dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

Similar documents
Low voltage bushings for pad-mounted distribution transformers Technical information guide

Micafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB

General information on handling and maintenance of SDC TM Solid Dielectric Capacitor Bushings

Type DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003

Flush Mount AIN ALPHA Meters. General. Hardware Kit

Transformer bushings, type GOH. Technical guide

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper

Bushings for High Voltage AC Applications

High-voltage primary bushings installation instructions

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

Effective March 2015 Supersedes S August 2012

IL Instruction Leaflet Page 1 November,2001. Type DTW De-energized Tap Changer Application, Installation & Selection Guide

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

Transformer bushings, type GOA 250. Installation and maintenance guide

High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide

Two-way cable interlock kit for Magnum fixed circuit breakers

DANGER. See Wiring Diagrams on page 7 for illustrations of both internal and connection wiring diagrams. WARNING

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

LV Bushing Oil to Air Dry Insulation PTAB-SLV832

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

CCP2-FLR1-21_ flange-rod operating mechanism

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

Type NR oil switch installation and operation instructions

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st New RIS transformer bushings The paper-free solution

Effective November 2016 Supersedes February 2012 (S )

Factory Authorized Mechanism Enhancement (FAME)

Two-way cable interlock kit for Magnum drawout circuit breakers

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC

3-way multi-family drawout cable interlock kit - type 32 - RF

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

5/15/27 kv, 25/31.5/50/63 ka Manual Ground & Test Devices Installation, Operations and Maintenance Manual

Test report. Type VRLTC load tap changer VRLTC 1500A Type test summary report

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

Effective June 2016 New Issue

Instruction Booklet IB E. Contents

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

TBM Series 3-Way Ball Valve

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

EMPAC Metal enclosed capacitor bank for wind applications

Eaton s Cooper Power Systems

Advanced Test Equipment Rentals ATEC (2832)

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

Effective November 2016 Supersedes September 1998 (S )

REDI-LINE. Rugged, Reliable, DC to AC Power Conversion ELECTRIC GENERATORS USER'S GUIDE. KARAM A.L.

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

Transformer components. De-energized tap changer, type DTW Technical information guide

O & M Manual for the EATON Generator Ready Loadcenter

Product Description: Objective and Certification: Test Samples and Test Cable:

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

Users Guide for Ac-sync

15 kv and 25 kv Thru-Bushings

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

3 TM Cold Applied Barrier Boot System

Volt Instrument Transformers

TRUCK PRODUCT LINE A DIVISION OF DAKOTA FLUID POWER, INC.

Operation Key D4BS - K Head Mounting Direction F: Four mounting directions possible (front-side mounting at shipping)

TVSS Installation for RLCM/CHGENLC, RLCU, and CHGEN ATSs

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

STAINLESS STEEL FORGED FITTINGS 3000lb 304/304L & 316/316L Forged Stainless Steel Fittings Product Specifications

Technical Specification For Outdoor Substation Harmonic Filter Banks

ActuLink ABS Module - ABS-MOD-400

1ZSE en, Rev. 9. Transformer bushings, type GSA-OA Technical guide

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

Manufacturing Facility is ISO9001:2000. Welded Steel Pipe Conform to ASTM A53. Threads Conform to ASME B1.20.1

Condenser Bushings. OIL-TO-AIR - Oil-Impregnated Paper ANSI STANDARDS IEEE C AND IEEE C AN ALSTOM COMPANY

NorthStar. brand. Instruction Manual. SLIM Tach SL Thru-Shaft Diameter. Magnetoresistive Encoder Designed for GE Wind Energy

PABS. AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS ANSI STANDARDS AN ALSTOM COMPANY

II DISTRIBUTION & SUBSTATION TYPE C

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

Transcription:

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

Table of contents 1 Introduction... 3 1.1 Style Number... 3 1.1.1 Style Number Examples... 3 2 Basic Characteristics... 4 2.1 Standards... 4 2.2 Ratings... 4 2.3 Features... 4 2.4 Mounting... 5 2.5 Test Tap... 5 2.6 Installation Instructions... 5 3 Testing... 5 3.1 Pressure/Vacuum Tests... 5 3.2 Electrical Tests... 5 4 Bushing Loading... 6 4.1 Current Rating & Over Load... 6 4.2 Short Circuit Current Rating... 6 4.3 Draw-Lead Application... 6 4.4 Distance of Grounded Edge from Live Parts... 7 4.5 Distance of Grounded Flat Surface from Live Parts... 7 5 Ordering Details... 8 5.1 Draw-lead Connected... 8 5.2 Bottom Connected... 8 5.3 Draw-rod Connected... 8 5.4 Top Terminal Connections... 8 6 Drawings: Bushing Top End and Bottom End... 9

1 Introduction The 34.5 kv and 69 kv Type O Plus C II, condenser bushings, replace the Type AB, 34.5 and 69 kv, condenser bushings. The electrical and mechanical characteristics and physical dimensions are unchanged in the transition from Type AB to Type O Plus C II bushing. The change does two things: 1) the Type O Plus C II bushing uses much simpler style numbers (very similar to the standard Type O Plus C bushing) and 2) the Type O Plus C II bushing is not reconfigurable in the field except to change from 800 A draw lead to 1200 A bottom connected or visa versa. 1.1 Style Number The style number for the 34.5 kv and 69 kv Type O Plus C II condenser bushing will be written as: 034 Z nnnn αα or 069 Z nnnn αα where nnnn is the current rating in amperes except in the case of a dual rated bushing, eg 400 draw lead / 1200 bottom connected which is written as 0412. The final two characters eg, αα, are used by ABB to describe the other characteristics of the bushing. Note that the fourth character Z becomes Y for brown porcelain. 1.1.1 Style Number Examples Type O Plus C II Style Number 034Z0412UT 034Z2000AA 034Z3000AS 034Z1200AE 034Z2000AM 034Z3000AT 069Z0412AN 069Z2000AA 069Z3000AX 069Z1200AF 069Z2000AR Replaces 1ZUA034012-AAASFSCBA, CA Through CF 1ZUA034020-AAASGBAXX 1ZUA034030-AAASMBBXX 1ZUA034012-AAASFDAXX 1ZUA034020-AAASGDAXX 1ZUA034030-AAASMDAXX 1ZUA069012-AAASFSCBA, CA THRU CF 1ZUA069020-AAASGBAXX 1ZUA069030-AAASMBBXX 1ZUA069012-AAASFDAXX 1ZUA069020-AAASGDAXX Information Standard 34.5 kv bushing 400 A, draw-lead or 1200 A bottom connect Standard 34.5 kv bushing 2000 A, bottom connect Standard 34.5 kv bushing 3000 A, bottom connect Standard 34.5 kv bushing 1200 A, draw rod Standard 34.5 kv bushing 2000 A, draw rod Standard 34.5 kv bushing 3000 A, draw rod Standard 69 kv bushing 400 A, draw-lead or 1200 A bottom connect Standard 69 kv bushing 2000 A, bottom connect Standard 69 kv bushing 3000 A, bottom connect Standard 69 kv bushing 1200 A, draw rod Standard 69 kv bushing 2000 A, draw rod Page 3 of 13

2 Basic Characteristics 2.1 Standards The Type O Plus C II condenser bushing meets all requirements of the IEEE bushing standards, ie, C57.19.00, C57.19.01, C57.19.100 and IEEE Seismic standard 693 (qualified at HIGH level). These bushings will also meet the electrical, mechanical and thermal requirements of the CSA bushing standard and of IEC 137. 2.2 Ratings The standard ratings for this family of bushings are as follows: Parameter 34.5 kv Bushing 69 kv Bushing Nominal System Voltage 34.5 kv 69 kv Maximum line-to-ground voltage 22 kv 44 kv Lighting impulse voltage withstand (BIL) 200 kv 350 kv Current rating 400 A to 3000 A 400 A to 3000 A Creep distance min 44 mm/kv L-G & higher, see outline drawing Seismic (IEEE 693) Qualification Level High High For other bushing technical features, please consult the specific bushing outline drawing 2.3 Features The 34.5 kv and 69 kv Type O Plus C II bushing is designed to operate under Usual Service Conditions as defined in IEEE C57.19.00, IEEE Standard General Requirements and Test Procedures for Power Apparatus Bushings. If you require a bushing to operate outside of these defined, Usual Service Conditions, please contact ABB. The 34.5 kv and 69 kv Type O Plus C II bushing is of center-clamped construction, ie, the bushing is held together by the action of clamping springs which act on the bushing central conductor and hold the entire bushing assembly under a compressive load. The bushing is built around the central conductor tube on which the condenser body is wound. The upper and lower insulators, mounting flange, flange extension, spring assembly, sight bowl, lower support and clamping nut form an oil tight shell to contain the condenser Figure 1 and insulating oil. O-rings in grooves and/or flat fiber reinforced gaskets create the seals between components. High-grade transformer oil fills the space between the shell and the condenser. This oil is part of the insulating and Page 4 of 13

cooling systems of the bushing. Above the oil, there is a gas space to provide for thermal expansion of the oil. The gas space is filled with dehydrated nitrogen gas. The bushing oil level is easily visible in the sight bowl. The sight bowl is prismatic to enhance observation of the oil level. See Figure 1. The mounting flange and flange extension are high strength corrosion-resistant aluminum. The upper (air-side) insulator is a one-piece, high quality porcelain with a shed configuration designed for maximum performance. The insulator meets the IEEE requirement for Heavy Creep which is 44 mm/ kv L-G. Note that higher creep versions are also available. The 34.5 kv and 69 kv Type O Plus C II bushings meet or exceed the cantilever test requirements for interchangeable/circuit breaker (TBI) per Table 8 of IEEE standard C57.19.01 1991. 2.4 Mounting Most 34.5 kv and 69 kv Type O Plus C II bushings are suitable for use at angles of up to 60 degrees from the vertical position. You should always verify maximum mounting angle by reviewing the outline drawing. 2.5 Test Tap The bushing has a test tap which is normally grounded. This tap is connected to an inner foil electrode of the condenser. ABB tests the voltage tap at 2 kv, 50/60 Hz for 1 minute. The maximum continuous service voltage is 600 volts, AC. This tap is grounded under normal operation. 2.6 Installation Instructions ABB publishes a separate document, which should be followed when installing these bushings. You can download the Installation Guide from our web site or contact ABB for a copy 3 Testing As part of the manufacturing process, the bushing is subject to a number of routine tests. 3.1 Pressure/Vacuum Tests Vacuum tightness is performed at nearly a full vacuum and a test is made with an oil over pressure of 41 psig for 6 hours at ambient temperature. No evidence of a leak is permitted. 3.2 Electrical Tests Each bushing is subject to final electrical tests at ambient temperature with the lower end of the bushing submerged in transformer oil. The power-factor and capacitance are measured and the bushing is subjected to a one-minute power frequency test at a level of one-half the BIL rating. During power frequency testing, the level of partial discharge is carefully monitored. The power-factor and capacitance are also confirmed after the one-minute test. Page 5 of 13

4 Bushing Loading 4.1 Current Rating & Over Load The current rating of the 34.5 kv and 69 kv Type O Plus C II bushing indicates the maximum continuous rating of the device without abnormal loss of life. 4.2 Short Circuit Current Rating The bushing will withstand a short circuit of 25 times rated current for 2 seconds or the I 2 t equivalent with the following exceptions: Draw-lead bushings: short circuit rating is defined by the draw-lead cable Draw-rod applications have contacts with short circuit ratings of 20 times the continuous rating for not more than 2 seconds and a dynamic peak not to exceed 2.5 times the rms value of the fault. For short circuit loss of life data relative to the bushing condenser insulation, contact ABB. 4.3 Draw-Lead Application The sizing of the draw-lead cable is the responsibility of the transformer designer. The maximum rated current for the bushing in the draw-lead application is 400 amperes. The transformer designer must note the inside diameter of the bushing conductor tube because this will limit the choice of cable size. As a service to our transformer customers, we make the following suggestions relative to draw-lead cable size. Suggested Draw-lead Cable Sizing Cable Size (MCM) Cable Size (mm 2 ) Maximum Continuous Current 167 85 265 250 127 350 300 152 400 Note that you must insulate the draw lead cable to isolate it from the internal diameter of the bushing s conductor tube. Page 6 of 13

4.4 Recommended Positioning The maximum stresses in the oil at the lower end of the bushing must be limited to those values normal for uninsulated conductors of similar components in the same transformer. The lower insulator must be totally under oil for all operating conditions. The following recommendations are intended as guidelines only. ABB recommends that specific design calculations be made to verify the proper clearances. Figure 2 4.4.1 Distance of Grounded Edge from Live Parts Within the angle of 0-45 from the end of the ground sleeve, the Radius A shall be a minimum of 0.125" (3.175 mm). Minimum Electrical Clearances 34.5 kv 69 kv Within the angle of 45-60 from the end of the ground sleeve, the Radius B shall be a minimum of 0.25" (6.35 mm). Dimension S (inches) 3.25 6.00 Dimension S (mm) 83 153 4.4.2 Distance of Grounded Flat Surface from Live Parts S is the minimum distance from bushing live parts to a large surface such as a tank wall or core clamp. Page 7 of 13

5 Ordering Details When ordering please specify the following: Bushing type and style number Current Rating Voltage Class and BIL Special requirements Special Requirements: Any nonstandard requirement, such as impulse tests or high temperature application, must be specified at the time of quotation. 5.1 Draw-lead Connected If a draw-lead bushing is ordered, it will be shipped with the standard draw-lead connector as shown in Figure 3. In many cases, ABB has other draw-lead connectors. If you cannot use the standard draw-lead connector, please contact ABB for other options. Ø 0.375 0.25 1.62 Ø 0.18 0.75-12 Thd 1.44 3.5 5.2 Bottom Connected The standard 34.5 kv and 69 kv Type O Plus C II bushing has the IEEE Std C57.19.01-2000 lower end configuration. Connection is made directly to the lower support of the bushing. Figure 5 shows the various lower support configurations for this line of bushings. Ø0.29 Figure 3 1.19 0.19 5.3 Draw-rod Connected Draw-rod configurations of 34.5 kv and 69 kv Type O Plus C II bushings are available. Figure 6 shows a typical draw-rod configuration. Bushings that are suitable for draw-rod applications have an opening through the main axis of the bushing conductor and a special bottom end configuration. The draw-rod is pulled through this opening and secured at the top of the bushing. This makes it possible to remove/install bushings without draining the apparatus on which it is applied. With this application, the current is not carried by the rod but is transferred to the bushing conductor at the lower end of the bushing. The bushing s current rating with draw rod is the same as the bushing s current rating when bottom connected. 5.4 Top Terminal Connections The standard 34.5 kv and 69 kv Type O Plus C II bushings have IEEE Std C57.19.01 top terminals (see Figure 4). The purchaser can order bushings with other terminals if desired. Note that the terminal thread size is: 1.50-12 thread for the 400/1200 A and 2000 A bushing and it is 2.00 12 thread for the 3000 A bushing. Page 8 of 13

6 Drawings: Bushing Top End and Bottom End All dimensions are inches unless otherwise noted. Page 9 of 13

Page 10 of 13 Figure 4

34.5 kv, 400 A / 1200 A 34.5 kv, 2000 A 34.5 kv, 3000 A 1.50-12 Thread 2.12 Long (Typical) 1.75 1.75 0.563 Diameter Hole (Typical) 0.625 1.75 0.625 1.75 1.75 Tube ID = 0.88 (Typical) 1.75 0.625 0.625 69 kv, 400 A / 1200 A 69 kv, 2000 A 69 kv, 3000 A Figure 5 Page 11 of 13

0.312 18 UN Female Thread - 0.500 Deep Flats for wrench 1.25 Transformer Mounting Flange Fixing Hardware Upper & Lower Rods Thread Together Upper Rod Lower Rod Bushing Flange Transfer of Current to the Bushing Note: drawing is rotated 90 CCW to fit publication Figure 6 Page 12 of 13

Contact us ABB Inc Components & Insulation Product Group 1128 South Cavalier Drive Alamo, Tennessee 38001, USA +1 731 696 5561 +1 800 955 8399 Fax: +1 731 696 5377 Email: Alamo.customer_service@us.abb.com www.abb.com/electricalcomponents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY THERE ARE NO UNDERSTANDINGS, AGREEMENTS, REPRESENTATIONS OR WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OTHER THAN THOSE SPECIFICALLY SET OUT BY AN EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF SEELER. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY PRIOR OR EXISTING AGREEMENT, COMMITMENT OR RELATIONSHIP. THE INFORMATION, RECOMMENDATIONS, DESCRIPTION AND SAFETY NOTATIONS IN THIS DOCUMENT ARE BASED ON OUR EXPERIENCE AND JUDGEMENT WITH RESPECT TO BUSHINGS. THIS INFORMATION SHOULD NOT BE CONSIDERED TO BE ALL INCLUSIVE OR COVERING ALL CONTINGENCIES. IF FURTHER INFORMATION IS REQUIRED. ABB INC. SHOULD BE CONSULTED. NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS, DESCRIPTIONS AND SAFETY NOTATIONS CONTAINED HEREIN. IN NO EVENT WILL ABB INC BE RESPONSIBLE TO THE USER IN CONTRACT, IN TORT (INCLUDING NEGLIGENCE), STRICT LIABILITY OR OTHERWISE FOR ANY SPECIAL. INDIRECT. INCIDENTAL OR CONSEQUENTIAL DAMAGE OR LOSS WHATSOEVER INCLUDING BUT NOT UMITED TO DAMAGE TO OR LOSS OR USE OF EQUIPMENT, PLANT OR POWER SYSTEM, COST OF CAPITAL, LOSS OF PROFITS OR REVENUES, COST OF REPLACEMENT POWER, ADDITIONAL EXPENSES IN THE USE OF EXISTING POWER FACILITIES, OR CLAIMS AGAINST THE USER BY ITS CUSTOMERS RESULTING FROM THE USE OF THE INFORMATION, RECOMMENDATIONS, DESCRIPTION AND SAFETY NOTATIONS CONTAINED HEREIN Copyright 2009, ABB Inc. Document Number 1ZUA2751-242en Page 13 of 13