NOVATEK-ELECTRO LTD Research-and-Manufacture Company SINGLE PHASE VOLTAGE MONITORING RELAY RN-113 USERS MANUAL

Similar documents
Legat-65. Voltage Stabilizer Technical Certificate. NOVATEK-ELECTRO LTD Research-and-Manufacture Company

UNIVERSAL SINGLE PHASE INDUCTION ELECTRIC MOTOR PROTECTION UNIT

NOVATEK-ELECTRO LTD Research-and-Manufacture Company Voltage Stabilizer Legat-15

NOVATEK-ELECTRO LTD Research-and-Manufacture Company Voltage Stabilizer Legat-35

UNIVERSAL SINGLE-PHASE INDUCTION ELECTRIC MOTOR PROTECTION UNIT WITH THE POSSIBILITY OF SOFT START

NOVATEK-ELECTRO LTD Research-and-Manufacture Company. Legat-5M. Voltage Stabilizer. Technical Certificate.

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Control panel. For 3 three-phase electric pumps with thermal protection and exchanger

Components for EEx e Panels

Power Electronics. Motor brake relay GA 9031 ministop

M440 MOTOR PROTECTION, EARTH FAULT LOCKOUT & MANAGEMENT RELAY VERSION 3.5 NINGI SERVICES (PTY) LTD

Contactors and Overloads MC

POWER SUPPLY aps-412_en 06/16

Application Engineering

Ktec Contactors and thermal overloads

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

TECHNICAL SPECIFICATION

Bulletin 825 SMM Smart Motor Manager

Essential equipment for all your requirements

Time scale: from 0.05 s to 100 h Multi-function Plug-in for use with 96 series sockets. Relay + socket. Wiring diagram (without control signal)

AUTOMATIC STANDBY ACTIVATION. Operation Manual

Approved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN

7 Switching Equipment and Control Devices

TA-05/C. Instruction and Operation Manual. valid for art.-no.: F-TA-05/C-ISO. (start at modification No. 1601)

DEVICE STATE/BYPASSED FAILURE OVERLOAD

KD LV Motor Protection Relay

Application Engineering

INTER PLANT STANDARD STEEL INDUSTRY NO CORRESPONDING IS

DIP SWITCH BASED EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE CURRENT TRANSFORMER (CBCT / ZCT) EL SERIES

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

Time scale: from 0.05s to 100h Multi-function Plug-in for use with 90.02, 90.03, and sockets

5. OVERCURRENT RELEASE (OCR)

DIFFERENTIAL THERMOSTAT

5. OVERCURRENT RELEASE (OCR)

Shenzhen Alpha Inverter Co., Ltd. ALPHA6300V Series Special AC Drive for Tension Control

Technical Information

Industrial contactors CTX-1

MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGERS. MicroStart. IBC control

HIGH POWER SOLENOID DRIVER 1

Data sheet. CI-tronic Soft start motor controller Type MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 50 I-O 520B1443

KCR1. Kiln Controller Handbook. Kilncare Ltd. The Kiln Works 907 Leek New Road Baddeley Green Stoke-on-Trent Staffordshire, ST2 7HQ United Kingdom

ENGINE PROTECTION BOARD PDM1

HWP Protection Board

Starters. Overview. Siemens caters with following types of starters to agricultural and industrial sector.

Series Motor Protection

Exercise 4-1. Friction Brakes EXERCISE OBJECTIVE DISCUSSION. Understand the construction and operation of friction brakes.

BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!

Electronic Timer - Series Micon 225 Signal Based Multi - Function

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

REVISED ATM72 Auto Transfer Module

MAKING MODERN LIVING POSSIBLE. Pressure switch BCP. Technical brochure

CI-tronic Soft Start Motor Controller Type MCI 25B with Brake

Flight Systems. Replacement for KASSEC DESCRIPTION

MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER. MicroMax. Article no. F IBC control Made in Sweden

Electric actuators type EA25-250

ECONOMISER SERIES E2T USER MANUAL

SWA-24X2C PID Temperature Controller with Timer (SWA-2442C/2452C)

FEED WATER REGULATOR EVM-1F FOR CONTINUOS REGULATION

Emotron DCM Control Unit

XM1 - Motor protection relay

Blue Air. Commercial Refrigeration Inc. Installation & Operation Manual Chef Bases

KC5 PV Charge Controller Instruction Manual

Indoor air quality sensor.

Power Electronics. POWERSWITCH Semiconductor Relay / - Contactor With Load Circuit Monitoring PH 9270

MANUAL. MiniMax V / VK

Electric Actuated Ball Valves 3-Piece Stainless Steel, Full Port 1/4 to 3 inch NPT

Electric Actuated Ball Valves 2-way Stainless Steel, Full Port 1/4 to 2 inch NPT

SBC V In-Car Charger Dual Input (Solar MPPT & DC)

BM16LP. Thanks for your purchasing the cell monitor for your vehicle.

fluid technology temperature sensors 1600 intelligent temperature sensor membrane keyboard, USB opto interface

EG Series Screw Air Compressors


SAFETY FUSES PP57U SERIES Technical description and user manual

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller

Energy Division

Soft Starter. Types RSBD. Product Description. Type Selection. Ordering Code RSB D E V 61 HP

USER S MANUAL GPC SERIES LOW VOLTAGE DISCONNECT. Galley Power LLC.

Automatic Sliding Door Retrofit Drive Assembly. Installation Manual DoorControlsUSA.com

RVS-DN Digital Reduced Voltage Motor Starter

Installation & Operation Manual Chef Base

CIRCUIT-TEST OPERATION MANUAL. Switching Mode Power Supply with Remote Sensing PSC V 5A / 0-27V 3A / 0-36V 2.2A (80W)

Braking Devices BR 230/ Assembly- and Commissioning Instructions

use & maintenance MANUAL Rotar Cube Rotar Cube - Cod.197AA Rev.01 01/2008

MULTI FUNCTIONAL COUNT CHECKER MODEL Poka Patrol CNA-4mk3

Safety Control HR1S-AC. Safety Relay HR1S-AC

ER100 Series OUT. Specifications. Working fluid Working pressure range Control pressure range. Input voltage 2 wire Input impedance.

ISO 9001, ISO1400, ISO13485, CE and WHO-GMP certified.

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves Electrically modulating GB-M(P) 057 D01

BOX A3 TEST REL. DATE R.T. Check and Approval

1. SPECIFICATIONS OF RK - STICS

Continental Hydraulics Installation Manual CEM-AA-A

INSTRUCTIONS MANUAL CLAM BALL / CLAM CAP

Softstarters Type PSS. Softstarters. General information

SWA-2441/2451 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL

From the dawn of Excellence emanates the high noon of Performance.

Pneumatic Timer. TECHNICAL DATA Display digit roll s, s or s, depending on version Operating pressure 2...

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

DKG-215 MANUAL AND REMOTE START UNIT

Three-Phase Soft Starters

ENGINEERING FLOW SOLUTIONS PROTECTION & CONTROL PANELS. Control ST series

Transcription:

LTD Research-and-Manufacture Company SINGLE PHASE VOLTAGE MONITORING RELAY USERS MANUAL

1.APPLICATION Voltage monitoring relay (hereinafter ) is designed to turn OFF home used consumer equipment or industrial power load in case of unallowable voltage drops or fluctuations. And when the voltage parameters returns back to normal values after the fault it automatically turns ON the power load with the user adjusted time delay (autoreclosing time). If power load is less than 7,0 kw (32A) then may operate with the power load directly using its own output terminals; If power load is more than 7,0 kw (32A) then it should be commutated using contactor of appropriate power rating. So operates with the magnetic coil of the contactor and thus turn ON/OFF the power load when necessary. Kindly note that contactors of appropriate power rating should be chosen by User and not supplied along with. has four independent modes of operation: 1. Minimal/Maximal voltage protection relay; 2. Minimal voltage protection relay; 3. Maximal voltage protection relay; 4. Turn ON time delay relay. Digital display of indicates the value of acting voltage level and the remaining time to Open/Close (ON/OFF) state of the output contacts. The position of the contacts is additionally shown using green color LED indicator. 1-4 - input terminals 5-7- output terminals 8- ON/OFF state indicator showing the position of the output contacts (power load) 9- toggle switch (ON/OFF): Maximal voltage tripping (Umax) 10- toggle switch (ON/OFF): Minimal voltage tripping(umin) 11- Digital LED segment display 12- Autoreclosing time delay (Ton) 13- Minimal voltage tripping threshold (Umin) 14- Maximal voltage tripping threshold (Umax) Figure 1 Front panel controls and dimensions diagram 2. TECHNICAL CHARACTERISTICS

- 3 - Rated voltage, V 220 Rated voltage frequency, Hz 48 52 Adjustment ranges: - minimal voltage tripping range (Umin), V - maximal voltage tripping range (Umax), V - autoreclosing time delay (Ton), sec Fixed tripping time delay in case maximal voltage fault (Umax) detected, sec 1 Fixed tripping time delay in case minimal voltage fault (Umin) detected, sec 12 Fixed tripping time delay in case of voltage decrease more than 50V than the adjusted minimal voltage tripping threshold (Umin), sec 0,2 Fixed tripping time delay in case of voltage increase more than 30V than the adjusted maximal voltage tripping threshold (Umax), sec 0,2 Maximal commutation current (active power load), A 32 Tripping Voltage level accuracy, V 3 Maximal current at ~ 250V AC Specification of the Output contacts 1-2-3 Maximal power when contacts are closed Maximal allowed AC/DC Voltage Maximal current at 30V DC Cos = 1,0 32 A 7200 VA 250/110 V 30 А 3. START-UP PROCEDURE AND CONNECTION 160 220 230 280 5 900 Minimal operation voltage level at which will keep working, V Maximal operation voltage level at which will keep working, V 100 420 Voltage hysteresis, V (no less than) 5 Operational temperature range, С from -35 to + 55 Storage temperature, С from -45 to + 70 Total power consumption, ma 15 Commutation life of the output contacts: - under 16A power load, times (no less than) - under 5A power load, times (no less than) 100 000 1 000 000 Outer dimensions, (3 S-modules),mm 52,6 х 90 х 66,3 Weight, kg, no less than 0,150 Mounting to standard 35mm DIN rail ALL CONNECTIONS MUST BE DONE ONLY ON REENERGIZED AND ACCORDING ALL SAFETY REGULATIONS 3.1 Using toggle switches on the front panel set necessary mode of operation(see Section 4); 3.2 In case of using as Minimal/Maximal protection relay or Minimal protection relay connect wires according the Wiring Diagram (see below). If is being used as a maximal voltage protection relay power load (contactor coil) should be connected to terminals 1 and 3. If power load is less than 7kW (32A) then it could be commutated directly by the output contacts of the ; if the power load is more than 7 kw then it should be commutated using contactor of appropriate rated parameters and the should operate with the magnetic coil of the contactor. 3.3 Connect to the power circuit. For easier wiring purposes there are coupled input terminal contacts 4-4 and 5-5. 3.4 By spinning the knobs on the front panel set the required Minimal and Maximal voltage tripping thresholds (Umin and Umax) and set necessary turn ON time delay (Ton). Please pay attention that the Ton time should be adjusted taking into consideration the technical documentation and requirements of the protected power load for example airconditioners, refrigerators and other compressor containing equipment usually need 3-4 minutes pause before turn ON again after they were disconnected. 3.5 Give the power supply to the input terminals of the and by spinning the adjustment knobs set precisely the required values for the Umin, Umax and Ton. When spinning the knobs on the LED digital display it is shown the exact value of the adjusted parameter.

L1 N ~220V/50Hz PROTECTED POWER LOAD LESS THAN 32A PROTECTED POWER LOAD OF ANY CAPACITY Variant A If power is less than 32 A, then RN113 operates with the power load directly by output terminals Variant B If power is more than 32 A, then RN113 commutates the power load by operating the magnetic coil of the contactor. Figure 2 Connecting diagram 4. OPERATION MODE 4.1 has several functional states: Normal operation mode: Power load is ON, Green LED indicator ON. Digital LED display shows measured voltage value; Alarm mode: Power load is OFF, Green LED indicator OFF. Digital LED display shows blinking value of the measured voltage; Indication of the remaining time to turn ON the power load (Ton): Power load is OFF, Green LED indicator OFF. Digital LED display shows the remaining time to turn ON the power load (in seconds) and dot is being displayed in the lower digit. After the Ton time elapse will return to Normal operation mode if voltage parameters on the input terminals are within the permitted range adjusted by the user. 4.2 User may select four independent operation modes: - Minimal/Maximal voltage protection relay: This mode is active when both toggle switches (Umin, Umax) are set to the Left position. In case the voltage level will get lower/higher than the user adjusted allowable values the power load will be turned OFF. will turn ON the power load with the user preset time delay (Ton) only after voltage parameters returned back to normal. - Minimal voltage protection relay This mode is active when toggle switch Umin is set to the Left position and Umax is set to the right position. will turn OFF the power load if voltage level will get lower than the Minimal voltage threshold preset buy the user. - Maximal voltage protection relay This mode is active when toggle switch Umax is set to the Left position and Umin is set to the right position. will turn OFF the power load if voltage level will get higher than the Maximal voltage threshold preset buy the user. - Turn ON time delay relay This mode is active when both toggle switches (Umin, Umax) are set to the Right position. 4.3 At first start-up procedure At first start-up or after the was completely reenergized additional time delay of 0,3-0,4 sec is required for self testing. During this time LED display indicates StA and then start showing the remaining time to turn ON the power load. If is being used as maximal voltage protection relay then no time delay for the first start-up. 4.4 Minimal voltage protection relay

- 5 - If was initially reenergized or the power load was OFF due to the wrong voltage parameters then after correct voltage appear on the input terminals and after the time delay Ton contacts 1,3 will open and contacts 2,3 will close. If input voltage get lower than minimal voltage threshold for more than 12 sec becomes to Alarm mode contacts 1,3 close and contacts 2,3 open and thus the power load should be turned OFF. If input voltage gets 50V lower than the minimal voltage tripping threshold turns OFF the power load within 0,2 sec (accelerated tripping time). After the recovery of the voltage parameters to the value of hysteresis (4-5V) 4.5 Maximal voltage protection relay Power load (contactor coil) should be connected to the output terminals 1, 3. When normal voltage applied to the input terminals of the state of the output relay doesn t change so the stay in the cold state: contacts 1,3 are closed and contacts 2,3 are opened. If input voltage gets higher than the maximal tripping voltage threshold for more than 1 sec or accelerated tripping time of 0,2 sec is applied if the voltage is 30V higher than the maximal tripping threshold then the comes to Alarm mode contacts 1, 3 open and contacts 2,3 close. When voltage level decrease lower than the maximal tripping voltage threshold to the hysteresis value 4-5V 4.6 Minimal/Maximal voltage protection relay If was initially reenergized or the power load was OFF due to the wrong voltage parameters then after correct voltage appear on the input terminals and after the time delay Ton contacts 1,3 will open and contacts 2,3 will close. If input voltage get lower than minimal voltage threshold for more than 12 sec becomes to Alarm mode contacts 1,3 close and contacts 2,3 open and thus the power load should be turned OFF. If input voltage gets 50V lower than the minimal voltage tripping threshold turns OFF the power load within 0,2 sec (accelerated tripping time). After the recovery of the voltage parameters to the value of hysteresis (4-5V) If input voltage gets higher than the maximal tripping voltage threshold for more than 1 sec or accelerated tripping time of 0,2 sec is applied if the voltage is 30V higher than the maximal tripping threshold then the comes to Alarm mode contacts 1, 3 open and contacts 2,3 close. When voltage level decrease lower than the maximal tripping voltage threshold to the hysteresis value 4-5V 4.7 Turn ON time delay relay In this mode voltage parameters are not controlled and will turn ON the power load with the user preset time delay (Ton) if the input voltage parameters are within the operation voltage range. If the input voltage is more than 160V will turn ON the power load after the delay time will finish. If the voltage will get lower than 152V will go to Alarm mode contacts 1,3 close and contacts 2,3 open and thus the power load should be turned OFF. 5. WARRANTY AND CLAIMS CONDITIONS Novatek-Electro Ltd. company warrants a trouble-free operation of the device within three years from the date of sale, on condition that following terms are provided: -- the proper connection; -- the safety of the inspection quality control department seal; -- the integrity of the case, no traces of opening, cracks, spalls etc. 6 TRANSPORTATION Transportation of in package may be effected by any type of transport according to the transportation rules and regulations valid for such mode transportation. During transportation, shipping and storing in a warehouse must be protected form blows, shocks and moisture. 7 QUALITY ASSURANCE NOTES The multifunctional time delay relay has been manufactured and accepted in conformity with the requirements of current technical documentation, and is approved fit for operation.