GHD Global Help Desk. HOISTING commissioning with ATV71 03/2010

Similar documents
Standard Drives A & D SD Application Note

Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module.

TRIPS AND FAULT FINDING

StepSERVO Tuning Guide

TYPICAL CONFIGURATIONS SD700 Pump Control Macro single VSD with Jockey Pump

VLT AutomationDrive for marine winch applications

DYNEO Synchronous motors with permanent magnets-drive Commissioning

Good Winding Starts the First 5 Seconds Part 2 Drives Clarence Klassen, P.Eng.

Inverter control of low speed Linear Induction Motors

TOSVERT VF-S11. V/F control functions

ALTIVAR 58 AC Drives

Application Note CTAN #234

LIFT INVERTER SERIES L1000V DE ES FR IT 1000V L1000V L1000V L1000V L1000V

RVS-AX Instruction Manual

TROUBLESHOOTING. Ecomat EASY / Girotec WRS Ecomat EASY H / Girotec WRS H V2.0

C2000 driving IM with TQC+PG

Overvoltage Suppression F7 Drive Software Technical Manual

HIDRA CRONO Controller VVVF Control Techniques Unidrive SP (Asynchronous motors)

VFD E Series. Features

Yaskawa AC Drive L1000A Supplement to the L1000A Technical Manual No. SIEP C , SIEP C , and SIEP C

Technical Explanation for Inverters

Motor parameters setting. Motor Control Parameters. These motor parameters below are needed to set:

Código de rotor bloqueado Rotor bloqueado, Letra de código. Rotor bloqueado, Letra de código

Technical Information

Product Manual (Revision A, 8/2015) Original Instructions. ProAct II Digital Speed Control System. Technical Supplement

TROUBLESHOOTING TP. Index

SP4 DOCUMENTATION. 1. SP4 Reference manual SP4 console.

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

CRANE FUNCTION MANUAL. FR-A (0.4K) to 04750(90K)-CRN FR-A (0.4K) to 06830(280K)-CRN FR-A (315K) to 12120(500K)-CRN

Frame size R2, IP20 / NEMA 1

MAGPOWR Spyder-Plus-S1 Tension Control

Technical Guide No. 7. Dimensioning of a Drive system

UNIT 7: STEPPER MOTORS

APPLICATION NOTES VALVE CHECKER M

USER INSTRUCTION FOR PROGRAMMING INVERTER FUJI FRENIC LIFT

Tuning the System. I. Introduction to Tuning II. Understanding System Response III. Control Scheme Theory IV. BCU Settings and Parameter Ranges

Tension Control Inverter

APPLICATION NOTE

Automatic control. of the doors. 99 VF Evolution

Quick Start Guide of CV50- ControlVIT Series

Troubleshooting. YASKAWA ELECTRIC SIEP C D YASKAWA AC Drive A1000 Technical Manual 301

ADJUSTABLE FREQUENCY CRANE CONTROLS

Application Note: SyMAX Permanent Magnet Motor Simple Startup Procedure

APPLICATION GUIDE. Pure easiness for a wide range of applications ACS580 general purpose drives

FLL Workshop 1 Beginning FLL Programming. Patrick R. Michaud University of Texas at Dallas September 8, 2016

Motor Tuning Instructions

Appendix A: Motion Control Theory

Standard VVMC-1000 or VFMC-1000 controls, dispatched by an M3 Group System, allow group configurations with 64 landings and as many as 12 cars.

1-3 RAMP AND TORQUE BOOST EXERCISE OBJECTIVE

1. An inverter can be programmed to stop an AC motor quickly by enabling

Exercise 6. Three-Phase AC Power Control EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to three-phase ac power control

TCwin AND THE STC THROTTLE CONTROLLER... 3 INSTALLATION... 3 SOFTWARE INSTALLATION... 3 DEFINITION OF TERMS... 4 MAP EDITING KEYS... 4 DIAGNOSTICS...

Merih DDCA60 Operation and User Manual I Merih Asansör A.Ş.

1. WARNINGS CAUTION BEFORE FIRST USE GENERAL NOTE. Merih DDCA60 Operation and User Manual I Merih Asansör A.Ş.

CI-tronic Soft Start Motor Controller Type MCI 25B with Brake

Unit Protection System for Pumped-Storage Power Stations

Servo and Proportional Valves

CPW Current Programmed Winder for the 890. Application Handbook. Copyright 2005 by Parker SSD Drives, Inc.

user's manual nx frequency converters brake resistors

SDC,Inc. SCR-Regenerative Ac Drive

Utilizing Kollmorgen Goldline Series Servo Motors with the AKD Drive

User Manual. V6/V5 T T8 Tension Control Inverter

SE-3SCR-LM MANUAL MOTOR LOAD MANAGER

Application Description

Wheeled Locomotion. Geared Drive Vs. Direct Drive. Driving DC motors. Stepper motors. Open-loop and Closed-loop Control

Instruction manual with V3 motor

5001TCP SPEED CONTROLLER

Electronic Ballast EVG 2000-T

Fusesaver specification form

vacon nx ac drives brake resistors user manual

ALTIVAR 18 AC Drives. File 8805

General Purpose Permanent Magnet Motor Drive without Speed and Position Sensor

BG45 BG65S BG75 Axial Parallel Axial Parallel Axial Parallel CASM-32 (LS/BS/BN) X X CASM-40 (LS/BS/BN) X X X X CASM-63 (LS/BN/BF) X X

THE COMPLETE SOLUTION FOR STARTING AND STOPPING AC MOTORS. MCD 3000 Soft starter

RVS-DN Digital Reduced Voltage Motor Starter

Parker AC10 Frequency Inverter (to 22kW) Easy Start Guide

Silvertel. Ag Features. Multi-Stage Charging. Battery Reversal Protection. Reduced Power Consumption. Wide DC or AC Input Voltage Range

Loadcell Tension Control

Measurement and Analysis of the Operation of a Single-Phase Induction Motor

Understand how soft starters operate.

Principles of iers (intelligent

MCW Application Notes 24 th August 2017

MDC Series

FUJI FRENIC INVERTER USER GUIDE

TTT802 Gearshift Controller, Part # R1N-S (Standard), -P (Paddleshift)

Configuration IN THIS CHAPTER 23

Bistable Rotary Solenoid

690+ Series Integrator

Installation & Operation Manual

Kelly HSR Series Motor Controller with Regen User s Manual V 3.3. Kelly HSR Opto-Isolated Series Motor Controller with Regen.

Application Note 5283

Ramp Profile Hardware Implementation. User Guide

GRUNDFOS INSTRUCTIONS. Control HVAC. Installation and operating instructions. Other languages. net.grundfos.com/qr/i/

INTELLIGENT FLANGE STRÖTER. Magnetic pulse generator

SECTION MOTOR CONTROL

ABS. Prof. R.G. Longoria Spring v. 1. ME 379M/397 Vehicle System Dynamics and Control

ESD5500E Series Speed Control Unit

VFD - Mitsubishi. VFD Manuals. Mitsubishi D700 VFD Installation. Mitsubishi FR-D700 VFD User Manual. Mitsubishi D700 Parallel Braking Resistors

For motors controlled

RVS-DX Digital Reduced Voltage Motor Starter

Transcription:

GHD Global Help Desk HOISTING commissioning with ATV71 03/2010

Table of contents 1. Presentation...5 2. Starting procedure ATV71 in Open Loop...6 2.1. Motor data...6 2.2. I/O configuration...7 2.3. Optimisation of speed loop...7 2.4. Brake sequence optimization...9 2.4.1. Adjustment of start... 9 2.4.1.1 Adjustment of the Brake Release time (BRT)...10 2.4.1.2 Adjustment of brake release current (IBR)...12 2.4.2. Adjustment of stop...14 2.4.2.1 Adjustment of brake engage time (BET)...14 2.4.2.2 Adjustment of brake engage delay (TBE)...16 2.5. Motor slipping optimization...16 2.5.1. Method to adjust the nominal motor slip: speed measurement...17 2.5.2. Another method to adjust the nominal motor slip: time measurement...17 3. Starting procedure ATV71 in Close Loop...18 3.1. Motor data...18 3.2. I/O configuration...19 3.2.1. Ensure the easiness of braking setting...19 3.2.2. Define the motor feedbacks...19 3.3. Optimization of speed loop...20 3.4. Brake sequence optimization...21 3.4.1. Adjustment of start...22 3.4.1.1 Adjustment of the Brake Release time (BRT)...23 3.4.1.2 Adjustment of brake release current (IBR)...24 Version : 00 of 01.03.2010 Page : 2/30

3.4.2. Adjustment of stop...25 3.4.2.1 Adjustment of brake engage time (BET)...25 3.4.2.2 Adjustment of brake engage delay (TBE)...27 4. Annexe 1: Load measurement...28 5. Annexe 2: Table of known issues...30 Version : 00 of 01.03.2010 Page : 3/30

Pictograms Important information or caution. Computation or calculation. Purpose of the chapter or paragraph. Additional information or remark. Definition type information. Clever idea (astuteness). Version : 00 of 01.03.2010 Page : 4/30

1. Presentation This document provides additional information and must be used in conjunction with the ATV71 user manuals. In this document, all the directives for the correct installation have not been considered; this is the responsibility of the installer of the product. Definitions and abbreviations: BEN: Brake engine frequency BET: Brake engage time BFR: Standard motor frequency BRT: Brake release time FRO: Frequency reference FRS: Rated motor frequency IBR: Brake release time ITH: Motor thermal current MMF: Measured output frequency NCR: Rated motor current NPR: Rated motor power NSL: Nominal motor slip NSP: Rated motor speed SIT: Speed time integral SMMF: Unfiltered measured motor speed SOTR: Motor torque SPG: Speed proportional gain SRFR: Motor frequency TBE: Adjustment of brake engage delay TFR: Maximum frequency UNS: Rated motor voltage Version : 00 of 01.03.2010 Page : 5/30

2. Starting procedure ATV71 in Open Loop This procedure has to be used for asynchronous motor in open loop. What is important to keep in mind is that in open loop, there is no torque at 0 Hz. The VSD cannot hold the load when the frequency is under the slip of motor. In basic access level, the VSD sets the low speed to the rated motor slip. To make the settings of product become easier, we recommend you to use the hoisting macro-configuration in SIMPLY START menu. The first step is to perform the adjustment of setting without load. Then, when you find a good working, you can perform some tests at full load to optimize your settings. 2.1. Motor data In 1.1 Simply start menu: this step ensures the optimum motor control. For hoisting application, the motor control type is voltage flux vector control (SVC V). You must set the standard motor frequency (BFR), the rated motor power (NPR), the rated motor voltage (UNS), the rated motor current (NCR), the rated motor frequency (FRS), the rated motor speed (NSP), the maximum frequency (TFR) and the motor thermal current (ITH = NCR). About the power, if there is no information you have to calculate it with the formula below: NPR = UNS NCR 3 0.85 cosϕ Version : 00 of 01.03.2010 Page : 6/30

The Auto tuning must be performed with a cold motor (one day off). Set the Macro configuration to: CFG = Hoisting. 2.2. I/O configuration This step ensures the easiness of braking setting. Now, you can perform the first movement of the hook to check the sense of rotation. This is important for the setting of brake control: LI1 is Forward ==> the hook must go UP LI2 is Reverse ==> the hook must go DOWN If the sense of rotation is not correct, you can change it by the output phase rotation in Motor control menu: PHR = ACB (factory setting: PHR = ABC). The speed reference can be given via analogical input or via logical input by using preset speed function. In most of hoisting application, the mode of motor is generator when the load goes down and it is motor when the load goes up. When the mode of motor is generator, the dissipation of this generator energy must be done through resistor or network braking unit. 2.3. Optimisation of speed loop In 1.3 Settings menu: this step reduces the vibration and reduces the overshoot or the undershoot. Most of case, the factory settings of speed loop are sufficient. But the factory setting values are corresponding to an application inertia which equals to 3 times the motor inertia. For hoisting, there is a gear box after the motor, so, the application inertia on the motor shaft is similar to the motor inertia. In this case with a standard motor, the SPG can be set between 20 and 40, and SIT can be set between 100 and 150: Speed proportional gain = SPG = 40%; When you increase SPG, you reduce the speed overshoot due to a torque jerk. But, if you increase too much SPG, you saturate the motor, and you can see it with lots of oscillation on the torque. When you decrease SPG, you reduce the saturation of motor but you increase the overshoot due to a torque jerk. Speed time integral = SIT = 100%; Version : 00 of 01.03.2010 Page : 7/30

When you increase SIT, you reduce the low oscillation of torque. But the speed overshoot becomes higher. When you decrease SIT, you reduce the speed overshoot due a torque jerk. But, the motor torque starts to oscillate. The following curves correspond to the speed reference (FRO in red) and the motor speed (SRFR in green) and the motor torque (SOTR in blue): If there is lots of oscillation on the torque waveform: If there is an overshoot on the speed like that: Then, decrease SPG. If the speed waveform looks like that: Then, decrease SIT. If the speed waveform looks like that: Then, SPG is OK. If there is an overshoot on the speed like that: Then, SIT is OK. If the torque is oscillating like that: Then, increase SPG. Then, increase SIT. With the scope of PowerSuite V2.6, you can see frequency reference (FRO), the motor frequency (SRFR) and the motor torque (SOTR). Warning: A too much slack setting of speed loop can make the load slip without any detection from product! So you need to perform some tests at full load to check the speed loop setting. Version : 00 of 01.03.2010 Page : 8/30

2.4. Brake sequence optimization In 1.3 Application funct. menu: this step improves the start and stop of movement. The brake control consists in controlling the release and the engage of brake. Both phases have different goals: 2.4.1. Adjustment of start The delay between the command of brake (R2) and the mechanical opening of brake corresponds to the brake release time (BRT). During BRT, ATV71 must hold the load: for this, the brake impulse must be set to Yes (BIP = Yes) and the brake release I FW to the nominal motor current (factory setting of hoisting CFG: IBR = NCR). Version : 00 of 01.03.2010 Page : 9/30

2.4.1.1 Adjustment of the Brake Release time (BRT) Set BRT to more than necessary and gradually reduce it. You find the good value of BRT when the brake releases without allowing the rotor to move before following the acceleration ramp. At the real opening of brake, the shaft moves in up direction during BRT. You can see that the motor speed (in yellow) increases on the following curve. The real opening of brake is when the motor torque (SOTR in blue) is decreasing from the level of IBR: SOTR in blue, FRO in red, SRFR in yellow Version : 00 of 01.03.2010 Page : 10/30

On the same curve, you can find the value that you need to decrease in BRT. With cursor (period), the first cursor is on the start of decreasing of SOTR, and the second cursor is when the speed reference is different from 0 Hz: Here, BRT must be reduced by 0.25s. SOTR in blue, FRO in red, SRFR in yellow If BRT is too short, the motor torque (SOTR in blue) increase suddenly when the brake is really engaged: SOTR in blue, FRO in red, SRFR in yellow Version : 00 of 01.03.2010 Page : 11/30

Here, BRT is well set: SOTR in blue, FRO in red, SRFR in yellow SOTR is the link to the sign of motor speed. When the motor speed is near 0 Hz, you can have some points with the opposite sign like on this scope of SOTR. This is only due to the calculation of SOTR, the real motor torque seen by the drive is correct. 2.4.1.2 Adjustment of brake release current (IBR) With the IBR current, you adjust the torque current to hold the load during BRT time. So, for hoisting, you must adjust it to the torque that the motor requires to start at full load. The first setting is to adjust IBR to the rated motor current: IBR = NCR. After checking this value, you can adjust IBR to the real motor torque at full load. Version : 00 of 01.03.2010 Page : 12/30

SOTR in blue, FRO in red, SRFR in yellow By doing some tests at full load (after the adjustment of stop), you can adjust the IBR value for the full load. SOTR in blue, FRO in red, SRFR in yellow Here the IBR corresponds exactly to the load of motor. Version : 00 of 01.03.2010 Page : 13/30

2.4.2. Adjustment of stop When the VSD receive a stop order, the speed comes down following the deceleration ramp until the brake engage frequency (BEN) is reached. This output frequency is maintained during the brake engage time (BET). 2.4.2.1 Adjustment of brake engage time (BET) Set BET to more than necessary and gradually reduce it to a point where the current is cancelled just after the brake is engaged. SOTR in blue, FRO in red, SRFR in green Here BET is too long because the motor torque (in blue) increases up to limitation at the end of BET. There is this behaviour because the brake is really engaged and the ATV71 is still energizing the motor. On this example, BET must be reduced by 0.406s. Version : 00 of 01.03.2010 Page : 14/30

SOTR in blue, FRO in red, SRFR in green Then the motor torque does not increase at the end of BET. The good value of BET is when the motor current does not increase at the end of BET. Nota: If BET is too short, the load will slip a little bit, just after engaging the brake: Here, BET must be increased by 0.094s. SOTR in blue, FRO in red, SMMF in yellow Version : 00 of 01.03.2010 Page : 15/30

2.4.2.2 Adjustment of brake engage delay (TBE) When the motor speed reaches the brake engage frequency (BEN), the brake engage order is immediately given. To reduce this jerk, with TBE, you can stabilize the motor speed around BEN and then at the end of TBE, the drive gives the engage order. SOTR in blue, FRO in red, SRFR in green With a little value of TBE (here, TBE=0.3s), the engage of brake is really soft. 2.5. Motor slipping optimization The slip optimization is necessary if you need an accurate speed versus the load and a reactive regulation. It reduces the speed difference between no-load and full load operation. The ATV71 calculates the nominal motor slip (NSL) with the nominal motor speed (NSP) that you set before. The NSP parameter can be revised if the nominal speed indicated on the motor rating plate is not reliable. If you do not want to change the rated motor speed NSP, the other way to adjust motor slip is to modify the slip compensation SLP parameter. This parameter is a coefficient applied to the nominal motor slip NSL. If SLP is too low, the motor never reach the reference speed. If SLP is too high, the motor is overcompensated and becomes unstable. Version : 00 of 01.03.2010 Page : 16/30

2.5.1. Method to adjust the nominal motor slip: speed measurement Put SLP = 0 Run the motor at the nominal motor frequency FRS with nominal load (==> the motor current LCR is equal to the nominal motor current NCR) Measure the real speed with a tachymeter Set the measured value in NSP, set SLP to 100% 2.5.2. Another method to adjust the nominal motor slip: time measurement Measure the time in going down with the nominal load Measure the time in going up with the nominal load If the time difference is less than 5%, your setting is good If the time down is higher than the time up, you must increase SLP Version : 00 of 01.03.2010 Page : 17/30

3. Starting procedure ATV71 in Close Loop This procedure has to be used for asynchronous motor in close loop. What is important to keep in mind is that in close loop, you can have some torque at 0 Hz. To make the settings of product become easier, we recommend you to use the hoisting macro-configuration in SIMPLY START menu. The first step is to perform the adjustment of setting without load in open loop. Then, when you find a good working, you can perform some tests in close loop to check the settings. After, you need to perform some tests at full load to optimize your settings. 3.1. Motor data In 1.3 Simply start menu: this step ensures the optimum motor control. Before working in close loop, we must ensure that the working is correct in open loop. The following is to check the setting of speed loop, of brake control, and to check the encoder. So at first, the motor control type is voltage flux vector control (SVC V). You must set the standard motor frequency (BFR), the rated motor power (NPR), the rated motor voltage (UNS), the rated motor current (NCR), the rated motor frequency (FRS), the rated motor speed (NSP), the maximum frequency (TFR) and the motor thermal current (ITH = NCR). Version : 00 of 01.03.2010 Page : 18/30

About the power, if there is no any information you have to calculate it with the formula below: NPR = UNS NCR 3 0.85 cosϕ Then, the Auto tuning must be performed with a cold motor (one day off). Set the Macro configuration to: CFG = Hoisting. 3.2. I/O configuration 3.2.1. Ensure the easiness of braking setting Now, you can perform the first movement of the hook to check the sense of rotation. This is important for the setting of brake control: LI1 is Forward ==> the hook must go UP LI2 is Reverse ==> the hook must go DOWN If the sense of rotation is not correct, you can change it by the output phase rotation in Motor control menu: PHR = ACB (factory setting: PHR = ABC). The speed reference can be given via analogical input or via logical input by using preset speed function. In most of hoisting application, the motor mode is generator when the load goes down or it is motor when the load goes up. When the motor mode is generator, the dissipation of this generator energy must be done through resistor or network braking unit. 3.2.2. Define the motor feedbacks Choose the encoder type (ENS), according to the feedback and the option board. Set the encoder usage to feedback monitoring: ENU = SEC. With this setting, you will be able to see the measured output frequency (MMF) in the monitoring menu. For incremental encoder, the number of pulse (PGI) must be set correctly. If not, the MMF will be different from the reference (FRH). Version : 00 of 01.03.2010 Page : 19/30

Then, without load, you can perform the encoder check to validate the encoder coupling (with low speed: 15Hz). You can find the encoder check procedure in the motor control menu (page 77). If the test is bad, you can try to change the wiring of encoder (inverse A, A/ by B, B/). If the test is again bad, you have to verify your wiring encoder (supply, signals ). When the encoder test is good you can work in close loop, Ctt parameter to FVC. 3.3. Optimization of speed loop In 1.3 Settings menu: this step reduces the vibration and reduces the overshoot or the undershoot. Most of case, the factory settings of speed loop are sufficient. But, the factory setting values are corresponding to an application inertia which equals to 3 times the motor inertia. For hoisting, there is a gear box after the motor, so, the application inertia on the motor shaft is similar to the motor inertia. In this case with a standard motor, the SPG can be set between 20 and 40, and SIT can be set between 100 and 150: Speed proportional gain = SPG = 40%; When you increase SPG, you reduce the speed overshoot due to a torque jerk. But, if you increase too much SPG, the speed loop becomes unstable, and you create some oscillation on the speed. You can also see it with lots of oscillation on the torque. When you decrease SPG, you reduce the instability of motor speed but you increase the overshoot due to a torque jerk. Speed time integral = SIT = 100%; When you increase SIT, you reduce the low oscillation of torque. But the speed loop reaction becomes longer and longer, so the speed overshoot becomes higher. When you decrease SIT, you reduce the speed overshoot due a torque jerk. But, the speed loop becomes unstable and it starts to oscillate. Version : 00 of 01.03.2010 Page : 20/30

The following curves correspond to the speed reference (FRO in red) and the motor speed (SRFR in green) and the motor torque (SOTR in blue): If the speed oscillates like that: If the speed waveform looks like that: Then, decrease SPG. Then, decrease SIT. If the speed waveform looks like that: If the speed waveform looks like that: Then, SPG is OK. If there is a big overshoot like that: Then, SIT is OK. If the speed waveform looks like that: Then, increase SPG. Then, increase SIT. With the scope of Power Suite V2.6, you can see frequency reference (FRO), the motor frequency (SRFR) and the motor torque (SOTR). Warning: A too much slack setting of speed loop can make the load slip (ANF fault)! So you need to perform some tests at full load to check the speed loop setting. 3.4. Brake sequence optimization In 1.3 Application funct. menu: this step improves the start and stop of movement. Version : 00 of 01.03.2010 Page : 21/30

The brake control consists in controlling the release and the engage of brake. Both phases have different goals: in close loop, the main advantage is that the drive can regulate 0 speed. So, it means that the release and the engage of the brake are done at 0 Hz (instead of slip frequency in open loop). 3.4.1. Adjustment of start The delay between the command of brake (R2) and the mechanical opening of brake corresponds to the brake release time (BRT). During BRT, ATV71 must hold the load: for this, the brake impulse must be set to Yes (BIP = Yes) and the brake release I FW to the nominal motor current (factory setting of hoisting CFG: IBR = NCR). Version : 00 of 01.03.2010 Page : 22/30

3.4.1.1 Adjustment of the Brake Release time (BRT) Set BRT to more than necessary and gradually reduce it. You find the good value of BRT when the brake releases without allowing the rotor to move before following the acceleration ramp. At the real opening of brake, the shaft moves in up direction during BRT. You can see that the motor speed (in green) increases on the following curve. The real opening of brake is when the motor torque (SOTR in blue) is decreasing from the level of IBR. SOTR in blue, FRO in red, SRFR in green On this curve, you can find the value that you need to decrease in BRT. With cursor (period), the first cursor is on the start of decreasing of SOTR, and the second cursor is when the speed reference is different from 0Hz: Here, BRT must be reduced by 0.393s. If BRT is too short, the motor torque (SOTR in blue) increase when the brake is really engaged: SOTR in blue, FRO in red, SRFR in yellow Version : 00 of 01.03.2010 Page : 23/30

Another way to see it is that the motor speed stays at 0 Hz after BRT (with SMMF: unfiltered measured motor speed). Here, BRT is well set: SOTR in blue, FRO in red, SRFR in green 3.4.1.2 Adjustment of brake release current (IBR) With the IBR current, you adjust the torque current to hold the load during BRT time. So, for hoisting, you must adjust it to the torque that the motor requires to start at full load. The first setting is to adjust IBR to the rated motor current: IBR = NCR. After verifying this value, you can adjust IBR to the real motor torque at full load. SOTR in blue, FRO in red, SRFR in green By doing some test at full load (after the adjustment of stop), you can adjust IBR value for the full load. Version : 00 of 01.03.2010 Page : 24/30

SOTR in blue, FRO in red, SRFR in green Here IBR corresponds exactly to the load of motor. 3.4.2. Adjustment of stop When the VSD receive a stop order, the speed comes down following the deceleration ramp until the 0 Hz is reached. The product holds the load at 0 Hz during the brake engage time (BET). 3.4.2.1 Adjustment of brake engage time (BET) Set BET to more than necessary and gradually reduce it to a point where the current is cancelled just after the brake is engaged. SOTR in blue, FRO in red, SMMF in green Here BET is too long because the motor speed stays at 0 Hz during a long time. It can be reduced by 0.39s. Version : 00 of 01.03.2010 Page : 25/30

Nota: If BET is too short, the load will slip a little bit, just after engaging the brake: SOTR in blue, FRO in red, SMMF in green Here, you can see that the load is slipping on SMMF measurement. This is because BET is too short and the brake is not mechanically engaged at the end of BET. So, BET must be increased by 0.06s. SOTR in blue, FRO in red, SMMF in green The good value of BET is when the load does not slip at the end of BET. Version : 00 of 01.03.2010 Page : 26/30

3.4.2.2 Adjustment of brake engage delay (TBE) For a smother stop, you can set a value for TBE to stabilize the motor speed before engaging the brake: SOTR in blue, FRO in red, SMMF in green Here, the value of TBE is good because the speed is really stabilized before engaging the brake. Version : 00 of 01.03.2010 Page : 27/30

4. Annexe 1: Load measurement For hoisting application, the brake release current (IBR) must be adjusted to hold the full load. Depending on application, the load can change (empty or half load) and the setting of IBR for the full load generates some movement in up direction during the brake release time (BRT). This behaviour can be avoided by the use of an external weight sensor that measures the load. With this feedback, the drive adjusts automatically the value of IBR for the torque that the actual load of motor needs. To commission weights measurement function we have to find the coordinates of two points: (LP1; CP1) and (LP2; CP2). Increase BRT to 4 s and activate the external weight measurement: PES = Aix. Then set both coordinates: (LP1; CP1) = (25%; NCR) and (LP2; CP2) = (100%; NCR). Verify the working of the weight sensor: check that the value of analogical input in the monitoring menu is different from 0 V (or 4 ma) or different from 10 V (or 20 ma). Nota: For the two following points, be careful because the load goes up at the brake release frequency. For the first coordinates (LP1; CP1), with a weak load: Calculate the ratio of load to set it in LP1 = actual weight / maximum weight. Read also the value of analogical input in the monitoring menu. Version : 00 of 01.03.2010 Page : 28/30

Perform several starts and reduce gradually the value of CP1 up to avoid any shock at the mechanical release of brake. For the second coordinates (LP2; CP2), with another load (full load or more than the first one): Repeat the same manipulation for CP2 and LP2 than for CP1 and LP1. When you are in close loop, to find the good value for CP1 and CP2, you do not need to increase BRT to 4 s. You just need to set the speed reference to 0 Hz and then after BRT, read the motor current value (LCR in A). Perform no load and full load tests, to check that there is no shock when the brake is open no matter what the load is. At the end of test, decrease BRT to the value that you find during the adjustment of the brake control function. Version : 00 of 01.03.2010 Page : 29/30

5. Annexe 2: Table of known issues Problem Condition Cause Solution The load is slipping after giving a stop order In open loop with HHP product Bad result of auto tuning with V1.1 product version Upgrade the product version with V1.2 or higher Vibration on the motor speed Only in close loop, No vibration in open loop. Strong mechanical coupling of encoder to the motor shaft Use another mechanical coupling of encoder SCF1 nuisance tripping HHP product Motor saturation Read the application note: SCF1fault motor saturation.pdf Version : 00 of 01.03.2010 Page : 30/30