Product Data. 48TC Gas Heat/Electric Cooling Packaged Rooftop 3to12.5NominalTons. (Unit shown with optional economizer.) C08514

Similar documents
Product Data. 48TC Gas Heat/Electric Cooling Packaged Rooftop 3to15NominalTons. (Unit shown with optional economizer.) C08514

Product Data 558J COOLING ONLY/ELECTRIC HEAT PACKAGED ROOFTOP 3 TO 15 TONS. (Unit shown with optional louvered hail guard.) C08515

Product Data KUWAIT SERIES

50TC 50 Hz Packaged Rooftop Electric Cooling Units to 42.5 kw 5to12.5NominalTons. Product Data C the environmentally sound refrigerant

48TC Gas Heat/Electric Cooling Packaged Rooftop 3to15NominalTons. Product Data C08613

ASHRAE 90.1 COMPLIANT PACKAGED ROOFTOP ELECTRIC COOLING UNITS, R 410A, TONS 3 Phase, 50 Hz. BUILT TO LAST, EASY TO INSTALL AND SERVICE

Product Data. 50TCQ Packaged Heat Pump 3to12.5NominalTons C08613

Product Data. 50TCQ Packaged Heat Pump 3to12.5NominalTons C08613

Product Data. 50HC High Efficient Cooling Only/Electric Heat Packaged Rooftop 3to12.5NominalTons C10222

48TC Gas Heat/Electric Cooling Packaged Rooftop 3to15NominalTons. Product Data C the environmentally sound refrigerant

548J PACKAGE HEAT PUMP 3 TO 12.5 NOMINAL TONS. Product Data C the environmentally sound refrigerant

Product Data. 48HC Gas Heat/Electric Cooling Packaged Rooftop 3to10NominalTons. Catalog No:48HC---03PD C10222

50TC Cooling Only/Electric Heat Packaged Rooftop 3to15NominalTons. Product Data C the environmentally sound refrigerant

Product Data. 50HCQ High Efficient Packaged Rooftop Heat Pump Units 3to10Tons C10222

Product Data. 50HCQ High Efficiency Packaged Rooftop Heat Pump Units 3to10Tons C Except 04 models in single phase

Product Data. (Unit shown with optional louvered hail guard)

580J GAS HEAT/ELECTRIC COOLING PACKAGED ROOFTOOP 3 TO 15 NOMINAL TONS. Product Data C (Unit shown with louvered hail guard.)

48LC WeatherExpert Series Ultra High Efficient Single Package Rooftop and Single Zone VAV Gas Heating/Electric Cooling Sizes with Puron

COOLING, R 410A SINGLE PACKAGE ROOFTOP 5 10 TONS

High Cap. (Btuh) HSPF COP

Product Data. 50TC Cooling Only/Electric Heat Packaged Rooftop 15 to 27.5 Nominal Tons. (Unit shown with economizer and power exhaust.

PERFORMANCE, INNOVATION, RELIABILITY

50TC Cooling Only/Electric Heat Packaged Rooftop 3to15NominalTons. Product Data C the environmentally sound refrigerant

50HC High Efficiency Cooling Only/Electric Heat Packaged Rooftop 3 to 12.5 Nominal Tons. Product Data C the environmentally sound refrigerant

Product Data. 50HC High Efficiency Cooling Only/Electric Heat Packaged Rooftop 15 to 25 Nominal Tons

RHS. Product Specifications. PACKAGE HEAT PUMP UNIT R 410A SINGLE PACKAGE ROOFTOP TONS (1 & 3 Phase)

48HC High Efficiency Gas Heat/Electric Cooling Packaged Rooftop 3 to 12.5 Nominal Tons. Product Data C the environmentally sound refrigerant

PACKAGE GAS HEATING/ELECTRIC COOLING, R- 410A SINGLE PACKAGE ROOFTOP 3-15 TONS (1 & 3- Phase)

ASHRAE 90.1 COMPLIANT PACKAGED ROOFTOP ELECTRIC COOLING UNITS, R 410A, TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

RAS. Product Specifications. ELECTRIC COOLING, R 410A SINGLE PACKAGE ROOFTOP 3 15 TONS (1 & 3 Phase) BUILT TO LAST, EASY TO INSTALL AND SERVICE

HIGH EFFICIENCY PACKAGE GAS HEATING/ELECTRIC COOLING, R 410A SINGLE PACKAGE ROOFTOP TONS

50TC Cooling Only/Electric Heat Packaged Rooftop 3to15NominalTons. Product Data C the environmentally sound refrigerant

RHS. Product Specifications. PACKAGE HEAT PUMP UNIT R 410A SINGLE PACKAGE ROOFTOP TONS (1 & 3 Phase)

Product Data. 48LC WeatherExpert R Series

50HC High Efficiency Cooling Only/Electric Heat Packaged Rooftop 3to12.5NominalTons. Product Data C10222

Unit Dimensions UNIT. Unit Dimensions UNIT

EFFICIENCY PACKAGE ELECTRIC COOLING, R 410A SINGLE PACKAGE ROOFTOP TONS

HIGH EFFICIENCY PACKAGE ELECTRIC COOLING, R 410A SINGLE PACKAGE ROOFTOP TONS [1 & 3 Phase] BUILT TO LAST, EASY TO INSTALL AND SERVICE

PACKAGE GAS HEATING/ELECTRIC COOLING, R 410A SINGLE PACKAGE ROOFTOP 3 15 TONS (1 & 3 Phase) BUILT TO LAST, EASY TO INSTALL AND SERVICE

RAS Product Specifications

GAS HEATING/ELECTRIC COOLING, R 410A SINGLE PACKAGE ROOFTOP 3 15 TONS

PACKAGE GAS HEATING/ELECTRIC COOLING, R 410A SINGLE PACKAGE ROOFTOP TONS (3 Phase) BUILT TO LAST, EASY TO INSTALL AND SERVICE

HIGH EFFICIENCY PACKAGE ELECTRIC COOLING, R 410A SINGLE PACKAGE ROOFTOP TONS

Advanced Product Data

GAS HEATING/ELECTRIC COOLING, R 410A SINGLE PACKAGE ROOFTOP 3 15 TONS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

PACKAGE GAS HEATING/ELECTRIC COOLING, R 410A SINGLE PACKAGE ROOFTOP TONS (1 & 3 Phase) BUILT TO LAST, EASY TO INSTALL AND SERVICE

Advanced Product Data

Operating Net Capacity BTU/h. Input BTU/h Efficiency. lbs (kg) PGR524040KGP* 23, ,000/26, /8 x 47 x 31-7/16

CAS. Product Specifications

PACKAGE GAS HEATING/ELECTRIC COOLING, R 410A SINGLE PACKAGE ROOFTOP 3 15 TONS (1 & 3 Phase) Unit Weight UNIT

PHR5. Product Specifications

R6GP Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6, 7½ and 10 Ton Packaged Gas/Electric Units, with R-410A WARRANTY

R6GN Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Gas/Electric Units with R-410A WARRANTY

S/T Ratio. Input BTU/h

COMMERCIAL SINGLE PACKAGE ROOFTOP UNITS GAS HEATING/ELECTRIC COOLING UNITS

Q6SP Series Rev A TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 7.5 and 10 Ton Packaged Electric Heat Pump Units with R-410A 11.

DESCRIPTION TECHNICAL GUIDE SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS D(CE, CG) 036, 048, 060 & YTG-A-0207

GR4GN Series TECHNICAL SPECIFICATIONS. Single Packaged Gas/Electric Units. GR4GN 10.1 EER Commercial System 7½ and 10 Ton Units FEATURES AND BENEFITS

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CAS. Product Specifications

38AUM Air Cooled Condensing Units 50Hz

Q6SP Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 7.5 and 10 Ton Packaged Electric Heat Pump Units with R-410A 11.

Product Data. Features/Benefits 50JS SINGLE-PACKAGED HEAT PUMP 50 HZ UNITS 7 TO 18 KW (2 TO 5 NOMINAL TONS)

Product Data. Fig. 1 - Unit 48VG -A and 48VG -B

COMMERCIAL ASHRAE EFFICIENT PACKAGE AIR CONDITIONER UNITS R 22 SINGLE PACKAGE ROOFTOP 6 25 TONS (3 Phase)

Product Data. Features/Benefits. OMNIZONE 50XCR06-24 Remote Air-Cooled Indoor Self-Contained Systems with PURON Refrigerant (R-410A)

PACKAGE AIR CONDITIONERS

CPH COMMERCIAL 7½- TO 10-TON SELF-CONTAINED PACKAGED HEAT PUMP

P6SP Series Rev A TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6, 7½ and 10 Ton Packaged Electric Cooling Units EER Commercial System Units

Product Data PH3Z 13 SEER SINGLE -PACKAGED HEAT PUMP SYSTEM WITH R -22 REFRIGERANT SINGLE AND THREE PHASE 2-5 NOMINAL TONS ( )

Product Data. Features/Benefits. Omnizone 50XCA06-14 Air-Cooled Indoor Self-Contained Systems with Puron Refrigerant (R-410A) 5 to 12 Nominal Tons

Sizes 156, 180. COOLING HEATING (High Temp) Unit Dimensions. COOLING HEATING (High/Low) Unit Dimensions

Product Data. Features/Benefits. 50TFF Single-Package Rooftop Units Electric Cooling with Electric Heat Option. 3 to 12.

SUNLINE 2000 SINGLE PACKAGE GAS / ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS DESCRIPTION FEATURES

Product Data FEATURES/BENEFITS. 575J 6 to 20 TONS HEAT PUMP OUTDOOR UNIT SPLIT SYSTEM with PURONr REFRIGERANT 60 Hz

GP4SN Series TECHNICAL SPECIFICATIONS. Single Packaged Electric Cooling Units. P4SN 10.3 EER Commercial System 7½ and 10 Ton Units

Q6SP Series Rev A TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 7.5 and 10 Ton Packaged Electric Heat Pump Units 11.0 EER

Models 542J, 548F, 549B, 549C SINGLE PACKAGE ROOFTOP

CPC Commercial. 15- & 20-Ton, Three-Phase Packaged Air Conditioner. 20-Ton Cooling Capacity: 240,000 BTU/h

GPG15 Series 80% AFUE. Single-Phase, Self-Contained. up to 15 SEER. Cooling Capacity: 23,200 56,500 BTU/h. Heating Capacity: 69, ,000 BTU/h

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS

TECHNICAL GUIDE DESCRIPTION SINGLE PACKAGE AIR CONDITIONERS AND SINGLE PACKAGE GAS/ELECTRIC UNITS PRELIMINARY DATA

Product Data. Features/Benefits. 50TFQ Single-Package Standard Efficiency Rooftop Heat Pump Units. 3 to 10 Nominal Tons

SINGLE PACKAGE ROOFTOP

CPG COMMERCIAL 5-TON SELF-CONTAINED PACKAGED GAS/ELECTRIC UNIT

COMMERCIAL HIGH EFFICIENCY PACKAGE AIR CONDITIONER UNITS R 22 SINGLE PACKAGE ROOFTOP 3 5 TONS (3 Phase 575 Volt)

14 SEER R -410A PACKAGE GAS / ELECTRIC UNIT 2 to 5 TON

Product Data. Features/Benefits. 50TJQ Single-Package Standard Efficiency Rooftop Heat Pump Units. 3 to 10 Nominal Tons

PCB COMMERCIAL SERIES

Product Data. Features/Benefits. 50SZ SINGLE-PACKAGED HEAT PUMP UNITS 2 to 5 Nominal Tons

CPG COMMERCIAL 10-TON SELF-CONTAINED PACKAGED GAS/ELECTRIC UNITS

R8HE Series Rev A. Single-Phase and Three-Phase TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

13 SEER PACKAGE GAS / ELECTRIC UNIT (3 Phase) 35 to 53 MBtuh

Product Data. 38AUZ/D 50 Hz Commercial Split Systems Air Conditioning Condensing Units 18.3 kw to 59.2 kw FEATURES/BENEFITS

Packaged Gas/Electric Rooftop Units

Product Data. Catalog No:48PM---04PD. Copyright 2010 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231

Packaged Gas/Electric Rooftop Units

EFFICIENCY 17 SEER TWO STAGE AIR CONDITIONER WITH OBSERVER

Transcription:

Gas Heat/Electric Cooling Packaged Rooftop 3to12.5NominalTons Product Data (Unit shown with optional economizer.) C08514 the environmentally sound refrigerant This product has been designed and manufactured to meet Energy Star criteria for energy efficiency. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow all manufacturer s refrigerant charging and air flow instructions. Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life.

TABLE OF CONTENTS PAGE FEATURES AND BENEFITS... 3 MODEL NUMBER NOMENCLATURE... 4 FACTORY OPTIONS AND/OR ACCESSORIES... 6 ARI COOLING RATING TABLES... 8 HEAT RATING TABLE... 9 SOUND PERFORMANCE TABLE... 10 PHYSICAL DATA... 12 CURBS & WEIGHTS DIMENSIONS... 16 APPLICATION DATA... 22 PAGE COOLING TABLES... 25 STATIC PRESSURE ADDERS... 35 FAN PERFORMANCE... 36 OUTDOOR AIR INTAKE & EXHAUST PERF... 48 ELECTRICAL INFORMATION... 49 MCA / MOCP... 53 TYPICAL WIRING DIAGRAMS... 57 SEQUENCE OF OPERATION... 61 GUIDE SPECIFICATIONS... 63 Your Carrier rooftop unit (RTU) was designed by customers for customers. With no-strip screw collars, handled access panels, and more we ve made your unit easy to install, easy to maintain and easy to use. Easy to install: All WeatherMakerr units are field-convertible to horizontal air flow; no special adapter curbs or kits are necessary. Convertible airflow design makes it easy to adjust to unexpected job-site complications. Lighter units make easy replacement. Carrier 3-12.5 ton rooftops fit on existing Carrier curbs dating back to 1989. Also, our large control box gives you room to work and room to mount Carrier accessory controls. Easy to maintain: Easy access handles by Carrier provide quick and easy access to all normally serviced components. Our no-strip screw system has superior holding power and guides screws into position while preventing the screw from stripping the unit s metal. Take accurate pressure readings by reading condenser pressure with panels on. Simply remove the black, composite plug, route your gauge line(s) through the hole, and connect them to the refrigeration service valve(s). Now, you can take refrigeration system pressure readings without affecting the condenser airflow. Easy to use: The newly designed, master terminal board by Carrier puts all your connections and troubleshooting points in one convenient place, standard. Most low voltage connections are made to the same board and make it easy to find what you re looking for and easy to access it. Carrier rooftops have high and low pressure switches, a filter drier, and 2 (51mm) filters standard. the environmentally sound refrigerant This product has been designed and manufactured to meet Energy Star criteria for energy efficiency. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow all manufacturer s refrigerant charging and air flow instructions. Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life. 2

FEATURES AND BENEFITS S Single cooling stage models are available from 3-10 ton. S Two cooling stage models are available from 7.5-12.5 ton with NOVATIONt condenser coil technology. S SEER up to 13.0. S EER s up to 11.2. S IPLV s up to 12.2. S Up to 28% lighter than similar industry units. Lighter rooftops make easier replacement jobs. S Utility connections are the same because 3-12.5 ton units fit on existing Carrier rooftop curbs. This saves time and money on replacement jobs. S Standardized components and layout. Standardized components and controls make service and stocking parts easier. S Scroll compressors on all units. This makes service, stocking parts, replacement, and trouble-shooting easier. S Field convertible airflow (3-12.5 ton). Being able to convert a unit from vertical airflow to horizontal makes it easy to overcome job site complications. S Easy-adjust, belt -drive motor available. Carrier provides a factory solution for most points in the fan performance table. There s no need for field-supplied drives or motors. S Provisions for bottom or side condensate drain. S Capable of thru-the -base or thru-the -curb gas-line routing. S Single -point gas / electrical connection. S Sloped, composite drain pan. Sloped, composite drain pan sheds water; and won t rust. S Standardized controls and control box layout. Standardized components and controls make stocking parts and service easier. S Tool-less filter access door. S Clean, easy to use control box. S Color-coded wiring. S Large, laminated wiring and power wiring drawings which are affixed to unit make troubleshooting easy. S Single, central terminal board for test and wiring connections. S Fast-access, handled, panels for easy access on normally accessed service panels. S No-strip screw system guides screws into the panel and captures them tightly without stripping the screw, the panel, or the unit. S Exclusive, newly-design indoor refrigerant header for easier maintenance and replacement. S Mechanical cooling (115_F to25_f or46_c to-4_c) on Direct Digital Controller (DDC) with Winter Start Kit (PremierLinkt or RTU-MP controller). S Mechanical cooling (115_F to25_f or46_c to-4_c) on Electro-Mechanical (E/M) models, with Winter Start Kit. S High efficiency, gas heat with induced-draft flue exhaust design (3-12.5 tons). S Induce draft motor ensures no flue gas can escape into the indoor air stream. S Carrier designed naturally draining heat exchanger, unlike positive pressure heat exchangers, do not need to be periodically, manually drained. This saves labor and maintenance expense. S 2 (51mm) disposable filters on all units. S Refrigerant filter-drier on each circuit. S High and low pressure switches. Added reliability with high pressure switch and low pressure switch. S Many factory-installed options ranging from air management economizers, 2 position dampers, plus convenience outlets, disconnect switch and smoke detectors. S Standard Warranty: 10 year aluminized heat exchanger, 5 year compressor, 3 year NOVATIONt condenser coil, 1 year parts. S Factory-installed Humidi-MiZert adaptive dehumidification system. 3

MODEL NUMBER NOMENCLATURE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 4 8 T C D A 0 4 A 1 A 5 -- 0 A 0 A 0 Unit Heat Type 48 = Cooling/Gas Heat RTU Brand / Packaging 0=Standard Tier / Model 1=LTL TC = Entry tier (with Puron refrigerant) Electrical Options A=None Heat Size C = Non --- fused disc D=Lowheat D=Thruthebase E = Medium heat F = Non---fused & thru the base F=Highheat L=LowNO x,lowheat Service Options M=LowNO x, medium heat 0=None N=LowNO x,highheat 1 = Unpowered convenience outlet S = Stainless steel, low heat 2 = Powered convenience outlet R = Stainless steel, medium heat T = Stainless steel, high heat Intake / Exhaust Options A=None Refrig. System Options B=Tempeconow/barorelief A = Standard 1---stage cooling F = Enthalpy econo w/ baro relief B = Standard 1 --- stage cooling w/humidi --- MiZer K = 2 --- Position damper D = 2--- stg. cooling comp. w/novation coil Base Unit Controls Cooling Tons 0 = Electromechanical 04 = 3 Ton 08 = 7.5 Ton 1 = PremierLink DDC controller 05 = 4 Ton 09 = 8.5 Ton 2 = RTU--- MP multi protocol controller 06 = 5 Ton 12 = 10 Ton 07 = 6 Ton 14 = 12.5 Ton Design Rev Factory assigned Sensor Options A=None Voltage B = RA smoke detector 1 = 575/3/60 C = SA smoke detector 3 = 208---230/1/60 D=RA&SAsmokedetector 5 = 208---230/3/60 E=CO 2 sensor 6 = 460/3/60 F = RA smoke detector & CO 2 G = SA smoke detector & CO 2 1 --- Stage Cooling Coil Options (Outdoor --- Indoor) H=RA&SAsmokedetector&CO 2 A = Al/Cu --- Al/Cu B = Precoat Al/Cu --- Al/Cu C = E coat Al/Cu --- Al/Cu Indoor Fan Options D=EcoatAl/Cu---EcoatAl/Cu 1 = Standard static option E = Cu/Cu --- Al/Cu 2 = Medium static option F = Cu/Cu --- Cu/Cu 3 = High static option M = Al/Cu --- Al/Cu --- Louvered Hail Guards N = Precoat Al/Cu --- Al/Cu --- Louvered Hail Guards P = E coat Al/Cu --- Al/Cu --- Louvered Hail Guards Q = E coat Al/Cu --- E coat Al/Cu --- Louvered Hail Guards R = Cu/Cu --- Al/Cu --- Louvered Hail Guards S = Cu/Cu --- Cu/Cu --- Louvered Hail Guards 2 ---Stage Cooling Coil Options (Outdoor --- Indoor) G = Al/Al --- Al/Cu H = Al/Al --- Cu/Cu J = Al/Al --- E --- coat Al/Cu K = E --- coat Al/Al --- Al/Cu L = E --- coat Al/Al --- E --- coat Al/Cu T = Al/Al --- Al/Cu --- Louvered Hail Guards U = Al/Al --- Cu/Cu --- Louvered Hail Guards V = Al/Al --- E --- coat Al/Cu --- Louvered Hail Guards W = E --- coat Al/Al --- Al/Cu --- Louvered Hail Guards X = E --- coat Al/Al --- E --- coat Al/Cu --- Louvered Hail Guards 4

TABLE 1 FACTORY-INSTALLED OPTIONS AND FIELD-INSTALLED ACCESSORIES CATEGORY ITEM FACTORY INSTALLED OPTION FIELD INSTALLED ACCESSORY Cabinet Thru---the---base electrical or gas---line connections X X Cu/Cu indoor and/or outdoor coils 1 X Coil Options Pre---coated outdoor coils 1 X Premium, E---coated outdoor coils 1 X Humidity Control Humdi---MiZer Adaptive Dehumidification System X Condenser Protection Condenser coil hail guard (louvered design) X X Thermostats, temperature sensors, and subbases X PremierLink DDC communicating controller X X Controls RTU---MP open---protocol controller X Smoke detector (supply and/or return air) X Time Guard II compressor delay control circuit X Phase Monitor X Economizers & Outdoor Air Dampers Economizer Sensors & IAQ Devices Gas Heat EconoMi$ert IV (for electro---mechanical controlled RTUs) X X EconoMi$ert2 (for DDC controlled RTUs) X X Motorized 2 position outdoor---air damper X X Manual outdoor---air damper (25% and 50%) X Barometric relief 2 X X Power exhaust X Single dry bulb temperature sensors 3 X X Differential dry bulb temperature sensors 3 X Single enthalpy sensors 3 X X Differential enthalpy sensors 3 X Wall or duct mounted CO 2 sensor 3 X Unit mounted CO 2 sensor 3 X Propane conversion kit X Stainless steel heat exchanger X High altitude conversion kit X Flue Shield X Flue Discharge Deflector X Indoor Motor & Drive Multiple motor and drive packages X Low Ambient Control Winter start kit 4 Motormaster head pressure controller 4 Convenience outlet (powered) X Power Convenience outlet (unpowered) X Options Non---fused disconnect X Roof Curbs Roof curb 14 (356mm) Roof curb 24 (610mm) X X X X NOTES: 1. NOVATION coils (2---stage cooling models 08---14): Condenser Coil = E---coat, Indoor Coil = Cu/Cu or E---coat 2. Included with economizer. 3. Sensors used to optimize economizer performance. 4. See application data for assistance. 5

FACTORY OPTIONS AND/OR ACCESSORIES Economizer (dry -bulb or enthalpy) Power Exhaust with Barometric Relief Economizers save money. They bring in fresh, outside air for ventilation; and provide cool, outside air to cool your building. This is the preferred method of low-ambient cooling. When coupled to CO 2 sensors, economizers can provide even more savings by coupling the ventilation air to only that amount required. Economizers are available, installed and tested by the factory, with either enthalpy or dry-bulb temperature inputs. There are also models for electromechanical as well as direct digital controllers. Additional sensors are available as accessories to optimize the economizers. Economizers include gravity controlled, barometric relief equalizes building pressure and ambient air pressures. This can be a cast effective solution to prevent building pressurization. CO 2 Sensor Improves productivity and saves money by working with the economizer to intake only the correct amount of outside air for ventilation. As occupants fill your building, the CO 2 sensor detects their presence through increasing CO 2 levels, and opens the economizer appropriately. When the occupants leave, the CO 2 levels decrease, and the sensor appropriately closes the economizer. This intelligent control of the ventilation air, called Demand Control Ventilation (DCV) reduces the overall load on the rooftop, saving money. Smoke Detectors Trust the experts. Smoke detectors make your application safer and your job easier. Carrier smoke detectors immediately shut down the rooftop unit when smoke is detected. They are available, installed by the factory, for supply air, return air, or both. Louvered Hail Guards Sleek, louvered panels protect the condenser coil from hail damage, foreign objects, and incidental contact. Convenience Outlet (powered or un -powered) Reduce service and/or installation costs by including a convenience outlet in your specification. Carrier will install this service feature at our factory. Provides a convenient, 15 amp, 115v GFCI receptacle with Wet in Use cover. The powered option allows the installer to power the outlet from the line side of the disconnect or load side as required by code. The unpowered option is to be powered from a separate 115/120v power source. Non -fused Disconnect This OSHA-compliant, factory-installed, safety switch allows a service technician to locally secure power to the rooftop. Superior internal building pressure control. This field-installed accessory may eliminate the need for costly, external pressure control fans. PremierLink, DDC Controller This CCN controller regulates your rooftop s performance to tighter tolerances and expanded limits, as well as facilitates zoning systems and digital accessories. It also unites your Carrier HVAC equipment together on one, coherent CCN network. The PremierLink can be factory-installed, or easily field-installed. RTU -MP, Multi -Protocol Controller Connect the rooftop to an existing BAS without needing complicated translators or adapter modules using the RTU-MP controller. This new controller speaks the 4 most common building automation system languages (Bacnet, Modbus, N2, and Lonworks). Use this controller when you have an existing BAS. Time Guard II Control Circuit This accessory protects your compressor by preventing short -cycling in the event of some other failure, prevents the compressor from restarting for 30 seconds after stopping. Not required with PremierLink, RTU-MP, or authorized commercial thermostats. Motorized 2 -Position Damper The new Carrier 2-position, motorized outdoor air damper admits up to 100% outside air. Using reliable, gear-driven technology, the 2-position damper opens to allow ventilation air and closes when the rooftop stops, stopping unwanted infiltration. Manual OA Damper Manual outdoor air dampers are an economical way to bring in ventilation air. The dampers are available in 25% and 50% versions. Optional Humidi -MiZert Adaptive Dehumidification System Carrier s Humidi-MiZer adaptive dehumidification system is an all-inclusive factory-installed option that can be ordered with any WeatherMaker -04-07 rooftop unit. This system expands the envelope of operation of Carrier s WeatherMaker rooftop products to provide unprecedented flexibility to meet year-round comfort conditions. The Humidi-MiZer adaptive dehumidification system has the industry s only dual dehumidification mode setting. The Humidi -MiZer system includes two new modes of operation. 6

The WeatherMaker -04-07 ooftop coupled with the Humidi-MiZer system is capable of operating in normal design cooling mode, subcooling mode, and hot gas reheat mode. Normal design cooling mode is when the unit will operate under its normal sequence of operation by cycling compressors to maintain comfort conditions. Subcooling mode will operate to satisfy part load type conditions when the space requires combined sensible and a higher proportion of latent load control. Hot Gas Reheat mode will operate when outdoor temperatures diminish and the need for latent capacity is required for sole humidity control. Hot Gas Reheat mode will provide neutral air for maximum dehumidification operation. Motormaster Head Pressure Controller The Motormaster motor controller is a low ambient, head pressure controller kit that is designed to maintain the unit s condenser head pressure during periods of low ambient cooling operation. This device should be used as an alternative to economizer free cooling not when economizer usage is either not appropriate or desired. The Motormaster will either cycle the outdoor-fan motors or operate them at reduced speed to maintain the unit operation, depending on the model. Winter Start Kit The winter start kit by Carrier extends the low ambient limit of your rooftop to 25_F (-4_C). The kit bypasses the low pressure switch, preventing nuisance tripping of the low pressure switch. Other low ambient precautions may still be prudent. Propane Heating Convert your gas heat rooftop from standard natural gas operation to Propane using this field-installed kit. High Altitude Heating High altitudes have less oxygen, which means heat exchangers need less fuel. The new gas orifices in this field-installed kit make the necessary adjustment for high altitude applications. They restore the optimal fuel to air mixture and maintain healthy combustion at altitudes above 2000 ft (610m). Kits may not be required in all areas. Flue Discharge Deflector The flue discharge deflector is a useful accessory when flue gas recirculation is a concern. By venting the flue discharge upwards, the deflector minimizes the chance for a neighboring unit to intake the flue exhaust. Optional Stainless Steel Heat Exchanger The stainless steel heat exchanger option provides the tubular heat exchanger be made out of a minimum 20 gauge type 409 stainless steel for applications where the mixed air to the heat exchanger is expected to drop below 45_F (7_C). Stainless steel may be specified on applications where the presence of airborne contaminants require its use (applications such as paper mills) or in area with very high outdoor humidity that may result in severe condensation in the heat exchanger during cooling operation. Flue Discharge Heat Shield The flue discharge heat shield keeps people from touching the rooftop unit s potentially hot flue discharge. This is especially useful for ground level applications, where more, untrained people could have access to the unit s exterior. Alternate Motors and Drives Some applications need larger horsepower motors, some need more airflow, and some need both. Regardless of the case, your Carrier expert has a factory installed combination to meet your application. A wide selection of motors and pulleys (drives) are available, factory installed, to handle nearly any application. Thru -the -Base Connections Thru-the -base connections, available as either an accessory or as a factory option, are necessary to ensure proper connection and seal when routing wire and piping through the rooftop s basepan and curb. These couplings eliminate roof penetration and should be considered for gas lines, main power lines, as well as control power. 7

TABLE 2 ARI COOLING RATING TABLE UNIT COOLING STAGES NOM. CAPACITY (TONS) 1-STAGE COOLING NET COOLING CAPACITY (MBH) TOTAL POWER (KW) SEER EER IPLV A04 1 3 34.6 3.1 13.00 11.00 N/A A05 1 4 45.0 4.0 13.00 11.00 N/A A06 1 5 59.0 5.5 13.00 10.75 N/A A07 1 6 70.0 6.4 N/A 11.00 N/A A08 1 7.5 88.0 8.0 N/A 11.00 N/A A09 1 8.5 97.0 8.8 N/A 11.00 N/A A12 1 10 117.0 10.6 N/A 11.00 N/A TABLE 3 ARI COOLING RATING TABLE UNIT COOLING STAGES NOM. CAPACITY (TONS) 2-STAGE COOLING NET COOLING CAPACITY (MBH) TOTAL POWER (KW) SEER EER IPLV D08 2 7.5 83.0 7.5 N/A 11.00 12.0 D12 2 10 114.0 10.3 N/A 11.10 12.2 D14 2 12.5 140.0 12.9 N/A 10.80 11.4 LEGEND ARI --- Air Conditioning, Heating and Refrigeration Institute Test Standard ASHRAE --- American Society of Heating, Refrigerating and Air Conditioning, Inc. EER --- Energy Efficiency Ratio IPLV --- Integrated Part Load Value SEER --- Seasonal Energy Efficiency Ratio NOTES: 1. Rated and certified under ARI Standard 210/240---06 or 340/360---07, as appropriate. 2. Ratings are based on: Cooling Standard: 80_F (27_C) db, _F (19_C) wb indoor air temp and 95_F (35_C) db outdoor air temp. IPLV Standard: 80_F (27_C) db, _F (19_C) wb indoor air temp and 80_F (27_C) db outdoor air temp. 3. All units comply with ASHRAE 90.1 2001, 2004 Energy Standard for minimum SEER and EER requirements. 4. units comply with US Energy Policy Act (2005). To evaluate code compliance requirements, refer to state and local codes or visit the following website: http://bcap---energy.org. This product has been designed and manufactured to meet Energy Star criteria for energy efficiency. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow all manufacturer s refrigerant charging and air flow instructions. Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life. 8

TABLE 4 HEATING RATING TABLE - NATURAL GAS & PROPANE Single Phase Units Gas Heat INPUT / OUTPUT STAGE 1 (MBH) AL/SS HEAT EXCHANGER INPUT / OUTPUT STAGE 2 (MBH) TEMP RISE (DEG F) THERMAL EFFICIENCY (%) LOW --- / 59 25 --- 55 82% 81% 04 MED --- 115 / 93 55 --- 85 80% 80% HIGH --- --- --- --- --- LOW --- / 59 25 --- 55 82% 81% 05 MED --- 115 / 93 35 --- 65 81% 80% HIGH --- 150 / 120 50 --- 80 80% 80% LOW --- / 59 20 --- 55 82% 81% 06 MED --- 115 / 93 30 --- 65 81% 80% HIGH --- 150 / 120 40 --- 80 80% 80% LOW --- / 59 25 --- 55 82% N/A 04 MED 82 / 66 115 / 93 55 --- 85 80% N/A HIGH --- --- --- --- --- LOW --- / 59 25 --- 55 82% N/A 05 MED --- 115 / 93 35 --- 65 81% N/A HIGH 120 / 96 150 / 120 50 --- 80 80% N/A LOW --- / 59 20 --- 55 82% N/A 06 MED --- 115 / 93 30 --- 65 81% N/A HIGH 120 / 96 150 / 120 40 --- 80 80% N/A LOW --- / 59 15 --- 55 82% N/A 07 MED --- 115 / 93 25 --- 65 81% N/A HIGH 120 / 96 150 / 120 35 --- 80 80% N/A LOW --- 125 / 103 20 --- 50 82% N/A 08 MED 120 / 98 180 / 148 35 --- 65 82% N/A HIGH 180 / 147 224 / 184 45 --- 75 82% N/A LOW --- 125 / 103 20 --- 50 82% N/A 09 MED 120 / 98 180 / 148 30 --- 65 82% N/A HIGH 180 / 147 224 / 184 40 --- 75 82% N/A LOW 120 / 98 180 / 148 25 --- 65 82% N/A 12 MED 180 / 147 224 / 184 30 --- 65 82% N/A HIGH 200 / 160 250 / 205 35 --- 70 80% N/A LOW 120 / 98 180 / 148 20 --- 65 82% N/A 14 MED 180 / 147 224 / 184 25 --- 65 82% N/A HIGH 200 / 160 250 / 205 25 --- 70 80% N/A NOTES: Heat ratings are for natural gas heat exchangers operated at or below 2000 ft (610 m). For information on Propane or altitudes above 2000 ft (610 m), see the Application Data section of this book. Accessory Propane/High Altitude kits are also available. Three Phase AFUE (%) In the USA the input rating for altitudes above 2000 ft (610m) must be derated by 4% for each 1000 ft (305 m) above sea level. In Canada, the input rating must be derated by 10% for altitudes of 2000 ft (610 m) to 4500 ft (13 m) above sea level. 9

TABLE 5 HEATING RATING TABLE - LOW NO X 1 Three Phase Single Phase UNIT 04 05 06 04 05 06 GAS HEAT LOW NOx HEAT EXCHANGER INPUT / OUTPUT STAGE 1 (MBH) INPUT / OUTPUT STAGE 2 (MBH) TEMP RISE (DEG F) THERMAL EFFICIENCY (%) AFUE (%) LOW --- 60 / 50 20 --- 50 81% 80% MED --- 90 / 74 30 --- 60 81% 81% HIGH --- --- --- --- --- LOW --- 60 / 50 20 --- 50 81% 80% MED --- 90 / 74 30 --- 60 81% 81% HIGH --- 120 / 101 40 --- 70 81% 80% LOW --- 60 / 50 15 --- 50 81% 80% MED --- 90 / 74 25 --- 60 80% 81% HIGH --- 120 / 101 35 --- 70 80% 81% LOW --- 60 / 50 20 --- 50 81% 80% MED --- 90 / 74 30 --- 60 81% 81% HIGH --- --- --- --- --- LOW --- 60 / 50 20 --- 50 81% 80% MED --- 90 / 74 30 --- 60 81% 81% HIGH --- 120 / 101 40 --- 70 81% 80% LOW --- 60 / 50 15 --- 50 81% 80% MED --- 90 / 74 25 --- 60 80% 81% HIGH --- 120 / 101 35 --- 70 80% 81% NOTE: 1. Units meet California s South Coast Air Quality Management District (SCAQMD) Low---NO x emissions requirement of 40 nanograms per joule or less. TABLE 6 SOUND PERFORMANCE TABLE UNIT COOLING STAGES OUTDOOR SOUND (db) A --- WEIGHTED 63 125 250 500 1000 2000 4000 8000 A04 1 80 90.6 80.9 80.2 74.6 71.3 68.5 63.9 A05 1 81 90.9 84.6 79.5 77.9.5 71.1 66.9.5 A06 1 78 84.0 82.2.3 74.8.5 68.8 65.6 61.8 A07 1 78 88.8 81.8.9 74.4 73.3 69.8 66.3.7 A08 1 82 90.1 82.6 81.0 79.4 77.0 73.0 70.4 66.7 D08 2 82 85.8 84.3 80.5 78.7.4.7 68.3 65.1 A09 1 83 91.2 86.4 81.9 81.0 78.3 73.9 71.4.3 A12 1 82 88.6 85.0 81.6 79.5 77.4 74.1 71.0 66.3 D12 2 82 89.0 83.1 80.5 78.5 75.5 71.6 69.6 69.3 D14 2 87 87.0 85.2 84.6 84.9 82.2 78.4 75.3.9 LEGEND db --- Decibel NOTES: 1. Outdoor sound data is measure in accordance with ARI standard 270---2008. 2. Measurements are expressed in terms of sound power. Do not compare these values to sound pressure values because sound pressure depends on specific environmental factors which normally do not match individual applications. Sound power values are independent of the environment and therefore more accurate. 3. A---weighted sound ratings filter out very high and very low frequencies, to better approximate the response of average human ear. A---weighted measurements for Carrier units are taken in accordance with ARI standard 270---2008. 10

TABLE 7 MINIMUM - MAXIMUM AIRFLOW RATINGS - NATURAL GAS & PROPANE UNIT HEAT LEVEL COOLING HEATING MINIMUM MAXIMUM MINIMUM MAXIMUM LOW 990 2190 **04 MED 900 1500 1000 1550 HIGH --- --- LOW 990 2190 **05 MED 1200 2000 1330 2460 HIGH 1390 2220 LOW 990 2730 **06 MED 1500 2500 1330 2880 HIGH 1390 2780 LOW 990 3640 **07 MED 1800 3000 1330 3450 HIGH 1390 3170 LOW 1900 4750 **08 MED 2250 3750 2100 3900 HIGH 2270 3780 LOW 1900 4750 **09 MED 2550 4250 2100 4560 HIGH 2270 4250 LOW 2100 5470 **12 MED 3000 5000 20 50 HIGH 2650 5290 LOW 2100 6830 **14 MED 3600 6000 20 6800 HIGH 2650 7410 11

TABLE 8 PHYSICAL DATA (COOLING) 3-6 TONS *A04 *A05 *A06 *A07 Refrigeration System #Circuits/#Comp./Type 1/1/Scroll 1/1/Scroll 1/1/Scroll 1/1/Scroll Puronr refrig. (R---410A) charge per circuit A/B (lbs---oz) 5 --- 10 / --- 8 --- 8 / --- 10 --- 11 / --- 14 --- 2 / --- Operating charge (lbs --- oz) --- Humidi --- MiZer Unit 8 --- 12 14---13 16 --- 0 22 --- 4 Metering Device Acutrol Acutrol Acutrol Acutrol High---press. Trip / Reset (psig) 630 / 505 630 / 505 630 / 505 630 / 505 Low---press. Trip / Reset (psig) 54 / 117 54 / 117 54 / 117 54 / 117 Evap. Coil Material Cu / Al Cu / Al Cu / Al Cu / Al Coil type 3/8 RTPF 3/8 RTPF 3/8 RTPF 3/8 RTPF Rows / FPI 2 / 15 2/15 4/15 4/15 Total Face Area (ft 2 ) 5.5 5.5 5.5 7.3 Condensate Drain Conn. Size 3/4 3/4 3/4 3/4 Evap. Fan and Motor Standard Static 1phase Medium Static 1phase Standard Static 3phase Medium Static 3phase High Static 3phase Motor Qty / Drive Type 1/ Belt 1/ Belt 1/ Belt --- Max BHP 1.2 1.2 1.2 --- RPM Range 560---854 560---854 770---1175 --- Motor Frame Size 48 48 48 --- Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal --- Fan Diameter (in) 10 x 10 10 x 10 10 x 10 --- Motor Qty / Drive Type 1/ Belt 1/ Belt 1/ Belt --- Max BHP 1.2 1.2 1.5 --- RPM Range 770---1175 770---1175 1035---1466 --- Motor Frame Size 48 48 56 --- Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal --- Fan Diameter (in) 10 x 10 10 x 10 10 x 10 --- Motor Qty / Drive Type 1/Belt 1/Belt 1/Belt 1/Belt Max BHP 1.2 1.2 1.5 2.4 RPM Range 560---854 560---854 770---1175 1073---1457 Motor Frame Size 48 48 48 56 Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal 1/Centrifugal Fan Diameter (in) 10 x 10 10 x 10 10 x 10 10 x 10 Motor Qty / Drive Type 1/Belt 1/Belt 1/Belt 1/Belt Max BHP 1.2 1.2 2.4 2.9* RPM Range 770---1175 770---1175 1035---1466 1173---1518 Motor Frame Size 48 48 56 56 Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal 1/Centrifugal Fan Diameter (in) 10 x 10 10 x 10 10 x 10 10 x 10 Motor Qty / Drive Type 1/Belt 1/Belt 1/Belt 1/Belt Max BHP 2.4 2.4 2.9 3.7 RPM Range 1035---1466 1035---1466 1303---1687 1474---1788 Motor Frame Size 56 56 56 56 Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal 1/Centrifugal Fan Diameter (in) 10 x 10 10 x 10 10 x 10 10 x 10 Cond. Coil Humidi --- MiZer Coil Cond. fan / motor Filters Material Cu / Al Cu / Al Cu / Al Cu / Al Coil type 3/8 RTPF 3/8 RTPF 3/8 RTPF 3/8 RTPF Rows / FPI 1 / 17 2/17 2/17 2/17 Total Face Area (ft 2 ) 14.6 16.5 16.5 21.3 Material Cu / Al Cu / Al Cu / Al Cu / Al Rows..Fins/in. 1 / 17 2/ 17 2/ 17 2/ 17 Total Face Area (ft 2 ) 3.9 3.9 3.9 5.2 Qty / Motor Drive Type 1/ Direct 1/ Direct 1/ Direct 1/ Direct Motor HP / RPM 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 Fan diameter (in) 22 22 22 22 RA Filter # / Size (in) 2 / 16 x 25 x 2 2/16x25x2 2/16x25x2 4/16x16x2 OA inlet screen # / Size (in) 1/20x24x1 1/20x24x1 1/20x24x1 1/20x24x1 * 575V motor utilizes 3.7 BHP. 12

TABLE 9 PHYSICAL DATA (HEATING) 3-6 TONS **04 **05 **06 **07 Gas Connection #ofgasvalves 1 1 1 1 Nat. gas supply line press (in. w.g.)/(psig) 4 --- 13 / 0.18 --- 0.47 4 --- 13 / 0.18 --- 0.47 4 --- 13 / 0.18 --- 0.47 4 --- 13 / 0.18 --- 0.47 Propane supply line press (in. w.g.)/(psig) 11 ---13 / 0.40 --- 0.47 11 ---13 / 0.40 --- 0.47 11 ---13 / 0.40 --- 0.47 11 ---13 / 0.40 --- 0.47 Heat Anticipator Setting (Amps) 1st stage 0.14 0.14 0.14 0.14 2nd stage 0.14 0.14 0.14 0.14 Natural Gas, Propane Heat #ofstages/#ofburners(total) 1/2 1/2 1/2 1/2 Connection size 1/2 NPT 1/2 NPT 1/2 NPT 1/2 NPT Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 195 / 115 Temperatureriserange(F) 25 --- 55 25 --- 55 20 --- 55 15 --- 55 LOW MED #ofstages/#ofburners(total) 1or2/3 1/3 1/3 1/3 Connection size 1/2 NPT 1/2 NPT 1/2 NPT 1/2 NPT Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 195 / 115 Temperatureriserange(F) 55 --- 85 35 --- 65 30 --- 65 25 --- 65 HIGH Connection size --- 1or2/3 1or2/3 1or2/3 # ofstages/# ofburners(total) --- 1/2 NPT 1/2 NPT 1/2 NPT Rollout switch opens / closes --- 195 / 115 195 / 115 195 / 115 Temperatureriserange(F) --- 50 --- 80 40 --- 80 35 --- 80 Low NO x Gas Heat #ofstages/#ofburners(total) 1/2 1/2 1/2 --- Connection size 1/2 NPT 1/2 NPT 1/2 NPT --- Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 --- Temperatureriserange(F) 20 --- 50 20 --- 50 15 --- 50 --- LOW MED HIGH #ofstages/#ofburners(total) 1/3 1/3 1/3 --- Connection size 1/2 NPT 1/2 NPT 1/2 NPT --- Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 --- Temperatureriserange(F) 30 --- 60 30 --- 60 25 --- 60 --- --- #ofstages/#ofburners(total) --- 1/3 1/3 --- Connection size --- 1/2 NPT 1/2 NPT --- Rollout switch opens / closes --- 195 / 115 195 / 115 --- Temperatureriserange(F) --- 40 --- 70 35 --- 70 --- 13

TABLE 10 PHYSICAL DATA (COOLING) 7.5-12.5 TONS *A08 *D08 *A09 *A12 *D12 *D14 Refrigeration System #Circuits/#Comp./Type 1/1/Scroll 2/2/Scroll 1/1/Scroll 1/1/Scroll 2/2/Scroll 2/2/Scroll Puronr refrig. (R--- 410A) charge per circuit A/B (lbs --- oz) 13 --- 12 / --- 4 --- 6 / 4 --- 6 15 --- 4 / --- 20 --- 0 / --- 6 --- 0 / 6 --- 0 7 --- 6 / 8 --- 0 Oil A/B (oz) 60 42 / 42 85 110 42 / 42 56 / 56 Metering Device Acutrol Acutrol Acutrol Acutrol Acutrol Acutrol High---press. Trip / Reset (psig) 630 / 505 630 / 505 630 / 505 630 / 505 630 / 505 630 / 505 Low---press. Trip / Reset (psig) 54 / 117 54 / 117 54 / 117 54 / 117 54 / 117 54 / 117 Evap. Coil Material Cu / Al Cu / Al Cu / Al Cu / Al Cu / Al Cu / Al Coil type 3/8 RTPF 3/8 RTPF 3/8 RTPF 3/8 RTPF 3/8 RTPF 3/8 RTPF Rows / FPI 3 / 15 3/15 3/15 4/15 4/15 4/15 Total Face Area (ft 2 ) 8.9 8.9 11.1 11.1 11.1 11.1 Condensate Drain Conn. Size 3/4 3/4 3/4 3/4 3/4 3/4 Evap. Fan and Motor Standard Static 3phase Medium Static 3phase High Static 3phase Motor Qty / Drive Type 1/Belt 1/Belt 1/Belt 1/Belt 1/Belt 1/Belt Max BHP 1.7 1.7 1.7 2.4 2.4 2.9* RPM Range 489---747 489---747 518---733 591---838 591---838 652---843 Motor Frame Size 56 56 56 56 56 56 Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal 1/Centrifugal 1/Centrifugal 1/Centrifugal Fan Diameter (in) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 Motor Qty / Drive Type 1/Belt 1/Belt 1/Belt 1/Belt 1/Belt 1/Belt Max BHP 2.9* 2.9* 2.4 3.7 3.7 3.7 RPM Range 733---949 733---949 690---936 838---1084 838---1084 838---1084 Motor Frame Size 56 56 56 56 56 56 Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal 1/Centrifugal 1/Centrifugal 1/Centrifugal Fan Diameter (in) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 Motor Qty / Drive Type 1/Belt 1/Belt 1/Belt 1/Belt 1/Belt 1/Belt Max BHP 4.7 4.7 3.7 4.7 4.7 4.7 RPM Range 909---1102 909---1102 838---1084 1022---1240 1022---1240 1022---1240 Motor Frame Size 145TY 145TY 56 145TY 145TY 145TY Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal 1/Centrifugal 1/Centrifugal 1/Centrifugal Fan Diameter (in) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 Cond. Coil Material Cu / Al Al / Al Cu / Al Cu / Al Al / Al Al / Al Coil type 3/8 RTPF NOVATION 3/8 RTPF 3/8 RTPF NOVATION NOVATION Rows / FPI 2 / 17 1/20 2/17 2/17 1/20 2/20 Total Face Area (ft 2 ) 20.5 20.5 21.4 25.1 25.1 25.1 Cond. fan / motor Qty / Motor Drive Type 2 / Direct 2/direct 2/Direct 2/Direct 2/direct 1/direct Motor HP / RPM 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 1 / 1175 Fan Diameter (in) 22 22 22 22 22 30 Filters RAFilter#/Size(in) 4/16x20x2 4/16x20x2 4/20x20x2 4/20x20x2 4/20x20x2 4/20x20x2 OA inlet screen # / Size (in) 1/20x24x1 1/20x24x1 1/20x24x1 1/20x24x1 1/20x24x1 1/20x24x1 * 575V motor utilizes 3.7 BHP. 14

TABLE 11 PHYSICAL DATA (HEATING) 7.5-12.5 TONS **08 **09 **12 **14 Gas Connection #ofgasvalves 1 1 1 1 Nat. gas supply line press (in. w.g.)/(psig) 4 --- 13 / 0.18 --- 0.47 4 --- 13 / 0.18 --- 0.47 4 --- 13 / 0.18 --- 0.47 4 --- 13 / 0.18 --- 0.47 Propane supply line press (in. w.g.)/(psig) 11 ---13 / 0.40 --- 0.47 11 ---13 / 0.40 --- 0.47 11 ---13 / 0.40 --- 0.47 11 ---13 / 0.40 --- 0.47 Heat Anticipator Setting (Amps) 1st stage 0.14 0.14 0.14 0.14 2nd stage 0.14 0.14 0.14 0.14 Natural Gas, Propane Heat #ofstages/#ofburners(total) 1/3 1/3 2/4 2/4 Connection size 1/2 NPT 1/2 NPT 3/4 NPT 3/4 NPT Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 195 / 115 Temperatureriserange(F) 20 --- 50 20 --- 50 25 --- 65 25 --- 65 LOW MED #ofstages/#ofburners(total) 2/4 2/4 2/5 2/5 Connection size 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 195 / 115 Temperatureriserange(F) 35 --- 65 30 --- 65 30 --- 65 25 --- 65 HIGH #ofstages/#ofburners(total) 2/5 2/5 2/5 2/5 Connection size 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 195 / 115 Temperatureriserange(F) 45 --- 75 40 --- 75 35 --- 70 35 --- 70 15

CURBS & WEIGHTS DIMENSIONS - CHASSIS 1 Fig. 1 - Dimensions 04-07 C08517 16

CURBS & WEIGHTS DIMENSIONS - CHASSIS 1 (cont.) Fig. 2 - Dimensions 04-07 C08593 GASKET (SUPPLIED WITH CURB) NAIL COUNTER FLASHING (FIELD SUPPLIED) ROOFING FELT (FIELD SUPPLIED) CANT STRIP (FIELD SUPPLIED) ROOFING FELT (FIELD SUPPLIED) Fig. 4 - Curb Installation Detail (Typical) C07457 C D B A Fig. 3 - Curb Dimensions C074 Fig. 5 - Service Clearance C08337 LOC DIMENSION CONDITION 48 (1219 mm) Unit disconnect is mounted on panel A 18 (457 mm) No disconnect, convenience outlet option 18 (457 mm) Recommended service clearance 12 (305 mm) Minimum clearance 42 (10 mm) Surface behind servicer is grounded (e.g., metal, masonry wall) B 36 (914 mm) Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass) Special Check for sources of flue products within 10---ft of unit fresh air intake hood C 36 (914 mm) Side condensate drain is used 18 (457 mm) Minimum clearance 48 (1219 mm) No flue discharge accessory installed, surface is combustible material D 42 (10 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit) 36 (914 mm) Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass) Special Check for adjacent units or building fresh air intakes within 10---ft of this unit s flue outlet 17

CURBS & WEIGHTS DIMENSIONS - CHASSIS 2 Fig. 6 - Dimensions 08-12 C08519 18

CURBS & WEIGHTS DIMENSIONS - CHASSIS 2 (cont.) Fig. 7-08 -12 C08520 GASKET (SUPPLIED WITH CURB) NAIL COUNTER FLASHING (FIELD SUPPLIED) ROOFING FELT (FIELD SUPPLIED) CANT STRIP (FIELD SUPPLIED) ROOFING FELT (FIELD SUPPLIED) Fig. 9 - Curb Installation Detail (Typical) C07457 C D B A Fig. 8 - Curb Dimensions C08309 Fig. 10 - Service Clearance LOC DIMENSION CONDITION 48 (1219 mm) Unit disconnect is mounted on panel 36 (914 mm) If dimension--- B is 12 (305 mm) A 18 (457 mm) No disconnect, convenience outlet option 18 (457 mm) Recommended service clearance (use electric screwdriver) 12 (305 mm) Minimum clearance (use manual ratchet screwdriver) 36 (914 mm) Unit has economizer B 12 (305 mm) If dimension--- A is 36 (914 mm) Special Check for sources of flue products within 10---ft of unit fresh air intake hood C 36 (914 mm) Side condensate drain is used 18 (457 mm) Minimum clearance 48 (1219 mm) No flue discharge accessory installed, surface is combustible material D 42 (10 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit) 36 (914 mm) Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass) Special Check for adjacent units or building fresh air intakes within 10---ft of this unit s flue outlet C08337 19

CURBS & WEIGHTS DIMENSIONS - CHASSIS 3 Fig. 11 - Dimensions -14 C08521 20

CURBS & WEIGHTS DIMENSIONS - CHASSIS 3 (cont.) GASKET (SUPPLIED WITH CURB) NAIL C08522 COUNTER FLASHING (FIELD SUPPLIED) ROOFING FELT (FIELD SUPPLIED) CANT STRIP (FIELD SUPPLIED) ROOFING FELT (FIELD SUPPLIED) Fig. 13 - Curb Installation Detail (Typical) C07457 C D B A Fig. 12 - Curb Dimensions C08309 Fig. 14 - Service Clearance LOC DIMENSION CONDITION 48 (1219 mm) Unit disconnect is mounted on panel 36 (914 mm) If dimension--- B is 12 (305 mm) A 18 (457 mm) No disconnect, convenience outlet option 18 (457 mm) Recommended service clearance (use electric screwdriver) 12 (305 mm) Minimum clearance (use manual ratchet screwdriver) 36 (914 mm) Unit has economizer B 12 (305 mm) If dimension--- A is 36 (914 mm) Special Check for sources of flue products within 10---ft of unit fresh air intake hood C 36 (914 mm) Side condensate drain is used 18 (457 mm) Minimum clearance 48 (1219 mm) No flue discharge accessory installed, surface is combustible material D 42 (10 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit) 36 (914 mm) Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass) Special Check for adjacent units or building fresh air intakes within 10---ft of this unit s flue outlet C08337 21

APPLICATION DATA Min operating ambient temp (cooling): Outdoor air application strategies: In mechanical cooling mode, your Carrier rooftop unit can safely operate down to an outdoor ambient temperature of 40_F (4_C) and 25_F (-4_C), with an accessory winter start kit. It is possible to provide cooling at lower outdoor ambient temperatures by using less outside air, economizers, and/or accessory low ambient kits. Max operating ambient temp (cooling): The maximum operating ambient temperature for cooling mode is 115_F (46_C). While cooling operation above 115_F (46_C) may be possible, it could cause either a reduction in performance, reliability, or a protective action by the unit s internal safety devices. Min mixed air temp (heating): Using the factory settings, the minimum temperatures for the mixed air (the combined temperature of the warm return air and the cold outdoor air) entering the dimpled, gas heat exchangers are: Aluminized 50_F (10_C) continuous 45_F (7_C) intermittent Stainless Steel 40_F (4_C) continuous 35_F (2_C) intermittent Operating at lower mixed-air temperatures may be possible, if a field-supplied, outdoor air thermostat initiates both heat stages when the temperature is less than the minimum temperatures listed above. Please contact your local Carrier representative for assistance. Min and max airflow (heating and cooling): To maintain safe and reliable operation of your rooftop, operate within the heating airflow limits during heating mode and cooling airflow limits during cooling mode. Operating above the max may cause blow-off, undesired airflow noise, or airflow related problems with the rooftop unit. Operating below the min may cause problems with coil freeze-up and unsafe heating operation. Heating and cooling limitations differ when evaluating operating, the minimum value is the HIGHER of the cooling and heating minimum values published in Table 7 and the maximum value is the LOWER of the cooling and heating minimum values published in Table 7. Heating -to -cooling changeover: Your unit will automatically change from heating to cooling mode when using a thermostat with an auto-change-over feature. Airflow: All units are draw-though in cooling mode and blow-through in heating mode. Economizers reduce operating expenses and compressor run time by providing a free source of cooling and a means of ventilation to match application changing needs. In fact, they should be considered for most applications. Also, consider the various economizer control methods and their benefits, as well as sensors required to accomplish your application goals. Please contact your local Carrier representative for assistance. Motor limits, break horsepower (BHP): Due to internal design of Carrier units, the air path, and specially designed motors, the full horsepower (maximum continuous BHP) band, as listed in Table 8 and 10, can be used with the utmost confidence. There is no need for extra safety factors, as Carrier motors are designed and rigorously tested to use the entire, listed BHP range without either nuisance tripping or premature motor failure. Propane heating: Propane has different physical qualities than natural gas. As a result, Propane requires different fuel to air mixture. To optimize the fuel/air mixture for Propane, Carrier sells different burner orifices in an easy to install accessory kit. To select the correct burner orifices or determine the heat capacity for an Propane application, use either the selection software, or the unit s service manual. High altitude heating: High altitudes have less oxygen, which affects the fuel/air mixture in heat exchangers. In order to maintain a proper fuel/air mixture, heat exchangers operating in altitudes above 2000 ft (610 m) require different orifices. To select the correct burner orifices or determine the heat capacity for a high altitude application, use either the selection software, or the unit s service manual. High altitudes have less oxygen, which means heat exchangers need less fuel. The new gas orifices in this field-installed kit make the necessary adjustment for high altitude applications. They restore the optimal fuel to air mixture and maintain healthy combustion on altitudes above 2000 ft (610 m). NOTE: Typical natural gas heating value ranges from 975 to 1050 Btu/ft 3 at sea level nationally. The heating value goes down approximately 1.7% per every thousand feet elevation. Standard factory orifices can typically be used up to 2000 ft (610m) elevation without any operational issues. NOTE: For installations in Canada, the input rating should be derated by 10% for altitudes from 2000 ft (610m)to 4500 ft (13m) above sea level. 22

Sizing a rooftop Bigger isn t necessarily better. While an air conditioner needs to have enough capacity to meet the design loads, it doesn t need excess capacity. In fact, excess capacity typically results in very poor part load performance and humidity control. Using higher design temperatures than ASHRAE recommends for your location, adding safety factors to the calculated load, are all signs of oversizing air conditioners. Oversizing the air conditioner leads to poor humidity control, reduced efficiency, higher utility bills, larger indoor temperature swings, excessive noise, and increased wear and tear on the air conditioner. Rather than oversizing an air conditioner, engineers should right -size or even slightly undersize air conditioners. Correctly sizing an air conditioner controls humidity better; promotes efficiency; reduces utility bills; extends equipment life, and maintains even, comfortable temperatures. Please contact your local Carrier representative for assistance. Low ambient applications The optional Carrier economizer can adequately cool your space by bringing in fresh, cool outside air. In fact, when so equipped, accessory low-ambient kit may not be necessary. In low ambient conditions, unless the outdoor air is excessively humid or contaminated, economizer-based free cooling is the preferred less costly and energy conscious method. In low ambient applications where outside air might not be desired (such as contaminated or excessively humid outdoor environments), your Carrier rooftop can operate to ambient temperatures down to -20_F (-29_C) using the recommended accessory Motormaster low ambient controller. 23

SELECTION PROCEDURE (WITH *A07 EXAMPLE) 1 I. Determine cooling and heating loads. Given: Mixed air dry bulb 80_F (27_C) Mixed air wet bulb _F (19_C) Ambient dry bulb 95_F (35_C) TC Load.0 MBH SHC Load 54.0 MBH Vertical supply air 2100 Heating load 85.0 MBH External static pressure 0. in. wg Electrical characteristics 230-3-60 II. Make an initial guess at cooling tons. Refrig. tons = TC Load / 12 MBH per ton Refrig. tons =.0 / 12 = 6.0 tons In this case, start by looking at the **07. III. Look up the rooftop s TC and SHC. Table 15 shows that, at the application s supply air, mixed air and ambient temperatures, the *A07 supplies: TC = 73.7 MBH 2 SHC = 54.4 MBH 2 IV. Calculate the building latent heat load. LC Load =TC Load - SHC Load LC Load =.0 MBH - 54.0 MBH = 18.0 MBH V. Calculate RTU latent heat capacity. LC = TC - SHC LC = 73.7 MBH - 54.4 MBH = 19.3 MBH VI. Compare RTU capacities to loads. 3 Compare the rooftop s SHC and LC to the building s sensible and latent heat loads. VII. Select factory options (FIOP) Local code requires an economizer for any unit with TC greater than 65.0 MBH. VIII. Calculate the total static pressure. External static pressure 0. in. wg Sum of FIOP / Accessory static +0.13 in. wg Total Static Pressure 0.80 in. wg IX. Look up the indoor fan RPM & BHP. Table 36 shows, at 2100 & ESP= 0.8, RPM = 13 & BHP = 1.52 X. Convert BHP (Step VIII) into fan motor heat. Fan motor heat = 2.546* BHP/Motor Eff. 4 Fan motor heat = 4.9 MBH XI. Calculate RTU heating capacity. Building heating load 85.0 MBH Fan motor heat -4.9 MBH Required heating capacity 80.1 MBH XII. Select a gas heater. Table 4 shows the heating capacities of the EA07 = 93.0 MBH. Select the EA07 XIII. Determine electrical requirements. Table 56 shows the MCA and MOCP of a *A07 (without convenience outlet) as: MCA = 30.5 amps & MOCP = 45.0 amps Min. disconnect size: FLA = 30 & LRA = 157. LEGEND BHP Break horsepower FLA Full load amps LC Latent capacity LRA Lock rotor amp MBH (1,000) BTUH MCA Min. circuit ampacity MOCP Max. over---current protection RPM Revolutions per minute RTU Rooftop unit SHC Sensible heat capacity TC Total capacity NOTES: 1. Selection software by Carrier saves time by performing many of the steps above. Contact your Carrier sales representative for assistance. 2. Unit ratings are gross capacities and do not include the effect of evaporator fan motor heat. See Step X. for determining amount of evaporator fan motor heat to subtract from total and sensible capacities to obtain net cooling and net sensible capacities. 3. Selecting a unit with a SHC slightly lower than the SHC Load is often better than oversizing. Slightly lower SHC s will help control indoor humidity, and prevent temperature swings. 4. Indoor fan motor efficiency is available in Table 49. Use the decimal form in the equation, eg. 80% =.8. 24

TABLE 12 COOLING CAPACITIES 1-STAGE COOLING 3 TONS 900 Cfm 1050 Cfm 1200 Cfm 1350 Cfm 1500 Cfm AMBIENT TEMPERATURE *A04 85 95 105 115 EAT (db) EAT (db) EAT (db) EAT (db) 75 80 85 75 80 85 75 80 85 75 80 85 TC 28.1 28.1 31.7 26.3 26.3 29.8 24.5 24.5 27.7 22.6 22.6 25.5 SHC 24.4 28.1 31.7 22.9 26.3 29.8 21.3 24.5 27.7 19.6 22.6 25.5 TC 30.3 30.3 31.0 27.8 27.8 29.8 25.1 25.1 28.4 22.6 22.6 26.5 SHC 22.6 26.8 31.0 21.5 25.7 29.8 20.2 24.3 28.4 18.7 22.6 26.5 TC 35.5 35.5 35.5 33.1 33.1 33.1 30.5 30.5 30.5 27.5 27.5 27.5 SHC 19.5 23.7 27.9 18.5 22.7 26.9 17.4 21.6 25.8 16.2 20.4 24.6 TC 39.0 39.0 39.0 37.1 37.1 37.1 35.1 35.1 35.1 32.7 32.7 32.7 SHC 15.3 19.5 23.7 14.5 18.8 23.0 13.7 17.9 22.2 12.9 17.1 21.3 TC --- 41.4 41.4 --- 39.6 39.6 --- 37.6 37.6 --- 35.4 35.4 SHC --- 16.0 21.0 --- 15.4 20.2 --- 14.6 19.3 --- 13.8 18.3 TC 30.2 30.2 34.2 28.4 28.4 32.2 26.5 26.5 30.0 24.5 24.5 27.7 SHC 26.3 30.2 34.2 24.7 28.4 32.2 23.1 26.5 30.0 21.3 24.5 27.7 TC 31.9 31.9 34.2 29.4 29.4 32.8 26.7 26.7 31.2 24.5 24.5 28.8 SHC 24.6 29.4 34.2 23.4 28.1 32.8 22.0 26.6 31.2 20.3 24.5 28.8 TC 36.7 36.7 36.7 34.8 34.8 34.8 32.2 32.2 32.2 29.1 29.1 29.1 SHC 20.6 25.4 30.2 19.8 24.6 29.4 18.8 23.6 28.4 17.6 22.4 27.2 TC 40.1 40.1 40.1 38.2 38.2 38.2 36.1 36.1 36.1 33.7 33.7 33.7 SHC 15.7 20.5 25.3 15.0 19.8 24.6 14.2 19.0 23.8 13.4 18.2 23.0 TC --- 42.4 42.4 --- 40.6 40.6 --- 38.5 38.5 --- 36.2 36.2 SHC --- 16.6 22.2 --- 15.9 21.3 --- 15.2 20.4 --- 14.4 19.5 TC 32.2 32.2 36.4 30.4 30.4 34.3 28.4 28.4 32.1 26.3 26.3 29.7 SHC 28.0 32.2 36.4 26.4 30.4 34.3 24.7 28.4 32.1 22.8 26.3 29.7 TC 33.3 33.3 37.0 30.8 30.8 35.5 28.4 28.4 33.4 26.3 26.3 30.9 SHC 26.4 31.7 37.0 25.1 30.3 35.5 23.4 28.4 33.4 21.7 26.3 30.9 TC 37.7 37.7 37.7 35.6 35.6 35.6 33.4 33.4 33.4 30.4 30.4 30.4 SHC 21.7 27.0 32.4 20.9 26.3 31.6 20.0 25.4 30.8 18.8 24.2 29.6 TC 40.9 40.9 40.9 39.0 39.0 39.0 36.9 36.9 36.9 34.4 34.4 34.4 SHC 16.1 21.5 26.8 15.4 20.8 26.1 14.7 20.0 25.4 13.8 19.2 24.5 TC --- 43.1 43.1 --- 41.3 41.3 --- 39.1 39.1 --- 36.8 36.8 SHC --- 17.1 23.1 --- 16.4 22.3 --- 15.7 21.4 --- 14.9 20.5 TC --- --- --- 32.1 32.1 36.3 30.0 30.0 34.0 27.9 27.9 31.5 SHC --- --- --- 27.9 32.1 36.3 26.1 30.0 34.0 24.2 27.9 31.5 TC 28.4 28.4 30.5 32.2 32.2 37.8 30.1 30.1 35.3 27.9 27.9 32.8 SHC 17.6 24.1 30.5 26.6 32.2 37.8 24.8 30.1 35.3 23.0 27.9 32.8 TC 33.2 33.2 33.2 36.4 36.4 36.4 34.1 34.1 34.1 31.5 31.5 32.0 SHC 15.0 21.4 27.9 21.9 27.8 33.7 21.0 26.9 32.9 20.0 26.0 32.0 TC 37.5 37.5 37.5 39.7 39.7 39.7 37.5 37.5 37.5 35.0 35.0 35.0 SHC 11.8 18.3 24.8 15.8 21.7 27.5 15.0 20.9 26.8 14.2 20.1 26.0 TC --- 40.1 40.1 --- 41.8 41.8 --- 39.6 39.6 --- 37.3 37.3 SHC --- 15.3 22.7 --- 16.8 23.2 --- 16.1 22.3 --- 15.3 21.5 TC 28.1 28.1 34.2 33.7 33.7 38.1 31.6 31.6 35.7 29.3 29.3 33.2 SHC 21.9 28.1 34.2 29.3 33.7 38.1 27.4 31.6 35.7 25.5 29.3 33.2 TC 30.3 30.3 33.8 33.7 33.7 39.6 31.6 31.6 37.1 29.4 29.4 34.5 SHC 19.8 26.8 33.8 27.8 33.7 39.6 26.1 31.6 37.1 24.2 29.4 34.5 TC 35.5 35.5 35.5 36.9 36.9 36.9 34.6 34.6 34.9 32.0 32.0 34.0 SHC 16.7 23.7 30.7 22.8 29.2 35.7 21.9 28.4 34.9 21.0 27.5 34.0 TC 39.0 39.0 39.0 40.2 40.2 40.2 38.0 38.0 38.0 35.5 35.5 35.5 SHC 12.4 19.5 26.6 16.1 22.5 28.8 15.4 21.7 28.1 14.6 21.0 27.4 TC --- 41.4 41.4 --- 42.2 42.2 --- 40.0 40.0 --- --- --- SHC --- 16.0 24.3 --- 17.2 24.0 --- 16.5 23.2 --- --- --- LEGEND: --- --- Do not operate Cfm --- Cubic feet per minute (supply air) EAT(db) --- Entering air temperature (dry bulb) EAT(wb) --- Entering air temperature (wet bulb) SHC --- Sensible heat capacity TC --- Total capacity 25