INSULATION RESISTANCE TESTER FOR PHOTOVOLTAIC SYSTEMS MSEI-200C INSTRUCTION MANUAL

Similar documents
DIGITAL CLAMP TESTER MODEL HCL-5000D

ROGOWSKI LEAK METER MODEL RLM-1

Clamp Earth Tester MET-2. Instruction Manual

AC CURRENT ANALOG CLAMP-ON TESTER MODEL MCL-350 INSTRUCTION MANUAL

DIGITAL RCD(ELCB) TESTER

1.Safe testing IMPORTANT:

OPERATING INSTRUCTION

TES-1601 INSTRUCTION MANUAL AUTORANGING INSULATION TESTER SAFETY INFORMATION TES ELECTRICAL ELECTRONIC CORP. Warnings and Safety symbols:

EZYPAT / EZYPAT+ / SMARTPAT PORTABLE APPLIANCE TESTER INSTRUCTION MANUAL

INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER

OPERATING INSTRUCTION

OPERATING INSTRUCTION

INSTRUCTION MANUAL ANALOGUE INSULATION TESTER KEW 3131M KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD., TOKYO JAPAN

Table of Contents Title Page No.

l The Battery Tester is designed for measuring the l AC four-terminal method to measure the internal

DIGITAL INSULATION RESISTANCE TESTER (5KV, 1T )

Table of Contents. Title Page UT501/UT502 OPERATING MANUAL. Introduction. Unpacking the Meter. Safety Information. International Electrical Symbols

Attention ETCR8600 Leakage Protector Tester To read this user manual carefully. To comply with the operating cautions presented in this manual.

MAX. AC 600V HOLD V M H.V. LIVE CIRCUIT DIGITAL INSULATION TESTER DO NOT OPERATE IF LIT POWER DATA HOLD TEST ON / OFF 250V 500V 1000V OFF CAT.

SafetyPAT Plus A B P/N:

Instruction Manual. Digital Panel Meter Model 3126 CAUTION. Code Type of T/C Measuring Range Display Range Accuracy

Digital/Analog Megohmmeter Model 1026 USER MANUAL

User Guide. Model Insulation Tester / Megohmmeter. Introduction

Dawson DDM190D. Digital Multimeter User s Manual

Distributor. Kewtech Corporation Limited 76 St. Catherine s Grove Lincoln LN5 8NA KEWTECH

Model ST Instruction Manual. Digital Insulation Tester. reedinstruments. www. com

User's Manual Digital High Voltage Insulation Tester Model

PRM-2 PHASE SEQUENCE TESTER PRM-3 PHASE SEQUENCE & MOTOR ROTATION TESTER User s Manual

Model Insulation Tester / Megohmmeter. User Manual

Digital/Analog Megohmmeter Model 1026

POWERED BY KT71 / Portable Appliance Tester. Instruction Manual

Contents. Introduction Inspection Notes on Safety Precautions. Chapter 1 Overview Product Overview Names of Parts 2

BENCHTOP INSTRUMENT BENCH TYPE DIGITAL MULTIMETER DM-1140B OPERATION MANUAL V2.0

Digital Insulation Resistance Testers. you can depend on

Safety design conforming to the following provisions

EVS RP6020. Instruction Manual

Electrostatic Fieldmeter

Instruction manual. High voltage insulation resistance tester KEW3121B/3122B

AMB V Insulation Resistance Tester. Users Manual. For detailed specifications and ordering info go to

Air duct switching damper

MODEL 3567A. Digital MΩ Tester. Instruction Manual

User Guide. Model Insulation Tester / Megohmmeter

User's Manual. High Voltage Megohmmeter. Analog Insulation Tester plus AC Voltage and Continuity Tests. Model

User Guide. Model Insulation Tester / Megohmmeter

TMD90A Dual Input Digital Thermometer

Lumitester PD-20 Control Kit

Instruction Manual. 99 Washington Street Melrose, MA Fax TestEquipmentDepot.com. Model 308A Digital Insulation & Continuity Meter

Digital Apex Locator. ipex OPERATION MANUAL OM-E0285E

Flue Gas Analyzer IMR 1100F

BATTERY OPERATED DIGITAL MILLI-OHMMETER

TESTER SET SOCKET & VOLTAGE

TOWA SEIDEN INDUSTRIAL CO., LTD.

Safety design conforming to the following provisions

99 Washington Street Melrose, MA Fax TestEquipmentDepot.com. Instruction Manual. Model 2831D 4 ½ Digit True RMS Digital Multimeter

INSTRUCTION MANUAL MARTINDALE CM52 CLAMP METER. ELECTRIC Trusted by professionals. Other products from Martindale:

Filterpack FR-BFP2-(H)0.4K to (H)15K

Transmitter CSA-591 Instruction Manual

NEW 15KV HIGH VOLTAGE INSULATION RESISTANCE TESTER MODEL KM 7015 IN FEATURES : CAT IV 600V. Short Circuit Current 5mA.

MARTINDALE MARTINDALE IN2001/IN2003 INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL IN2001/IN2003 INSULATION & CONTINUITY TESTERS

KMP Insulation-Continuity Tester. Users Manual

PY-11 Voltage & Continuity Tester

Digital Electronic Torque Wrench. Operating Manual. Model 60648

IN1001/IN1003 ANALOGUE INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL IN1001/IN1003 ANALOGUE INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL

Item ref: UK & UK MTB01 & MTB02 DIGITAL MULTITESTERS. User Manual

Component Test Fixture

4-20mA DC PROCESS CLAMP METER

SDM320D / SDM320A. Single phase din rail meter SDM320D / SDM320A user manual

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions.

2-Color Display High-Precision Digital Pressure Switch

MCA-700Ⅱ JAPAN BONKOTE CO.,LTD. Instruction manual. Preparation in April The 1st edition

ION JET NOZZLE NIH-55

Pneumatic Drive Type Drill Bit Breakage Detection Sensor. DFM3 Series. The World's First!! Pneumatic-Drive Type. Catalog / Instruction Manual US.PAT.

0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h)

Declaration of Conformity

Instruction Manual IVT-10 / IVT-20 Voltage Tester

DIGITAL EARTH RESISTANCE Model KM 2030

MODELS 100/200/400 AVIATION LIFE SUPPORT EQUIPMENT TESTER

FALL-OF-POTENTIAL GROUND RESISTANCE TESTER

RP Instruction Manual

POWER REGULATOR LD -40PSU

For technical questions and replacement parts, please call

OPERATING INSTRUCTIONS

INSTRUCTION MANUAL DM5B Fax: (503)

DT33B/C/D OPERATOR S MANUAL LIMITED WARRANTY AND LIMITATION OF LIABILITY

cause injury to humans and other physical damage. : Gives information that does not fall in the WARNING or CAUTION categories.

Digital Low Resistance Ohm Meter

Series ZSE30/ISE30. High Precision, 2-color Display Digital Pressure Switch. With One-touch fittings are newly introduced. PSE

SL101 Manual_SL101 User Manual 05/10/ :06 Page 1. Instruction Manual

Installation and Operating Instructions. Solar System Controller ISC3020

USER MANUAL. Insulation Tester + DMM. Model MG320

KTD30 Digital Insulation and Continuity Tester. User Manual. kewtechcorp.com

Cable Length Meter INSTRUCTION MANUAL

MARTINDALE INSTRUCTIONS ELITE FUSE FINDER KIT ELECTRIC. Trusted by professionals. 4.4 Storage Conditions

Monicon Instruments Co., Ltd. CHR-1285/2485 CHR-1285/2485 BATTERY CHARGER

PROVA 1011 Solar System Analyzer

True RMS Autoranging Multimeter

UP Series Miniature Pilot Lights

PIECAL 520B & 521B Thermocouple Source Operating Instructions

MULTI FUNCTIONAL COUNT CHECKER MODEL Poka Patrol CNA-4mk3

Autoranging Multimeter

Transcription:

INSULATION RESISTANCE TESTER FOR PHOTOVOLTAIC SYSTEMS MSEI-200C INSTRUCTION MANUAL Thank you for your purchasing our model MSEI-200C INSULATION RESISTANCE TESTER FOR DC CURRENT CIRCUIT OF PHOTOVOLTAIC SYSTEMS. Before use the instrument, read this instruction manual thoroughly and operate it correctly. Keep this instruction manual carefully to take out whenever you need. MULTI MEASURING INSTRUMENT CO., LTD. Akihabara Murai Bldg. 7F, 1-26 Kanda Sakuma-cho, Chiyoda-ku, Tokyo 101-0025 JAPAN TEL: +81-3-3251-7013 FAX: +81-3-3253-4278 Website: http://www.multimic.com E-mail: multi@multimic.com

SAFETY SUMMARY observe by all means To use this instrument safely, read this "SAFETY SUMMARY" carefully and apply the instrument correctly. The CAUTIONs and WARNINGs which appear on the following pages are stated to prevent the operator & other people from the dangers and their properties from the damages beforehand.! WARNING : This symbol indicates the contents "Possibilities of the death or the serious wound can be supposed" caused from mis-operations.! CAUTION : This symbol indicates the contents "Possibilities of the injury or only the material damage can be supposed" caused from misoperations. OPERATION ENVIRONMENT CAUTION! Do not use or storage this instrument under the condition of direct rays of the sun, high temperature & humidity and or condensation, as it may cause the deformation and or the isolation defect of the instrument. Do not use this instrument in the environment influenced by acids, alkalis, organic solutions, corrosive gas, etc. Do not use or storage this instrument where the mechanical vibration can be directly transmitted, as it may cause defect of the instrument. Do not use this instrument nearby the appliances which generate strong magnetic field and or electric field, as it may cause mis-movement of the instrument. This instrument does not have the water/dust-proof structure. Do not use this instrument in the environment with a lot of dust and drops of water, as it may cause defect of the instrument. OPERATION CONDITION & CONNECTION! WARNING POSSIBLE ELECTRICAL SHOCK This instrument is for the use of low voltage circuit. Do not make measurements of power lines carrying more than DC 1000V. Before use, check and confirm the voltage of circuit to be measured. POSSIBLE ELECTRICAL SHOCK OR ACCIDENT Do not handle the instrument in the rain, at humid place, with a drop of water and or with wet hands. - 2 -

1. GENERAL This insulation resistance tester (MSEI-100C) can measure insulation resistance of DC current circuit in PV systems (between PV module and power conditioner) on the live line and can distinguish the deteriorated part between Power Phase, Neutral Phase, P/N Phase and or PV modules. 2. BEFORE USE After opening the package, check the appearance of instrument and confirm if there is no lack of accessories. If any damage and or any lack has been found, contact the dealer you bought this instrument. Accessories Voltage Input Connector(Red, Black, and, Green) Instruction Manual Carrying Case Battery (LR6) 1 set 1 pce. 1 pce. 4 pcs. 3. CONNECTION & OPERATION OF CONNECTOR CORD & ACCESSORIES! WARNING Connect voltage input cords to the live lines after connected to the instrument. Be careful that the short circuit and or electric shock accident might be caused from slip off of the clips and touch of them between 2 lines. Before use, check the connecting cables (including AC adaptor) about disconnection, contact failure, breakage of coating conductor, etc. In case of finding any unusual point after inspection, do not use these accessories.! CAUTION For the safe operation Do not drop and or give the hand shock to the instrument. Do not put heavy material to each cable and do not modify it. - 3 -

4. NAME OF PART & EXPLANATION 42 1 2 190 3 5 4 6 140 7 8 9 MSEI-200C (Name of Part & Explanation) 1Battery Case 2AC ADP Jack 3Contrast Volume 4Left, Right, Up, Down Switch : For battery installation : For connecting AC adaptor(option) : For adjusting display contrast : For moving cursor on display and setting value 10 5Display (LCD) : 20 letters/characters x 4 lines LCD, for displaying settings item for measuring condition and numeral values. 6Input Switch (ENT) 7Power Switch (POWER) : For inputting measurement condition or value : For switching ON and OFF. Automatically off in approx. after 40 minutes 8Menu Switch 9Insulation Resistance Lamp 10Voltage Input Terminal : For returning to initial screen : For displaying judgment for insulation condition by LED : For connecting Red lead to P Phase, Black lead to N Phase, and Green lead to E Phase. - 4 -

5. OPERATION PROCEDURE 5.1 Preparation before use 1) Place the battery 1. Unscrew and slide a battery cover to remove a battery cover(as shown at right) 2. Place the battery observing correct polarity as indicated in the battery compartment. Use four LR-6(AAA) batteries. 3. Install the battery cover and tighten the screws.! WARNING It may cause electric shock. Never replace the battery during a measurement. Be sure to set back the battery cover to original position. Never make measurement when left the battery cover opened.! CAUTION It may cause malfunction. When the instrument will not be in use for a long period, place it in storage after removing the batteries. Do not mix old and new batteries. Do not use the battery not specified in the instruction. - 5 -

2) Use AC adaptor for long time use. 1. Insert the plug of AC adaptor to the jack of the instrument body(ac ADP). 2. Connect AC adaptor to the outlet(ac 100-240V). or AC240V Built-in battery is supplementary for unexpected power failure. Normally, use AC adaptor included in the package. MSEI-200C! WARNING Do not input power to AC adaptor except the indication, as it may cause a fire. Do not touch the plug with wet hands or in the condition of water drops, as it may cause electrical shock. Do not use AC adaptor (options) other than accessory, as it may cause damage of instrument and or electrical accident.! CAUTION Protection of Standard Resistor MSE-200C has the standard resistor internally and the protection circuit is installed, as the power to be loaded to the standard resistor will exceed the rating in case of lower insulation resistance. In case that the protection circuit works during operation, the measurement will be proceeded with over on measuring voltage display and 0S on the remaining time display. When the protection circuit operating, the calculation of insulation resistance values will be done by fixing Vrp & Vrn to 400.0V. - 6 -

5.2 OPERATION PROCEDURE 1) Once press POWER switch 7 [MSEI-200C Ver.] appears on the display and [ZERO setting] will be displayed for a few seconds after lightening LED of display judgment. Then, [Top Menu](initial display) will appear. Initial Screen (Top Menu) Measure Operate Memory Set Configuration * In several seconds during [ZERO setting] on the display after power on, zero adjustment is automatically done in the internal MSEI-200C. Do not operate voltage input by test leads during these seconds. Connect each voltage input lead clip to respective measuring point after [Top Menu] (initial display) appeared. 2) Connection of Test Leads (Standard Accessory) Connect test lead(red) to P phase, (Black) to N phase and (Green) to E of the instrument body. Connect alligator clip of each test lead to measuring point. PV Systems Modules Modules Modules P Phase (+) Red Black N Phase(-) Disconnector Green GND MSEI-200C Power Conditioner Make off the disconnector between PV panels and power conditioner. - 7 -

3) Display before measurement Set the cursor to Measure and press ENT switch 6 once. Display will become as under: Internal Standard Resistance Generated Voltage P Phase Voltage N Phase Voltage Rr : *.***kω 05/17 V : ***.* V 13:38 Vrp : ***.* V 30S Vrn : ***.* V 30S Present Time Measuring Time 4) Start of Measurement Press again ENT switch 6 and then, measurement will start. Vrp and Vrn are measured at the point of OS by decreasing each measuring time. Display Example of Measurement Rr : 4.966kΩ 05/17 V : 300.0 V 13:40 Vrp : -497.1m V 0S Vrn : ***.* V 28S LO Display for Low Battery (Replace the batteries in this case) To stop the measurement on the way, press ENT switch 6 once. To start the measurement again, press ENT switch 6 once again. Top Menu display will appear before or during measurement in case of press MENU switch 8. 5) Display of Measurement Result Measurement will be made at respective points by measuring time. Respective insulation resistance values are displayed and the insulation condition lamp lightens. (1) Good (Green) Lamp Lightening Display Example of Measurement Result Generated Voltage V : 300.0 V 05/17 P Phase Insulation Resistance R p : 10.00MΩ 13:43 N Phase Insulation Resistance R n : 10.00MΩ Green lamp lightens when Rp (P phase insulation resistance), Rn (N phase insulation resistance) & Rpn (insulation resistance between PN phase and PV modules), all are more than 1MΩ. - 8 -

(2) No good (Red) Lamp Lightening In case that the judgment is as no good, the corresponding lamp (P phase failure, N phase failure, PN phase failure) lightens. To start the measurement again, press ENT switch 6 once again, Top Menu display will appear before or during measurement in case of press MENU switch 8. (3) Series Panels Numbers Input (Orange) Lamp Lightening Generated Voltage P Phase Insulation Resistance N Phase Insulation Resistance PV Module Numbers Display Example of Measurement Result V : 300.0 V 05/17 R p : 0.20MΩ 13:51 R n : 0.50MΩ Set Module : 12 In case that there is insulation resistance failure, [Serial Panel Number Input Lamps] (Orange) lightens and [Set Module] is displayed on LCD. In case that the alteration for PV module numbers requires, the change of numbers can be made by UP & DOWN switch 4. The setting limit is 2~28. After setting, press ENT switch 6 and the judgment result is displayed. In case that the judgment is good, [Good] lamp lightens. In case that the judgment is no good, the corresponding lamp (P Failure, N Failure, PN Failure, Rpn Failure) lightens. In case of Rpn Failure, Rpn lamp (Red) lightens and the failure point is displayed on LCD at the same time. Display Example of Judgment Result Generated Voltage V : 300.0 V 05/17 P Phase Insulation Resistance R p : 0.96MΩ 13:57 N Phase Insulation Resistance R n : 5.02MΩ Insulation Resistance between Modules Rpn : 0.63MΩ PS : 6 Module Failure Point PS: is the number from P direction. In case of 1, it means insulation failure between 1 and 2 and in case of 6, between 6 and 7. To start the measurement again, press ENT switch 6 once again. Top Menu display will appear before and during measurement in case of press MENU switch 8. - 9 -

5.3 FUNCTION SETTING 1) Measurement Time Setting (Set Timer) Measuring time means the time after the connection of instrument internal standard resistor to each phase to measure voltage between standard resistors. The setting times are 30 sec., 180 sec., 300 sec., 600 sec., and 900 sec. (1) Press DOWN switch twice at the initial display (Top Menu) and set the cursor to Set Configuration and then, press ENT switch. Operate Memory cannot be used Initial Display (Top Menu) Measure Cursor Operate Memory lightening Set Configuration (2) Set Timer 30 sec. is displayed and Press ENT switch. ENT Switch Set Timer 30sec (3) Using UP & DOWN switch 4. Set the cursor to appropriate point and then, Press ENT switch once. ENT Switch (Set Timer) 30sec 600sec 180sec 900sec 300sec (4) Measuring Time will be set. ENT Switch Set Timer 180sec 2) Present Time Setting (Now Time) (1) Press DOWN switch twice at the initial display (Top Menu) and set the cursor to set Configuration and then, press ENT switch. Operate Memory cannot be used. Initial Display (Top Menu) Measure Cursor Operate Memory Lightening Set Configuration ENT Switch - 10 -

(2) Set Timer 30 sec. is displayed and press DOWN switch. (3) Now Time (System) is displayed. Press ENT switch and set the present time. Set Timer 30sec DOWN Switch Now Time(System) 2013/05/17 14:26 (4) By UP switch and DOWN switch, set the numerical value and by RIGHT switch, move the underline (_) to the right. After adjusted minute, press ENT switch according to the time-signal. (Now Time) ENT switch 2013/05/17 14:26 After finished all setting, press MENU switch once and return to initial display (Top Menu). Replace of Batteries When [Lo] is displayed, replace the batteries (page ), as the voltage of batteries are getting low. When the display does not appear even by pressing Power Switch. The display may get thinner at the adjustment of CONTRAST. Adjust the display contrast by turning the contrast knob to the left. Check the voltage of batteries.! WARNING Voltage Input Do not input voltage by test lead during a few second displaying ZERO Setting on LCD after power-on, as zero-adjustment is being done automatically at the inside of instrument. Apply the clips of each voltage input lead to the measuring point after appeared Top Menu (initial display) on LCD. - 11 -

6. SPECIFICATIONS 6.1 MEASUREMENT SPECIFICATIONS 1) Detection Method : DC Voltage measurement between the earth by standard resistor. 2) Measurement Items : Generated Voltage (DCV), P Phase Insulation Resistance, N Phase Insulation Resistance, PN Phase Insulation Resistance, Insulation Resistance between modules, Standard Resistance Value. 3) Measuring Range : Generated Voltage (V): DC0.01V~599.9V (5 range auto) Insulation Resistance (MΩ): 0.01 MΩ~19.99 MΩ, OVER (exceeded 19.99 MΩ) P Phase Insulation Resistance (Rp) N Phase Insulation Resistance (Rn) Insulation Resistance between P Phase, N Phase and Module (Rpn) Insulation resistance values are calculated by the formula. 4) Judgment Method When the insulation resistance value is getting lower than 1.00 MΩ, LED of failure point lightens. In case that there is no problem for insulation resistance value, [Good] LED lightens. LED Color: Good LED-Green No Good LED-Red Judgment whether PN Phase or between modules is made by calculation from numbers of module. 5) Display Part : 20 letters/characters x 4 lines. LCD 6) Actual Time Display : Year, month, date & time on the display 7) Actual Time Accuracy : ±200ppm±10 sec. (at 25 ) 8) Measurement : Generated Voltage: ±1%rdg±10dgt Accuracy Insulation Resistance 0.01MΩ~10MΩ: ±5%rdg 10.01 MΩ~19.99 MΩ: ±10%rdg - 12 -

5.2 FUNCTION SPECIFICATIONS 1) Measuring Time : 30 sec., 180 sec., 300 sec., 600 sec., and 900 sec. Setting 2) Time Function : can set the present time 3) Module Number : can specify the insulation failure point between which modules Setting by input of PV module numbers, in case that there is insulation failure between modules, Setting Module Numbers: 2~28 4) Protection of Standard The protection circuit is installed internally, as the power will be Resistor loaded to the standard resistor will exceed the rating in case of lower insulation resistance. In case that the protection circuit works during operation, the measurement will be proceeded with over on measuring voltage display and 0S on the remaining time display. When protection circuit working, the insulation resistance value will be calculated by fixing Vrp & Vrn to 400.0V. Generated Voltage Insulation Resistance Value (Vrp&Vrn) 1000V 7.5KΩ 800V 5.0KΩ 600V 2.5KΩ V=generated voltage Rp: P phase insulation resistance Rn: N phase insulation resistance The protection circuit will work when V/(Rp+5000)>0.08 during Vrp measurement and when V/(Rn+5000)>0.08 during Vrn measurement. 5) Auto Power-off : After final switch operation, automatically power of in approx. Function 40 minutes. 6) Contrast Knob : Knob to adjust the depth of display on LCD. - 13 -

5.3 GENERAL SPECIFICATIONS 1) Operation Circuit : DC1000V PV generation circuit 2) Operation Temperature : 0 ~50, less than RH85% without condensation 3) Storage Temperature : -10 ~60, less than RH80% without condensation 4) Withstanding Voltage : AC2200V(50/60Hz)/1 minute between voltage terminal and housing case 5) Insulation Resistance : more than 100MΩ by DC1000V insulation resistance tester between voltage input terminal and housing case 6) Power Supply Source : 1) AA alkaline battery LR-6x4 2) AC adaptor (option) 7) Current Consumption : Approx. 30mA 8) Dimension & Weight : 190(W) x140 (H) x42 (D), approx. 600gs 9) Accessories : Voltage Input Cable 1 set (One each Red, Black, Green) Carrying Case 1 pce. Instruction Manual 1 pce. AA alkaline battery LR-6x4 7. Repair Service When requesting for repair service, please bring the instrument directly to the dealer where you bought. When mailing the instrument, always pack it in its original or equivalent packing materials to avoid any damage during the transportation and also put together with documents showing your name, address, phone number and defect point. 8. Warranty This instrument is sent out from our factory after the sufficient internal inspections but if you find any defect due to the fault in our workmanship or the original parts, please contact the dealer where you bought the instrument. The warranty period is 12 months from the date of purchase and instrument shall be repaired at free of charge, provided that we judge the cause of defect is obviously resulted from our responsibility. - 14 -