AEC PHOTOVOLTAIC TEST FACILITY FIRST YEAR TEST DATA

Similar documents
Solar Power. Demonstration Site. Annual Performance Report 2017

SOLAR ENERGY ASSESSMENT REPORT. For 115 kwp. Meteorological Data Source Meteonorm. Date 18 October, Name of Place California.

SOLAR TRACKER SITE DESIGN: HOW TO MAXIMIZE ENERGY PRODUCTION WHILE MAINTAINING THE LOWEST COST OF OWNERSHIP

Introduction: Supplied to 360 Test Labs... Battery packs as follows:

Title Goes Here and Can Run Solar Photovoltaic up to 3 lines as shown here Systems as you see

Why array oversizing makes financial sense

AeroVironment Universal Solar Pump Controllers

Glossary. * Credit for glossary starter: Florida Solar Energy Center. August 2015 PV Installer's Course: Glossary 1

LAYOUT REPORT OF GROUND MOUNTED PROJECT

21st European Photovoltaic Solar Energy Conference, 4-8 September 2006, Dresden, Germany

Figure 1b: Daily Production Profile Non Power Limiting Day


EXPERIMENTAL INVESTIGATON OF SOLAR PANEL PERFORMANCE AT VARIOUS ENVIRONMENTAL CONDITIONS

INVERTER PERFORMANCE COMPARISON

Annex 1. Field Report: Solar Electric Light Fund Energy Harvest Control Study

LAYOUT REPORT OF ROOFTOP PROJECT. For 115 kwp. Order No. # Date 13 October, Name of Place California.

Portland General Electric Company Eleventh Revision of Sheet No. 7-1 P.U.C. Oregon No. E-18 Canceling Tenth Revision of Sheet No.

A 3-Year Case Study of a Residential Photovoltaic System with Microinverters

Recap of this Builder Group s Requests

Welcome to the SEI presentation on the basics of electricity

Solar inverter From Wikipedia, the free encyclopedia

Development of the Single Phase PV Inverter SANUPS P61A

SOLAR PV CAROUSEL TRACKERS FOR BUILDING FLAT ROOFTOPS: THREE CASE STUDIES

Get More When Shopping for Solar

ANALYZING POWER LOSSES AND THEIR EFFECTS IN COMPLEX POWER SYSTEMS

Field Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems

Design and Installation of A 20.1 kwp Photovoltaic-Wind Power System

Total number of PV modules: 42 Energy usability factor: 99.9 % Number of PV inverters: 1

Alliant Energy Solar Demonstration Project October 4, 2017

O&M Requirements for Utility-Scale Solar PV and Energy Storage. Nicholas Jewell, Ph.D., PMP Sr. Research Engineer Research & Development LG&E and KU

OPTIMIZATION OF DC PLANT TOPOLOGY USING AE 1000NX INVERTERS

Reduction of vehicle noise at lower speeds due to a porous open-graded asphalt pavement

Performance Analysis of 40 KW Solar Photovoltaic System at DTU

Solar Charge Controller

Analysis of Grid Connected Solar Farm in ETAP Software

Solar Electric Modules

Airports Going SOLAR! Michael Shonka

String Sizing with SkyBox

Dynamic Modelling of Hybrid System for Efficient Power Transfer under Different Condition

Y9. GEH2.3: FREEDM Cost Benefit Analysis based on Detailed Utility Circuit Models

14 October 09 Vas Kandiah AOQ SSMBB

Analysis of Impact of Mass Implementation of DER. Richard Fowler Adam Toth, PE Jeff Mueller, PE

PV-Wind SOFTWARE for Windows User s Guide

Hardware Testing of Photovoltaic Inverter Loss of Mains Protection Performance

Development of the 3-phase PV Inverter SANUPS P83D

White Paper. How Do I Know I Can Rely on It? The Business and Technical Cases for Solar-Recharged Video Surveillance Systems


City Title. . Is System Owner interested in being contacted about energy efficiency opportunities at this site? Title. City. Site Contact.

Galapagos San Cristobal Wind Project. VOLT/VAR Optimization Report. Prepared by the General Secretariat

Impact of Reflectors on Solar Energy Systems

Solar Power Energy Harvesting Electrical Integration

Georgia Pacific Crossett Operations Hydrogen Sulfide and Meteorological Monitoring Program

Solar Power for Home...

SR30 Next level digital secondary standard pyranometer

Project Title: Lowertown Ballpark (CHS Field) Solar Arrays Contract Number: EP4-34 Milestone Number: 1 Report Date: June 21, 2016

the National PhotoVoltaic protection note 5 I rated Introduction points of interest When to Fuse, When Not to Fuse

How Much Can a Campus Save on Utility Bills By Turning a 5-Workday Week Into a 4-Workday Week?

RESILIENT SOLAR CASE STUDY: SUNY New Paltz NYPA Integrated Grid Pilot

Renewable Energy. Presented by Sean Flanagan

SOLAR ELECTRIC INVESTMENT ANALYSIS

CP-250E-60/72-208/240-MC4 Microinverter with Modular Trunk Cable

Technical Information Temperature Derating for Sunny Boy and Sunny Tripower

Unitil Energy Demand Response Demonstration Project Proposal October 12, 2016

Inverter control of low speed Linear Induction Motors

Up to 45% more yield - possible only with the DEGERconecter.

American Samoa Power Authority

Reference: Photovoltaic Systems, p References: Photovoltaic Systems, Chap. 7 National Electrical Code (NEC), Articles 110,

Development of the SANUPS P73K Power Conditioner with Peak Power Cut Function

DC Power Grid System Lighting for a Typical Conference Room Evaluation

PROFITABILITY THRESHOLDS OF RESILIENT MICROGRIDS (and how to exceed them) Baltimore, MD October 27th, 2018

Ambient Magnetic Field Compensation for the ARIEL (Advanced Rare IsotopE Laboratory) Electron Beamline. Gabriela Arias April 2014, TRIUMF

ISES Solar Charging Station

Technical Information SUNNY BOY / SUNNY TRIPOWER Temperature Derating

Surface- and Pressure-Dependent Characterization of SAE Baja Tire Rolling Resistance

OPTIMIZATION OF SOLAR-WIND-DIESEL HYBRID POWER SYSTEM DESIGN USING HOMER. I. A. Wibowo *, and D.Sebayang

Boston Scientific Energy Storage Project. Final Report (PUBLIC) November 2016

Performance of Photovoltaic and Wind Hybrid Inverter

A Portable Photovoltaic Powerplant for Emergency Electrical Power Supply in Disaster Affected Areas

APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.

PROVA 1011 Solar System Analyzer

Data Analytics of Real-World PV/Battery Systems

Exploring Electric Vehicle Battery Charging Efficiency

Micro-Inverter. Corporate and Product Presentation. AEconversion GmbH & Co. KG. Micro vs. String. Product Details. USPs. Market Overview.

Meter Insights for Downtown Store

Todae Solar s 1.22 MWp Rooftop Solar Photovoltaic Installation for Stockland Shellharbour, NSW.

Final Report. Competitive Analysis: Levelized Cost of Electricity (LCOE) Rev C: January 24, 2008

PV Inverter SUNNY MINI CENTRAL 9000TL / 10000TL / 11000TL with Reactive Power Control

Technical Information Average Efficiency of the SMA Flexible Storage System

CITY DRIVING ELEMENT COMBINATION INFLUENCE ON CAR TRACTION ENERGY REQUIREMENTS

SINGLE-PHASE LINE START PERMANENT MAGNET SYNCHRONOUS MOTOR WITH SKEWED STATOR*

Solar Seminar. July 21st, Barry Cinnamon

UTILITY-SCALE SOLAR LOAD CONTROL. Richard Perez, ASRC Christy Herig, NREL Ruth Mac Dougall, SMUD Bruce Vincent, SMUD

UPDATE OF THE SURVEY OF SULFUR LEVELS IN COMMERCIAL JET FUEL. Final Report. November 2012

All of Texas Has Excellent Solar Resources. United States Solar Installed (as of mid 2013): 10 GW Germany Solar Installed (end of 2013): 35.

Solar Powered System - 2

Energy Management and Control System for Smart Renewable Energy Remote Power Generation

Hybrid Solar Panel Fuel Cell Power Plant

Energy Savings through Solar Energy for Municipalities

String Monitoring and Control System for Solar Photo Voltaic Power Plants

Impact Evaluation of 2004 Compressed Air Prescriptive Rebates

Transcription:

AEC PHOTOVOLTAIC TEST FACILITY FIRST YEAR TEST DATA James Krumsick Alternative Energy Consortium 100 West 13 th Eugene, OR 97405 e-mail: jpkrumsick@aol.com Frank Vignola Rich Kessler University of Oregon Solar Radiation Lab 1274 University of Oregon Eugene, OR 97403-1274 e-mail: fev@uoregon.edu ABSTRACT Alternative Energy Consortium s Photovoltaic test facility (AEC PV) came on line in August, 2004. System monitoring, using Fat Spaniel Technologies software was installed in December 2004. In May, 2005, the University of Oregon Solar Radiation Monitoring Lab (UO SRML) under a contract with the Energy Trust of Oregon, installed additional monitoring equipment at the site, expanding the number of monitoring points and providing a means to collaborate the information collected by the Fat Spaniel monitoring system. Information was gathered in the first year of monitoring about component efficiencies, system monitoring and system loading that can be applied to future installations. 1. INTRODUCTION The purpose of the test facility is to evaluate different photovoltaic products and to monitor the performance of these products under different environmental conditions. The test facility consists of a 25 KW rooftop array separated into eight systems. Each system uses a different combination of collector and inverters, with five different types of and four different types of inverter. Measurements taken include input DC current and voltage for 5 inverters, AC current and voltage output from each inverter to a combiner panel, wind speed, global and incidental solar radiation, ambient temperature, and panel temperature. The University of Oregon Solar Radiation Monitoring Lab has been monitoring photovoltaic systems through a grant from the Energy Trust of Oregon. Previous studies have looked at the effects of shading and individual system performance. The AEC project provides an opportunity to directly compare the performance of different systems 2. PROJECT GOALS 2.1 System Performance: One of the goals of the test facility is to evaluate inverter and panel performance under different environmental conditions. Since are subject to comparable daylight conditions direct comparisons between systems can be made. 2.2 System Loading: As can be noted from the system configuration description, Total panel DC capacity exceeds inverter rating for systems 6, 7 and 8. How these inverters perform in peak power production periods will be evaluated. 2.3 Inverter heating: Inverter temperature is measured against AC power output and the effects of temperature on inverter efficiency will be evaluated. 2.4 Comparison of monitoring methods: Fat Spaniel Technologies offers a very cost effective PV monitoring option. Accuracy of Fat Spaniel s transducers will be measured by comparing metered results with the Solar Radiation Lab s monitoring equipment. The accuracy of RS 485 output data from the inverters, when available, will also be measured. 2.5 Test the ability of system monitoring to detect system problems: System monitoring should be an effective tool in identifying system problems and monitoring system performance.

3. SYSTEM DESCRIPTIONS The AEC PV test facility provides a method for comparing performance of different PV arrays and inverters. In addition to power production, solar radiation, wind speed, outdoor temperature and PV module temperature readings are recorded. The following table describes the monitored systems: TABLE 1: SUMMARY OF MONITORED SYSTEMS System DC Rating 1 2338 2 2338 3 2505 4 3465 5 3465 6 3600 7 3600 8 3675 Inverter SMA 2500U/208 2500 Watt SMA 2500U/208 2500 watt Fronius 2500- LV 2500 Watt Sharp Sunvista 3500 3500Watt Sharp Sunvista 3500 3500 Watt PV Powered 2800/208 2800 Watt PV Powered 2800/208 Watt PV Powered 2800/208 2800 Watt Panels Sharp #ND-167UI 1 string of 14 Kyocera #KC167G 1 string of 14 Sanyo #HIP-G751 BA2 3 strings of 5 Sharp #NE-165UI 3 strings of 7 Isofoton #1-165 (1) string of 10 & (1) string of 11 Isofoton #1-150S - 24V 3 strings of 8 BP # BP 3150 3 strings of 8 Sharp #NT-175UI 3 strings of 7 The system modularity allows for easy modifications to made to the system, such as pairing of inverters with PV arrays and adding modules to test inverter loading. In the coming year changes will be made to the current configuration in order to analyze the performance differences between systems. 3.1 Monitoring Equipment The eight systems were monitored using software developed by Fat Spaniel Technologies. Additional equipment installed by the University of Oregon Solar Radiation Monitoring Lab augments the data collected by Fat Spaniel equipment. The Fat Spaniel monitoring system uses transducers for AC power production data collection. In addition, data is collected from the 485 output port from the SMA inverters. Specific equipment used L is as follows: Fat Spaniel Monitoring: Current transformers: Ion CT-5B model 1052 ARW Meters: Ion 6200 Thermocouple: Superlogics 61xjbex36a Pyranometer: Apogee Instruments Gateway: N-Port programmable communication gateway University of Oregon Solar Radiation Monitoring Lab: DC Voltage transducers: OSI VT7 DC AC Watt transducers: OSI PC5 Current transducers: OSI CTL DC Hall effect current sensor with Empro DC current shunt Li-cor LI-200 horizontal and tilted pyranometers Minco RTD PV temperature sensor Campbell Scientific 107 air temperature sensor RM Young 03101 anemometer Campbell Scientific data logger system 4. SAMPLE RESULTS 4.1 System Performance: A performance comparison for the 8 systems tested over the course of one year is summarized in Table 2. TABLE 2: POWER PRODUCTION COMPARISION Data Summary - January 1,2005 through December 31, 2005 % % Sys DC Watt kwh Efficiency Deviation Deviation # Rating generated Average w/o 4 & 5 1 2338 2517.06 0.1229 2.5860-0.2451 2 2338 2599.41 0.1269 5.9423 3.0186 3 2505 2689.79 0.1226 2.3175-0.5062 4 3465 3517.28 0.1159-3.2741 5 3465 2783.51 0.1030-14.0156 6 3600 3746.19 0.1188-0.8423-3.5788 7 3600 3616.41 0.1230 2.6755-0.1581 8 3675 4032.24 0.1253 4.5510 1.6656 Average Efficiency Rating: 0.1198 Average without Systems 4 & 5: 0.1232 Efficiency, or capacity factor, is defined as AC power output in kilowatt hours / DC KW power rating x hours of operation. Data are from Fat Spaniel s monitoring system.

The results in Table 1 show very similar performance between systems, with all systems within 6% of the average except system #4. Systems 4 &5 show the poorest performance over the year. These two systems use 240 volt inverters and the power is converted to 208 volts using dry type transformers. Monitoring data are taken at the secondary of these transformers. Since inclusion of systems 4 and 5 skews the data due to transformer losses, deviation from average was calculated with systems 4 & 5 included and recalculated with these systems excluded. With systems #3 and #4 removed, the performance of all other systems is within ±4% of the average. This is remarkable considering the shading and other factors affecting performance. It is suspected that the relatively poor performance of system #5 is also related to the PV panel performance. In the coming year the PV will be rewired to different inverters in order to determine how much of the performance difference is related to the PV and how much is related to the inverter. Performance of the eight systems on a typical summer day is shown in Fig. 1. AC power over time is normalized by dividing by the peak DC system rating and plotted against incident solar radiation. 4.2 System Loading Fig. 2 is a plot of three measurements of AC Power Output by PV Powered inverter number 8 on a sunny day in September. Fig. 2: System #8 plotted against Incident Solar Radiation Note that the power production curve flattens at peak power production of 2800 watts. The DC power rating on this array is 3675 watts. We conclude that considerable power is lost at high levels of solar radiation due to the mismatch of DC power rating and AC inverter rating. At peak power production the inverter electronics regulate voltage and current in order to dissipate excess energy. This is illustrated in Figs 4 & 5. The jagged line in Fig. 2 is the output of the 1 minute data from the PV Powered transducer averaged over 5 minutes. There is considerable variation (noise) in the output of the PV Powered transducers. The PV Powered 2800 inverter produces a large magnetic field (0.5 Gauss at frequencies above 120 kilohertz near the inverter) and this affects measurements made with Hall effect sensors (This measures DC current). The Ohio Semitronic Instruments (OSI) watt transducer is a current transformer. Noise problems were only noted with the PV Powered inverters. Fig. 1: Comparative System Performance The compromised performance of the Sharp Sunvista systems (Systems 4 and 5) due to transformer losses can be clearly seen in this plot. It should also be noted that performance of systems 2 and 3 are affected by shading, resulting in a decrease in performance. The symmetry of the surve was somewhat surprising. We had expected morning production to be higher than afternoon production due to lower morning temperatures. Comparing readings at 10:20 and 14:20 shows a 7% drop in performance in the afternoon at 8% higher levels of irradiance. We do not have a good explanation for this result, and will study it more in the coming year. Fig. 3: Voltage changes at peak power production

Figs. 3 and 4 show incident solar radiation for the same inverter on the same day plotted against inverter voltage and current. performance for this installation. In the coming year we plan to locate one of the inverters outdoors where it will be subject to additional heating on summer days. 4.4 Comparison of monitoring methods Fig. 6 is a plot of the ratio of the AC output for the transducers used by Fat Spaniel and OSI transducers. The reason for the slope is that the time in the Fat Spaniel is off by about 8 minutes. The two sets of transducers are consistent in their reading, although Fat Spaniels transducer readings are consistently about 6% below the readings of the OSI watt transducers. The readings of the SMA output a few prevent higher than the reading from the OSI watt transducers. Differences in readings can be attributed to grounding to shield from magnetic flux from the PV Powered inverters and calibration. Fig.4: Current changes at peak power production It appears that when the inverter reaches its nameplate rating that it moves away from peak AC power production voltage. This voltage change reduces AC current which protects the inverter. As a result, power is lost during peak solar radiation periods when systems are loaded beyond their nameplate rating. The PV Powered inverters, systems 6, 7, and 8 are loaded 30-40% above its nameplate rating. In the coming year the load will be reduced on these inverters. We anticipate some system efficiency improvement with a better match between panel DC power rating and inverter rating. 4.3 Affects of temperature on performance Fig. 5 is a scatter plot of power output versus temperature throughout the month of February. The data is fairly consistent and is linear indicating there is no fall off in efficiency with inverter heating. Fig. 6: Comparison of Fat Spaniel and OSI Transducers Fig. 7 is a comparison of the RS485 output from the SMA inverters, Fat Spaniel transducer output and the OSI transducers used by the Solar Radiation Lab s monitoring equipment for systems 1 and 2. Fig. 5: AC power output versus temperature The inverter remperature increases about 1 degree C for each 100 watts of AC output. We have concluded that moderate temperature is not negatively affecting Fig. 7 Comparison of RS 485 and OSI transducer data

Note that the SMA inverter records are 3-4% higher output than the OSI transducers used by the Solar Radiation Lab, except at levels of solar radiation below 100 W/m^2. This is a characteristic shown by both SMA inverters. The data were taken over the last 5 days of October and there were not any completely sunny days in this time period. Note that the data from the Fat Spaniel transducers is about 10% below the OSI values for high periods of irradiance and very close to the OSI values during low periods of irradiance. Average difference in readings was about 6%. Fig. 8 plots the ratio of the PV Powered inverter output to the OSI transducers over time. Fig. 9 shows a comparison of efficiency readings by Fat Spaniel s and UOSML s monitoring equipment for the two SMA inverters. The efficiency of system #1 is fairly linear across irradiance levels. System #2 shows lower efficiency at lower irradiance levels. It was determined that this was due to differences in the monitoring equipment. 4.5 Ability of system monitoring to detect system problems During the course of monitoring it was discovered that systems 6 and 8 would drop out under peak power conditions. After a five minute pause, the system would come back up. The inverter manufacturer determined that this is characteristic of the system utility voltage or phase out of range. A firmware change by the manufacturer was able to correct this problem. Without monitoring, the problem could have continued unnoticed. Fig. 10 shows system #6 dropping off line during periods of high solar irradiance. Fig. 8 Transducer output ratio over time There is an excessive amount of noise in the PV Powered data, but they agree fairly well with the measurements of the OSI transducers. The ratio stays fairly consistent over the course of the day and the scatter is typically less than 5%. The PV Powered values are one minute samples averaged over 5 minutes. It is postulated that differences in readings can be attributed to calibration of the transducers and the need to ground the shield wire in order to minimize the effect of magnetic flux from the PV Powered inverters. Fig. 10 Dropout of inverter #6 Fig. 9: Comparison of Efficiencies, Systems 1 & 2 Fig. 11 Shading effects on systems 2, 3, 4, 6 and 7

Fig. 11 shows the effects of shading on systems 2, 3, 4, 6 and 7. Note that potential shading problems can be identified for specific time periods. This potentially allows the Owner to address power losses due to shading by identifying the source of shading. Even though system #3 has a noticeable decrease in production in late afternoon, the annual power production of this system was only slightly compromised due to production level at the peak of the day. At this time we are not sure of the cause for the decrease in power production in the afternoon. 5. CONCLUSIONS 5.1 System Performance. Small efficiency differences between manufacturer s equipment were noted. Ongoing studies will attempt to determine specific reasons for these performance differences. 5.2 Effect of Inverter Loading The DC watt load for inverters 6, 7, and 8 exceeded the inverter watt rating by 30 35%. The effect of this loading condition was a flattening of the AC power production curve as inverter nameplate rating was reached. This was characterized by an increase in voltage and decrease in current as the inverter moved away from peak power voltage to protect the equipment. The compensation at peak power production appeared to have a negligible effect on performance. The overall annual performance of these three systems was comparable to the other systems studied. In the coming year we will be reducing the load on these three inverters to evaluate the effects of overloading system inverters, especially to see if system overloading affects overall efficiency. 5.3 Effect of Inverter Temperature System performance showed little efficiency decrease with rise in inverter temperature. It should be noted that inverters are located indoors and measured temperatures were well within inverter manufacturer s recommendations. It was observed that the inverter temperature rises approximately 1 degree Celsius per 100 watts of AC output. Temperature rise could become an issue for installations where the inverter is exposed to sunlight. 5.4 Comparison of monitoring methods. Photovoltaic system monitoring is highly recommended for all photovoltaic systems in order to maximize system performance by identifying systemic problems and enabling notifications of system shutdowns. Fat Spaniel Technologies offers a very cost effective PV monitoring option. In general we found that the data from Fat Spaniel s transducers were about 6% lower than the data from the OSI transducers used by the Solar Radiation Lab. This difference was consistent across systems. We found the RS485 output readings from the SMA inverters to be about 3-4 % higher than the values read from the OSI transducers. The conclusions we have drawn from these monitoring comparisons is that any of the monitoring methods can be a useful tool in evaluating system performance. However, calibrating the measurement instruments is essential for detailed analysis of power production. In addition, one must be careful to make sure the transducers are properly grounded and interference electrical and magnetic emissions are minimized. 5.5 Ability of system monitoring to detect system problems. The monitoring equipment proved to be quite an effective tool in identifying system performance problems.. 6. FURTHER STUDIES In the coming year the following system modifications will be made to further analyze system performance: 1. The PV arrays feeding inverters 2 and 3 will be reversed to determine whether performance differences are related to the inverter or to the PV array. 2. As noted earlier, inverters 6, 7 and 8 are loaded to 30 35% over inverter nameplate rating. One of the strings will be disconnected from inverter #7 and compared to the power produced by inverters #6 and #8. 3. The PV arrays feeding inverters 6 and 8 will be reversed to determine whether performance differences are related to the inverter or to the PV array. 4. Inverters 4 and 5 will be replaced with two different manufacturer s inverters, eliminating the losses associated with the step down transformers. 7. Acknowledgements We would like to thank the Energy Trust of Oregon, the Eugene Water and Electric Board and the Bonneville Power Administration for project funding and support of the UO SRML solar and PV monitoring efforts. 8. REFERENCES 1. Frank Vignola: Using Sun Path Charts to Estimate the Effect of Shading on PV Arrays, Proc. Solar 2004, American Solar Energy Society Conference, Portland, OR. 2004.