Application Guide Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1. Carlyle Controller Part No.

Similar documents
Application Engineering

Application Engineering

Vission 20/20 micro-controller. Operation and service manual

Control Panel. Operation and Service Manual

SE8300 Series Installation Guide 24 Vac Low Voltage

Vission 20/20 micro-controller. Operation and service manual Version 2.6

PCT-3001 plus. Display LCD

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

RSMD Technical Guide

CONTROL PANEL OPERATING MANUAL

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide

Fan Coil Thermostat. Specification & Installation instructions TFC54F3X1. Technical Data

Application Engineering Europe

With Starter Information

INSTRUCTIONS FOR INSTALLING AND OPERATING THE UNIVERSAL AUTOSYNC MODEL ASPSS DUAL COMPRESSOR SEQUENCER CONSOLE S/N 1638 AND ABOVE

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS

Service Facts. WARNING: HAZARdOuS VOLTAGe - disconnect POWeR and discharge 4TTX6048-SF-1K. ComfortLink II System Cooling 4TTX6048C1000A.

Centrifugal Operating Manual With Starter Information

Service Facts. WARNING: HAZARdOuS VOLTAGe - disconnect POWeR and discharge 4TWX6024-SF-1K. ComfortLink II System Heat Pump 4TWX6024C1000A.

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING

CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS

OUTDOOR UNIT CONTROLLER (OUC)

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

ACCESSORY KIT INSTALLATION INSTRUCTIONS

Vibralert Mechanical Switch Model 5550

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTZ0036B-SF-1B. ComfortLink II System Cooling 4TTZ0036B1000A CAUTION

HS Refrigeration Screw Compressor Troubleshooting Guidelines. SG March 2014

Hardware Installation. Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN

RVS-DN Digital Reduced Voltage Motor Starter

NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors

P445 Series Electronic Lube Oil Control

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016

LG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units

INSTALLATION INSTRUCTIONS

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 10/14

LG Air conditioning CAC and Multi Split unit Fault code sheet Universal and Multi Split Units

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 06/18

RVS-DX Digital Reduced Voltage Motor Starter

INSTRUCTIONS FOR INSTALLING AND OPERATING THE UNIVERSAL AUTODUAL MODEL ADSE-2 DUAL COMPRESSOR SEQUENCER (firmware ver 1.02

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

Designed for ease of integration with automation systems

Service Facts. WARNING: HAZARdOuS VOLTAGE - disconnect POWER and discharge 4TWZ0024-SF-1F. ComfortLink II System Heat Pump 4TWZ0024A1000A.

ZIP Economizer Fault Detection and Diagnostics (FDD) Table

BAPI-Stat 3 Room Sensor

MANUAL TROUBLESHOOTING. ECM Motor. ECM / ECM-DX Series. v100 Issue Date: 08/15/ Price Industries Limited. All rights reserved.

INSTALLATION AND OPERATING INSTRUCTIONS REGENERATIVE DRIVE MODEL KBRG-255 (5HP) KB Part No FULL WAVE 4 QUADRANT FWD ACCEL REV ACCEL FWD CL

POWER TROLLEY 8 INSTRUCTION MANUAL POWER TROLLEY 8. Model: SINE Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System

Northwest RV Supply Manual Compliments of Printed From TROUBLESHOOTING

Description. functions including single duct pressure dependent or pressure independent systems.

Digital Room Thermostats with Touch Screen LCD

TECHNICAL BROCHURE BSPDDRIVE. Aquavar SPD (Single Pump Drive) SIMPLEX VARIABLE SPEED PUMP CONTROLLER FOR SUBMERSIBLE AND CENTRIFUGAL PUMPS

COMMUNICATIONS SETUP DBS STARTER PANEL

Product Catalog. NQ Series. Portable and Remote Air-Cooled Condenser Chillers 4 to 43 Tons

Power Distribution System User s Manual. Model: PDS-100

MANUAL INSTALLATION. Tracking Controller. TC Series. v100 Issue Date: 02/25/ Price Industries Limited. All rights reserved. Firmware: 1.3.

Installation. Part A, Section 3. This section covers the following unit configurations. 3400V 3500V. Voltage 4. Pump Piston (E, F, G)

Engineering Bulletin. IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51)

INSTALLATION AND OPERATING INSTRUCTIONS REGENERATIVE DRIVE FULL WAVE 4 QUADRANT REV S/LT NLT R33 AC LINE FUSE ARMATURE F2 FUSE TB2

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control

TCM D Single Zone, 24 Volt DC Timer Control Module User s Manual D-M-E Company

SE7200 Series Installation Guide

PCT-3000 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS

OnCommand Troubleshooting Guide Hayward Industries

Installation. Part A, Section 3. This section covers the following unit configurations. Voltage 1, 2, 3. Vista Standard (V) A3EN-04-[3V-A-AAXV]-11

Model 550 Series Vibration Switches

Mount directly to 1.05 jackshafts. AF230 US (p. 02) AF230-S US (p. 20) AF24-S US (p. 18)

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION

Warm. DFC Direct Fired Gas Heating System. Applied Air. Keeps You. Technical Guide for: Outdoor Mounted Units To 100,000 CFM And 14M BTUH

SOLAR SMART. 12/24V 20Amp MPPT Solar Charge controller with Ethernet

SmartOnline 120V 2.2kVA 1.8kW Double-Conversion UPS, 2U, Extended Run, Network Card Slot, LCD, USB, DB9

QUICK START GUIDE FOR DEMONSTRATION CIRCUIT DC1259A BATTERY BACKUP MANAGER BOARD

This Datasheet for the IC670MDL930. Relay 2A 8 Pt. 6 form A/2 form C Isolated.

User Manual 1KVA-5KVA INVERTER / CHARGER

Uninterruptible Power System

Tattletale Annunciators and Magnetic Switches

CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration

EZ-TRAC Digital Tension Readout and Control

Uninterruptible Power System

FIRE DOOR OPERATOR WARNING INSTALLATION LOGIC BOARD REPLACEMENT KIT K , K A-400 & K B-400 APPLICATION REMOVE AC AND DC POWER

GE Energy. The Becker * DNGP: Fail-Safe Protection for Your Gas Pipeline

SECTION MOTOR CONTROL

MCC Automatic Start-Stop Microcomputer Charger Control

Uninterruptible Power System

Installation Instructions

Modbus Integration Integration for Modbus Functionality for VT8600 Series

KBVF Adjustable Frequency Drive

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint

PS1 Single High and Low Pressure & PS2 Dual Pressure Refrigeration Controls. Instruction Sheet PA October 2007

Supersedes CL2 (512) Form CL2 (615) STARTUP CHECKLIST PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT NO:

CONTROLLED CHILLED BEAM PUMP MODULE OWNER S MANUAL

Appendix A: Inputs, Outputs, and Parameters

Wiring diagrams on page 29 are for reference only. For detailed vehicle wiring refer to Navistar documents.

TOTALINE PROTECTION CONTROLS

CDI series Model TW. Residential Water to Water Heat Pump. Engineering Submittal Sheet. Standard Features. Overview and Certifications

PoolPak ECCIII User s Guide Supplement to Form NM-1(1198)

Model No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Transcription:

Application Guide 575-012 Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1 Carlyle Controller Part No. 2BSB000928 1

General Description The PCM is part of Paragon Compressor control packages 6BSB000929 and 6BSB000930. Besides this Application Guide, the following manuals, I/O Zone Installation Guide and I/O Zone Integration Guide are necessary for proper installation and Network Protocol configuration. PCM Configuration 2

Compressor Protection See Table A & B for Tm control points. See Table A & B for Td control points. Run Recognition Signal The Slide Valve and Compressor Protection functionality are not active until the PCM receives the Run Recognition signal from the System Controller. LED Fault Indication Fault Description LED Indication (Output #4) Output #5 Compressor Manual Reset Required Table C 3

Slide Valve Control: LED Indicators are provided in the PCM Controller Kit. Install labels next to each LED light identifying the indication. The end user will have to configure the PCM in the following way: PressureTemperature Physical InputNetwork Input See Table/Chart D & E Logic 1.) UpperDB-1 UpperDB-2. Upper DB-2Lower DB-3 3.) LowerDB-4 Slide Valve Coil #1, Coil #2 Slide Valve Coil #1, Coil #2 Logic 2.) UpperDB-2 Upper DB-2Lower DB-3 4.) LowerDB-3 lower and upper dead-bands are adjustable inputs Note: 12 34 4 Place adhesive label in a location next to the PCM Controller so it is visible for Field Service and Refrigeration Technicians. 33

32 5

PCM Module Inputs Input #1: Slide-Valve Capacity Control See Chart E See Table F Input #2: Motor Temperature Control Note: The motor thermistor connection points are located in the compressors electrical box at terminals S1 and C. In the event of a thermistor failure, a spare thermistor is available between S2 and C terminal points. Table D Table A & B. Input #3: Discharge Temperature Control Table D Table A & B 6 31

General Installation Pictorials (for example only) Input #4: Dry Contact for Compressor Oil Protection Input #5: Compressor recognition signal (received from Master Controller) Tells the PCM Controller that the compressor is actually on/running. Slide Valve Control and Compressor Protection are activated when the PCM receives the recognition signal that the compressor is on. PCM controller initiates a 15 second delay regarding monitoring input#1 (suction pressure or thermistor temperature). PCM controller allows for a 3 second delay prior to beginning to monitoring inputs and taking action for inputs #2, #3, and #4 (eliminate nuisance trips on startup). When the compressor is off, there will be no oil flow. Therefore the oil flow switch will be open, causing output #5 to open, therefore not allowing the compressor to start. Therefore the controller must ignore the oil flow switch until the compressor is started and actual compressor oil flow is established, resulting in a closed oil flow switch. Input #6: Dry Contact for Manual Reset Compressor Operational PCM Module Outputs 30 7

Web Control Software Output #1 & #2: Slide Valve Control Output #3: Open/Close Motor Cooling Valve Output #4: LED Status indication for a Compressor Trip Table C.. Output #5: Enables the Compressor to Run When output is closed (energized), the compressor is enabled to run and therefore there are no fault conditions. Output must be part of Refrigeration System s pilot duty Start/Stop Compressor circuit. An alternative to output #5 is the end user receiving this compressor start/stop signal (run enable) via the PCM s communication port to the System Controller. Output will open (de-energize), tripping the compressor off line if the following fault conditions arise o High Discharge Temperature o High Motor Temperature o Low oil level o Low oil flow o Faulty pressure transducer (open or short) o Faulty thermistor (open or short) Controller Default Setting: PCM Default Setting Slide Valve Control: Enabled Upper Deadband-B: 2 F Compressor Protection: Enabled Upper Deadband-A: 1 F Upper Deadband-B: 2 psig Lower Deadband-A: 1 F Upper Deadband-A: 1 psig Lower Deadband-B: 2 F Lower Deadband-A: 1 psig Suction Pressure set-point: 30 psig Lower Deadband-B: 2 psig Temperature set-point: 35F 8 29

PCM Control Points Motor and Discharge Temperature Control Points ALC Controller Injection On ( F ) Injection Off( F) Shutdown Compressor ( F) Manually Reset Compressor( F) Time Delay required before manual reset (sec) Table A Slide Valve Override Control Points ALC Controller Restrict Further Compressor Unloading Energized SV Coil #2 continuously ( F) Fully Load Compressor and restrict unloading below 100% Energize SV Coil #1 and Coil #2 continuously ( F) Table B 28 9

Sensor Profile 1.2 1 0.8 5K NTC, Part# HH79NZ065 Deg F vs VDC VDC 0.6 0.4 0.2 0 50 100 150 200 250 300 Deg F VDC Table D Sig Gnd 10 27

ZS PRO Display For permanent installation with the PCM Controller. See the I/O Zone Installation Guide for specifications and installation instruction for the ZS Pro. Large, easy-to-read LCD on the ZS Pro can be configured to display virtually any analog or digital value in your equipment. Here are some examples: zone temperature, outside air temperature, energy-saving mode icon, heating set-point, cooling set-point, relative humidity, CO2, VOCs, override time remaining, fan status, compressor status, alarms, and much more. Occupancy override is simple using the "Manual On" momentary push button on the ZS Pro. A single push switches the zone to an Occupied mode for a preset period of time. The user can increase or decrease the override time with the up or down arrows, and the LCD displays precisely how long the zone will stay occupied. The occupied time increment and maximum override time are fully adjustable. Zone set-points can be changed on the ZS Pro by pressing the up or down arrow buttons. Setpoint adjust increment amount and the maximum total adjustment are fully adjustable. Chart E 120 100 80 60 40 20 0-20 -40 NTC Thermistor, Part# A1004MS24P1 VDC vs Deg F -60 1.000 1.500 2.000 2.500 3.000 3.500 Deg F Chart F PCM Layout and Interface: Note: The I/O Zone Installation Guide is for controller specifications, mounting requirements, and electrical requirements and installation. The I/O Zone Integration guide is for instruction regarding using the PCM with Network Protocols. 26 11

BACview6 Virtual Display BACview User Guide 24 VAC Supply Power Input required. End User interface for pilot duty compressor on/off control circuit. 24VAC Supply Power Input required for BUS Outputs. 24 VAC input Supply Power required to the BUS. 12 25

Hardwire connection location for permanent installations. How to Wire the Inputs for Pressure Transducer, Thermistor, or Dry Contact Connection port for portable or temporary installation. White Wire Red Wire 5vdc Power Supply 24 13

PCM Input #1 (Process Control Set-point): PCM Controller Display Features (3 WIRE) Carlyle kit 6BSB000931 BLACK WHITE RED BACview6 Handheld BACview6 Software ZS PRO Web Control BACview6 Handheld Display BACview User Guide Set the configuration jumper for input #1 depending on if the control set-point will be measured via Pressure or Temperature. The jumper comes installed on the PCM and may already be in the correct position. Place the configuration jumper to this position if the Process Control Variable is a thermistor sensor for Input #1. OR Place the configuration jumper to this position if the Process Control Variable is a 0-5 vdc Pressure Transducer sensor for Input #1. 14 23

Slide Valve Wiring Diagram with System Controller I/OZ 560 Module Supply Power 24/120/240 Vac System Controller Slide Valve Override Output #1 Output #2 22 SV Coil #1 (Capacity Control) SV Coil #2 (Capacity Control) PCM Input #2: 15 S1 C S2 Must set the configuration jumper to this position for Input #2. This sets the type of signal the input will receive as a Thermistor. Failure to do so will result in input #2 not working correctly.

PCM output #5: PCM Input #3: Table A & B. must Output will open (de-energize), tripping the compressor off line, for the following fault conditions: o High Discharge Temperature o High Motor Temperature o Low oil level o Low oil flow o Faulty pressure transducer (open or short) o Faulty thermistor (open or short) Slide Valve Override Table B. See wiring diagram below. Slide Valve Override Control Points ALC Controller Restrict Further Compressor Unloading Energized SV Coil #2 continuously ( F) Fully Load Compressor and restrict unloading below 100% Energize SV Coil #1 and Coil #2 continuously ( F) Table B 16 21

PCM output #3: PCM output #4: PCM Input #4: Fault Description LED Indication (Output #4) Output #5 Compressor Manual Reset Required Flow Switch Ratings VA Volts AMPS AC AMPS DC 20 17

PCM Input #5: PCM outputs #1 & #2: Note: All PCM outputs are rated for 24vac @ 1 amp. User must set the configuration jumper to this position for Input #5. This configures Input #5 as a Dry Contact. Failure to do so will result in input #5 not working correctly. PCM Input #6 Loads Comp Unloads Comp Freezes Unloading 18 19