Application Guide 575-012 Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1 Carlyle Controller Part No. 2BSB000928 1
General Description The PCM is part of Paragon Compressor control packages 6BSB000929 and 6BSB000930. Besides this Application Guide, the following manuals, I/O Zone Installation Guide and I/O Zone Integration Guide are necessary for proper installation and Network Protocol configuration. PCM Configuration 2
Compressor Protection See Table A & B for Tm control points. See Table A & B for Td control points. Run Recognition Signal The Slide Valve and Compressor Protection functionality are not active until the PCM receives the Run Recognition signal from the System Controller. LED Fault Indication Fault Description LED Indication (Output #4) Output #5 Compressor Manual Reset Required Table C 3
Slide Valve Control: LED Indicators are provided in the PCM Controller Kit. Install labels next to each LED light identifying the indication. The end user will have to configure the PCM in the following way: PressureTemperature Physical InputNetwork Input See Table/Chart D & E Logic 1.) UpperDB-1 UpperDB-2. Upper DB-2Lower DB-3 3.) LowerDB-4 Slide Valve Coil #1, Coil #2 Slide Valve Coil #1, Coil #2 Logic 2.) UpperDB-2 Upper DB-2Lower DB-3 4.) LowerDB-3 lower and upper dead-bands are adjustable inputs Note: 12 34 4 Place adhesive label in a location next to the PCM Controller so it is visible for Field Service and Refrigeration Technicians. 33
32 5
PCM Module Inputs Input #1: Slide-Valve Capacity Control See Chart E See Table F Input #2: Motor Temperature Control Note: The motor thermistor connection points are located in the compressors electrical box at terminals S1 and C. In the event of a thermistor failure, a spare thermistor is available between S2 and C terminal points. Table D Table A & B. Input #3: Discharge Temperature Control Table D Table A & B 6 31
General Installation Pictorials (for example only) Input #4: Dry Contact for Compressor Oil Protection Input #5: Compressor recognition signal (received from Master Controller) Tells the PCM Controller that the compressor is actually on/running. Slide Valve Control and Compressor Protection are activated when the PCM receives the recognition signal that the compressor is on. PCM controller initiates a 15 second delay regarding monitoring input#1 (suction pressure or thermistor temperature). PCM controller allows for a 3 second delay prior to beginning to monitoring inputs and taking action for inputs #2, #3, and #4 (eliminate nuisance trips on startup). When the compressor is off, there will be no oil flow. Therefore the oil flow switch will be open, causing output #5 to open, therefore not allowing the compressor to start. Therefore the controller must ignore the oil flow switch until the compressor is started and actual compressor oil flow is established, resulting in a closed oil flow switch. Input #6: Dry Contact for Manual Reset Compressor Operational PCM Module Outputs 30 7
Web Control Software Output #1 & #2: Slide Valve Control Output #3: Open/Close Motor Cooling Valve Output #4: LED Status indication for a Compressor Trip Table C.. Output #5: Enables the Compressor to Run When output is closed (energized), the compressor is enabled to run and therefore there are no fault conditions. Output must be part of Refrigeration System s pilot duty Start/Stop Compressor circuit. An alternative to output #5 is the end user receiving this compressor start/stop signal (run enable) via the PCM s communication port to the System Controller. Output will open (de-energize), tripping the compressor off line if the following fault conditions arise o High Discharge Temperature o High Motor Temperature o Low oil level o Low oil flow o Faulty pressure transducer (open or short) o Faulty thermistor (open or short) Controller Default Setting: PCM Default Setting Slide Valve Control: Enabled Upper Deadband-B: 2 F Compressor Protection: Enabled Upper Deadband-A: 1 F Upper Deadband-B: 2 psig Lower Deadband-A: 1 F Upper Deadband-A: 1 psig Lower Deadband-B: 2 F Lower Deadband-A: 1 psig Suction Pressure set-point: 30 psig Lower Deadband-B: 2 psig Temperature set-point: 35F 8 29
PCM Control Points Motor and Discharge Temperature Control Points ALC Controller Injection On ( F ) Injection Off( F) Shutdown Compressor ( F) Manually Reset Compressor( F) Time Delay required before manual reset (sec) Table A Slide Valve Override Control Points ALC Controller Restrict Further Compressor Unloading Energized SV Coil #2 continuously ( F) Fully Load Compressor and restrict unloading below 100% Energize SV Coil #1 and Coil #2 continuously ( F) Table B 28 9
Sensor Profile 1.2 1 0.8 5K NTC, Part# HH79NZ065 Deg F vs VDC VDC 0.6 0.4 0.2 0 50 100 150 200 250 300 Deg F VDC Table D Sig Gnd 10 27
ZS PRO Display For permanent installation with the PCM Controller. See the I/O Zone Installation Guide for specifications and installation instruction for the ZS Pro. Large, easy-to-read LCD on the ZS Pro can be configured to display virtually any analog or digital value in your equipment. Here are some examples: zone temperature, outside air temperature, energy-saving mode icon, heating set-point, cooling set-point, relative humidity, CO2, VOCs, override time remaining, fan status, compressor status, alarms, and much more. Occupancy override is simple using the "Manual On" momentary push button on the ZS Pro. A single push switches the zone to an Occupied mode for a preset period of time. The user can increase or decrease the override time with the up or down arrows, and the LCD displays precisely how long the zone will stay occupied. The occupied time increment and maximum override time are fully adjustable. Zone set-points can be changed on the ZS Pro by pressing the up or down arrow buttons. Setpoint adjust increment amount and the maximum total adjustment are fully adjustable. Chart E 120 100 80 60 40 20 0-20 -40 NTC Thermistor, Part# A1004MS24P1 VDC vs Deg F -60 1.000 1.500 2.000 2.500 3.000 3.500 Deg F Chart F PCM Layout and Interface: Note: The I/O Zone Installation Guide is for controller specifications, mounting requirements, and electrical requirements and installation. The I/O Zone Integration guide is for instruction regarding using the PCM with Network Protocols. 26 11
BACview6 Virtual Display BACview User Guide 24 VAC Supply Power Input required. End User interface for pilot duty compressor on/off control circuit. 24VAC Supply Power Input required for BUS Outputs. 24 VAC input Supply Power required to the BUS. 12 25
Hardwire connection location for permanent installations. How to Wire the Inputs for Pressure Transducer, Thermistor, or Dry Contact Connection port for portable or temporary installation. White Wire Red Wire 5vdc Power Supply 24 13
PCM Input #1 (Process Control Set-point): PCM Controller Display Features (3 WIRE) Carlyle kit 6BSB000931 BLACK WHITE RED BACview6 Handheld BACview6 Software ZS PRO Web Control BACview6 Handheld Display BACview User Guide Set the configuration jumper for input #1 depending on if the control set-point will be measured via Pressure or Temperature. The jumper comes installed on the PCM and may already be in the correct position. Place the configuration jumper to this position if the Process Control Variable is a thermistor sensor for Input #1. OR Place the configuration jumper to this position if the Process Control Variable is a 0-5 vdc Pressure Transducer sensor for Input #1. 14 23
Slide Valve Wiring Diagram with System Controller I/OZ 560 Module Supply Power 24/120/240 Vac System Controller Slide Valve Override Output #1 Output #2 22 SV Coil #1 (Capacity Control) SV Coil #2 (Capacity Control) PCM Input #2: 15 S1 C S2 Must set the configuration jumper to this position for Input #2. This sets the type of signal the input will receive as a Thermistor. Failure to do so will result in input #2 not working correctly.
PCM output #5: PCM Input #3: Table A & B. must Output will open (de-energize), tripping the compressor off line, for the following fault conditions: o High Discharge Temperature o High Motor Temperature o Low oil level o Low oil flow o Faulty pressure transducer (open or short) o Faulty thermistor (open or short) Slide Valve Override Table B. See wiring diagram below. Slide Valve Override Control Points ALC Controller Restrict Further Compressor Unloading Energized SV Coil #2 continuously ( F) Fully Load Compressor and restrict unloading below 100% Energize SV Coil #1 and Coil #2 continuously ( F) Table B 16 21
PCM output #3: PCM output #4: PCM Input #4: Fault Description LED Indication (Output #4) Output #5 Compressor Manual Reset Required Flow Switch Ratings VA Volts AMPS AC AMPS DC 20 17
PCM Input #5: PCM outputs #1 & #2: Note: All PCM outputs are rated for 24vac @ 1 amp. User must set the configuration jumper to this position for Input #5. This configures Input #5 as a Dry Contact. Failure to do so will result in input #5 not working correctly. PCM Input #6 Loads Comp Unloads Comp Freezes Unloading 18 19