables the user to meet a wide variety of application requirements. The use of vacuum as the interrupting medium and air as the insulating medium improves safety and substantially reduces long term maintenance costs. The VSA20B circuit breaker provides service-proven dependability and long operating life. Commanded by an Eaton's Cooper Power Systems electronic control, this automatic circuit breaker offers superior coordination and application capability, unmatched by other system protection apparatus. Breaker operations are programmed on the electronic control panel with accurate, preset tripping characteristics and reclosing times, enabling close coordination with other protective devices on the system. When system requirements change, program settings are easily altered with no sacrifice of accuracy or consistency. Breaker and control accessories enable further tailoring of the protective program to achieve maximum system operating flexibility. When needed, application expertise, backed by world wide application experience, is readily available. Eaton's Cooper Power Systems design capability is based on over 50 years of switchgear manufacturing experience. Progressive product development programs, using the latest technologies, have resulted in the production of modern, efficient breakers from Eaton's Cooper Power Systems. VSA20B circuit breakers are designed and built in accordance with ANSI/IEEE C37.04-1979, ANSI C37.06-1987, ANSI/IEEE C37.09-1979, and ANSI/ IEEE C37.012-1979. 290-25-1

Technical Data 290-25 VSA20B power circuit breaker Ratings The Type VSA20B circuit breaker can be applied on distributions systems ranging from 2.4 through 14.4 kv. Standard duty cycle is; CO-15 seconds-co. Basic ratings are shown in Table 1. Characteristic features Fault-sensing information for VSA20B circuit breakers is supplied to the electronic control by bushing-type current transformers mounted in the circuit breaker. Tripping and closing signals from the control energize operating circuits in the circuit breaker. Minimum-trip values of the control are independent of the continuous current and interrupting ratings of the circuit breaker. Flexibility in coordination with other protective devices is provided by dual time-current characteristics available from a broad choice of time-current curves, a wide range of minimum-trip values, and a variety of programmable reclosing times. Energy to operate the vacuum interrupters is provided by a motordriven operator supplied from a 240 Vac source. The motor operator closes the circuit breaker by charging the closing springs, which in turn provides the force to close the vacuum interrupters and charge the opening springs. Eaton's Cooper Power Systems vacuum interrupters have had an excellent field reliability record since their initial introduction in 1966 in the most complete line of vacuum switchgear available in the industry. Mounting equipment VSA20B circuit breakers are furnished in standard frames with corner lifting eyes. Mounting equipment is available for substation installation of the circuit breaker (see Table 6 for mounting accessories). Surge protection Best operating results are achieved when circuit breakers are protected with surge arresters. In substations, arresters should be located on the load side. Eaton's Cooper Power Systems distribution-class surge arresters provide excellent protection. See Catalog Section 235-35, UltraSIL Polymer-Housed VariSTAR Surge Arresters and 235-99, UltraSIL Polymer-Housed Evolution Surge Arresters. Table 1. Summary of Ratings and Related Capabilities Nominal Operating Voltage (kv) 14.4 Maximum Design Voltage (kv) 15.5 Voltage Range Factor K 1 Rated Impulse Voltage (kv) 110 Continuous Current Rating (amps) 1,200 Symmetric Interrupting Current (amps) 20,000 Interrupting Time (cycles) 2.5 Three-Second Current, Symmetric (amps) 20,000 Momentary Current, Asymmetric (amps) 32,000 Table 2. Basic Breaker Catalog Number Breaker Type VSA20B Catalog Number KVB-15-20-1200 The circuit breaker, control, and interconnecting cable are ordered and priced separately. Accessories for the circuit breaker and the control are ordered and priced separately. To order a circuit breaker, electronic control, and control cable: 1. Use Table 2 to specify the catalog number for the circuit breaker. 2. From Tables 3-6, specify the catalog numbers that describe the required circuit breaker accessories and mounting equipment. 3. Order the required electronic control (control is priced separately from circuit breaker). Ordering information A complete electronically controlled VSA20B circuit breaker installation includes: Circuit breaker and its accessories Electronic control and its accessories Control cable Mounting equipment 290-25-2

VSA20B power circuit breaker Technical Data 290-25 Table 3. Multi-Ratio Bushing Current-Sensing Transformers; Factory-Installed Description Catalog Number Three 600:5 BCTs (accuracy class C100) on bushings 1, 3, and 5 KA65VS1 Three 600:5 BCTs (accuracy class C100) on bushings 2, 4, and 6 Three 1200:5 BCTs (accuracy class C200) on bushings 1, 3, and 5 Three 1200:5 BCTs (accuracy class C200) on bushings 2, 4, and 6 KA65VS2 KA65VS3 KA65VS4 Table 4. Service-Related; Factory-Installed Description Catalog Number 120 Vac motor operator KA60VSM2 Potential-type battery charger in operator cabinet* 120 Vac 240 Vac External spring-charging accessory** External contact-position-indicating accessory KA58VSM1 KA58VSM2 KA59VSM2 KA61VSM2 * Required if the breaker is to be used with the Form 3A electronic control. The Form 3A control must be equipped with the KA1144ME accessory. ** Cannot be used with 2 sets of multi-ratio BCTs. Table 5. Mounting Equipment Description Substation mounting frame extension Electronic control mounting bracket Single-size cabinet Double-size cabinet Catalog Number KA55VS8 KA55VS2 KA55VS9 Table 6. Remote Operation and Indication; Factory-Installed Description Three-stage auxiliary switch Catalog Number KA55VSM3 290-25-3

Technical Data 290-25 VSA20B power circuit breaker Circuit breaker features and detailed description THREADED STUD TERMINALS 1 1 / 4-12UNF WEATHERPROOF OPERATOR CABINET provision for padlocking; window to view contact position indicator. VACUUM INTERRUPTER ASSEMBLY permits convenient interrupter inspection and replacement. STANDARD FRAME leg extensions are available for substation use. BUSHINGS wet-process porcelain; can be field replaced. LIFTING EYES at four corners enable balanced lifting for easy installation. BUSHING LEAD silverplated copper for ample current carrying capacity. INTERRUPTER SUPPORTS epoxy-fiberglass; provide mechanical and electrical strength. Figure 1. Type VSA20B air-insulated vacuum circuit breaker with inspection cover removed. Circuit breaker VSA20B circuit breakers feature vacuum interruption with air insulation and low-voltage motor operation. VSA20B circuit breakers are designed for circuit protection on systems operating through 14.4 kv. Because of the large selection of trip ratings and the flexibility provided by Eaton's Cooper Power Systems electronic controls, VSA20B circuit breakers can be applied to meet a wide variety of requirements. The vacuum interrupters in VSA20B circuit breakers provide reliable, shock-free fault-current interruption with long interrupter life. The combination of vacuum interruption and air insulation provides longer maintenance intervals and lower maintenance costs than comparable oil-insulated circuit breakers. Vacuum interruption also provides greater safety for indoor applications than arc interruption in oil. Closing and tripping operations of the circuit breaker are both powered by springs. The motor operator loads the closing springs, which charge the opening springs during closing. An external 240 Vac source is required to supply power for the motor operator and the cabinet heaters. The 240 Vac supply is not required to trip the circuit breaker. Fault currents are sensed by 2000:1-ratio bushing current transformers mounted in the circuit breaker, which provide sensing of both phase and ground (zero sequence) currents. They provide a continuous measurement of line current that is monitored by the circuit breaker control. When the control s programmed minimum trip level is exceeded, the control energizes the trip solenoid in the circuit breaker operating mechanism, opening the circuit breaker. Construction Eaton's Cooper Power Systems air-insulated vacuum circuit breakers offer extra-long service life and require minimal maintenance. Vacuum interrupter contacts, as well as the entire circuit breaker, require no service other than periodic maintenance inspection. Housings are fabricated of hot-rolled steel which is phosphatized to resist corrosion, then finished with polyester powder paint. Finish color is light gray, Munsell 5BG 7.0/0.4. Nonferrous alloys are used for mechanism linkages; stainless steel is used for shafts and hardware. Other steel parts are plated. Needle bearing or hard brass bushings are swaged into mechanism plates and linkages to provide long, trouble-free life for moving parts. All gears and latches are permanently lubricated; sealed ball bearings are used in the motor. For ease of inspection, all internal parts are readily accessible by removing an inspection panel on either side of the circuit breaker. Vacuum interrupters are mounted independently of the bushings. The bushing rods clamp to a current transfer member of the interrupter mounting assembly. Therefore, the bushings can be replaced quickly and easily without disturbing the interrupter or requiring any interrupter adjustment. Insulating supports for the three interrupters are made of filamentwound glass epoxy for high electrical and mechanical strength and moisture resistance. 290-25-4

VSA20B power circuit breaker Technical Data 290-25 Figure 3. Vacuum interrupter assembly. Cabinet heaters are provided in both the operator mechanism cabinet and the interrupter mechanism cabinet. The heaters are supplied from the 240-Vac auxiliary power source and are connected through a DPST on-off toggle switch and one amp fuses. The mechanism cabinet heater operates at 57 watts. The enclosure heaters operate at 115 watts total. Motor operation VSA20B air-insulated, vacuum circuit breakers employ a 240 Vac, motor-driven operating mechanism to charge closing and opening springs. Tripping Circuit breaker tripping employs stored spring energy. When line current exceeds the programmed minimum-trip value, in one or more phases, the control energizes a trip solenoid in the operating mechanism. The solenoid trips a latch which releases a spring-loaded toggle assembly, opening the circuit breaker contacts and a switch which interrupts the 24-volt signal from the control. Maximum clearing time is 2 1 ¼2 cycles. Tripping, because it employs stored spring energy released by a 24-volt signal from the control, will occur even if the 240-volt supply is lost. Closing Closing energy, as well as the force to charge the opening springs, is supplied by the motor operating mechanism, through motor-loaded closing springs. A 240 Vac motor charges the closing springs through a multi-stage gear drive. When 240 Vac is present, the motor is automatically operated to keep the closing springs in a charged state. To close the circuit breaker, the control initiates a signal which energizes a solenoid in the circuit breaker operating mechanism. Once actuated, the solenoid releases the closing springs, which close the vacuum interrupters and charge the opening springs. Stored energy provides multiple operations Should the circuit breaker lose 240 Vac motor supply voltage while the closing spring is charged and contacts are closed, an Open- Close-Open sequence remains stored in the circuit breaker operating mechanism. If the circuit breaker trips under these conditions, the stored closing operation allows an immediate reclosing, if required. After such a closing, one additional trip operation then remains stored. Once closed, the circuit breaker always contains energy for at least one trip operation. CONTACT POSITION INDICATOR linked to main operating shaft; visible through window in operator cabinet. DRIVE MOTOR 240 Vac operates closing mechanism; needs no lubrication. SPRING CHARGE INDICATOR linked to closing springs; for indication of stored energy operation in event of loss of low voltage motor supply. MANUAL CLOSE LEVER permits manual closing of the circuit breaker. MANUAL CLOSE PULLRING permits manual closing of the circuit breaker. AUXILIARY SWITCH (accessory) is available to provide remote indication of circuit breaker contact position. MANUAL RESET-TRIP KNOB provides means for manual tripping; must be in RESET position to permit closing. OPERATOR CABINET HEATER control switch and fuse. MULTI-RATIO CT TERMINAL BOARD (accessory) provides convenient customer connection to the desired current transformer ratio. MANUAL TRIP PULLRING provides means for manual tripping. Figure 2. VSA20B circuit breaker operating mechanism components. 290-25-5

Technical Data 290-25 VSA20B power circuit breaker Manual operation A closed circuit breaker can be manually tripped from inside the operator cabinet, using the RESET-TRIP knob, or from outside the cabinet by pulling down the Manual Trip Pullring. When the circuit breaker is manually tripped, the closing circuit is opened to prevent reclosing. The circuit breaker can be manually restored to service by placing the RESET-TRIP knob at RESET and moving the manual control switch on the circuit breaker control to CLOSE. The manual control switch on the circuit breaker control panel can also be used for tripping. The circuit breaker can be manually closed by pulling down the Manual Close Pullring located under the operator cabinet. An emergency means is provided to manually close a VSA20B circuit breaker on a de-energized line in the absence of the 240 Vac power supply. A hand crank can be applied to the motor to charge the closing springs. Once charged, the closing springs can be released either from inside or from below the operator mechanism cabinet. As with electrical operations, the opening springs are charged by release of the closing springs, so even a manually closed unit has sufficient stored energy for a trip operation. Vacuum interrupters The high quality vacuum interrupters used in VSA20B circuit breakers are manufactured exclusively at Eaton's Cooper Power Systems Switchgear plant. Our vacuum interrupters are used worldwide in the industry s broadest line of fault protection and switching apparatus, where they have established a proven record of long term reliability. Vacuum interrupters provide fast, low energy arc interruption with long contact and interrupter life and low mechanical stress. With arc interruption taking place in a vacuum, contact and interrupter life are four times greater than with interruption in oil. At the same time, mechanical stress and wear on the mechanism is substantially reduced. Combined, these factors result in greatly reduced maintenance costs over the life of the circuit breaker. Vacuum interrupters from Eaton's Cooper Power Systems are designed with a metal-and-ceramic housing for maximum strength. The high-alumina ceramic used in our vacuum interrupters permits a high processing temperature to develop maximum purity of the assembly and is impervious to helium penetration. Metal end closures and the arcing chambers are of high-purity alloys to minimize contamination. Enclosed in the interrupter is a stationary and a moving contact assembly. The moving contact has a travel of 7/16 in., its shaft passing through a flexible bellows which maintains vacuum integrity. Figure 5. Form 4C microprocessor-based control. Contacts are made of a special non-welding alloy. Because even the smallest amount of internal contamination can significantly shorten a vacuum interrupter s life, a state-ofthe-art clean-room manufacturing facility is used for vacuum interrupter production. Special care is taken to avoid even minute contamination; whether it be from dust particles, machining oils, or human body salts. Choice of electronic circuit breaker controls The operation of a VSA20B circuit breaker is commanded by an electronic control from Eaton's Cooper Power Systems. We offer a choice of two controls that can be used in conjunction with these circuit breakers. This permits the user to select the control that best fits the requirements of each application. Form 4C microprocessor-based control The Form 4C microprocessor-based control, shown in Figure 6, incorporates computer technology to provide enhanced application versatility and ease of operation. The Form 4C primary source of power is 120 Vac or 240 Vac (customer supplied). All standard control operating parameters including phase- and ground-fault minimum trip levels, time-current curve selection, and sequence of circuit breaker operation are keyboard programmable. Simple keyboard sequences and dedicated function keys provide convenient programming and interrogation of the control s various operating parameters. A large LCD display provides control feedback during programming and interrogation and 10 front panel LCD indicators provide control and circuit breaker status, at a glance. A front panel data port is provided to permit temporary connection to a data reader for downloading control data files, or for temporary connection to a personal computer for uploading or downloading control programming information and stored data. Figure 4. Vacuum interrupters are used in VSA20B circuit breakers. 290-25-6

VSA20B power circuit breaker Technical Data 290-25 The control is equipped with 41 keyboard-selectable time-current curves which are interchangeable for either phase or ground. Each of the curves can be custom modified to provide almost unlimited coordination flexibility. The control provides a wide range of standard features, which include: supervisory operation, remote status indication, fault indication via LCD targets and counters, event recorder, circuit breaker duty monitor, demand metering, and load profile monitor. The microprocessor-based control can be equipped with an accessory supervisory input/output board to extend the supervisory operation capabilities of the control. A fiber optic digital communications accessory is also available for distribution automation applications. FXA microprocessor-based control The FXA microprocessor-based recloser control provide the operational intelligence for three-phase electronically controlled reclosers. The control is equipped with features that provide application flexibility, metering, and event recording. The FXA primary source of power is 120 Vac or 240 Vac (customer supplied). The FXA control makes use of a unique Microsoft Windows -based application to program and interrogate the controls. Connection to a computer is made via a front panel EIA232 port for easy customer access. The FXA control can be ordered with supervisory I/Os for remote operation (SCADA option). The control interface application makes it possible to upload operating parameters to the control as well as download present operating parameters from the control and collected data from the control data bases. Operating parameters and collected data can be saved to disk, for future reference or to provide system documentation. Figure 6. FXA microprocessor-based recloser control. 290-25-7

Technical Data 290-25 VSA20B power circuit breaker Ratings and Specifications Table 7. Voltage Ratings Maximum Design Voltage (kv) 15.5 Nominal Operating Voltage (kv) 2.4-14.4 Basic Insulation Level (BIL) (kv) 110 60 Hertz Withstand Voltage (kv) Dry, one minute 50 Wet, ten seconds 45 Max RIV at 1.0 MHz/9.41 kv (micro-volts) 100 Table 8. Current Ratings Continuous Current Rating (amps) 1,200 Symmetric Interrupting Current (amps) 20,000 Cable Charging Current (amps) 2 Magnetizing Current (amps) 42 Three-Second Current, Symmetric (amps) 20,000 Momentary Current, Asymmetric (amps) 32,000 Capacitive Switching, General Purpose, Isolated Bank (amps). 250 Table 9. Electrical Specifications Trip Solenoid: Operating voltage (Vdc) 24 Peak current (A) 12.2 Actuation time (cycles) 1.25 Close Solenoid: Operating voltage (Vdc) 24 Peak current (A) 15.5 Actuation time (cycles) 1.5 Spring Charging Motor: Standard Accessory Operating Voltage (Vac) 240 120 Voltage Range (Vac) 160-257 90-127 Maximum Current, RMS (A) 14 18 Steady State Current (A) 4.1 9 Motor Running Time (cycles) 40 40 Sensing Current Transformers 2000:1 Maximum Arcing Time (cycles) 1.0 Interrupting Time (cycles) 2.5 Table 10. Mechanical Life Open-Close, no load, operations 2500 290-25-8

VSA20B power circuit breaker Technical Data 290-25 Table 11. Bushing Specifications Bushing creepage distance (in.) 17 Arcing distance (in.) - phase to ground Arcing distance (in.) - phase to phase 11 7 3 ¼4 Table 12. Mechanical Specifications Operating Temperature ( C) Minimum -30 Maximum +40 Closing Mechanism Spring Operated Opening Mechanism Spring Operated Contact Gap (inches) 7/16 Close Contact Travel Time (cycles) 0.5 Open Contact Travel Time (cycles) 0.5 Allowable Contact Erosion (inches) 0.125 Opening Time (24 Vdc solenoid), signal to Contact Part (msec.) 25 Closing Time (24 Vdc solenoid), signal to Contact Make (msec.) 32 Table 13. Auxiliary Switch Interrupting Ratings Volts Inductive ac (amps) Non- Inductive ac (amps) Inductive dc (amps) 24 15.0 20.0 48 7.5 10.0 120 60 80 125 1.5 2.0 240 30 60 250 0.45 0.5 Non- Inductive dc (amps) 290-25-9

Technical Data 290-25 VSA20B power circuit breaker Dimensions and weights VSA20B 1-1/4-12 UNF THREADED STUD TERMINALS 62 3 /4 26" CLEARANCE REQUIRED FOR BUSHING REMOVAL 32-1 /2 14 3-7 /16 13 11 1 /4 11 3 /4 14 51 1 /2 14 50 62-3 /4 14 3 /4 DOOR OPEN 30 49 KNOCKOUTS (3) FOR 1" CONDUIT FITTING IN BOTTOM OF OPERATING CABINET 20 1 /4 4 SOURCE 10 1 /4 8 1 /4 Breaker Type Weight (lbs) VSA20B 740 *Add 25 lbs. for each accessory bushing current transformer. Figure 7. Outline dimensions for Type VSA20B circuit breaker. 290-25-10

VSA20B power circuit breaker Technical Data 290-25 STANDARD ELECTRONIC CONTROL CABINET MOUNTING BRACKETS: FRONT KA55VS2 KA55VS4 (DOUBLE-SIZE CONTROL CABINET) BACK KA55VS3 KA55VS5 (DOUBLE-SIZE CONTROL CABINET) FRONT OPTIONAL ARRANGEMENTS FOR MOUNTING ELECTRONIC CONTROL (FOR CLARITY, OPERATOR ON FRONT OF RECLOSER IS NOT SHOWN) A B C D E F VSA20B 30 1 /2 84 7 /8 39 1 /4 22 38 3 /4 49 1 /2 1 1 /4-12 UNF THREADED OPER. CAB. ELEC. CNTRL. CAB. B (AT MINIMUM HEIGHT) ADJUSTABLE 97 7 /8 TO 115 7 /8 IN 3" INCREMENTS 13 1 /2 C 18 STD. SIZE CAB. D DOUBLE-SIZE CAB. E STANDARD CABINET 34 3 /4 DBL. SIZE CAB. SUBSTATION MOUNTING FRAMES: VSA20B KA55VS8 ALTERNATE MOUNTING ELECTRONIC CONTROL (SEE DETAIL) GROUNDING CONNECTOR 2/0-250 MCM A 1 1 /4 1 1 /4 Breaker Type VSA20B 890 Weight (lbs) 1 1 /4 F 1-1 /4 3 / 4 DIA. HOLES FOR 5 / 8 ANCHOR BOLTS (4), NOT FURNISHED *Add 25 lbs. for each accessory bushing current transformer. Figure 8. Outline dimensions and weight for VSA20B circuit breaker with substation mounting frame accessory (weight shown is for circuit breaker and mounting frame extension only). 290-25-11

Technical Data 290-25 VSA20B power circuit breaker Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Cooper Power Systems Business 2300 Badger Drive Waukesha, WI 53188 United States Cooperpower.com 2014 Eaton All Rights Reserved Printed in USA Publication No. 290-25 May 2014 Eaton, Cooper Power Systems, UltraSIL, and Evolution, are valuable trademarks of Eaton in the U.S. and other countries. You are not permitted to use the these trademarks without the prior written consent of Eaton. IEEE is a registered trademark of the Institute of Electrical and Electronics Engineers, Inc. ANSI is a registered trademark of American National Standards Institute. NEMA is a registered trademark of the National Electrical Manufacturers Association. Microsoft and Windows are registered trademarks of Micorsoft. For Eaton s Cooper Power Systems VSA20B power circuit breaker product information call 1-877-277-4636 or visit:. 290-25-12

Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Cooper Power Systems Business 2300 Badger Drive Waukesha, WI 53186 United States CooperPower.com 2014 Eaton All Rights Reserved Printed in USA Eaton and Cooper Power Systems are valuable trademarks of Eaton in the U.S. and other countries. You are not permitted to use these trademarks without the prior written consent of Eaton. All other trademarks are property of their respective owners.