Wilo Stratos Z Variable Speed, Wet Rotor Inline Pumps. Engineering Specification

Similar documents
Wilo Helix Vertical Multi-Stage, High Pressure Pumps. Engineering Specification

Wilo IL Vertical Inline Pumps. Engineering Specification

Wilo CO-Helix Pressure Boosting Systems. Engineering Specification

Heating, air-conditioning, cooling

Heating, air-conditioning, cooling

Wilo Abrasive Separator SCP and NL Kits Installation and operating instructions

Wilo SP Series Submersible Utility Pumps ETT. ETT Installation and operating instructions

Pumps Certified for North American Market

Data sheet: Wilo-Stratos-Z 25/1-8

Data sheet: Wilo-Stratos-D 32/1-8

Data sheet: Wilo-Stratos-D 50/1-12

UNIT TAG: TYPE OF SERVICE: SUBMITTED BY: APPROVED BY: ORDER NO.: UP B5. Circulator pumps. Motor Data Flow: Head: Efficiency: Pump Data

3 Specification Magneta Smedegaard

UNIT TAG: TYPE OF SERVICE: SUBMITTED BY: APPROVED BY: ORDER NO.: MAGNA F N. Pump Data

Series description: Wilo-Stratos

High-efficiency Drinking Water Pump. Rio-Eco Therm N. Type Series Booklet

Data sheet: Wilo-Stratos PICO 25/1-6

Circulator Pumps with Continuously Variable Differential Pressure Control and I.R. Interface for Remote Control

Data sheet: Wilo-Stratos PICO 25/

High pressure centrifugal pumps

KS / SKS Vertical Split Coupled Inline Pumps

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

Data sheet: Wilo-Yonos MAXO 40/0,5-16

4 Specification Magneta Smedegaard twin pumps

Wilo TWI & TWU 4 Submersible Well Pumps Installation and operating instructions

4-Way Mixing Panel Submittal - Page 1 of 6

Lenntech. Calio S. Type Series Booklet. High-efficiency Circulator Pump. Tel Fax.

Series description: Wilo-Stratos ECO-STG

PROJ. NO SECTION HYDRONIC PUMPS

FI / SFI Frame-Mounted End Suction Pumps

KV / SKV Vertical Inline Pumps

Wilo Price Book. Pumps and systems for Building Services and Groundwater. Pioneering for You USA 60 Hz.

Eclipse Hermetic Gas Boosters

UNIT TAG: TYPE OF SERVICE: SUBMITTED BY: APPROVED BY: ORDER NO.: CME3-7 A-S-I-E-AVBE. Pump Data

3x3x7B Series 80 In-Line Mounted Centrifugal Pumps

OIL SMART PLUG AND PLAY SYSTEM, Model #OSS-100

HYDROMATIC SK75/100 SUBMERSIBLE SEWAGE EJECTOR

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

Data sheet: Wilo-Yonos PICO 25/

HYDROMATIC HE8/HE12/HE20/HE25/ HE30/HE35/HE50 HIGH HEAD FILTERED EFFLUENT

Lenntech. Calio-Therm S. Type Series Booklet. High-efficiency Drinking Water Pump

Pump Specifications LE100-Series 1HP Submersible Sewage Pump

HYDROMATIC SKHS SERIES SUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

HYDROMATIC SPD50H/100H SUBMERSIBLE HIGH HEAD, DOUBLE SEAL EFFLUENT

HYDROMATIC SPX50/SPX50H EXPLOSION PROOF, SEWAGE EJECTOR

SKV40. Performance Data. Wholesale Products Page: Section: Performance Data Dated: January RPM: 1550 Discharge: 2" Solids: 2" GPM: TDH:

NOTE: LEH100-Series high-head pumps require a minimum application of 15' head. Do not use pump in this area use a smaller pump.

Pump Specifications LE70-Series 3/4 HP Submersible Sewage Pump

Air Handling Unit Construction Checklist

Pump Specifications 290 Series 3/4 hp Submersible Effluent Pump

Pump Specifications LE70-Series 3/4 HP Submersible Sewage Pump

SPD50H/100H. Performance Data SPD100H SPD50H. Wholesale Products Page: Section: Performance Data Dated: April 2002 Supersedes: January 2001

TPED /4-S-A-F-A-BAQE 3X400 50HZ

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

Pump Specifications 280 Series 1/2 hp Submersible Effluent Pump

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION PUMPS GENERAL PUMPS PART RELATED DOCUMENTS

DIG Corporation Irrigation product Specifications

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.

Instruction Sheets for ECM Variable Speed Pumps. AM55 Pages 2-3 AM99 Pages 4-7

SECTION ROLLER WINDOW SHADES

Pump Specifications FL100 Series Submersible Effluent Pump

TPE S-A-F-A-BUBE

Hamilton 3VO Submittal

SECTION METERS AND GAUGES

Pump Specifications 250 Series Submersible Sump / Effluent Pump

Pump Specifications LE40 Series 4/10 HP Submersible Sewage Pump Pump

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

Pump Specifications. LE50 Series ½ HP Submersible Sewage Pump

Dolan Mechanical, Inc. 638 Johnson Road, PO Box 326 Sicklerville, NJ (856) FAX (856) NO EXCEPTION TAKEN

University of Houston Master Construction Specifications Insert Project Name

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

TPE /2-S-A-F-A-BAQE 3X400 50HZ

PT, PTS & PTP Series Pump/Reservoirs

Pump Specifications FL50 Series 1/2 hp Submersible Effluent Pump

Pump Specifications FL60/FLH60 Series 6/10 hp Submersible Effluent Pump

Data sheet: Wilo-TOP-S 40/4 (1~230 V, PN 6/10)

SECTION WELDING FUME EXHAUST SYSTEM

Pump Specifications 405 Series Commercial Drain Pump (High-Temp)

A Series 50HZ. A - Series. Vertical Multistage Centrifugal in-line Pumps AVC/AVI/AVS ISO-9001

Pump Installation and Service Manual HRS Hydromatic Retractable System

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL

Japanese Technology since Ego Circulators. Databook

Instructions for Installing and Operating Clark Reliance EA100 Series Levalarm

SECTION GENERAL-SERVICE AIR COMPRESSOR PART 1 - GENERAL

SKHS SERIES 2 HP 1-1/2 HP 1 HP 1/2 HP CAPACITY-U.S. G.P.M.

Pump Specifications FL150 Series Submersible Effluent Pump

SECTION MOTOR CONTROL

University of Delaware

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

TPE /4-A-F-A-BAQE 3X400 50HZ

1. Wiring Diagrams: Power, signal, and control wiring.

A Series 50HZ. A - Series. Vertical Multistage Centrifugal in-line Pumps AVC/AVI/AVS ISO-9001

TPE S-A-F-I-BQQE

Pump Specifications. D3648LSG, D3648LSGX Series Omnivore 2HP Duplex Grinder Packages LITERS PER SECOND

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

Positive Displacement Flowmeters GM020 series instruction manual

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

Transcription:

Wilo Stratos Z Variable Speed, Wet Rotor Inline s Engineering Specification

PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install inline circulating pumps consistent with the hydronic system s performance, requirements and specifications. The circulating pumps shall be suitable for the specified system function and capacity. 1.2 REGULATORY A. Circulating pumps shall be rated to a maximum pressure of 145 PSI and temperature of 230 F (110 C) and where applicable, bear the approval symbol of the required regulatory body (NSF/ANSI 61). B. Electrical assemblies (circuitry, wiring terminals and internal connections) of the circulating pumps shall be certified and registered to bear the emblem of UL, CSA or ETL as required. Electrical assembly shall meet codes and standards established by national bodies. 1.3 REFERENCES A. UL 778 Standard B. NSF/ANSI 61, Annex G Standard 1.4 SUBMITTALS A. Provide submittals, warranty information and shop drawings in accordance with the General Requirements and as specified herein. Submit detailed product drawings including wiring schematics. Indicate critical dimensions of the circulating pumps. B. Submit manufacturer s technical data in the form of published Installation, Operation and Maintenance Manuals to be supplied with the circulating pumps at time of installation. C. Circulating pumps shall be tested and verified for performance. Copies of Submittals shall be made available to the specifying engineer if requested. D. Submit dimensional data on for the pump in order to facilitate or allow the end-user/installer to anticipate the necessary pipe, fittings, fasteners, etc. to complete the system installation. 1.5 DELIVERY, STORAGE AND HANDLING A. Inline circulating pumps are shipped in boxes and are to remain in factory shipping condition until immediately prior to installation. B. Circulating pumps are to be stored indoors in a conditioned space, protected from exposure to the elements, and from exposure to other potential contaminants. C. Factory applied labels are to remain in place and unobscured. These identification tags are to display model numbers, serial numbers, and evidence of certifications/listings. 2

1.6 WARRANTY A. The Manufacturer shall warrant the circulating pumps for a period of 4 years from date of purchase, subject to the Terms and Conditions of said Warranty. A copy of the Manufacturer s Warranty shall be provided as part of the Submittals as outlined in Section 1.4 of this specification. PART 2 - PRODUCTS 2.1 TERMINAL BOXES A. The circulating pumps shall have high quality composite terminal box with NPT electrical connections and a secure, gasketed cover, Class 2 protection level. Included on the face of the terminal box cover is the single red button adjustment button, front readable graphical pump display, field adjustable for horizontal or vertical positioning of the terminal box. B. The display shall indicate: Operation status Control mode Differential pressure or speed/setpoint Fault and warning signals 2.2 ELECTRICAL CONNECTIONS A. Inline circulating pump shall have a coded terminal strip indicating common/neutral/ground within the terminal box for field connections for single phase 230 volt, 60 Hz power. 2.3 ELECTRICAL - GENERAL A. All low voltage interface (IF) wiring shall be of 18 gauge or larger, UL/CSA approved, 220 F (110 C) maximum / 167 F (75 F) minimum temperature. B. All 230 volt main power wiring shall be of 14 gauge or larger, UL/CSA approved, 230 deg F maximum (167 deg F minimum) temperature. C. The motor shall be a minimum of class H winding insulation as defined by UL 778. D. Voltage variances shall be less than +/- 10% from rated voltage with pump under load conditions. Maximum amperage not to be exceeded is indicated on the pump nameplate. Electrical power to the pump is confirmed when the face of the graphic display is lit. 2.4 CONTROL, OPERATION AND DIAGNOSTICS A. Wet rotor, glandless inline circulating pumps shall include electronic variable speed control to operate at constant/variable differential pressure control without external sensors. Automatic night setback control available as standard using self taught, FUZZI technology. B. s to include integrated synchronous motors using ECM technology with permanent magnetic rotors, special sensorless control electronics and single phase electronic converters. 3

C. s to include IR (Infra-red) interface for wireless communication with the optional infra-red monitor. D. Integrated overload motor protection shall protect the pump against over/under voltage, over temperature of motor and/or electronics, over current, locked rotor and dry run (no load condition). E. Fault contact FC terminals shall be included in the terminal box and are to be potentially free, normally closed contacts that open on the event of a failure. F. Interface (IF) modules will be included where specified, installed in the terminal box. The modules will allow BMS communication via LONworks, BACnet, MODbus, and 0 10 volt DC control of speed or head setpoint, external minimum speed, external off, dual pump communication and pump operation status. 2.5 MATERIALS AND CONSTRUCTION A. Circulating pumps shall be constructed with lead free, Stainless Steel, NSF-61 Annex G certified. B. flanges shall be: Combination 1.25 2 bolt commercial oval type (rotated, 90 ) for types 1.25x3-25 and 1.25x3-35 Combination 1.5 2 bolt commercial oval type (rotated, 90 ) for types 1.5x3-25 and 1.25x3-40 2 4 bolt pump flange for type 2x3-30 3 4 bolt, 125# ANSI raised face flange for type 3x3-30 C. Shafts shall be constructed of high quality stainless steel. D. Motor bearings shall be metal-impregnated carbon. E. Impellers with three-dimensional curved blades are constructed of Polyphenylene Sulfide (PPS) plastic, 40% glass filled for models 1.25x3-25, 1.25x3-35, 1.5x3-25 and 1.25x3-40 or polyphenylene (PPE) plastic, 30% glass filled for model 3x3-30. PART 3 EXECUTION 3.1 PREPARATION A. Prior to commencing work, the contractor will have read and understood the Installation, Operation and Maintenance Manual (IOM) supplied and enclosed with the attendant circulating pumps. This manual is supplied in English, French and Spanish. B. The effectiveness of the system is dependent on the system being designed and installed correctly. Proper consideration of factors such as BTU loads, outdoor design temperature, indoor design temperature, room set-point temperature(s), differential fluid temperatures, head loss, flow rates and transfer capacities of the heat emitters is critical. C. Prior to final connection of the circulators as part of the hydronic system, the system piping shall be flushed of all contaminants and foreign objects. 3.2 INSTALLATION A. The circulating pumps must be installed by a qualified installer/service technician. B. The circulating pumps shall be installed in accordance with the relevant requirements of the local authority having jurisdiction, as required to meet the performance requirements and function specified for the system. C. The circulating pumps must be installed and operated strictly in accordance with the terms set out in the Installation, Operation and Maintenance Manual supplied and enclosed with the attendant pumps. 4

D. The pump shall be installed with the motor shaft in a horizontal plane with no exceptions. The electrical terminal box shall be installed either horizontally with the IR window to the left of the Red Button (wiring connections to the right of the terminal box) or vertically with the IR window above the Red Button (wiring connections below the terminal box). E. The pump must be installed in a way that it is not stressed by the pipework. A minimum of three pipe diameters is recommended on the inlet of the pump. F. Where antifreeze protection is required, the maximum concentration of heating system glycol is 50% by volume. High concentrations of glycol at lower system design temperatures may require increasing the design operating point. Use of leak sealant products or automotive antifreeze is not permitted. G. Fluid temperature limitations are 14 to 230 F (-10 to 110 C) for HVAC systems. Maximum ambient temperature surrounding the pump is 104 F (40 C). H. Fluid temperature limitations are 32 to 176 F (0 to 80 C) for secondary hot water circulation systems. Maximum ambient temperature surrounding the pump is 104 F (40 C). I. Minimum Inlet pressure at pump suction port to avoid cavitation at fluid temperatures: 122 F (50 C) 203 F (95 C) 230 F (110 C) 1.25x3-25 1.25x3-35 1.5x3-25 1.5x3-40 7.1 psi [.5 bar] 17.1 psi [1.2 bar] 25.6 psi [1.8 bar] 2x3-30 7.1 psi [.5 bar] 17.1 psi [1.2 bar] 25.6 psi [1.8 bar] 3x3-30 10.0 psi [0.7 bar] 2 [1.5 bar] 32.7 psi [2.3 bar] 3.3 FIELD QUALITY CONTROL A. Upon receipt and prior to commissioning the circulating pumps should be inspected for any sign of visible damage. B. Prior to commissioning the circulating pumps, the system connections should be complete and leak free. The system should be filled and purged as per instructions in the IOM manuals. The system fluid should be tested and have a ph level of between 6.5 and 9.5 and be suitable for hydronic system use. C. Following fill and purge, the system should undergo a pressure test. Wilo USA LLC 9550 W. Higgins Rd, #300 Rosemont, IL 60018 Tel: 888-945-6872 Fax: 888-945-6873 Email: info@wilo-usa.com Web: www.wilo-usa.com Wilo Canada Inc. Bay 7-2915 10th Ave NE Calgary, AB T2A 5L4 Tel: 866-945-6236 Fax: 403-277-9456 Email: info@wilo-canada.com Web: www.wilo-canada.com Wilo Mexico Managua No 978, Colonia Lindavista 07300 México, D.F., México Tel: + 52 55 5586 3209 Fax: + 52 55 5586 3209 Email: info@wilo.com.mx Web: www.wilo-mexico.com 5