ELECTRICAL POWER DISTRIBUTION FOR INFORMATION TRANSPORT SYSTEMS

Similar documents
Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1. UNIT 2 ELECTRICAL CIRCUITS...49 Introduction...49

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

TABLE OF CONTENTS. About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1

TABLE OF CONTENTS CHAPTER 1 ELECTRICAL THEORY About This Textbook...xi. Passing Your Exam...xiv. How to Use the National Electrical Code...

Standby Power Systems

Chapter 1 Electrical Theory...1

Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers

Managing Electric Vehicle Supply Equipment (EVSE) Installations

PSNH INTERCONNECTION REQUEST

TRANSMISSION SYSTEMS

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

Switchgear and Distribution Systems for Engineers and Technicians

ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Lecture 8 Motor Control Circuits

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

Pretest Module 24 Three-phase Service Entrance

ECET 211 Electric Machines & Controls Lecture 3-1 (Part 1 of 2) Motors, Transformers and Distribution Systems

NEC REQUIREMENTS FOR GENERATORS

90.2 Scope. The installation of electrical conductors, equipment and raceways for:

CHAPTER 3. Basic Considerations and Distribution System Layout

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

Volume 2 Charts, Formulas, and Other Useful Information

University of Houston Master Construction Specifications Insert Project Name

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE

A. General: Deliver, store and handle wire and cable in accordance with the manufacturer's instructions and as specified in Division 1.

Net Metering Interconnection Requirements

Grounding Of Standby & Emergency Power Systems

Targeted Application of STATCOM Technology in the Distribution Zone

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008

Generator Fire Safety: Generator assemblies should be located outside the building.

Service Entrance Methods

Table of Contents. CHAPTER 1 ElECTRiCAl THEoRY Mike Holt enterprises, inc neC.Code ( )

7. SERVICES OVER 600 VOLTS

A. This section includes unit capacitors for power factor correction.

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections

Electrical Depth. Josh Kreutzberger Lighting/Electrical

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1

TECHNICAL TERMS AND ABBREVIATIONS

Alternator protection, part 1: Understanding code requirements

Approved Contractor Construction e-guide Residential Commercial

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

Selective Coordination Requirements

Transformer Protection

A. This section includes enclosed dry type transformers for lighting and power loads, with primaries and secondaries rated 600 volts and less.

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

University of California, San Diego Cal (IT) 2 Technical Assignment #2. Brian Smith

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

SECTION MOTOR CONTROL

Customer Installation Standards for Electric Service

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

SINGLE PHASE WIRING SPECIFICATIONS

GENERAL INFORMATION 1.01 PURPOSE

THREE PHASE WIRING SPECIFICATIONS

SECTION 27 - PAD-MOUNTED TRANSFORMERS TABLE OF CONTENTS

Table of Contents. CHAPTER 1 BASIC ELECTRICAL THEORY (Essential for Journeyman and Master s Licensing Exams)... 1

Optimizing Emergency Power Systems for Health Care Applications

Design Standards NEMA

Legal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:

NORTH CAROLINA INTERCONNECTION REQUEST APPLICATION FORM. Utility: Duke Energy Progress

Modular Standardized Electrical and Control Solutions for Fast Track Projects

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

Working Principle of Power Saver as per Manufacture:

Guidelines for connection of generators:

Contents. 1 Introduction. 2. Advisory and Information Systems. 3. Supply. 3.1 Quality of Electric Supply. 3.2 Interference with other Customers

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

White Paper. Application of Resistive/Reactive Load Banks for kva Testing

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 Lihue, Kauai, Hawaii Original Sheet 5 RULE NO. 2 CHARACTER OF SERVICE

9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC

Reliable Power Distribution Design for Water and Wastewater Facilities By Van Wagner, P.E., Schneider Electric Water Wastewater Competency Center

DEWALT Electrical Licensing Exam Guide CONTENTS

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Spring Test 10 due 05/11/2013

REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDING 50 kw

Net +Plus Connection Code

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

2014 NEC Changes Part 4

A. Submit manufacturer's literature and technical data before starting work.

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Spring Test 7 due 05/03/2013

Recommended Procedures

New Safety Rules for Large Scale Photovoltaic Systems, Energy Storage Systems, and Microgrids

COMMERCIAL QUICK REFERENCE

Clark Public Utilities Commercial Electric Service Handbook. This page left blank intentionally.

MYRON ZUCKER CALMANUAL POWER FACTOR CORRECTION APPLICATION GUIDE INC.

MANAGING NEW CONNECTIONS FOR YOUR BUSINESS

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

IEEE-PES Chicago Chapter Presentation November 11, Smart Grid. Mike Born. Principal Engineer, Capacity Planning

ITT Technical Institute. ET3480T Power Systems Onsite Course SYLLABUS

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY

PRESENTER PETER NJENGA CHIEF ENGINEER, CUSTOMER SERVICE, KENYA POWER EAST AFRICAN POWER INDUSTRY CONVENTION 2012

Reactive Power Compensation using 12 MVA Capacitor Bank in 132/33 KV Distribution Substation

Street Address. City-Village-Township

Transcription:

ELECTRICAL POWER DISTRIBUTION FOR INFORMATION TRANSPORT SYSTEMS Bob Hertling Senior Communications Engineer / RCDD, OSP PARSONS

Your ITS equipment requires AC power Do you know what is on the other side of that receptacle before you plug it in??? What you should know (and do) before you plug it in!!!

How we got where we are Then (1843-1955) Telecommunications equipment and networks largely powered by local battery installations and large centralized DC power sources (e.g. Central Offices), typically at 24/48/130 VDC.

How we got where we are Then (1843-1955) Majority of telecommunications equipment was electromechanical (CO/PBX switching systems, telephone sets, teletypewriters, etc.).

How we got where we are Then (1843-1955) Electronic equipment (audio/voice amplifiers, carrier equipment, RF transmitters and receivers, etc.) used in telecommunications networks and systems utilized electron tubes and hard-wired discrete components.

How we got where we are Then (1843-1955) Use of batteries and associated charging equipment effectively isolated equipment and networks from commercial AC power variations and disturbances and maintained service in the event of a commercial AC power failure. Equipment was largely immune to all but the most serious power disturbances.

How we got where we are Then (1843-1955) Service Providers (AT&T, Western Union, etc.) had almost total control of equipment installation and maintenance. Limited need to utilize commercial AC power, especially at the customer premises.

How we got where we are Transition (1955-1975) Installation of key systems (1A, 1A1, 1A2) and small PBX systems began.

How we got where we are Transition (1955-1975) Invention of transistor (1956) begins introduction of solid-state equipment Modem installations at customer premises for data communications usage begins.

How we got where we are Transition (1955-1975) FCC Carterfone Decision (1968) allows connection of customer-owned equipment to the telecommunications network. Use of commercial AC power at the customer premises for powering telecommunications equipment begins to increase.

How we got where we are Now (1975-Present) ITS equipment and networks are almost exclusively electronic and computer-based. Most, if not all, ITS equipment utilizes integrated circuit technology. Reduced use of centralized DC power sources.

How we got where we are Now (1975-Present) ITS equipment is now a consumer item, similar to other generic electronic equipment and appliances. A large need to utilize commercial AC power at customer premises for ITS equipment!!

ITS Power Requirements and Trends Availability Reliability Stability ITS power needs have been and are growing exponentially! Equipment and systems are becoming more efficient in terms of power usage but there is an ever-increasing number being installed!

Overview of Typical Electrical Power Distribution System GENERATION (11-24 KV) STEP-UP SUBSTATION TRANSMISSION (138-765 KV) STEP-DOWN SUBSTATION SUB-TRANSMISSION (66-138 KV) STEP-DOWN SUBSTATION DISTRIBUTION PRIMARY (2.4-34.5 KV) SECONDARY (120-480 V) UTILIZATION

General Commercial AC Service Characteristics Normally, both primary and secondary distribution systems utilize either: Wye-connected 3-phase circuits with multigrounded neutrals. Center tapped single-phase circuits with multigrounded neutrals.

General Commercial AC Service Characteristics (cont.) These arrangements provide: The greatest degree of flexibility for connecting loads. Generally a high degree of voltage stability. A high degree of protection for equipment and personnel in case of faults and rapid detection and clearance of faults in conjunction with appropriate overcurrent and fault detection devices.

General Commercial AC Service Characteristics (cont.) In certain cases, three-phase circuits may utilize delta instead of wye connection schemes for items such as motors, transformers and similar equipment.

General Commercial AC Service Characteristics (cont.) Depending on the distribution and utilization voltages and the size of the connected load, the associated transformers, switchgear, and overcurrent/fault detection and protection equipment may be provided by both the customer and the serving electrical Utility.

Typical Primary Distribution Voltages (Single-Phase/Three-Phase) 2400/4160 Volts Wye 4800 Volts Delta 7200/12,470 Volts Wye 7620/13,200 Volts Wye 14,400/24,940 Volts Wye 19,920/34,500 Volts Wye 13,800 Volts Delta

Secondary Distribution and Utilization Single-Phase - 120/240 volts SINGLE-PHASE PRIMARY PRIMARY SINGLE-PHASE DISTRIBUTION TRANSFORMER SECONDARY SINGLE-PHASE SECONDARY (BLACK) 120 V 2.4-19.9 KV (7200 V OR 7620 V TYPICAL) PRIMARY NEUTRAL SERVICE NEUTRAL & EQUIPMENT GROUND (GREEN) PRIMARY AND SECONDARY MULTI-GROUNDED NEUTRAL 120 V 240 V SECONDARY NEUTRAL (WHITE) SINGLE-PHASE SECONDARY (RED)

Secondary Distribution and Utilization (cont.) Three-Phase - 120/208 volts (scheme A) PRIMARY (WYE) (1) OR (3) SINGLE-PHASE DISTRIBUTION TRANSFORMER(S) SECONDARY (WYE) PRIMARY (A) SECONDARY (BLACK) 4.1-34.5 KV (7200/12470 V OR 7620/13200 V TYPICAL) 208 V 208 V 120 V SERVICE NEUTRAL & EQUIPMENT GROUND (GREEN) PRIMARY NEUTRAL PRIMARY (B) PRIMARY (C) 208 V 120 V 120 V SECONDARY NEUTRAL (WHITE) SECONDARY (RED) SECONDARY (BLUE) PRIMARY AND SECONDARY MULTI-GROUNDED NEUTRAL

Secondary Distribution and Utilization (cont.) Three-Phase - 277/480 volts PRIMARY (WYE) (1) OR (3) SINGLE-PHASE DISTRIBUTION TRANSFORMER(S) SECONDARY (WYE) PRIMARY (A) SECONDARY (BROWN) 4.1-34.5 KV (7200/12470 V OR 7620/13200 V TYPICAL) PRIMARY NEUTRAL PRIMARY (B) PRIMARY (C) 480 V 480 V 480 V SERVICE NEUTRAL & EQUIPMENT GROUND (GREEN/YELLOW STRIPE) 277 V 277 V 277 V SECONDARY NEUTRAL (GRAY) SECONDARY (ORANGE) SECONDARY (YELLOW) PRIMARY AND SECONDARY MULTI-GROUNDED NEUTRAL

Secondary Distribution and Utilization (cont.) Three-Phase - 120/208 volts (scheme B) PRIMARY (DELTA) (1) OR (3) SINGLE-PHASE DISTRIBUTION TRANSFORMER(S) SECONDARY (WYE) PRIMARY (BROWN) 480V 208V 208V 120V SECONDARY (BLACK) SERVICE NEUTRAL & EQUIPMENT GROUND (GREEN) PRIMARY (ORANGE) PRIMARY (YELLOW) 480V 480V 208V 120V 120V SECONDARY NEUTRAL (WHITE) SECONDARY (RED) SECONDARY (BLUE) SECONDARY MULTI-GROUNDED NEUTRAL

Secondary Distribution and Utilization (cont.) Typical Secondary Branch Circuit Arrangements - 120/240 volts DISTRIBUTION PANELBOARD WITH 120/240V 1-PHASE FEEDER WHITE BLACK RED 240V 120V 120V RED WHITE BLACK RED BLACK 240V BLACK WHITE 120V PANELBOAD GROUND GREEN EQUIPMENT GROUNDING CONDUCTORS

Secondary Distribution and Utilization (cont.) Typical Secondary Branch Circuit Arrangements - 120/208 volts DISTRIBUTION PANELBOARD WITH 120/208V WYE 3-PHASE FEEDER WHITE BLACK RED BLUE 208V 120V 120V BLACK WHITE RED BLACK RED BLACK RED 208V 208V 208V BLUE 208V BLACK WHITE 120V PANELBOAD GROUND GREEN EQUIPMENT GROUNDING CONDUCTORS

Secondary Distribution and Utilization (cont.) Typical Secondary Branch Circuit Arrangements - 277/480 volts DISTRIBUTION PANELBOARD WITH 277/480V WYE 3-PHASE FEEDER GRAY BROWNORANGE YELLOW 480V 277V 277V BROWN GRAY ORANGE BROWN ORANGE BROWN ORANGE 480V 480V 480V YELLOW 480V BROWN GRAY 277V PANELBOAD GROUND GREEN/YELLOW STRIPE EQUIPMENT GROUNDING CONDUCTORS

Secondary Distribution and Utilization (cont.) Special Cases - 120/208 volt and 277/480 volt metropolitan networks NETWORK TRANSFORMER AND PROTECTOR IN UNDERGROUND VAULTS NETWORK TRANSFORMER AND PROTECTOR IN UNDERGROUND VAULTS SECONDARY LINES ALONG ALLEYS/STREETS PRIMARY FEEDERS 12470/34500 VOLT NETWORK TRANSFORMER AND PROTECTOR IN UNDERGROUND VAULTS TO LOADS 120/208 VOLT WYE OR 277/480 VOLT WYE NETWORK TRANSFORMER AND PROTECTOR IN UNDERGROUND VAULTS PRIMARY FEEDERS 12470/34500 VOLT

Secondary Distribution and Utilization (cont.) Special Cases - 120/208 volt and 277/480 volt spot networks PRIMARY FEEDERS 12470/34500 VOLT NETWORK TRANSFORMER AND PROTECTOR PRIMARY FEEDERS 12470/34500 VOLT NETWORK TRANSFORMER AND PROTECTOR 277/480 VOLT WYE THREE- PHASE BUS STEP-DOWN TRANSFORMERS 120/208 VOLT WYE THREE- PHASE BUS TO UTILIZATION PANELBOARDS

Typical Unit Substation and Metal-Clad Switchgear Used in Spot Networks

What is your role in the process for obtaining AC power for ITS systems and equipment?

1. Understand That This is a Team Effort! Some or all of the KEY PLAYERS (besides yourself) involved in furnishing and meeting your ITS AC power requirements: Electrical Engineers, Electricians/Electrical Contractors/ Facilities Maintenance Personnel, Electrical Utility Personnel, Access/Service Provider Personnel, Facility/Building Owners, The Authority(ies) Having Jurisdiction (AHJ).

2. Determine ALL of Your ITS AC Power Requirements Include ALL of your ITS spaces and equipment this could include, in some cases: All CLA (Communications, Life Safety and Building Automation) elements, Work Area/end-user requirements and remote locations. Include loads related to test equipment used for maintenance and diagnostics, and equipment loads related to MAC (moves, adds and changes).

2. Determine ALL of Your ITS AC Power Requirements (cont.) Identify which equipment is to be directly connected (i.e. hard-wired) and which equipment is to be cordand-plug connected through a receptacle; also identify the correct NEMA plug and receptacle configurations required. If applicable, include auxiliary loads (e.g. lighting, HVAC) within your ITS spaces. Include loads required for Access/Service Provider Equipment. Allow for at least a 25 percent growth factor.

2. Determine ALL of Your ITS AC Power Requirements (cont.) Identify ALL of your individual loads in terms of voltage, amperage, and wattage. Separate your loads by required operating voltage (e.g. 120, 120/240, 120/208, 277 or 277/480 volts). Are your loads single-phase, three-phase or a combination of both? Group loads by location. Develop a detailed summary of your requirements.

3. Special Areas to Consider Grounding/Bonding Overcurrent/fault protection equipment: Selection and sizing Coordination Load demand characteristics (continuous, cyclical or intermittent) Load balancing Load segregation

3. Special Areas to Consider (cont.) Need for power conditioning Reactive versus non-reactive power loads: Reactive (large inductive and capacitive loads because of motors, transformers and similar equipment that result in a significant lagging or leading Power Factor). Non-reactive (all or mostly resistive loads such as incandescent lighting, heating and similar equipment that result in a unity or a reasonably close to unity Power Factor).

3. Special Areas to Consider (cont.) Reactive loads are normally stated in kilovolt-amperes reactive (KVAR), nonreactive loads are normally stated in kilowatts (KW). The total of both reactive and non-reactive loads are normally stated in kilovoltamperes (KVA).

3. Special Areas to Consider (cont.) Service continuity for critical loads Locations of AC Power Equipment used for ITS loads and related access and security issues: Service equipment Panelboards Transformers Power conditioning equipment (UPS, etc.) Codes, Standards and other published requirements

4. Discuss Your AC Power Needs With the Key Players Practice the three C s when meeting with the Key Players: Communicate Coordinate Cooperate! Support your needs and requirements with clear, complete, factual documentation (drawings, specifications, equipment data, calculations, etc.).

4. Discuss Your AC Power Needs With the Key Players (cont.) Meet with the Key Players as early as possible and as often as necessary. Understand their requirements and limitations in meeting your needs and be prepared to negotiate! If necessary, don t forget to discuss and agree on testing, acceptance, labeling and documentation tasks related to the AC Power system for your ITS installation. All agreements between you and the Key Players relating to technical, contractual, financial or legal areas should be in writing.

5. Moving Forward and Making it Work Continue to meet with the Key Players as the work progresses. Make sure you are informed about any changes made to the AC power system that may or will affect your ITS equipment during the installation. Likewise, inform the Key Players if your AC power needs change before completion of the installation. Keep up your end of the bargain regarding any agreements made for things like testing support, field coordination and similar items.

6. After the Installation Make sure you are informed about any changes made to the AC power system that may or will affect your ITS equipment. Likewise, inform the Key Players if your AC power needs change. Keep your records up-to-date! If possible, coordinate any ITS inspection efforts with any premises electrical inspections. Pay special attention to: Bonding/Grounding integrity, General condition and cleanliness of AC power installations supporting ITS installations, Unauthorized additions or modifications.

Conclusion A proactive approach to AC power needs for ITS equipment and systems will result in: Less downtime More reliable operation Satisfied customers Lower maintenance costs =

Some Useful References NFPA 70 National Electrical Code IEEE C2 National Electrical Safety Code BICSI Telecommunications Distribution Methods Manual; Chapter 16 Power Distribution IEEE 241 Recommended Practice for Electric Power Systems in Commercial Buildings (Gray Book) IEEE 142 Recommended Practice for Grounding of Industrial and Commercial Power Systems (Green Book) IEEE 242 Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems (Buff Book) IEEE 1100 Recommended Practice for Powering and Grounding Sensitive Electronic Equipment (Emerald Book) IEEE 446 Recommended Practice for Emergency and Standby Power Systems for Industrial and Commercial Applications (Orange Book) Electrical Power Distribution and Transmission by Faulkenberry and Coffer (Prentice-Hall) Standard Handbook for Electrical Engineers by Beaty and Fink (McGraw-Hill) American Electrician s Handbook by Croft and Summers (McGraw-Hill) Ugly s Electrical References by Hart and Hart (Burleson)