Medium Voltage Drives Overview, Evolution & Application

Similar documents
Product brochure. Medium voltage AC drive ACS2000, kw, kv

Product brochure. Medium voltage AC drive ACS 2000, 4kV 6.9kV HP

SINAMICS SM150. Siemens product performance features. Competitor product profile. Components. Power, transport units. Service friendliness

Product brochure. Medium voltage AC drive ACS 2000, kva, kv

Product brochure. Medium voltage AC drive ACS 1000, ACS 1000i 315 kw 5 MW, kv

Selecting Motor Controls. for Mining Process Torque Demands

Product brochure. Medium voltage AC drive ACS 2000, kva, kv

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

Drive IT ACS 1000i. Integrated Medium Voltage AC Drive

ACS 1000, ACS 1000i. Medium voltage AC drives for control of induction motors from kw

When to use a Soft Starter or an AC Variable Frequency Drive

TMdrive -MVG Product Guide. Medium Voltage Multilevel IGBT Drive Up to 10,000 kva at 11 kv. rubber & plastics. metals

ELECTRICAL POWER and POWER ELECTRONICS

ASHRAE - Variable Speed Drives. By Dan Watkins, LEED BD+C Bornquist, Inc.

AC DRIVES. AC Drives. The word "drive" is used loosely in the industry. It seems that people involved

Power Electronics

Medium voltage drive for single or multimotor applications, 3 27 MW

Variable Speed Drives Controlling Centrifugal Pumps Energy Savings

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

SDC,Inc. SCR-Regenerative Ac Drive

POWER IS IN OUR NATURE! WELCOME TO THE HOUSE OF COMPETENCE.

SINAMICS SM150. 4/2 Overview. 4/2 Benefits. 4/2 Design. 4/6 Function. 4/8 Selection and ordering data. 4/8 Options

AC/DC FFE converter power module

Practical Variable Speed Drives and Power Electronics

PowerFlex 6000 Medium Voltage AC Drives

Question Number: 1. (a)

Clean and compact drive for energy savings. Altivar Medium-voltage variable speed drive 0.3 to 10 MW

315 kw 5000 kw, kv. ACS1000 Medium Voltage Drive The flexibility you require. The reliability you expect.

ACS Medium Voltage AC Drive for Control of Motors up to 6.9 kv

Common Bus and Line Regeneration

Targeted Application of STATCOM Technology in the Distribution Zone

Power Protection Discrete Automation & Motion South Africa

Introduction to Variable Speed Drives. Pekik Argo Dahono Electrical Energy Conversion Research Laboratory. Institute of Technology Bandung

Steve Schouten. Donna Densmore

Qingdao Zener Electric Co., Ltd

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

Fast thyristors. When burning for induction heating solutions.

Concentrated savings for your applications. Altivar Medium-voltage variable speed drive 0.5 to 10 MW. DIA2ED EN.indd 1 17/07/08 8:58:49

Concentrated savings for your applications. Altivar Medium-voltage variable speed drive 0.5 to 10 MW

Lecture 2. Power semiconductor devices (Power switches)

VFD Best Practices: Getting the Most from Your VFD Investment

CT430 - Soft Starters on Motor Applications

SINAMICS GM150 IGCT version

Static frequency converter couples US paper mill s 25-Hz and 60-Hz electricity grids

Technical Explanation for Inverters

Application Note CTAN #127

ACS Medium Voltage AC Drives for Speed and Torque Control of 3 27 MW Motors

HIGH POWER RECTIFIER SYSTEMS

Softstarters. Softstarters Type SSM Medium voltage ,800V 1

The cement and minerals industry

A new static DC drive system with AFE for mining excavators

Standby Power Systems

VARIABLE FREQUENCY DRIVES

Diesel-Electric Propulsion Systems Power under Control

ACS Medium voltage AC drive for control of motors up to 6.9 kv

.3 Section Waste Management and Disposal.

SIMINE DRAG. Innovative solutions for maximum productivity and reliability. Mining Technologies

Technical Data Sheets

SD700FR. Regenerative Active Front End VARIABLE SPEED DRIVES POWER ELECTRONICS / SD700 SERIES 4 QUADRANT. icool

Optimizing Drive Systems for Energy Savings

Product brochure. Medium voltage AC drive ACS 6000, 3 36 MW, up to 3.3 kv

Variable Frequency Drives

315 kw 5000 kw, kv. ACS1000 Medium Voltage Drive The flexibility you require. The reliability you expect.

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.

ABB Softstarter Benefits Charnchanok Thongprad

Variable Frequency Drive Basics

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

Variable Speed Pumping

Technical Data Sheets

Inverter with MPPT and Suppressed Leakage Current

APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.

Product brochure. Medium voltage AC drive ACS 6000, 3 27 MW, up to 3.3 kv

Implications of Digital Control and Management for a High Performance Isolated DC/DC Converter

Introduction to Power Electronics - A Tutorial. Burak Ozpineci Power Electronics and Electrical Power Systems Research Center

MEDIUM VOLTAGE AC DRIVES. ABB drives ACS to 36 MW

Liebert. FP 50Z kva

D Series: UPS UPTO - 300KVA - Three / Three Phase

TLE Series UPS 400/500 kw With eboost Technology

Diversifying into Marine Energy. ABB March 2015

TLE Series UPS 160/200/225/250 kw with eboost Technology

ACS Medium voltage AC drives for control of 3 27 MW motors up to 3.3 kv

SERIES Pulse and 12 Pulse DC Power Supplies for Electrocoating and Industrial DC Powered Systems MODELS 506 & 5012

POWER ELECTRONICS & DRIVES

The Perfect Fit. Introducing the Next Generation of SINAMICS PERFECT HARMONY GH180 Air-Cooled Drive. usa.siemens.

1.1 Block Diagram of Drive Components of Electric Drive & their functions. Power Processor / Modulator. Control. Unit

Transforming Energy.. For Advanced Technology

MaxPak Plus Analog DC V S Drive

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES

team master medium voltage solid state starters

A Compact, Liquid-Cooled Variable Speed Drive for High Horsepower Applications

High-Voltage, High-Current DC- DC Converters Applications and Topologies

5 MW 36 MW, kv. ACS6000 Medium Voltage Drive The modularity you require. The reliability you expect.

SitePro UPS 400Vac / CE. GE Consumer & Industrial August 2004

Technical Data Sheets

SECTION V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2

PQC-STATCON. PPHVC-Power Quality Solutions. Instantaneous and stepless power quality compensation for dynamic reactive power and unbalanced loads

MEDIUM VOLTAGE AC DRIVES. ABB industrial drives ACS1000 drives 315 to 5000 kw

Motorpact Medium Voltage Motor Controller. Innovative solutions that deliver high performance and reliability

Power Electronics for Medium Voltage Grid Applications Topologies and Semiconductors

AC Adjustable Speed Drives (ASD s)

Transcription:

Medium Voltage Drives Overview, Evolution & Application November 2004 Bill Horvath, PE TMGE Automation Systems

MV Drive Session Overview Provide links to more reference materials. Review the benefits of ASDs in motor starting and control Cover basic drive application Cover basic tradeoffs between MV & LV drives Review one recent mining conveyor MV drive application Trace the Evolution of MV drives & circuit configuration Compare each historical and current major MV drive topology Compare each drive topology's major strengths and weaknesses. Review the TMGE Dura-Bilt5i MV IGBT Drive as an example of current technology November 2004 TMGE Automation Systems - All rights Reserved 2

MV Drive Materials -1 MV Drive Evolution White Paper GEZ-S1006 Engineering Reference Manual & CDROM, GET-S1009 Obtain from TMGE General Industries www.tmge.com November 2004 TMGE Automation Systems - All rights Reserved 3

More MV Drive Materials - 2 Electronic MV Newsletter http://www.imakenews.com/getoshiba_mve-news/ TM GE Automation Web Link: www.tmge.com November 2004 TMGE Automation Systems - All rights Reserved 4

AC Motors & Control Overview Induction Motor Basic Characteristics Load Types Starting and Running Torque-Speed Profiles Typical Applications Starting and Running Control Methods Variable Frequency Drives Low Voltage vs Medium Voltage MV Drive Evolution TMGE Automation Systems Dura-Bilt5i MV Overview November 2004 TMGE Automation Systems - All rights Reserved 5

Induction Motor Speed-Torque Profile Locked Rotor Tq Torque Pull Up Torque RPM Rated Torque Rated RPM Peak [Breakdown] Torque, BDT Sync Sync Rpm Rpm = 120 120 x Freq. Freq. #Poles #Poles Rated SlipRPM = Sync - Rated RPM Sync RPM November 2004 TMGE Automation Systems - All rights Reserved 6

Motor Starting November 2004 TMGE Automation Systems - All rights Reserved 7

Motor Starting Factors That Apply Inrush Amps and Duration Motor Limit on Number of Starts Per Hour Motor Connected Inertia Limits Load Mechanical Issues Pumps, Piping & Hydraulic issues Coupling Stress Starting Torque vs Load Requirements November 2004 TMGE Automation Systems - All rights Reserved 8

Full-Voltage Motor Starting Full Voltage Amps & Torque vs Speed Amps Single Motor, Single Starter Torque, Amps Torque Full Load Multiple Motors, Single Starter RPM > November 2004 TMGE Automation Systems - All rights Reserved 9

Reduced -Voltage Motor Starting Reduced Voltage Motor Amps & Torque vs Speed Reduced Voltage Starter Bypass Start Inrush amps ~ Volts Torque ~ Volts 2 Torque, Amps Amps Torque Full Load RPM > 1. Frequency is = line frequency 2. Inrush current and torque are limited for a soft start, but no true speed or torque control is possible. November 2004 TMGE Automation Systems - All rights Reserved 10

Motor on AC Adjustable Speed Drive Adjustable Speed Drive No Starting Inrush amps, Torque & Volts Controlled to Match Load M Torque, Amps AC Adjustable Speed Drive Motor Amps & Torque vs Speed Motor AvailableTorque Amps Full Load Torque Level 1. Frequency and voltage are controlled. 2. Line current, motor voltage torque regulation provide true speed and torque control. 3. KEY: Process and energy use can be optimized. November 2004 TMGE Automation Systems - All rights Reserved 11

Drive Ratings and Torques Variable Torque - ratings usually include 110-115% OL rating for 60 seconds at rated Temp 2/12/2001 VFD APPLICATION 12

Loads & Motor Capability Curves TEFC Induction Motor Capabilities Under Variable Speed Operation Theoretical Motor Capability 100% Load Point, NP RPM, Sine wave power Load Torque Actual Motor Capability Variable Load [Pump, Fan] Constant Torque Load, Example 1 Constant Torque Load, Example 2 RPM -- > imcapab1.drw June 4, 98 November 2004 TMGE Automation Systems - All rights Reserved 13

Pump & Fan Affinity Laws: 1-2-3-1 Flow Rate Varies 1 st power of Speed [Proportional] - 2 Pressure & Load Torque Varies as the 2 nd power [square] of Speed - 3 Horsepower at Motor Shaft varies as the 3 rd power [cube] of Speed 100.00% 90.00% 80.00% 70.00% 60.00% 50.00% 40.00% 30.00% 20.00% 10.00% 0.00% 0 10% 20% 30% 40% % Speed 50% 60% 70% 80% 90% 100% flow - % HP - % % of Total November 2004 TMGE Automation Systems - All rights Reserved 14

Fans -Things to Remember Fans have variable torque loads. Blowers may have constant torque or variable torque loads. Load torque goes up as the square of the speed. Horsepower load goes up as the cube of the speed. Torque needed to run an Induced Draft fan increases significantly as gas temperature decreases. Fan Motor sizing greatly effected by across the line November 2004 TMGE Automation Systems - All rights Reserved 15

November 2004 TMGE Automation Systems - All rights Reserved 16

Variable Torque Drive Applications November 2004 TMGE Automation Systems - All rights Reserved 17

Starting/ Running Drive Starting/Running Contactors Pump Motors 4160 V 4160 V Drive M1 ST1 MTR1 M2 ST2 MTR2 M3 ST3 MTR3 Across the Line Contactors Multiple Motor Pumping Application November 2004 TMGE Automation Systems - All rights Reserved 18

Drive Ratings and Torques Constant Torque [CT] rating usually includes 150% - 250% OL rating for 60 seconds when at rated Temp. November 2004 TMGE Automation Systems - All rights Reserved 19

Constant Torque Characterized as a load curve that looks like Theoretical Motor Capability 100% Load Point, NP RPM, Sine wave power Load Torque Actual Motor Capability Variable Fan] Load [Pump, Constant Torque Load, Example 1 Constant Torque Load, Example 2 RPM -- > November 2004 TMGE Automation Systems - All rights Reserved 20

Conveyor or Mill Loading BREAKAWAY TORQUE Typical Induction Motor Char on 60 Hz power TORQUE conveyor typical demand FREQ, SPEED November 2004 TMGE Automation Systems - All rights Reserved 21

Conveyor or Mill Loading VFD CONTROLLED MOTOR - ENOUGH TORQUE ACROSS THE RANGE BREAKAWAY TORQUE Typical Induction Motor Char on 60 Hz power TORQUE conveyor typical demand FREQ, SPEED November 2004 TMGE Automation Systems - All rights Reserved 22

November 2004 TMGE Automation Systems - All rights Reserved 23

Crushing and Conveying Systems November 2004 TMGE Automation Systems - All rights Reserved 24

Example MV Drive Mining Application MINE-MOUTH TO PROCESSING PLANT CONVEYOR

Application Story Long Conveyor 1. Underground Molybdenum Mine in Colorado had 15 mile long train to take ore from mine tunnel to processing plant 2. Train equipment became obsolete, unreliable 3. Three segment conveyor at variable speed was winning concept to replace train 4. Total length of conveyors over 15 miles! One section over 10 miles! November 2004 TMGE Automation Systems - All rights Reserved 26

Application Story Long Conveyor 0.76 miles, 1.2 km CONVEYOR PC-1 GRADE = Variable 0% to 8% 5% CONVEYOR PC-2 3% 10.5 miles, 16.8 km GRADE = Variable 5% to 1% 1% 2,400 ft Elev. 9,500 ft Elev. 7,100 ft 4.0 miles, 6.4 km CONVEYOR PC-3 C-1 Conveyor Plan View Head end equip house @ 7,100 feet AMSL PC-2 Conveyor Plan View Head end equip house @ 9500 feet AMSL Tail end equip house @ 9,500 feet AMSL PC-3 Conveyor Plan View Head end equip house @ 9,500 feet AMSL 4 3 2 1 7 1 x 1000 HP 2 x 1000 HP 1 x 2 x 1 x 1 x 2 x 2250 HP 2250 HP 2250 HP 1000 HP 1000 HP 6 5 ELECTRICAL ONE LINES ELECTRICAL ONE LINES 2140 kva 13,800/2400 V 1900 kva 13,800/2300 V 1000 HP 2.3 kv 900 kva 13,800/2300 V 13.8kV PWM-3. 2250 HP. A 2250 HP PWM-3 w/1 2250 HP Motor Basic Configuration for Pulleys 1, 2, 3 2250 HP 2.3 kv 13.8kV 2000 HP Drive Can Accommodate [2] 1000 HP Motors PWM-3 2000 HP. 1000 HP 2.3 kv B 2000 HP PWM-3 w/ two 1000 HP Motors Alternate for pulley 4 13.8kV PWM-3 1000 HP. 1000 HP 2.3 kv C 1000 HP PWM-3 w/1 1000 HP Motor Basic configuration for Pulleys 4, 5, 6, 7 November 2004 TMGE Automation Systems - All rights Reserved 27 8/18/97 Henpres1.ppt Slide S-21

Application Story Long Conveyor Conveyor Mechanical Application Considerations Stretch, Length, Belt weight, load weight, speed Friction T1 T2 D2 T3 T4 D1 D3 Tension Ratios, Dynamic Response, Programmed Torque, Load Sharing November 2004 TMGE Automation Systems - All rights Reserved 28

PC-2 UPHILL CONVEYOR with PWM Drives PC-2 Conveyor Plan View Head end equip house @ 9500 feet AMSL 3 1 x 2250 HP 2 1 2 x 1 x 2250 HP 2250 HP ELECTRICAL ONE LINES 2140 kva 13,800/2400 V 13.8kV PWM-3. 2250 HP. 2250 HP 2.3 kv A 2250 HP PWM-3 w/1 2250 HP Motor Basic Configuration for Pulleys 1, 2, 3 November 2004 TMGE Automation Systems - All rights Reserved 29 8/18/97 Henpres1.ppt Slide S-23

PC-3 OVERLAND CONVEYOR with PWM-3 Drives Tail end equip house @ 9,500 feet AMSL PC-3 Conveyor Plan View Head end equip house @ 9,500 feet AMSL 1 x 7 1000 HP 6 5 900 kva 13,800/2300 V 1 x 1000 HP 2 x 1000 HP 13.8kV PWM-3 1000 HP. 1000 HP 2.3 kv C 1000 HP PWM-3 w/1 1000 HP Motor Basic configuration for Pulleys 4, 5, 6, 7 November 2004 TMGE Automation Systems - All rights Reserved 30 8/18/97 Henpres1.ppt Slide S-24

PC-1 FEED CONVEYOR with PWM-3 Drives PC-1 Conveyor Plan View Head end equip house @ 7,100 feet AMSL 4 2 x 1000 HP 900 kva 13,800/2300 V 13.8kV PWM-3 1000 HP. 1000 HP 2.3 kv C 1000 HP PWM-3 w/1 1000 HP Motor Basic configuration for Pulleys 4, 5, 6, 7 November 2004 TMGE Automation Systems - All rights Reserved 31 8/18/97 Henpres1.ppt Slide S-22

Motor Challenges High Starting Torque for PC3 Two sizes: 1000 HP & 2250 HP each wide speed range Motor Solution GE 2.3 kv induction motor separate cooling air by user TM GE Automations Systems Application Story Long Conveyor Challenges & Solutions Drive Challenges 24/7 Reliable Energy Efficient Low Maintenance High overload torques in winter on PC3 Drive And Control Solution Control Challenges Precise, programmable torque for belt tension control Head-to-tail tension coordination for PC3. Allow variable speed operation of any motor GE Innovation PWM 2300 volt 3-level, 18 pulse rectifiers. Utilized Innovation Series Controller for torque programming & PLC Ethernet interface. Power Challenges Long power feeds Cable capacitance created resonance high order harmonics Power Solution 3-level Inverter with IEEE 519 compliant 18 pulse converters and high frequency filters to eliminate cable resonance at 19 th harmonic November 2004 TMGE Automation Systems - All rights Reserved 32

Application Story Long Conveyor Customer Benefits Train system replacement with conveyor has proven to be very reliable. Variable speed operation on the conveyor resulted in added energy savings, reduced friction and belt wear. Biggest risks and failure potentials were avoided by careful design: Slippage and stretch of long strand 20 mile total length PC2 with 4 x 2250 HP at head end Tension control of up-and-down PC3 overland with many curves November 2004 TMGE Automation Systems - All rights Reserved 33

All AC Drive Selection Factors Load type: CT, VT, CH, Regen or non-regen Physical Environment at drive location Power system compatibility Precision of control needed Overload ratings needed Operator control & digital communication needed Drive Output Voltage & Motor Application November 2004 TMGE Automation Systems - All rights Reserved 34

Drive Output Voltage & Motor Application LV drives: defined as having output volts <690 volts Why Pick LV [<690v] Drive & Motor? Why pick MV over LV? Trends: Some users select MV at >250 HP Many users select MV over 500 HP. November 2004 TMGE Automation Systems - All rights Reserved 35

Drive Output Voltage & Motor Application Why Pick LV [<690v] Drive & Motor? LV drives are lower cost / HP than MV Reduces some safety & MV training concerns HP range is small enough Individual preference Why pick MV [>690v] Drive & Motor over LV? Lower cost wiring, smaller cables Lower power system harmonic impact High HP LV require dual winding motors Individual preference Trend: Some users select MV at >250 HP Many users select MV over 500 HP. November 2004 TMGE Automation Systems - All rights Reserved 36

MV vs LV AC Drives: Cost Factors of Various Configurations MV drive $ / HP decreases with HP Harmonic content can be important: MV data is 24 pulse TMGE Automation Systems DB5i MV LV data is GE-Fuji AF300 P11 Installed cost must be considered Budgetary $ per Horsepower 500.0 400.0 300.0 200.0 100.0 0.0 MV vs LV AC Drives Budgetary $ per HP vs HP LV 6-Pulse w/o Transformer MV 4160 v 24-Pulse DB5i LV 6-Pulse w/8% Mirus filt LV 18 pulse incl transf 0 500 1000 1500 Horsepower November 2004 TMGE Automation Systems - All rights Reserved 37

Safety, Training & MV Drives Different level of training and personnel for MV vs LV equipment Different procedures MV vs LV Local maintenance staff may not be comfortable with MV equipment MV drive include many safety features: Optical control isolation: feedbacks and firing Electrical and mechanical interlocks & isolator switches Bolt on covers, warning labels November 2004 TMGE Automation Systems - All rights Reserved 38

MV vs LV Drives: Some Conclusions For drives > 1000 HP, MV makes sense For long cable runs, MV makes sense For drives < 500 HP, LV makes sense. If low system harmonics are required, LV filter or multi-pulse expense can favor MV over LV. In the range 500 to 1000 HP the various application & installation factors apply. Final choice may boil down to user preference. November 2004 TMGE Automation Systems - All rights Reserved 39

MV Drive Evolution History, Topology Comparisons, & Future Trends

Typical AC Inverter System Transformation Conversion Utilization AC TO DC OR OR OR DC TO AC OR AC MOTOR Load Utility Supply RECTIFICATION ENERGY STORAGE SWITCHING AC Inverter Technology Up To 97% Efficiency, including transformers November 2004 TMGE Automation Systems - All rights Reserved 41

Advances in Power Semiconductor Technology Lead the Way in MV Drive Development The Common Threads: All AC Drives rectify AC to DC All AC Drives use switches to create AC from DC Drive topologies were created as power rectifiers and switches grew in ratings and capabilities. Each new or uprated device opens up new applications A quick look at the device development timeline is useful November 2004 TMGE Automation Systems - All rights Reserved 42

Development Time Line of Power Semiconductors Transistor Devices Bipolar Power Transistor (BPT) Low Voltage Insulated Gate Bipolar Transistor (LV IGBT) Medium Voltage Insulated Gate Bipolar Transistor (MV IGBT) Injection Enhanced Gate Transistor (IEGT) 1955 1965 1975 1985 1995 2005 Diode (D) Silicon Controlled Rectifier (SCR) Gate Turn Off Thyristor (GTO) Integrated Gate Commutated Thyristor (IGCT) Symmetrical Gate Commutated Thyristor (SGCT) Thyristor Devices November 2004 TMGE Automation Systems - All rights Reserved 43

GTO Gate Driver & Cell Stack Equipment GE GTO-IMD Example Gate Power Supply Liquid-cooled configuration Many discrete parts in firing and auxiliary parts Snubber network also shown Physically quite large November 2004 TMGE Automation Systems - All rights Reserved 44

GCT Gate Driver Equipment Covers on Gate Power Supply Isolation Transformer Integrated Gate Signal Unit GCT 4.5kV-4kA November 2004 TMGE Automation Systems - All rights Reserved 45

GCT & Gate Driver Board Covers off 4.5kV-4kA 36 Electrolytic caps 21 FET Switches 4.5kV-800 A November 2004 TMGE Automation Systems - All rights Reserved 46

Typical IGBT & IGBT Gate Driver Circuit IGBT 400 amp 3300 volt dual package Larger ratings have 1/package Typical MV IGBT Dual Gate Driver Each board has 2 drivers, & fires 2 IGBT s 2 in, 50 mm Approximate Size: 4 inches x 4.5 inches November 2004 TMGE Automation Systems - All rights Reserved 47

IEGT Gate Driver Equipment Gate Drive Board IEGT 4.5kV-4kA IEGT = Injection Enhanced Gate Transistor November 2004 TMGE Automation Systems - All rights Reserved 48

IGCT vs IEGT Calculated Failure Rates of Gate Drivers Calculated Reliability of Gate Drivers IEGT Voltage Fired vs GCT Current Fired FITs Failures per Billion Hours 3500 3000 2500 2000 1500 1000 500 IC LED FILM CAPACITOR ELECTROLYTIC RESISTOR(1/4) RESISTOR(PWR) DIODE FET TRANSISTOR 0 IGCT IEGT November 2004 TMGE Automation Systems - All rights Reserved 49

Power Switching Devices Final Comparisons & Conclusions Current switched devices [SGCT, IGCT] require many more parts in firing / gate control than voltage switched devices [IGBT, IEGT]. Voltage switched devices [IGBT, IEGT] have MUCH lower switching losses than current switched. Conduction losses are nearly equal for equivalent volt & amp-rated device SGCT, IGCT vs IGBT, IEGT Voltage switched devices allow higher switching rates and can give better output waveforms November 2004 TMGE Automation Systems - All rights Reserved 50

AC Drive Topology: A map-like diagram showing the elements of an AC drive and the relationships between them. Two Basic AC Drive Topologies Current source drive: ENERGY STORAGE section between converter and inverter consists of an inductor. Voltage Source Drive: ENERGY STORAGE section between converter and inverter consists of capacitors. November 2004 TMGE Automation Systems - All rights Reserved 51

Comparing Topologies Current Source Drives LCI Load Commutated Inverter GTO/SGCT Current Source Induction Motor Drive Voltage Source Drives LV IGBT Paice Multilevel PWM MV IGCT PWM Diode or Active Source MV IGBT PWM Integrated package MV IEGT PWM Active or Diode Source November 2004 TMGE Automation Systems - All rights Reserved 52

Current Source Drives November 2004 TMGE Automation Systems - All rights Reserved 53

LCI Current Source Load Commutated Inverter UTILITY SCR DC Link Inductor SCR Volts Sync Motor Example: GE-Innovation Series LCI Alternate: Multi-pulse/ Multi-channel Converter Energy stored in Link Inductor Inverter Topology Advantages Drawbacks Practical Power Range Current source Load-Commutated Inverter SCR = Silicon Controlled Rectifier, Thyristor Low Parts Count Full Regen is inherent Rugged ultra reliable Economical High HP N+1 SCR device redundancy possible Requires a controlled front end High motor current THD Slow transient response Narrow motor frequency range Reduced Starting Torque Limited starting performance Poor PF at low motor speeds High harmonics unless multiple channels used; filters may be needed. Above 6 MW Synchronous Motors Only Primarily being offered by: TMGE, ABB, Siemens November 2004 TMGE Automation Systems - All rights Reserved 54

Current Source GTO / SGCT Induction Motor Drive UTILITY SCR DC Link Inductor GTO / GCT Volts Induct Motor Example: GE-GTO IMD Induction Motor Drive Inverter Topology Current Source GTO or SGCT PWM Inverter GTO = Gate Turn Off Thyristor SGCT = Symmetrical Gate-Controlled Thyristor Advantages Low power device (GTO/SGCT) parts count Low motor THD Low motor insulation stress when input isolation transformer is used Alternate: Multi-pulse/ Multi-channel Converter Drawbacks Requires a controlled front end extra complexity Poor input power factor, with SCR front end Slow transient response Narrow speed range Potential resonance between motor & caps Limited availability of power devices Complex firing circuit Practical Power Range 2-15 MW Primarily induction motor load November 2004 TMGE Automation Systems - All rights Reserved 55 Energy stored in Link Inductor Primarily being offered by: Allen Bradley

Current Source SGCT Induction Motor Drive With Isolation Reactor in Place of Transformer UTILITY "Isolation" Inductor SCR or GCT DC Link Inductor Volts Induct Motor* * nonstandard Energy stored in Link Inductor November 2004 TMGE Automation Systems - All rights Reserved 56

Voltage Source Drives November 2004 TMGE Automation Systems - All rights Reserved 57

Voltage Source General Drive Arrangements Diode Rectifier Converter Fed UTILITY 1 2 3 Alternate: Multi-pulse/ Multi-channel Converter Volts Motor Volts Motor Active Rectifier Converter Fed 1 2 3 November 2004 TMGE Automation Systems - All rights Reserved 58

PWM: Pulse Width Modulation A method of varying voltage by changing the average ON time of switches between source and load. Example Pulse-Width-Modulated [PWM] Waveform Voltage: The Average of the time the Voltage is on Plus the time the Voltage is Off. PEAK DC SOURCE VOLTAGE Current: The Motor tends to smooth the resulting current EXAMPLE SIMULATED SINE WAVE PRODUCED BY 2-LEVEL PWM INVERTER November 2004 TMGE Automation Systems - All rights Reserved 59

Example Two-Level Voltage Source Inverter Rectified 3-Phase 1.2 1 3 Phase Diode Bridge [ + ] 0.8 0.6 0.4 0.2 0 0 50 100 150 200 250 300 350 400 DC Buss Rectified Power PWM Motor Volts 1.2 0.7 AC Incoming Line Three Phase Input Cap Bank DBR a c b M 0.2 0 50 100 150 200 250 300 350 400-0.3-0.8-1.3 [- ] Motor Amps November 2004 TMGE Automation Systems - All rights Reserved 60

LV IGBT Multi-level Voltage Source PWM Inverter Example: GE Innovation Series Type H Inverter Topology Multi-level Voltage Source LV IGBT PWM Inverter LV IGBT = Low-voltage Insulated Gate Bipolar Transistor Diode Rectifier Major Advantages Fixed DC Bus Typical Power Cell Power Cell N+1 redundancy available Low motor current THD Fast transient response Wide motor frequency range No significant torque pulsations High starting torque. Multi-pulse converter for very low AC line harmonics High true pf over all speeds November 2004 TMGE Automation Systems - All rights Reserved 61 Inverter (IGBT) Major Limitations No regen or DB possible Large parts count lowers base MTBF N+1 redundancy adds parts and decreases MTBF Large footprint in high HP Electrolytic capacitors are sensitive to over temp & overvoltage Energy stored in electrolytic caps Practical Power Range 0.5 10 MW Sync or Induction motor Primarily being offered by: Robicon, Toshiba Japan

Power Cell N+1 Redundancy N+1 redundancy originated in LCI drive design, defined as having an extra SWITCHING DEVICE per leg, with no other added parts. One Robicon method re-defines N+1 as including a complete extra cell transformer secondary & SCR bypass switch: Cell must be intact and control 100% functional to work Added parts work all the time and decrease drive component MTBF Traditionally, increased reliability comes from reducing parts count and conservative design. Feed Transformer Source converter DC link reactor Load converter Sync Motor LCI drive N+1 requires 12 SCR s LV IGBT MV Drive N+1 [3 extra power cells] adds 18 diode Rectifiers 12 LV IGBTs, 15 bypass SCRs 42 electrolytic Caps, Firing circuits + 3 added transf windings TYPICAL LV IGBT POWER MODULE FOR REDUNDANT USE Fixed DC Bus BYPASS SCR Added Power Devices for Redundancy Shaded Green Diode Rectifier ELECTROLYTIC CAPS Inverter (IGBT) November 2004 TMGE Automation Systems - All rights Reserved 62

AC Input IGCT PWM Voltage Source Inverter Diode or IGCT Rectifier Fixed DC Bus Inverter (IGCT) Filter Induction Motor or sync Motor [req field exciter] Example: GE-Innovation Series SP IGCT Mill Drive Energy stored in liquid filled caps Inverter Topology Major Advantages Major Limitations Practical Power Range IGCT PWM Voltage Source Inverter Three Level Low power switch device count for voltage rating Fast transient response & wide motor frequency range High starting torque High power levels with largest IGCT devices Regen possible with active IGCT converter Complex high parts count firing circuit 3-level output above 3.3 kv requires output filter for low motor current distortion. Potential for electrical and mechanical resonance between load and filter. 0.5 4.8 MVA per inverter, air cooled 4.8 9.6 MVA, dual channel Primarily being offered by: TM GE, ABB November 2004 TMGE Automation Systems - All rights Reserved 63

Example: TMGE Automation Systems Dura-Bilt5i MV Inverter Topology Three / Five Level Voltage Source MV IGBT PWM Inverter MV IGBT = Medium- Voltage Insulated Gate Bipolar Transistor MV IGBT NPC Voltage Source Drive Multi-Winding Transformer Major Advantages Minimum parts count for voltage rating & waveform Simple firing circuit. High efficiency Low motor current THD Fast transient response Wide motor frequency range No significant torque pulsations High starting torque. Multi pulse converter for very low AC line harmonics High true pf over all speeds Multi-Pulse 2 Diode Rectifier Liquid Filled MV-IGBT Power Caps NPC Inverter Ind or Sync Motor No regeneration available Fast rise time IGBT switching may require dv/dt output filter in some cases Power Device redundancy not practical Practical Power Range 0.5 4.8 MVA per inverter, air cooled 4.8 9.6 MVA, dual channel Sync or Induction Motors November 2004 TMGE Automation Systems - All rights Reserved 64 1 Major Limitations 3 Energy stored in liquid filled caps Primarily being offered by: TMGE Automation Systems, Siemens

MV IGBT NPC Voltage Source Drive Details 24-P Source 24-P Source 24-Pulse Source V-Phase Leg U-Phase Leg Assembly N W-Phase Leg M Neutral Point Clamped [NPC] reduces voltage to ground 5 / 9 level waveform < 3% motor current distortion 24 pulse diode converter <2% line current distortion, better than IEEE 519 limits 460 Vac Voltage Detection Module Optical Link Module Example 5/9 level motor voltage & current waveforms November 2004 TMGE Automation Systems - All rights Reserved 65

Example: TMGE Automation Systems TMdrive 30 Inverter Topology LV IGBT NPC Voltage Source Drive AC Input Major Advantages Converter (IGBT) Fixed DC 3-level Bus Inverter (IGBT) Major Limitations Induction Motor or sync Motor [req field exciter] Energy stored in high reliability electrolytic caps Practical Power Range Three Level Voltage Source LV IGBT PWM Inverter LV IGBT = Low Voltage Insulated Gate Bipolar Transistor, 1700 volt rating With High reliability design and component selection, measured MTBF of > 50 years is possible. Simple firing circuit. High efficiency Low motor current THD Fast transient response No significant torque pulsations High starting torque. Active Front End for full regen, Harmonic, and PF control. Power Device redundancy not practical 1250 volt rating limits max power 0.5 10 MVA using up to 4 bridges, air cooled Sync or Induction Motors Primarily being offered by: TMGE Automation Systems November 2004 TMGE Automation Systems - All rights Reserved 66

MV IGBT NPC Voltage Source Drive Details + 900 M - 900 Simulated Inverter Voltage Waveforms of 3 level NPC PWM Neutral Point Clamped [NPC] reduces voltage to ground 3 level waveform ~ 3% motor current distortion Active PWM front end better than IEEE 519 guideline limits November 2004 TMGE Automation Systems - All rights Reserved 67 1.08 1.0 0.7 0.2 0 PEAK RMS Red = 3-level PWM Voltage output 50 100 150 200 250 300 350 400

IEGT PWM Voltage Source Inverter AC Input Converter (IEGT) Fixed DC Bus Example: TMGE Automation Systems 8 MW TM-70 IEGT drive with active IEGT Source Inverter Topology Three Level Voltage Source IEGT PWM Inverter IEGT = Injection Enhanced Gate Transistor Major Advantages Minimum power device count 24 for complete 8 mw regen system Simple firing circuit [4:1 more reliable than IGCT] and very high system MTBF. Low motor current THD Fast transient response & wide motor frequency range High starting torque with no significant torque pulsations Active front end for low harmonics, regeneration, unity or leading PF Major Limitations Inverter (IEGT) IEGT device limits allow 3300 volt motor output [European and Asian Standard] 3300 volts is not as common as 4160 volts in North American applications. Energy stored in liquid filled caps Practical Power Range 6 to 26 MW, water cooled, one or two channel At 3300 volts Sync or Induction Motor November 2004 TMGE Automation Systems - All rights Reserved 68 Induction Motor or sync Motor [req field exciter] Primarily being offered by: TMGE Automation Systems

IEGT PWM Voltage Source Inverter & Active Converter Circuit Details & Alternate Diode Converter Configuration 8 MW IEGT Inverter with active regen-capable source Transformer & Feed Reactor 20% Z AC Input IEGT PWM Voltage Source Inverter with Diode Converter Diode Rectifier Fixed DC Bus Inverter (IEGT) Induction Motor or sync Motor [req field exciter] 3 Level VFD Line-Line Output & Reference Sine Wave 1.08 1.0 PEAK 0.7 0.2 RMS Red = 3-level PWM Voltage output 0 50 100 150 200 250 300 350 400 Simulated Inverter Voltage Waveforms of 3 level NPC PWM Sync Field [If Applic] INDUCTION OR SYNC MOTOR November 2004 TMGE Automation Systems - All rights Reserved 69

A Modern MV Drive Example: TMGE Automation Systems Dura-Bilt5i MV

Dura-Bilt5i MV Overview An AC Fed Medium Voltage Drive Featuring: Compact/compartmentalized design Integral incoming fused disconnect Integral converter transformer 24 pulse IEEE 519 compliant ac to dc converter Advanced user interface and system features November 2004 TMGE Automation Systems - All rights Reserved 71

Covering a Broad Range of Medium Voltage Drive Applications Vac 4200 4000 3300 3000 4000 Series 3000 Series 400 10,000 HP [300 7500 kw] 300 8500 HP [225 6340 kw] 2400 2000 2000 Series 200 5000 HP [150 3730 kw] 200 300 400 1000 2000 4000 10000 HP 150 450 300 750 1500 3000 7500 kw November 2004 TMGE Automation Systems - All rights Reserved 72

300-900 HP 3.3 & 4kV Outline 24" fan top to ceiling for airflow clearance Very Compact Optional Redundant Fan Standard Fan No rear access required 110 [2794] flapper clearance 103.7 [2634] 90.1 [2288] Converter Section With Incoming Connections Inverter Control [front] Motor Connections [Behind Control, RH - Side] Front View 43.4 [1102] 74 [1880 ] Left Side / End View 300-900 HP Dura-Bilt5i MV Inverter, 3000 & 4000 series EST WT: 7,500 LBS 3,402 KG November 2004 TMGE Automation Systems - All rights Reserved 73

Integral 12 winding Transformer CONVERTER 24-P Source 24-P Source 24-Pulse Source INVERTER W-Phase Leg V-Phase Leg U-Phase Leg Assembly Main Power 7.2 kv class or below 3 Incoming Power circuit CompartmentACL M1 M2 Optional DV/DT Filter M E Integral Lightning Arrestor Integral Disconnect Option Aux & Control Power 460 std., others avail 3 Sensing PT's 120 output 3 Standard E.S. Shield 460 Vac Control power feed option Fan Fan Optional redundant fans shown dotted Voltage Detection Module Fan Fan Optical Link Module Hall CT Current Feedback Dura-Bilt5i MV 3300-4160 Volt Detailed One-Line Diagram Dura-Bilt5i MV Control November 2004 TMGE Automation Systems - All rights Reserved 74

Power System and Motor Friendly AMPS GREEN VOLTS BLACK Note: traces time-shifted for clarity Utility Motor Line Current Distortion < 3% Current Distortion: THD < 3%, Voltage Distortion: THD < 6% Meets IEEE-519-1992 With No Filters. Requires No Special Motor Thermal Rating NOTE: Utility current trace displaced in time for clarity Operating Conditions: Full Speed, 95% Load November 2004 TMGE Automation Systems - All rights Reserved 75

A Look Inside... BYPASS CONTACTOR [option] INCOMING POWER TRANSFORMER & DC CONVERTER INVERTER SECTION DRIVE CONTROL Typical Dura-Bilt5i MV 1850 kva Drive Compartmentalized Design Separate cooling for converter and inverter Control and power separated Voltage levels separated Only front access required November 2004 TMGE Automation Systems - All rights Reserved 76

Incoming Power Compartment Integral ac reactor for charging and protection of dc bus components Integral lightning arresters for transient and surge protection Dedicated wireways support bottom or top incoming cabling Built-in 3-phase fused disconnect, interlocked with cubicle door that can be padlocked in the open position Built-in 3-phase MV contactor interlocked with disconnect Fused potential transformers November 2004 TMGE Automation Systems - All rights Reserved 77

Transformer and Converter Compartment DC cables to inverter compartment minimizes connections; this speeds and simplifies installation 24-pulse rectification gives power quality better than IEEE 519 recommended limits Forced air cooled with dedicated fan. [Optional redundant fan with auto throw-over available] Transformer secondaries fused with blown fuse indicators Washable filters can be changed while drive is operational November 2004 TMGE Automation Systems - All rights Reserved 78

Drive Control Compartment Separate disconnect for control power Optional controls for drive by-pass or other auxiliary functions Process input-output [I/O] control board Microprocessor control boards for drive sequencing and motor speed/ torque control Communication board supporting Profibus, ISBus, DeviceNet and Tosline S20 November 2004 TMGE Automation Systems - All rights Reserved 79

Inverter Compartment Easy access roll-out inverter phase modules Inverter module consists of: MV IGBT s and heat sinks Liquid-filled capacitors Snubbers Gating power supplies Gate driver board Air cooled heat plate cooling system High efficiency, low fan noise Low device temperature rises and temperature cycling Optional redundant fan with auto throw-over available November 2004 TMGE Automation Systems - All rights Reserved 80

High Efficiency Plate Heat Exchanger for IGBTs How it works Devices are mounted to side of plates Current flow generates heat in devices With only a few degrees of temperature rise, coolant is vaporized within the plate Vapor rises to the top condensing unit passages Heat is removed by airflow over fine fins, which liquefies coolant Coolant returns to base of chill plate for next cycle November 2004 TMGE Automation Systems - All rights Reserved 81

High Efficiency Heat Pipe Exchanger for IGBTs Advantages Liquid-cooled performance is achieved with air-cooled simplicity! Low IGBT-to-plate thermal resistance keeps IGBTs cool Minimized temperature fluctuations during operation maximize IGBT life up to 10x Sealed system is maintenance free Like the proven GE Innovation Series heat pipe design, but even more effective, with a larger active surface November 2004 TMGE Automation Systems - All rights Reserved 82

Inside a Typical Power IGBT This example: 400 amp, 1700 Volt. Inside the package, many individual devices paralleled with bonding leads. Thermal cycling from wide load cycle can cause fatigue failure of bonds due to expansion and contraction Heat plate, like liquid cooling, keeps mounting plate surface more even during load cycles. Minimized temperature fluctuations during operation maximize IGBT life up to 10x November 2004 TMGE Automation Systems - All rights Reserved 83

By-Pass Contactor Compartment Requires optional additional cubicle integrated into drive line up Contactors are interlocked to allow drive by-pass and connect motor across the power lines Cubicle extension houses both input and output contactors Allows full speed motor operation from utility power if drive is not available. November 2004 TMGE Automation Systems - All rights Reserved 84

Dura-Bilt5i MV Display Unit Parameter Editing Intuitive menu interface for parameter editing Drive Status Graphic screen displays key variables in bar chart format with additional status icons Status Indicators Give quick indication of drive operation, without requiring separate panel lamps Control System Toolbox Interface 10-100 Mbps Ethernet can be multi-drop networked - access to GE 24-7 on-site monitoring Signal Monitor Analog signals for test instrumentation Local Drive Control Dedicated keys for local control of the drive for commissioning and maintenance activities November 2004 TMGE Automation Systems - All rights Reserved 85

Integrated Trend Window Drag and drop variables Real time trending or archiving to buffer for historical trending Auto scaling Zoom in/out function Different views by using variable hide feature Analyze specific time with cross hair Frequency-based analysis of trend with fast Fourier transform function Easy to Understand Data Structure: Drive parameters and variables in tree structure World Class TMGE Control System Toolbox Supplied with Every Drive! Animated Block Diagrams Same Toolbox as all GE System Drives and Many Exciters! November 2004 TMGE Automation Systems - All rights Reserved 86

Summary & Conclusions ASDs offer superior motor control MV Drives can make sense at even modest HP levels MV Drives have come a long way MV drives using MV IGBTs have simplest control MV Drive Reliability needs to be built in, not added on November 2004 TMGE Automation Systems - All rights Reserved 87

Thanks! Bill Horvath TMGE Automation William.horvath@tmeic-ge.com 540-387-8253 November 2004 TMGE Automation Systems - All rights Reserved 88