UPS BATTERY HANDBOOK. The Main Characteristics of UPS Battery Systems Power protection for critical infrastructure

Similar documents
Chapter 3. Direct Current Power. MElec-Ch3-1

Chapter 6. Batteries. Types and Characteristics Functions and Features Specifications and Ratings Jim Dunlop Solar

Lithium-ion battery systems for ABB UPS solutions Reliable, lightweight and compact UPS energy storage for critical applications

INSTRUCTION MANUAL. Maintenance-free Absorbent Glass Mat technology and valve-regulated batteries. (AGM / VRLA)

The use of batteries in hazardous areas. 1. Type of batteries and technical evolution. March 2018

power Seamless power A power protection magazine of the ABB Group

SPA AGM VRLA batteries

Batteries and more. Powered by (CE, UL & ISO9001 APPROVAL)

Vented fibre structure Nickel Cadmium batteries for stationary systems

Lithium battery charging

Why Ni-Cd batteries are superior to VRLA batteries. Statements and facts

IEEE IAS Atlanta Chapter

Guidelines for Battery Electric Vehicles in the Underground

Eclipse Solar Suitcase

12 VDC Power Sources For Your RV

Winter 2016 Conference

Valve Regulated Pocket Plate Nickel Cadmium Battery. Technical Manual

Industrial Batteries 101

Single Cell Range Technical manual

Single Cell Range Technical manual

INTRODUCING THE LEAD CRYSTAL BATTERY

Stationary Batteries and Battery Management

FUEL CELLS AND BATTERIES LECTURE NO. 9

Marine Recreational Vehicle Batteries Made Simple

EUROBAT EUROBAT GUIDE FOR MOTIVE POWER VRLA BATTERIES

Batteries generally classifies into two main groups: primary and secondary battery types. Primary batteries are

ENERGY SAFETY SUSTAINABILITY

UZB GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY REPLACEMENT BATTERY REPLACEMENT 12V, 12AH 1/6.

The introduction of Lead Crystal Battery

PRODUCT GUIDE Publication No: EN-SBS-PG-001 February 2003

Valve regulated sealed industrial battery. HAGEN OPzV

Charge & Discharge. Ed Erny - NZ1Q August 2017

The Traveler Series: Wanderer

The Traveler Series: Adventurer

NorthStar Battery Company DCN: SES DCR: 1548-S09 Date:

TECHNICAL BULLETIN Fig #1 - VRLA Battery Components. Intercell Welded Connection Strap joining neg. plates in parallel.

Low maintenance TAB OPzS vented stationary batteries

A Structure of Cylindrical Lithium-ion Batteries

Reference Number PDS 18 - (RIC Standard: EP SP)

Valve regulated Batteries for Stationary Applications. HAGEN dc plus. An EXIDE Company

Tel.X Ni-Cd batteries for telecom networks Technical manual

Customcells. Tailormade Energystorage Solutions.

Deep Cycle Battery Safety. First. Battery Handling, Maintenance & Test Procedures

Battery Market Trends and Safety Aspects

The Traveler Series TM : Adventurer

Acme NonStop Power. FNC Cell Technology Sealed fiber nickel-cadmium battery systems For commercial, military and space systems.

The Traveler Series: Wanderer

Acme NonStop Power. FNC Cell Technology

OSP Battery Training. Craig Paoli Director Strategic Platforms July 13 th Copyright 2010 The Alpha Group. All Rights Reserved.

Features and Benefits

Traction batteries Hawker XFC Fast charge battery system. Plug & Play power solution

Battery Storage Systems

Pure Lead-Tin Technology

PV System Components. EE 495/695 Spring 2011

THE FORGOTTEN BATTERY, LEAD ACID.

Types batteries. AGM Gel OpZs OpZv Lead Carbon LiFePO4 NCA Saltwater Zinc Bromine Etc,etc, etc, etc, etc, etc,

EE Chapter 2 Aircraft Storage Batteries

Vantage ultra-low maintenance batteries

Understanding Lithium-Ion Technology Jim McDowall (updated from Battcon 2008)

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. AGM Range. Monobloc

Charge Voltage(V/cell) Set point (V) (V)

Technical Note. Management of Sealed Lead Acid Batteries in Reliable Small DC Standby Power Supply Systems

SAFETY RULES. An Update on Lithium-ion Battery Use in Critical Facilities

BOOST POWER 1212 Product Description

Technical Manual. E-trek DM Series SHANDONG SACREDSUN POWER SOURCES CO.,LTD

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. AGM Range. Monobloc

New UPS Batteries Keep up so you can keep on backin -up

Introduction to Solar Electric Battery Systems. J-Tech Solar Training

Implementation and development of standards for Lithium-ion energy storage technologies within the South African context

Tubular Flooded (OPzS) Batteries

BATTERIES BATTERIES VRLA / SLA / GEL 2V/6V/12V. DP Electronics e.k (Deutsche Power Co., Limited)

SBC / 2140 / Stage Battery Charger User Manual

ELiTE Battery Information

FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual TABLE OF CONTENTS

Open-circuit voltages (OCV) of various type cells:

Known Worldwide as the Highest Quality AGM Batteries for Marine, RV and Industrial Applications

PALLET PRO ON-BOARD POWER SYSTEM AND 6 VOLT GROUP 27 DEEP CYCLE BLOC BATTERIES

Ni-Cd block battery. Technical manual. August 2018

Pb battery. Chemical equation: Pb+2 H 2 SO 4. + PbO 2 <charge. 2 PbSO 4 +2 H 2. discharge>

FAT. FAT Battery Range FIAMM.COM

Stationary Batteries: Why they fail and what can be done to prolong battery life

Congratulations, Dorothy!

PowerStor Standby Battery Systems

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. Gelled Electrolyte Range. Monobloc

Nickel Cadmium Batteries BLOCK TYPE

Stationary Battery Testing

NCPP. Nickel Cadmium Pocket Plate Batteries. Block Cell Dimensional and Electrical Data

Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

Product Guide. An Invensys company

OPERATION MANUAL. GFM-Series. Storage Battery Systems, Inc. N56 W16665 Ridgewood Dr. Menomonee Falls, WI (262)

Ni-Cd BLOCK BATTERY TECHNICAL MANUAL

PURE LEAD PLUS UPS APPLICATIONS. Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell

Gary Mackey National Sales Manager Associated Equipment Corporation

Duo Battery Charge Controller

Genset Starting Education Module #3: Solutions to Leading Causes of Battery Failure in Gensets

STANDARDIZATION ORGANIZATION FOR G.C.C (GSO) GSO 34/2007

Operation Manual. For GTS-L Range Stationary VRLA Batteries

FUM-24xxCBP Series 3 Stage Battery Charger User Manual

HIGHLIGHTS. What Every 3M Powered Air Purifying Respirator User Should Know About Batteries

Switch Mode, Automatic, Lead Acid Battery Charger Model: SEC A SEC A SEC A

Transcription:

UPS BATTERY HANDBOOK The Main Characteristics of UPS Battery Systems Power protection for critical infrastructure

2 ABB UPS SYSTEMS BATTERIES Understanding UPS batteries helps to ensure a continuous flow of clean power. The lifeblood of financial institutions is a reliable source of quality electrical power. This is why businesses install a UPS. The battery in a UPS is the most vulnerable part of the system. A secure supply of energy is the foundation for the success and continuity of many enterprises be they industrial plants, offices, healthcare facilities, utilities or data centers. For some of these concerns, power outages can be very expensive indeed, with costs sometimes running into the tens of millions of dollars. This is why many businesses install an uninterruptible power supply (UPS). A critical part of the UPS is the battery bank that provides the energy needed to ensure that a continuous flow of clean power is available to the critical process that the UPS is powering. Parameters that have to be taken into consideration in properly selecting battery systems are the desired power and autonomy, inverter efficiency, final discharge, and available charging voltage. These and many other factors must be carefully considered when choosing and configuring a UPS battery system. This handbook describes the main characteristics of UPS battery systems, with particular emphasis on the lead acid battery type, as these are in widespread use. Further information can be found in national and international standards, such as BS EN 50272-2:20 Safety requirements for secondary battery and battery installations Stationary batteries, released by the European Committee for Electrotechnical Standardization.

3 Batteries in UPS systems Internal and external components of a valveregulated lead-acid (VRLA) battery UPS applications make use of a wide variety of battery types; however, lead acid (LA) batteries are currently the most common technology. In specific instances with special requirements, nickel cadmium or lithium-ion batteries are sometimes used. Lithium-ion is a rapidly growing battery technology, used where high-energy density and low weight are the primary requirements. Lead acid batteries The LA battery represents the most economical choice for larger power applications where weight is of little or no concern. Most UPS systems use LA batteries as they provide excellent performance, high power efficiency with low internal impedance, high tolerance to improper treatment, and attractive purchasing costs. LA batteries use an electrolyte that consists of water and sulfuric acid, and plates made up of sponge lead (negative electrode) and lead oxide (positive). The two main LA battery types are: VRLA (valve-regulated lead acid), also known as sealed or maintenance-free Flooded, also called vented or open VRLA batteries VRLA batteries are sealed and can be mounted in any orientation. The battery case is equipped with a valve that vents any buildup of gas externally. Gas buildup is usually an exceptional event, which may occur, for example, when the battery is subject to a high charging rate or rapid discharge. VRLA batteries normally require no direct maintenance they do not need to be topped up with water, as any hydrogen released during charging is recombined internally with oxygen to form water. There are two main VRLA types, distinguished by their electrolyte composition: Absorbed glass material (AGM), where the electrolyte is held within a highly porous microfiber glass separator. Gel, which has an electrolyte gel made from a mixture of sulfuric acid and silica. UPS applications normally work with the VRLA AGM type because of its lower internal resistance, high specific power and efficiency, low self-discharge, and lower purchasing costs. AGM batteries also charge faster and can deliver high current of short duration. Positive terminal Lifting handle ABS lid Vent strip for valves Negative strap connector Negative terminal Positive strap connector Positive plate ABS battery case Separator Negative plate

4 ABB UPS SYSTEMS BATTERIES These graphs compare NiCd with different LA battery types. Active material composition varies by manufacturer, so performance may vary from case to case. Flooded batteries Flooded LA batteries, as the name suggests, have plates that are immersed in an acid electrolyte. Since they are not sealed, the hydrogen generated during operation escapes directly into the environment, meaning that ventilation systems must be more powerful than those for VRLA and, so, sized adequately. In most cases, the battery banks are accommodated in a dedicated room. DIN VDE 0510 Part 2, for example, sets out the provisions for equipping such a battery room. Flooded batteries must be kept and operated upright, and their water levels must be manually topped up. They provide a longer lifespan and higher reliability than sealed LA batteries. Nickel cadmium batteries Nickel cadmium (NiCd) battery electrodes are made of nickel hydroxide (positive plate) and cadmium hydroxide (negative plate). The electrolyte is an aqueous solution of alkaline potassium hydroxide. NiCd batteries provide a very long calendar life (up to 20 years) and can cope with temperature extremes (-20 C to +40 C). They also offer a high cycle life and have good tolerance to deep discharges. However, NiCd batteries cost much more than traditional VRLA equivalents. Nickel Cadmium Design life Lead Acid AGM Design life Price per system Cycle life Price per system Cycle life Storage Maintenance Storage Maintenance Energy density Energy density Lead Acid Gel Lead Acid Flooded Design life Design life Price per system Cycle life Price per system Cycle life Storage Maintenance Storage Maintenance Energy density Energy density

5 Internal and external components of a flooded battery 02 Internal and external components of nickelcadmium battery Other benefits relate to the low internal resistance, which offers high power density combined with fast-charging capability. The storage time of NiCd batteries is very long, especially if fully discharged, and they provide high protection against improper treatment e.g., overcharging, over-discharging, and high-ripple charging currents. Further, as both nickel and cadmium are toxic, battery disposal/recycling processes are costly. NiCd batteries also require maintenance in the form of topping up with water especially in high-cycle applications, or under heavy charging rates with some charging methodologies. Negative plate group Plate group Separator Positive plate group Negative plate Positive plate Negative flat grid Gauntlet Positive tubular grid Flame arresting vents Battery terminal Negative plate tab Positive plate tab Plate frame Separating grids Cell case Plate 02

6 ABB UPS SYSTEMS BATTERIES Different types of lithium-ion batteries Lithium-ion batteries In a lithium-ion battery (LIB), the "cathode" is usually made of a metal oxide, while the anode is usually porous carbon graphite. Both are immersed in a liquid electrolyte made of lithium salt and organic solvent. During discharge, the ions flow from the anode to the cathode through the electrolyte and separator; charging reverses the direction, and the ions flow from the cathode to the anode. A common way to distinguish the main different types of lithium-ion batteries is to consider the cathode composition. The choice of battery depends on various factors, including cell voltage, capacity, energy and power capabilities, cycle life, and temperature of operation. Various LIB chemistries exist, which can be simplified into six main types based on the composition of the cathode material (items 1 to 5) or anode material (item 6): 1. Lithium cobalt oxide (LCO) 2. Lithium manganese oxide (LMO) 3. Lithium-nickel manganese cobalt oxide (NMC) 4. Lithium iron phosphate (LFP) 5. Nickel cobalt alumina (NCA) 6. Lithium titanium oxide (LTO) It is not possible to compare these different families precisely, since many aspects other than technology play an important role in performance, such as mechanical form, cell size and active material mix. Different battery manufacturers also combine technologies to improve performance for a specific application. LCO NCA NMC Energy Energy Energy Cost Power Cost Power Cost Power Safety Life Safety Life Safety Life LMO LFP LTO Energy Energy Energy Cost Power Cost Power Cost Power Safety Life Safety Life Safety Life

7 The chemistries mostly used for UPS applications are LMO-NMC and LFP because of their long calendar life, high safety and high power density. ABB s first choice for battery technology is an LIB cabinet solution with a special combination of lithium manganese oxide and nickel manganese cobalt capable of providing over 200 kilowatts of continuous power for several minutes. The next part of this handbook mainly focuses on traditional VRLA batteries, since they are most common in UPS applications. Battery capacity and C-rate The nominal capacity (KN) of a battery is the guaranteed capacity when discharging over a specified discharge current (IN) for a certain duration (nominal discharge duration, tn), at nominal temperature, nominal density and nominal electrolyte level, without failing to achieve the final discharge voltage (UsN). The nominal battery capacity can, therefore, be expressed as KN = IN tn. The nominal capacity values (in ampere-hours) set by battery manufacturers typically refer to a ten-hour discharge (C/10) of a lead battery and a five-hour discharge (C/5) of a NiCd battery. In UPS system applications, the real usable, extractable capacity is significantly lower than the nominal capacity due to the shorter discharge duration. The amount of power requested within the specific autonomy time are major factors that impact battery sizing.

8 ABB UPS SYSTEMS BATTERIES Battery sizing Impact of operating temperature on battery life Sizing the batteries normally starts with two major requirements: power and autonomy. The power value to consider is the one coming out from the batteries, so the calculation should start with the load power and consider the power factor and inverter efficiency. P bat_out_ = (P load cosphi ) / Ups efficiency There are two main methodologies for proper battery sizing. One option is to refer to battery performance sheets that give details on autonomy values under different constant power/current discharge characteristics versus temperature and cutoff voltage limits. The other option is to use the ABB battery configurator tool or the online battery configurators available on suppliers websites. It is important to make sure that each system uses only one battery model, and that there are never more than four to five strings in parallel per system. (This is the best practice, but it may vary depending on the recommendations given by battery manufacturers.) Major aspects of battery selection to be carefully considered are: Battery life Performance at beginning or end of life (BOL or EOL) Operating temperature Depth of discharge Cutoff voltage Charging time Operating temperature Operating temperature has a strong impact on battery life and performance. All major manufacturers recommend operating their batteries at 20 25 C. Higher temperature values increase battery performance but decrease battery lifespan. According to the Arrhenius law, battery life is halved for each 10 C increase above the 20 25 C range. Battery manufacturers provide battery performance sheets for the specific operating temperature. 12 A A Very long life: over 12 years 10 B B Long life: 10 12 years Lifespan (years) 8 6 4 C D C General purpose: 6 9 D Standard commercial: 3 5 years 2 0 20 25 30 35 40 45 50 55 60 Temperature (C )

9 Cycle service life diagram Battery life A battery type consistent with the lifespan required by the project specifications should be chosen. All major battery manufacturers products are categorized by lifespan. Eurobat provides a clear picture of the four main categories: Standard commercial: 3 5 years General purpose: 6 9 years Long life: 10 12 years Very long life: over 12 years Battery lifespan depends on various factors, and real service life may differ significantly from the original design life specified by manufacturers - in most cases (e.g. where temperature is higher than nominal), it is 50 to 70 percent less. Beginning- and end-of-life performance Customer specifications may require a specific level of performance (e.g., power and autonomy) from batteries at their beginning of life (BOL) or end of life (EOL). Battery sizing must include an oversizing factor (typically 125 percent as for IEEE485) to account for aging in the case of an EOL requirement. Depth of discharge (DOD) Batteries can be discharged completely or partially. The less (state of charge) a battery discharges per cycle, the lower the number of cycles that the battery will provide during its entire life. The number of cycles is normally not so pertinent for UPS systems, since they normally utilize the batteries just a few times a year. However, in some cases, and for specific countries, this aspect may be more relevant. The following graph shows typical discharge/lifetime behavior for VRLA batteries used in UPS applications. 140 120 100 A Discharge depth 100% B Discharge depth 50% C Discharge depth 30% Capacity (%) 80 60 A B C Ambient temperature 25 C (77 F) 40 20 0 200 400 600 800 1000 1200 1400 Number of cycles (times)

10 ABB UPS SYSTEMS BATTERIES Floating charge at constant voltage Cutoff voltage The lower the cutoff voltage is, the more power a battery can deliver. All battery manufacturers declare battery performance relating to cutoff voltage limit. When sizing a battery system, it is important to consider the minimum cutoff voltage per cell (e.g., 1.65 V per cell, 1.7 V per cell, etc.). Normally, the project specifications indicate the requirement for this value. It is also very important to verify that the DC battery voltage range of the selected UPS is compatible with the calculated number of battery blocks. If batteries ever discharge below their minimum cutoff voltage, they are considered to be over-discharged. In such a case, internal resistance increases due to plate sulfation, and both capacity and life decrease dramatically. Charging time Charging time depends on the maximum power that a battery can accept without jeopardizing its lifespan. For LA batteries, charging power and voltage are normally sized to provide a maximum current of C/10 (a charge rate in amperes of one-tenth the overall battery capacity in ampere-hours), with a constant current and constant voltage charging methodology. In some cases where long autonomies are required, it is also very important to verify that the UPS charging power is sufficient to ensure proper battery charging within the required time. The DC charging voltage must be ripple-free, since this may strongly affect battery life. This voltage must also stay within the range specified for the particular battery: with a higher charging voltage, the internal pressure in the battery will increase and force open the valve to allow gas to escape. Overcharging like this will corrode the positive plate, shortening the battery life. A Charge Volume (%) B Charging Current (A) C Charging Voltage (V/cell) 0.1CA-2.25V/cell temparature 25 C 120 0.10C 2.4 B A Charging parameter 100 80 60 0.08C 0.06C 0.04C 2.3 2.2 2.1 C 40 0.02C 2.0 20 0C C 0 0 A B 4 8 12 16 20 24 28 32 36 Charging time (hours)

11 Main causes of failure Battery failure is the cause of 50 to 70 percent of UPS outages. Other than short circuits, there are three main mechanisms (excluding external and internal short circuits) that reduce VRLA battery life and performance: Plate corrosion Plate corrosion is usually the result of oxygenation of the positive plate. It reduces the amount of active material that can participate in chemical reactions, reducing battery performance and life. This factor is unavoidable. A battery that reaches end of life through this failure mode has met or exceeded its anticipated lifetime. Limiting the depth of discharge, reducing the cycle count, operating at moderate temperatures and controlling overcharge are preventive measures that keep plate corrosion under control. Dry-out Dry-out means a decrease in electrolyte quantity, which strongly impacts battery life and performance. The main reasons for battery dry-out are excessive temperatures and overcharging. With a higher charging voltage or current, the internal rate of gas recombination is not enough to compensate for the large amount of hydrogen and oxygen generated. This leads to an internal overpressure, which causes the relief valve to open. In a VRLA, the electrolyte lost to the environment cannot be recovered, strongly affecting battery performance and life. In the worst case, it may result in thermal runaway, or even in a fire or explosion. Sulfation In normal chemical reactions when a VRLA discharges, lead sulfate crystals are deposited on the plates. In charge mode, they are converted back to active materials. If batteries remain empty or only partially charged for a certain period, these lead sulfate crystals harden, and it is not possible to convert them back to lead or lead oxide during charging. This strongly impacts battery performance, life and capacity, so it is important to fully charge batteries after each discharge and to follow the battery manufacturer s instructions on proper charging voltage settings, since a charging voltage that is only slightly lower than specified may still cause this issue.

12 ABB UPS SYSTEMS BATTERIES Storage Capacity retention characteristic diagram VRLA batteries discharge themselves, so their available capacity decreases even when they are not operating. VRLA batteries must be stored fully charged, in their original packaging, and in a dry, clean and well-ventilated environment. There should be no visible traces of acid on their cases. Do not stack different pallets or batteries on top of each other unless instructed to so by the manufacturer. As a rule, inside buildings, flooded batteries should be stored on liquid-proof ground with acid collection trays. For VRLA cells/blocks, an acid collection tray is not necessary. Batteries must be well protected from metallic parts that may cause short circuits, and be guarded against accidental damage and falling objects. During storage, batteries must be correctly managed. After a certain period has elapsed since a battery s production date or most recent charging, the battery needs to be recharged according to the manufacturer s instructions. This period depends on aspects like storage temperature, battery model, etc. Higher ambient temperatures decrease the time allowed between charges. For this reason, the supplier s recommendations for the specific battery model should always be followed. It is also common to measure the battery s open-circuit voltage and postpone the charging process in cases where measurement results are higher than the limits. 100 90 No supplementary charge required (carry out supplementary charge before use if 100% capacity is required) 80 Capacity retention ratio % 70 60 50 40 C (104 F) 30 C (86 F) 25 C (77 F) 5 C (41 F) Supplementary charge required before use. This supplementary charge will help to recover the capacity and should be made as early as possible. Supplementary charge may often fail to recover the capacity. The battery should never be left standing until this state is reached. 40 0 2 4 6 8 10 12 14 16 18 20 Storage period (Months)

13 Maintenance and battery monitoring VRLA batteries do not need to be topped up with water like the flooded type does, but the following steps are important in order to ensure longer battery life and stable performance: Check battery voltage and temperature and verify that all connections are free of dust (never use solvents to clean batteries; a damp cloth is enough), corrosion or leakage. Check that the ventilation is working and that all connections are tight and fastened. This last check may be also done with a thermal scan while the batteries are operating, as bad connections are usually the site of hotspots. Perform a battery discharge test at least once a year to evaluate the battery s internal resistance and available capacity on all connected blocks. This specific test must be agreed to, and confirmed by, the customer, since the load may not be fully covered while this test is being run. To simplify this test, ABB has developed the AKKA diagnostic tool, which provides connections as well as acquisition systems to measure the most relevant battery parameters and detect weak batteries that may need replacing. Any damaged batteries must be replaced with one with a similar internal resistance. Normally, this is possible in the first two to three years of operation, depending on battery type. After that, the replacement should be a used battery of a similar age. If such aged spare parts are unavailable and the UPS cannot operate with a reduced number of batteries per string, the entire string of batteries must be replaced. To reduce the required maintenance work, a battery monitoring system can be used. Many systems are already available and used in the field in ABB UPS applications. These tools continuously monitor battery parameters such as voltage, current, temperature and internal resistance, providing real-time alerts and warnings. They also offer full data acquisition packages and tools for proper analysis and metrics. These systems usually also offer thermal runaway control and remote monitoring features, and in some cases even active balancing between batteries. The capex costs for such systems are quite high, but more notably than all the functionalities described below they provide the very important benefit of advance warning of which battery is going to fail so it can be promptly replaced, avoiding unexpected outages.

14 ABB UPS SYSTEMS BATTERIES Ventilation and safety Irrespective of whether they are sealed or not, all lead acid batteries can emit explosive gases especially while charging so adequate ventilation is mandatory (hydrogen gas emitted during charging is explosive at concentrations above 4 percent). Hydrogen and oxygen gases may also be released if, for example, if the battery is moved or shaken. Ventilation requirements EN 50272-2 states, the minimum air flow rate for ventilation of a battery location or compartment shall be calculated by the following formula: Q = 0.05 x n x I gas x Crt x 10-3 [m 3 /h] With In order to dilute gases (hydrogen and oxygen) generated during charging and discharging - and thus eliminate the risk of explosion - battery rooms must be ventilated in accordance with the EN 50272-2 standard. Such ventilation obviates the need for EX-proof electrical equipment. The ventilation system must be designed to cope with wet-room conditions. Do not install batteries in airtight enclosures! Spark-generating parts must be installed with a safety distance to cell or battery block. N = number of cells I gas = I float or boost [ma/ah} relevant for calculation (see table below) C rt = capacity C 10 for lead acid cells (Ah), U f = 1.80 V/cell at 20 C The following table states the values for I gas to be used: Operation Vented cells (Sb < 3%) VRLA cells Float charging 5 1 I gas according to EN 50272-2 for IU and U-charging depending on operation and lead-acid battery type (up to 40 C operating temperature). The gas-producing current, I gas can be reduced to 50 percent of the values for vented cells where recombination vent plugs (catalyst) are used. With natural ventilation (air convection), the minimum inlet and outlet areas are given by: A 28 x Q [cm 2 ] (Air convection speed 0.1 m/s) For more details on how to size the ventilation system for a battery room properly, refer to specific international and national standards (e.g., BS EN 502720-2:20).

15 Recycling and disposal At the recycling facility, used batteries are broken apart and separated into components to begin the recycling process. Nearly 100 percent of lead acid batteries are recycled. There are two main reasons for this: Recycling lead is cheaper than obtaining new raw material, and all the parts of the battery can be completely recycled. Polypropylene is recycled into more battery plastic to produce new battery cases, sulfuric acid is collected and resold as commodity acid, and lead is smelted and reused in batteries or other products. The lead acid recycling system is ecologically almost a closed loop, and it is highly regulated at the local, state, national, and international levels. Battery owners can safely dispose of their spent batteries at retailers and recycling drop off centers or even return them directly to the manufacturer, some of whom provide this service for free. For proper battery disposal, refer to national/international legislation and local waste disposal rules and regulations. PLASTIC LEAD ELECTROLYTE 1 ELECTROLYTE 2 Plastic pellets recycled from battery cases and covers are used to manufacture new cases and covers. Lead ingots recycled from battery grids, other battery parts and lead-oxide are used to manufacture new grids, parts, and lead oxide. Used electrolyte is reclaimed and reused in manufacturing new batteries. Sodium sulfate crystals separated from used electrolyte are recycled and sold for use in i.e. textiles and glass.

www.abb.com/ups ups.sales@ch.abb.com Copyright 27 ABB. All rights reserved. Specifications subject to change without notice. 4NWP1121R00 EN