Pressure controls, differential pressure controls Type RT REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Similar documents
INDUSTRIAL CONTROL INSTRUMENTS FOR PROCESS AUTOMATION

Pressure Control, Differential Pressure Control, Type RT

Temperature control, differential temperature control, type RT

Temperature controls, Type RT

When ordering, please state type and code number. Suitable sensor length. Max. Cap. range. tube adjust- see also Accessories. sensor. temp.

Pressure Controls type KPU REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Pressure switch and Thermostat Type CAS

Pressostats and thermostats CAS

Pressure and temperature controls, Type CAS

Data sheet Pressure controls and thermostats type CAS August 2000 DKACT.PD.P10.B B0616

MAKING MODERN LIVING POSSIBLE. Pressure switch BCP. Technical brochure

Pressure Control Type KPU

Heavy duty pressure switch MBC 5000 and MBC 5100

Pressure controls and thermostats, type KPS

Temperature Sensors Types MBT 5250, MBT 5260 and MBT 5252

Exhaust gas temperature sensors MBT 5113 and MBT 5116

Pressure control for air and water Type CS

Pressure transmitter for marine applications MBS 3100 and MBS 3150

YCAS AIR-COOLED LIQUID CHILLERS YCAS0373 THROUGH YCAS0653 STYLE G (R22) (50 Hz)

Pressure transmitter for marine applications Type MBS 5100 and MBS 5150

Thermostats Series 142

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

Bearing temperature sensor Type MBT 5310

Pressure operated water valve Type WVFX and WVS

D4B- N. Safety Interlock Switches. Safety Limit Switch. Specifications. Standards and EC Directives. Certified Standard Ratings D4BN

SUITABLE FOR. Wasserdampf. Steam EXAMPLES OF USE APPROVALS. Requirements PED 2014/68/EU. Classification society

CombiTemp Temperature Measuring System

D4BS. Safety-door Switch. Model Number Structure. Switch D4BS - S Operation Key D4BS - K. Ordering Information

XMLB300D2C11 pressure switch XMLB 300 bar - adjustable scale 2 thresholds - 1 C/O

Pressure transmitter for marine applications MBS 33M

SUITABLE FOR EXAMPLES OF USE APPROVALS. Type approval Deutsche Bahn. Requirements. AD 2000 Data sheet A2 DIN EN ISO PED 2014/68/EU

Solenoid valves, type EVRA 3 40 and EVRAT REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Level switch brochure

Safety Limit Switch

SUITABLE FOR. Steam EXAMPLES OF USE APPROVALS. Type approval WRAS. Type approval ACS. Requirements DIN EN ISO PED 2014/68/EU TRD 421

Mini Contactors CI 4-

LK Position Switches TECHNICAL DATASHEET.

Solenoid valves Type EVR 2 40 NC/ NO REFRIGERATION AND AIR CONDITIONING. Technical leaflet

SUITABLE FOR EXAMPLES OF USE APPROVALS. Requirements PED 2014/68/EU

SUITABLE FOR EXAMPLES OF USE APPROVALS. Type approval Deutsche Bahn. Requirements AD 2000 Data sheet A2 DIN EN ISO PED 2014/68/EU

CE Marking. Number of poles. Core Length. Frame size

Solenoid valves. Solenoid valves, type PKVD Solenoid valves, type EVR NC / NO

Limit switches. 7 Page 71. Presentation. OsiSense XC Basic Compact design, plastic, with reset knob, types XCNR and XCNTR. b XCNR.

SUITABLE FOR. Liquids. gases and vapours. Steam EXAMPLES OF USE. Requirements. AD 2000 Data sheet A2 TRD 421 TRB 801 No. 22 and No.

Data sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427

SUITABLE FOR. Liquids. Air, gases and vapours. Steam EXAMPLES OF USE APPROVALS

SUITABLE FOR EXAMPLES OF USE APPROVALS. TS EC type examination. Requirements AD 2000 Data sheet A2 DIN EN ISO PED 2014/68/EU

XMLA002A2C11 pressure switch XMLA 2.5 bar - fixed scale 1 threshold - 1 C/O

Metal tube flowmeters. Series SC250. Metal Tube Flow Meters. Series SC250. Variable area flowmeter for liquids, gases and steam

Panel-mounted Thermostats

SUITABLE FOR. Liquids. gases and vapours. Steam EXAMPLES OF USE APPROVALS

Solenoid coil for control in potentially explosive areas Type BZ

Differential pressure gauges with Bourdon tube

Metal tube variable area flowmeter for gases, liquids and steam

Data Sheet. A-Series Miniature Watertight Pressure Switches

Technical Datasheet. GR Series - Flameproof Pressure Switch Models: GR2 & GR4. GR Series. Key Features. Series Overview. Product applications

Control switch/load disconnect switch Series 8008

XMLA160D2S11 pressure switch XMLA 160 bar - fixed scale 1 threshold - 1 C/O

Solenoid valves for drinking water Types EV220BW and EV228BW

P77 Series. Single Pressure Controls for Refrigeration, Air-conditioning and Heatpump Applications. Product Bulletin

SX - se ries 150 SX 75-75

Marine Annex covering all VLT Drives Note

Hydraulic pressure switch 20D Acc. to ATEX

XMLB020A2S13 pressure switch XMLB 20 bar - adjustable scale 2 thresholds - 1 C/O

Ventilated Distribution Transformers

Three-phase motors for marine use

CI-TI TM Contactors and Motor Starters Contactors CI 6-50

Type 459. Type. 459 Safety Relief Valves spring loaded

Magnetic Float Switches horizontal 1003-h

I r A short-circuit protective device: Observe the maximum permissible fuse of the contactor with direct device mounting.

Level limit switch Series CN 4000 Selection list. Specifications 2. Applications 4

TER. Thermostats for Industrial Applications. Switching range: C to C. Housing material: aluminium. Capillary tube: copper

Thermostats for panel mounting Series ETH

Targeted en gi ne e ring de sign. Hedge and Grasscutter mowers

Explosion-protected surface-mounting Thermostat ATH-Ex Series

Catalog. Accessories Separ-Filter. Catalog: Accessories Separ-Filter Page 1 of 13

Solenoid valve Types EVR 2 EVR 40 NC/NO

Scheda prodotto Relè Series B

Modulating liquid level regulators, direct-controlled SV 1 and SV 3

HS5D Miniature Interlock Switches

SUITABLE FOR. Liquids. Air, gases and vapours. Steam EXAMPLES OF USE APPROVALS. Requirements AD 2000 Data sheet A2 TRD 421 DIN EN ISO

Series 812. TÜV/CE atmospheric discharge safety valves for industrial applications. Air, gases and vapours

Rod thermostats (without immersion tube)

Safety rope switch with reset for emergency stop

MODELS CA-1 & CA-2 MODEL CA-1 CA-TB TECHNICAL BULLETIN BACK PRESSURE / RELIEF REGULATOR FEATURES APPLICATIONS CAUTION

CI-TI Contactors and motor starters Types CI 61 - CI 98

Safety Control HR1S-AC. Safety Relay HR1S-AC

Introduction. Series P100. Encapsulated Pressure Control. Auto-reset Standard Duty and Heavy Duty. Manual reset Standard Duty. Feature and Benefits

DATASHEET - ZB Delivery program. Overload relay, 50-65A, 1N/O+1N/C. Catalog No Eaton Catalog No. XTOB065DC1 EL-Nummer

SUITABLE FOR. Warm water EXAMPLES OF USE APPROVALS. Type approval ACS. Type approval WRAS (up to 85 C)

NAMUR FLANGE: With integrated exhaust air recirculation Ordering information

SUITABLE FOR. Warm water EXAMPLES OF USE. Type approval ACS. Type approval WRAS (up to 85 C) Requirements. DIN DVGW guidelines DIN EN 1567 DIN 1988

Package Unit Modulating Economizer Installation Instructions

Motor types SMV/SMVE for MEV/MRV motorised valves

Monobloc and Sectional Directional Control Valves

Allfluid pressure switches 20D to ATEX

Scheda prodotto Relè Series E

Power consumption Wire/transformer sizing. Motor. Spring return. Motor. Spring return. EMC Low voltage directive

CI-TI Contactors and Motor Starters Type CI 6-50

MS General Information Extended Product Type: MS

Transcription:

Pressure controls, differential controls Type RT REFRIGERATION AND AIR CONDITIONING Technical leaflet

Technical data Pressure controls, differential controls, type RT Contents Page Introduction...................................................................................... 3 Features.......................................................................................... 3 Technical data.................................................................................... 3 Approvals......................................................................................... 3 Materials in contact with the medium.............................................................. 4 Ordering........................................................................................ 4-6 Desing/ Function, controls RT............................................................. 7 Design/ Function, control with deadzone RT L............................................. 8 Design/ Function, differential controls RT................................................. 9 Terminology..................................................................................... 10 Setting........................................................................................... 10 Dimensions and weight.......................................................................... 11 2 RD5BA502 DKRCC.PD.CB0.A1.02-520H1434 Danfoss A/S (AC-DSL/mr), 09-2006

Technical leaflet Pressure controls, differential controls, type RT Introduction An RT control contains a operated single-pole changeover contact, the position of which depends on the in the in let con nec tion and the set scale value. The RT series includes controls for general applications within in dus tri al and marine refrigeration. The RT series also includes differential controls, controls for neutral zone regulation, and special controls with goldplat ed contact surfaces for PLC ap pli ca tions. Features Waterproof versions Wide regulating range Wide range of units for industrial and marine ap pli ca tions Suitable for alternating and direct current Interchangeable contact system Special versions for PLC applications Technical data Cable connection Pg 13.5. Cable diameter 6 14 mm Enclosure IP 66 to EN 60529 / IEC 529, except for versions with ext. reset which are to IP 54. Ambient temperature 50 to +70 C for control housing. Switches See "Ordering, switches". Properties according to EN 60947: Wire dimensions solid/stranded 0.2-2.5 mm 2 fl exible, w/out ferrules 0.2-2.5 mm 2 fl exible, with ferrules 0.2-1.5 mm 2 Tightening torque max. 1.5 NM Rated impulse voltage 4 kv Pollution degree 3 Short circuit protection, fuse 10 Amp Insulation 400 V IP 54/66 Approvals RT 1 RT 1A RT 1AL RT 5A RT 6W, 6B, 6S RT 6AW, 6AB, 6AS RT 30AW, 30AB, 30AS RT 36B, 36S RT 117 RT 117L RT 200 RT 200L RT 260A RT 262A Lloyd s Register of Shipping, UK Germanischer Lloyd, Germany Vd TÜV, Germany Det norske Veritas, Norway Bureau Veritas, France RINA, Registro Italiano Navale, Italy RMRS, Russian Maritime Register of Shipping DIN CERTCO, Germany NKK, Japan Korean Register of Shipping CE marked according to 60947-4, -5 CE marked acc. to PED 97/23/EC category IV, safety equipm. CCC, China Compulsory Certificate Danfoss A/S (AC-DSL/mr), 09-2006 RD5BA502 DKRCC.PD.CB0.A1.02-520H1434 3

Technical data Pressure controls, differential controls, type RT Materials in contact with the medium Type Material W. no. To DIN Comments RT 117, RT 117L RT 200, RT 200L RT 1A, RT 1AL RT 5A, RT 5AL RT 260A, RT 262A RT 265A RT 1 RT 6W, 6B, 6S RT 6AW, 6AB, 6AS RT 30AW, 30AB, 30AS RT 36B, 36S Stainless steel 18/8 Stainless steel 17/7 Brass Brass Stainless steel 18/8 Plain carbon steel Deep drawing steel Plain carbon steel Case-hardened steel Aluminium Stainless steel 18/8 Plain carbon steel Deep drawing steel Stainless steel 18/8 Deep drawing steel Case-hardened steel Free-cutting steel Plain carbon steel Aluminium Stainless steel 18/8 Stainless steel 17/7 Deep drawing steel Stainless steel 18/8 STW 22 Free-cutting steel 1.4306 1.4568 2.0402 2.0321 1.4306 1.0338 1.0402 1.0401 3.0255 1.4306 1.0338 1.4306 1.0338 1.1141 1.0718 1.0402 3.0255 1.4306 1.4568 1.0338 1.4305 1.0332 1.0718 17440 17224 1782 17660 17440 17223 1624 1652 17210 1712 17440 17223 1624 17440 1624 1652 1651 1652 1712 17440 17224 1624 17440 1614 1651 Zinc plated, passivated (RT 1A, RT 1AL only) Nickel-plated, tinned Zinc plated, passivated Nickel-plated Zinc plated, passivated (RT 1 only) Nickel-plated, tinned Nickel-plated, tinned Nickel-plated Nickel-plated Zinc plated, passivated (RT 6AW, 6AB, 6AS only) (RT 6AW, 6AB, 6AS) Nickel-plated, tinned Nickel-plated Nickel-plated Ordering Pressure controls for fluorinated refrigerants Pressure Type Regulation range Differential Reset Max. working PB Max. test p Code no. Connection 1/4 in. / 6mm G 3/8 A 1 ) flare 0.8 5 0.5 1.6 aut. 22 25 017-524566 RT 1 Low 0.8 5 fixed 0.5 man. 22 25 017-524666 RT 200 0.2 6 0.25 1.2 aut. 22 25 017-523766 High RT 117 10 30 1 4 aut. 42 47 017-529566 1 ) BSP ext. thread, ISO 228/1. Safety - Pressure controls for R 717 (NH 3 ) and fluorinated refrigerants Pressure Low High Type RT 1A RT 5A 1 ) BSP ext. thread, ISO 228/1. Regulation range Differential Reset Max. working Pressure PB Max. test p Cutting ring 6 mm Code no. Connection G 3/8 A 1 ) + weld nipple 6.5/10 mm 0.8 5 0.5 1.6 aut. 22 25 017-501966 017-500166 0.8 5 fixed 0.5 man. 22 25 017-502766 017-500266 0.8 5 1.3 2.4 aut. 22 25 017-500766 4 17 1.2 4 aut. 22 25 017-505266 017-504666 4 17 fixed 1.2 man. 22 25 017-506166 017-504766 4 RD5BA502 DKRCC.PD.CB0.A1.02-520H1434 Danfoss A/S (AC-DSL/mr), 09-2006

Technical leaflet Pressure controls, differential controls, type RT Ordering (continued) *) Meets the requirements in VBG 20 on safety equipment and excess s. W = Wächter ( control). B = Begrenzer ( control S with external reset). = Sicherheitsdruckbegrenzer ( control with internal reset). A rupture in the bellows system of the unit will cause the compressor to stop. Safety controls w EN 12263 / DIN 32733 appr. and CE marked acc. PED, Pres sure Equipment Di rec tive*) Pressure High High High High Type Regulation range Differential (fixed) Reset Max. working PB 1) BSP ext. thread, ISO 228/1. 2) Pressure controls for fluorinated refrigerants. 3) Pressure controls for R 717 (NH3) and fluorinated refrigerants Max. test p 1/4 in./ 6 mm flare RT 36B 2) 0 2.5 max. 0.2 man. 22 25 017-525866 RT 36S 2) 0 2.5 max. 0.2 man. 22 25 017-525966 RT 6W 2) 5 25 2.0-3.0 aut. 34 38 017-503166 RT 6B 2) 10 28 max. 1.0 man. 34 38 017-503466 RT 6S 2) 10 28 max. 1.0 man. 34 38 017-507566 Cutting ring 6 mm Code no. Connection G 3/8 A 1) + weld nipple 6.5/10 mm G 1/2 A 1) RT 30AW 3) 1 10 0.2-0.8 aut. 22 25 017-518766 RT 30AB 3) 1 10 max. 0.4 man. 22 25 017-518866 RT 30AS 3) 1 10 max. 0.4 man. 22 25 017-518966 RT 6AW 3) 5 25 2.0-3.0 aut. 34 38 017-513166 017-503266 RT 6AB 3 ) 10 28 max. 1.5 man. 34 38 017-513366 017-503566 RT 6AS 3) 10 28 max. 1.5 man. 34 38 017-514666 017-507666 Pressure controls with adjustable dead zone for R 717(NH 3 ) and fluorinated refrigerants Pressure Low High Type Type Regulation range Differential Dead zone NZ Max. working PB Max. test p Code no. Connection Cutting ring G 3/8 A 1) + weld nipple 6 mm 6.5/10 mm RT 1AL 2 ) 0.8 5 fixed 0.2 0.2 0.9 22 25 017L001666 017L003366 RT 200L 3 ) 0.2 6 fixed 0.25 0.25 0.7 22 25 017L003266 RT 5AL 2 ) 4 17 fixed 0.35 0.35 1.4 22 25 017L001766 4) 017L004066 4) RT 117L 3 ) 10 30 fixed 1.0 1 3.0 42 47 017L004266 4) 1 ) BSP ext thread, ISO 228/1. 2) Pressure controls for (R 717 NH 3 ) and fluorinated refrigerants 3) Pressure controls for fluorinated refrigerants 4) Without nipple Differential controls for R 717(NH 3 ) and fluorinated refrigerants Regulation range Differential Operating range for LP bellows Max. working PB Max. test p' Code no. Connection Cutting ring G 3/8 A 1 ) + weld nipple 6 mm 6.5/10 mm 0.5 4 fixed 0.3 1 18 22 25 017D001466 017D002166 RT 260A 0.5 4 fixed 0.3 1 18 22 25 017D002266 2) 0.5 6 fixed 0.5 1 36 42 47 017D001566 017D002366 1.5 11 fixed 0.5 1 31 42 47 017D001666 017D002466 RT 252A 0.1 1.5 fixed 0.1 1 9 22 13 017D001366 017D002566 RT 265A 3 ) 1 6 fixed 0.5 1 36 42 47 017D007266 1 ) BSP ext thread, ISO 228/1. 2 ) Man. reset. 3 ) Filter monitor: Alarm = 0.8, cut-out = 1 (factory setting). Differential controls with adjustable dead zone for R 717(NH 3 ) and fluorinated refrigerants Type Regulation range Differential Dead zone NZ Operating range for LP bellows Max. working Max. test Code no. Connection PB p G 1/2 A 1) + Weld nipple 6.5/10 mm RT 262 AL 0.1 1.5 Fixed 0.1 0.1 0.33 1 9 11 13 017D004366 2) 1 ) BSP ext thread, ISO 228/1. 2 ) Differential control for R 717 (NH 3 ) and fluorinated refrigerants. Danfoss A/S (AC-DSL/mr), 09-2006 RD5BA502 DKRCC.PD.CB0.A1.02-520H1434 5

Technical data Pressure controls, differential controls, type RT Ordering (continued) Special versions RT can be supplied with special switches as follows. When ordering, please state: 1. Type 2. Code no. of standard unit 3. Code no. of special switch Switches 1 ) Version Symbol Description Contact load Code no. Standard Single-pole changeover switch with termi- Alternating current 2 ) 017-403066 nal board proof against leakage current Ohmic: Fitted in all standard versions of type RT. AC 1 = 10 A, 400 V Snap action changeover contacts. With man. reset For manual reset of unit after contact changeover on rising. For HP units prepared for reset facility. Induktive: AC 3 = 4 A, 400 V AC 15 = 3 A, 400 V Direct current DC 13 = 12 W, 220 V 017-404266 with man. reset With man. reset For manual reset of unit after contact changeover on falling. For LP-units prepared for reset facility. 017-404166 with man. reset With dead zone Single-pole changover switch with dead zone and terminal board proof against leakage current. Available only as a component part of RT controls with adjustable dead zone Standard With dead zone Single-pole changeover switch with gold plated (oxide-free) contact surfaces. Increases cut-in reliability on alarm and monitoring systems, etc. Snap action changeover contacts. Terminal board proof against leakage current. Single-pole changeover switch with dead zone and gold plated (oxide-free) contact surfaces. Increases cut-in reliability on alarm and monitoring systems, etc. Snap action changeover contacts. Terminal board proof against leakage current. Alternating current 2 ) Ohmic: AC 1 = 10 A, 400 V Induktive: AC 3 = 2 A, 400 V AC 15 = 1 A, 400 V Direct current DC 13 = 12 W, 220 V 017-424066 Available only as a component part of RT controls with adjustable dead zone Cuts in two circuits simultaneously Cuts out two circuits simultaneously Single-pole changeover switch that cuts in two circuits simultaneously on rising. Snap action changeover contacts. Terminal board proof against leakage current. Single-pole changeover switch that cuts out two circuits simultaneously on rising. Snap action changeover contacts. Terminal board proof against leakage current. Alternating current 2 ) Ohmic: AC 1 = 10 A, 400 V Induktive: AC 3 = 3 A, 400 V AC 15 = 1 A, 400 V Direct current DC 13 = 12 W, 220 V 3 ) 017-403466 017-403666 With nonsnap action changeover contacts Single-pole changeover switch with non-snap action changeover contacts. Alternating or direct currnent 25 VA, 24 V 017-018166 1 ) RT controls meet the conditions of EN 60947-2-9. 2 ) Max. starting current (L.R.) = 7 AC 3. 3 ) If current is led through the contacts 2 and 4, i.e. terminals and 4 con nect ed but not ter mi nal 1, the max. permissible load is increased by 90 W, 220V. The switches are shown in the position they assume on falling, i.e. after downward movement of the RT main spindle. The setting pointer of the control shows the scale value at which contact changeover occurs on falling. An exception is RT with switch code no. 017-404266 with Man. re set, where the set ting point er shows the scale value at which con tact changeover occurs on rising pres sure. 6 RD5BA502 DKRCC.PD.CB0.A1.02-520H1434 Danfoss A/S (AC-DSL/mr), 09-2006

Technical leaflet Pressure controls, differential controls, type RT Design Function Pressure control type RT 5. Setting knob 9. Regulation range scale 10. Loop terminal 11. Pg 13.5 screwed cable entry 12. Main spring 14. Terminals 15. Main spindle 16. Switch 17. Guide bush 18. Contact arm 19. Differential setting nut 23. Bellows element 25. Fixing hole 27. Connection 38. Earth terminal 39. Blow-out disc 44. Pressure setting spindle Key sketch RT control The bellows in the RT control is con nect ed to the low or high pres sure side of the con trol led system via the connection. By turning the setting knob (5) the main spring (12) can be set to balance the in the bellows. A rise in compresses the bellows and moves the main spindle (15) upwards until spring and bellows are in equilibrium. The main spin dle (15) is fitted with a guide bush (17) and a differential setting nut (19) that together transfer the main spindle move ment to the switch (16). The RT 6W, 6B, 6S, RT 6AW, 6AB, 6AS, RT 30AW, 30AB, 30AS, RT 36B, 36S are equipped with a double bellows (an outer bellows and a regulating bellows). These units have been tested and approved by TÜV (Technischer Überwachungs Verein, Germany) according to EN 12263 / DIN 32733. W = Wächter ( controls) B = Begrenzer ( controls with external re set) S = Sicherheitsdruckbegrenzer ( controls with internal reset). RT control General for EN 12263 / DIN 327333 approved units 1. The units are equipped with a double bellows system. When in the plant exceeds the set value, the unit will automatically stop the plant. The double bellows system prevents loss of system charge in the event of bellows rup ture. 2. Versions with designation W or AW cut in again automatically when the has fallen to the set value minus the differential. 3. Versions with designation B or AB are cut in manually with the external re set button. This is possible when the has fallen by a value cor re spond ing to the differential un der the set val ue. 4. Versions with designation S or AS can be cut in manually with the internal reset arm when the pres sure has fallen by a value corresponding to the differential under the set value. As laid down by EN 12263 / DIN 32733 requirements, if a rupture occurs in the reg u lat ing bellows of the unit the refrigerating system compressor will be stopped and can only be restarted when the control has been replaced. A rupture in the outer bellows will cause the cutout of RT 36 to fall 2.5, and the cut-out of RT 6 and RT 30 to fall 4.5 un der the set value. This means that the unit cuts out at normal condensing and thus provides a fail-safe func tion. All RT controls, including those which are EN 12263 / DIN 32733 approved, op er ate independently of changes in the ambient temperature around the control housing. Therefore the set cut-out pres sure and differential are held constant provided the permissible ambient temperatures are not exceeded. Danfoss A/S (AC-DSL/mr), 09-2006 RD5BA502 DKRCC.PD.CB0.A1.02-520H1434 7

Technical data Pressure controls, differential controls, type RT Design Function (continued) Pressure control with dead zone, type RT L 5. Setting knob 9. Regulation range scale 11. Pg 13.5 screwed cable entry 12. Main spring 15. Main spindle 16. Switch 17. Upper guide bush 18. 18a, 18b. Contact arm 20. Lower guide bush 23. Bellows element 25. Fixing hole 27. Connection 38. Earth terminal 39. Blow-out disc 40. Neutral zone setting nut 44. Pressure setting spindle Key sketch RT L control RT L controls are fitted with a switch (17-4032) with an adjustable neutral zone. This en a bles the units to be used for floating control. The neu tral zone switch contact arms (18a) and (18b) are operated by the spindle guide bushes (17) and (20). RT L control The upper guide bush (17) is Fixed while the low er guide bush (20) can be moved up or down by the setting nut (40). In this way the neu tral zone can be varied between a minimum val ue (equal to the mechanical differential of the unit) and a max i mum value (de pend ing on the type of RT unit). 8 RD5BA502 DKRCC.PD.CB0.A1.02-520H1434 Danfoss A/S (AC-DSL/mr), 09-2006

Technical leaflet Pressure controls, differential controls, type RT Design Function (continued) Differential control, type RT 3. LP connection 4. LP bellows element 5. Setting disc 9. Regulation range scale 10. Coil clamp 11. Pg 13.5 screwed cable entry 12. Main spring 14. Terminals 15. Main spindle 16. Switch 17. Upper guide bush 18. Contact arm 20. Lower guide bush 24. HP bellows element 25. Fixing hole 34. HP connection 38. Earth terminal 39. Blow-out disc Key sketch RT differential control RT differential control An RT differential control contains a single-pole changeover switch that makes or breaks depending on the differential between two coun ter act ing bellows elements (LP and HP). Differential controls are used primarily as protection against too low a differential across liquid circulation pumps. A secondary application is the safeguarding of lubricating oil in re frig er a tion compressors. The function of the control is con di tion al only on the differential pres sure, i.e. the difference in between the two counteracting bel lows, whereas it is in de pend ent of the absolute on both bellows. The bellows (4) and (24) are respectively connected to the LP port (lowest ) and the HP port (highest ). The main spring (12) can be set for different differential s by the set ting disc (5). If the differential between highest and lowest s falls, the spindle (15) moves down wards and via the upper guide bush (17) actuates the switch contact arm (18). The reverse function occurs if the differential rises. For RT 260A controls used on screw compressors the following applies 1 ) 1. Max. in low bellows condensing = 21. 2. Max. in high bellows lubricating oil = 24. 3. Differential between condensing and lubricating oil must not exceed 3. 4. Pressure change in the low and high pres sure bellows from start to nor mal operation must not exceed 8. 1 ) Since the operating conditions given, are out side the operating range of the unit, the life of the bellows will be reduced to approx. 10 000 op er a tions as against approx. the normal 400 000. Danfoss A/S (AC-DSL/mr), 09-2006 RD5BA502 DKRCC.PD.CB0.A1.02-520H1434 9

Technical data Pressure controls, differential controls, type RT Terminology Floating control A form of delayed control where the correcting element (e.g. valve, damper, or similar) moves towards one extreme position at a rate independent of the magnitude of the error when the error ex ceeds a definite positive value, and to wards the opposite extreme position when the er ror exceeds a definite neg a tive value. Hunting Periodic variations of the controlled variable from the Fixed reference. Neutral zone The interval between the make points of the two contacts. "Snap function" A certain contact force is maintained until irrevocable "snap" is initiated. The time during which the contact force approaches zero is thus limited to a very few milliseconds. Therefore contact bounce cannot occur as a result of, for ex am ple, slight vibrations, before the cut-out point. Contact systems with "Snap function" will change over even when micro-welds are cre at ed be tween the contacts during cut-in. A very high force is cre at ed during cut-out to separate the con tacts. This force immediately shears off all the welds. Thus the cut-out point of the unit remains very accurate and completely independent of the magnitude of the current load. Setting RT with automatic reset - LP The knob is used to set the lowest at which the contact system must be activated (cut-out or cut-in). This value can be read on the main scale of the unit. The differential roller must be used to set the differential. Highest activating = lowest activating pres sure + set differential. RT with manual reset - LP RT controls RT 1 and RT 1A are obtainable in versions with min. reset. When the pres sure falls to the setting value the con trol cuts out. Manual reset becomes possible when the in the bellows system has risen to a val ue cor re spond ing to the set value + the differential. On falling the follower activates the contact system arm and the con tact changes over. The scale is calibrated so that the scale value cor re sponds to contact changeover on falling pres sure. RT with automatic reset - HP The knob can be used to set the lowest pres sure at which the contact sys tem must be ac ti vat ed (cut-out or cut-in). This value can be read on the main scale of the unit. The differential must be set with the differential roll er. Highest activating pres sure = lowest activating + set differential. RT with manual reset - HP Pressure control RT 5A is obtainable with max. reset. When the has risen to the set value the control cuts out. Manual reset only becomes possible when the pres sure has fallen to a val ue corresponding to the set minus the differential. The differential roller is then used as a follower. On rising the differential roller ac ti vates the contact system arm and the contact changes over. The scale is calibrated so that the scale values cor re spond to contact changeover on rising, which is opposite to RT units with automatic reset. 10 RD5BA502 DKRCC.PD.CB0.A1.02-520H1434 Danfoss A/S (AC-DSL/mr), 09-2006

Technical leaflet Pressure controls, differential controls, type RT Dimensions and weight Weight approx. 1 kg RT control housing RT 1 RT 1A, 1AL RT 1A, 1AL RT 6A RT 6A RT 6, 36 RT 30A RT 117, 117L, 200, 200L RT 260A RT 262A RT 260A, 262A Danfoss A/S (AC-DSL/mr), 09-2006 RD5BA502 DKRCC.PD.CB0.A1.02-520H1434 11

Technical data Pressure controls, differential controls, type RT 12 RD5BA502 DKRCC.PD.CB0.A1.02-520H1434 Danfoss A/S (AC-DSL/mr), 09-2006