LUNERA BALLASTLED TECHNOLOGY AND POWER FACTOR

Similar documents
LUNERA BALLASTLED TM TECHNOLOGY AND POWER FACTOR

Electrical Power Electric power electrical electric power Electric power electric electric

LANCE-KASHIAN & COMPANY River Park Plaza Parking Lot Lighting Retrofit Fresno, CA May 21, 2013

Constant wattage for high intensity discharge (HID) lamps

Understanding Electronic UltraMax HID Ballasts

Pump ED 101. Power Factor (Part 2) - - Electricity Behaving Better

Working Principle of Power Saver as per Manufacture:

Alternator as a voltage Generating source and its response to the leading power factor loads

Lighting Tables for New Equipment 7/16/2008

Power Quality Luis Vargas Research Engineer 9/18/2008

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

GECAP24400V0 Capacitor For 400W MH BLST

DS-1 (Residential) Customer Charge Per electric service account $ 8.23 $ 8.23 $ 8.23 Meter Charge Per electric service account $ 6.06 $ 6.06 $ 6.

2001 TMT Associates 1

Emerging Lighting Technologies IEEE - March 21, 2001

Understanding Electronic UltraMax HID Ballasts

TECHNICAL TERMS AND ABBREVIATIONS

Lighting Tables for New Equipment 3/9/2016

Lighting Tables for Existing/Base Equipment 4/15/2011

Power Factor Correction

The simplest way to convert to LED

Lighting Tables for Existing/Base Equipment 4/15/2011

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Lucalox XO High Pressure Sodium Lamps with improved reliability Lucalox TM XO Tubular Clear 50W, 70W, 100W, 150W, 250W, 400W & 600W

Is Uncorrected Power Factor Costing You Money?

Eskisehir Light Train- Correcting Capacitive

Lighting Tables for New Equipment 2/24/2015

ELECTRICAL FUNDAMENTALS

Lighting Tables for New Equipment 1/1/2018

GE Lighting DATA SHEET. Product information. Features. Applications

Product Selection Card

Installation Planning (or what I didn t learn at meter school)

Power Factor Correction

Lighting Tables for Existing/Base Equipment 1/1/2014

DC CIRCUITS ELECTROMAGNETISM

Chapter 3.1: Electrical System

Non-Summer, First 800 kwh $ $ $ Non-Summer, Over 800 kwh $ $ $

Lucalox PSL. GE Lighting DATASHEET. Lucalox PSL Tubular Clear 230V 250W, 400W, 600W and 750W Lucalox PSL Tubular Clear 400V 600W and 750W

Volume 2 Charts, Formulas, and Other Useful Information

Lunera T-LED Lamp Family: Engineered for Quality & Reliability

White Paper. Application of Resistive/Reactive Load Banks for kva Testing

DESCRIPTION & APPLICATION

FROM YE OLDEN DAYS OF EFFICIENT LIGHTING TO TODAY S STANDARDS FOR EFFICIENCY. WE LL DISCUSS WHY EACH TECHNOLOGY WAS

Power Quality and Energy Management

Technical Information Guide

Be Off The Grid com Inc.

Lucalox Standard. GE Lighting. Product information. Applications areas

T5 versus T8 Fluorescent Lamps. The good, the bad, & the ugly about T8 and T5 lamps

Steve Sindoni Commercial Engineer OSRAM Sylvania

Arcstream Double Ended

ELECTRONIC HID BALLASTS

Microcontroller Based Power Factor Correction Using SCR

HSI-HX / HSI-THX SA HSI-THX 400W 4K E40 SLV PRODUCT OVERVIEW DATA TABLE. Optical data

Electrical Design/Build Guide

Mandatory Fluorescent Changes For 2012

TVA Distributor Retail Rates and Comprehensive Services Program Power Factor Case Studies. Gerald Johns, P.E. Power Utilization Engineer, TVA

Philips-Advance High Efficiency Ballasts & Energy-Saving Ballast Strategies

UNIT 2. INTRODUCTION TO DC GENERATOR (Part 1) OBJECTIVES. General Objective

POWER METER. my2010 (c)

TABLE OF CONTENTS CHAPTER 1 ELECTRICAL THEORY About This Textbook...xi. Passing Your Exam...xiv. How to Use the National Electrical Code...

kvah Billing - Frequently Asked Questions (FAQs)

Single-Phase Meter Components

ABB n.v Power Quality in LV installations

Lunera Product Catalog

Customer and Utility Energy Management Fundamentals 101

The Provincial Energy Goals. BC Provincial Energy Commitments: A Practical Solution. The Municipal Challenges

Energy Saving Options for Small ISDs. Presented by Casey Stone, PE, CEM

inductors Inductors Power Inductors/Chokes Precision Wound Heavy Duty Toroidal Inductors 120 Volts... I2-I3 240 Volts... I3

UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1. UNIT 2 ELECTRICAL CIRCUITS...49 Introduction...49

Table of Contents. CHAPTER 1 ElECTRiCAl THEoRY Mike Holt enterprises, inc neC.Code ( )

CUSTOMER / ACCOUNT INFORMATION Electric Utility Customer Information (As shown on utility bill)

ELECTRONIC HID BALLASTS

Technical Report 2: Electrical Systems Existing Conditions + Building Load Summary Report

MIPSYCON 2014 Can a Grid be Smart without Communications? A Look at an Integrated Volt Var Control (IVVC) Implementation

Other Devices. Installation Contactors Z-SCH. Connection diagrams Z-SCH NO 3 NO / 1 NC. Permitted Installation Positions

General Purpose Buck - Boost Wiring Diagrams... 86

LED Lighting Initiative. Presentation for Sales February 14, Time to catch the wave!

ELECTRONIC HID BALLASTS

GE Ballast HID Electromagnetic nomenclature

LUNERA T8 LED RETROFIT KITS 1/2/3/4-Lamp Replacement Kits for 2FT or 4FT T8 Fluorescent Lamps

Southern California Edison Revised Cal. PUC Sheet No E Rosemead, California (U 338-E) Cancelling Revised Cal. PUC Sheet No.

Power Systems Trainer

GE ConstantColor CMH StreetWise

NHPUC No. 3 - Electricity Delivery Thirtieth Revised Page 4 Unitil Energy Systems, Inc. Superseding Twenty-Ninth Revised Page 4

HOKKIM. Control & Protection Relays. giving you control. Utilization: Power Factor Regulator : 14-STEP CYCLIC POWER FACTOR REGULATOR.

Lucalox Standard Tubular Clear Product Code * * 11678* LU150/100/ HO/T/E40 LU150 /100/40

EFFICIENCY IMPROVEMENT OPPORTUNITIES IN OUTDOOR LIGHTING

CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION

LIGHTING COMPONENTS FOR ENERGY SAVING

SILICONES GLOBAL SOLUTIONS

Number 9 January SECTION 1 Dimming of T12 Fluorescent lamps 2. SECTION 2 Dimming of T8 Fluorescent lamps 4. SECTION 3 Do's and Don'ts 6

50 Hz Mini/Micro Computer Regulator (MCR) Series Installation and Operation Manual

ConstantColor CMH Supermini Ultra

Product Selection Card

Electric Utility Contact Information Indiana Michigan Power

LIGHTING SAVINGS CALCULATOR USER GUIDE CONTENTS SMART $AVER CUSTOM INCENTIVES CUSTOM-TO-GO

TED 5000 USER MANUAL

International Journal of Advance Research in Engineering, Science & Technology

Table of Contents. CHAPTER 1 BASIC ELECTRICAL THEORY (Essential for Journeyman and Master s Licensing Exams)... 1

ORTRONIC System GREEN PLANET COMPANY.

Transcription:

LUNERA BALLASTLED TECHNOLOGY AND POWER FACTOR Replacing metal halide lamps in magnetic ballast-driven fi xtures with the Lunera MH HID LED Gen 2, a LED plug-and-play replacement, causes the ballast to have a leading (capacitive) power factor. In most large facilities, this leading power factor can used to offset other lagging (inductive) devices such as motors and pumps resulting in an improvement of the building s overall power architecture and fi nancial savings to the user. What is Power Factor (PF) Power factor (PF) is a measurement of the alignment of the voltage and current waveforms in an AC system, a number from 1.0 (perfect aligned) to 0.0 (90 out of phase). What causes voltage and current to be misaligned are reactive loads which can either be lagging (inductive such as motors, pumps and most power converters) or leading (capacitive), as opposed to resistive loads. Neutral (Resistive) Load Voltage and Current Aligned PF=1.0 Lagging (Inductive) Load Current Lags Voltage PF < 1.0 Leading (Capacitive) Load Current Leads Voltage PF < 1.0 Fig. 1 Power factor for a neutral (resistive) load vs. lagging (inductive) or leading (capacitive) loads. Loads seen in buildings are typically a combination of resistive and inductive loads driven by electric motors, magnetic ballasts and mixed plug loads. + = Lagging (Inductive) Load Leading (Capacitive) Load Neutral (Resistive) Load Fig. 2 When lagging and leading loads are added together, they have the helpful effect of canceling each other out as can be seen in Fig. 2. For example a 10A load with a lagging 0.6PF and a 10A load with a leading 0.7PF when added together create a combined load of 13A with a lagging PF of 0.99. Watts are a measure of the power delivered to a device. In an AC system it is: Watts = Voltage (V rms) Current (A rms) Power factor As opposed to Volt-Amps (VA) which is simply a measure of Voltage x Current Voltage-Amps = Voltage (V rms) Current (A rms)

Why do Utilities Care about Power Factor? Utilities charge for watts consumed; however their infrastructure of switching yards, transformers and distribution lines must be sized to the amount of current delivered. The effect of power factor on current can be quite dramatic: 10kW load driven at 277V with a PF of 0.95 draws a current of 38A 10kW load driven at 277V with a PF of 0.65 draws a current of 56A (46% more) As we saw earlier, lagging loads can be compensated by adding leading loads to them, or practically by applying capacitors; this is typically done at key stages in the distribution process such as the switching yard in order to compensate the lagging load and minimize the distribution losses and infrastructure requirements as shown in fi g. 3. 2 of 6 Fig. 3 Utilities use large adjustable capacitor banks at various stages in the electrical distribution grid in order to compensate for lagging (inductive) loads and minimize the distribution losses and infrastructure requirements of supporting lagging loads. Fig. 4 Compensating capacitors perform power factor compensation at a utility switching yard.

Magnetic Ballasts, Compensation and Power Factor Arc lamps, such as fluorescent and HID lamps, require a high voltage to initially strike them. But once operating, they require a stable current flow in order to maintain the arc and light output. Magnetic ballasts use large magnetics (inductors) to accomplish this stable current flow. However, inductors have the downside of delivering a low power factor load so compensating capacitors are embedded in the ballast to compensate the load. The capacitor is sized to the delivered lamp load as shown in Fig. 5. 3 of 6 Constant Wattage Autotransformer (CWA) Ballast 120V Power Switch Ballast Coil 120 Volt Power Cord BLACK WHITE BLACK 120V COM Primary Secondary BROWN GROUND TO LAMP COM Capacitor NBL Ignitor BLACK WHITE Lamp Cord (To Lamp) LAMP COM GROUND Fig. 5 Simplified magnetic ballast architecture with compensating capacitor. An inductor is used to limit power and control current to the lamp while a capacitor is used to compensate for the lagging (inductive) load and generate a high power factor. The capacitor is sized to the relative load of the lamp. BallastLED Lamps and Magnetic Ballasts When a legacy arc lamp, driven by a magnetic ballast, is replaced with a Lunera BallastLED lamp which consumes 50% to 90% less power, the resulting ballast is now over-compensated for the reduced load it is driving. Simply put, after installing the Lunera BallastLED lamp, the capacitor installed in the ballast is larger than what is needed to compensate for the lagging power factor of the inductors in the ballast. This causes the ballast to have a leading (capacitive) power factor. In most large facilities this leading power factor can used to offset other lagging (inductive) devices such as motors and pumps resulting in an improvement of the building s overall power architecture and financial savings to the user. The following case studies explore the scenario of replacing a 400W metal halide lamp with a MH HID LED lamp.

4 of 6 Case Study #1 Replacing a 400W Metal Halide Lamp with a MH HID LED LAMP The Lunera MH HID LED Gen 2 lamp consumes 162W and delivers the same mean lumens as the 400W metal halide lamp it replaces. However, as the ballast is over-compensated, the load presented to the circuit is more complex. 400 300 400W Metal Halide Halide vs. 400W v. MH Susan HID Pro LED 4.0 4.0 3.0 3.0 Input Voltage (V) 200 100 Input Voltage (V) - - (100) (200) 2.0 1.0 1.0 0.0 Input Current (A) 0.0 (-1.0) - 1.0 (-2.0) - 2.0 Input Current (A) Voltage Metal Halide Lamp Current MH HID LED 400W Lamp Current (300) (300) (-3.0) - 3.0 (400) (400) (-4.0) - 4.0 Fig. 6 Input Volt-Amps of Metal Halide v. Lunera MH HID LED Gen 2. The MH HID LED Lamp creates a substantial reduction in both consumed power (watts) as well as volt-amps (VA). However, even more valuable, it creates a leading power factor load that can be used to offset other lagging power factor loads in the facility. For example, California utility company, PG&E, charges large customers (over 400kW) adjusts their kw rate based on the power factor of their load: A 0.06% premium is added for each point that a customer s power factor (PF) falls below 0.85 A 0.06% discount is applied for each point that a customer s power factor (PF) rises above 0.85 400W HID MH HID LED Lamp Power (W) 400 156 Ballast Power (W) 45 45 Total Power (W) 445 201 Current Phase Angle (Degrees) 26 (55) Ballast (VA) 494 353 Input Voltage (V rms) 277 277 Input Current (A rms) 1.78 1.27 Power Savings -55% VA Reduction -29% Tbl. 1 Power Savings and VA Reduction of the MH HID LED Lamps. Learn more at: http://bit.ly/pgedocs

5 of 6 Case Study #2 Building-Level Retrofit Implications of Replacing Metal Halide Lamps with the Lunera MH HID LED Gen 2 Assumptions 100,000 sq. ft. building lit with 400W Metal Halide (MH) lamps on a 20 x20 spacing Building is operated 4,370 hours per year Lighting represents 35% of building electrical load; HVAC represents 35% of the building electrical load, and plug loads represent the remaining 30% Metal halide lamps and HVAC have a lagging power factor of 0.9; plug loads have a lagging power factor of 0.7 Comparing Metal Halide and MH HID LED Lamp Solutions in the Building BEFORE the MH HID LED Lamp Retrofit AFTER the MH HID LED Lamp Retrofit W/sq. ft. Total Power Total Load W/sq. ft. Total Power Total Load Lighting 1.10 111kW 123kVA (lagging 0.90 PF) 0.50 52kW 91kVA (leading 0.57 PF) HVAC 1.20 139kW 155kVA (lagging 0.90 PF) 1.20 139kW 133kVA (lagging 0.90 PF) Plug Load 1.00 100kW 142kVA (lagging 0.70 PF) 1.00 100kW 142kVA (lagging 0.70 PF) Aggregate 3.5 350kW 415kVA (lagging 0.84 PF) 2.70 291kW 305kVA (lagging 0.95 PF) Tbl. 2 Comparing the building s power envelope before and after a MH HID LED Lamp retrofit. BEFORE the MH HID LED Lamp Retrofit AFTER the MH HID LED Lamp Retrofit Energy Consumed 1.53M kwh 1.27M kwh Base Rate Charge $230,155 $190,078 PF Surcharge +$924 (PF of 0.84 is below 0.85) -$11,198 (PF of 0.95 is above 0.85) Electric Bill $231,079 $178,880 (22.6% savings) Tbl. 3 Comparing the building s cost of energy before and after a MH HID LED Lamp retrofit using a PG&E PF calculation at a nominal rate of $0.15/kWh adjusted for power factor. Bottom Line Lighting power was reduced by 54%, including the ballast load from the HID fixtures. Total power was reduced by 18%. However total VA was reduced by 28% as the leading current going into the lighting fixtures now compensates for the lagging current inside the building. The result is a substantial improvement in the load presented to the utility, and a reduction in building load (VA) that is nearly twice as large as the power (watts) reduction enabled by the lamps.

6 of 6 Conclusion Retrofitting from legacy HID lamps to Lunera s BallastLED technology provides a building owner not only 50-90% energy savings and substantial maintenance savings, but also unlocks value in the magnetic ballasts to provide capacitive compensation for inductive loads in the building. These cost saving pillars justify the investment in your HID LED lamp retrofit: Energy Savings of 50-90% Up to a 5x extension in maintenance cycles for lamp replacement Improvement in light levels and light quality Building Level power factor Improvement of up to 11 basis points Potential for substantial rebates from your utility partner 2016 Lunera Lighting, Inc. All Rights Reserved. Lunera and the Lunera logo are registered trademarks. All other trademarks are the property of their respective owners. Specifications are subject to change without notice. This document is for informational purposes only. R08516