Optimising Thermoelectric Cooler Modules in a System

Similar documents
TABLE OF CONTENTS. 1. How Efficient is a Thermoelectric Cooler? What is a Thermoelectric System Over 2 a Compressor?

ME Thermoelectric -I (Design) Summer - II (2015) Project Report. Topic : Optimal Design of a Thermoelectric Cooling/Heating for Car Seat Comfort

5A LOW DROPOUT POSITIVE REGULATOR

Laboratory Exercise 12 THERMAL EFFICIENCY

TELEDYNE. PB 4213 June JUDSON TECHNOLOGIES A Teledyne Technologies Company TELEDYNE JUDSON TECHNOLOGIES TC8 TEMPERATURE CONTROLLERS

Title: Optimal Design of a Thermoelectric Cooling/Heating for Car Seat Comfort Developed by Dr. HoSung Lee on 10/18/2014 Car seat comfort is becoming

Development of the LPT W Concentric Pulse Tube

SECTION 2: ENERGY STORAGE FUNDAMENTALS. ESE 471 Energy Storage Systems

Cooler lighting for vertical and canopy installation

Laird Thermal Systems Application Note. Cooling Solutions for Automotive Technologies

FUSE TECHNOLOGY Ambient temperature

Location Options. Side flash hopper. Pro. Cons. High temp of 500 F Lower ambient temp Close to outside wall. Limited surface area Surface is uneven

MPT SERIES OPERATING MANUAL. Caution: To Operate this controller safely, use the Safe Operating Area Design Tool Online at

Thermoelectric Module Installation Guidance

AT1084 5A Low Dropout Positive Voltage Regulator

PID-1500 THERMOELECTRIC & RESISTIVE HEATER TEMPERATURE CONTROLLER INSTRUCTION MANUAL

Producing Light from Stoves using a Thermoelectric Generator

Integrated Shaker Manager The Future of Vibration Testing. Copyright IMV CORPORATION 2016 All right reserved.

Material Specifications (50 C hot side temperature) Material Specifications (27 C hot side temperature)

LABORATORY 2 MEASUREMENTS IN RESISTIVE NETWORKS AND CIRCUIT LAWS

4707 DEY ROAD LIVERPOOL, NY PHONE: (315) FAX: (315) M.S. KENNEDY CORPORATION MSK Web Site:

A thin film thermoelectric cooler for Chip-on-Board assembly

Laird Engineered Thermal Systems Application Note. Thermoelectric Modules and Assemblies for Medical Laser Cooling Applications

Analyzing the Thermal Operating Conditions of a Solenoid

ELECTRICAL INTERFACE TO DC BRUSHLESS MOTORS SUPPLIED IN TECNADYNE THRUSTERS, LINEAR & ROTARY ACTUATORS & HPU s

GEOMETRICAL PARAMETERS BASED OPTIMIZATION OF HEAT TRANSFER RATE IN DOUBLE PIPE HEAT EXCHANGER USING TAGUCHI METHOD D.

Thermoelectric Cooling System. Model 5473

The Study of Thermoelectric Power Generation in The Cooling of Fin and Vibration Heat Pipe

SCR Power Controllers

Design, Fabrication and Testing of helical tube in tube coil heat exachanger

AMS1117 1A Adjustable / Fixed Low Dropout Linear Regulator

Using the IMV s standard ECO system to improve shock capability. Optimising Vibration Test Systems for Battery Testing using ECO Technology

XLR Energy Storage Module

Reduction of Self Induced Vibration in Rotary Stirling Cycle Coolers

LM , LM mA and 500mA Voltage Regulators

DEVELOPMENT OF ELECTRONICALLY CONTROLLED PROPORTIONING DIRECTIONAL SERVO VALVES PROJECT REFERENCE NO.: 38S1453

CHAPTER 19 DC Circuits Units

P08451 Prototype Thermoelectric Heat Exchanger

LM , LM mA and 500mA Voltage Regulators

Thermo-Comfort Cushion & Back Car Seat

LM ma Low Dropout Regulator

Bistable Rotary Solenoid

Technical Note. Management of Sealed Lead Acid Batteries in Reliable Small DC Standby Power Supply Systems

Inverter control of low speed Linear Induction Motors

AUML Varistor Series. Surface Mount Varistors

Coriolis Density Error Compensating for Ambient Temperature Effects

INFRESCO 2KW VARIABLE CONTROLLER Issue 3

Pulse Tube Microcooler for Space Applications

The Traveler Series TM : Adventurer

XLM 62V Energy Storage Module

arxiv:submit/ [math.gm] 27 Mar 2018

Technical Explanation for Inverters

WITH BIO LUBRICANTS JATROPHA OIL, CASTOR OIL, NEEM OIL AND MINERAL OIL (SAE 20W50)

Use of Flow Network Modeling for the Design of an Intricate Cooling Manifold

RECOMMENDATIONS FOR USING FREQUENCY INVERTERS WITH POSITIVE DISPLACEMENT REFRIGERANT COMPRESSORS

Surface- and Pressure-Dependent Characterization of SAE Baja Tire Rolling Resistance

Silvertel. Ag Features. Multi-Stage Charging. Battery Reversal Protection. Reduced Power Consumption. Wide DC or AC Input Voltage Range

SECTION 6: BATTERY BANK SIZING PROCEDURES. ESE 471 Energy Storage Systems

IL1117-xx. 1.0A Low Dropout Positive Voltage Regulator TECHNICAL DATA. Features. Applications. Absolute Maximum Ratings. Rev. 02

Part C: Electronics Cooling Methods in Industry

Aluminum Capacitors Standard C Snap-In

Performance study on thermoelectric cooling and heating system with cascaded and integrated approach

P5 STOPPING DISTANCES

A REVIEW ON THERMOELECTRIC COOLING SYSTEM

Technical Notes. Introduction. LED Efficacy. Light Output and Efficacy. Issue 4 April The general equation for light output can be written as:

Industrial Motors. But first..servos!

EIS MTM/TTM THERMAL BALANCE TEST SPECIFICATION, PROCEDURES AND PREDICTIONS

Aluminum Electrolytic Capacitors Power Ultra Miniature Snap-In

Type 947D Polypropylene, High Energy Density, DC Link Capacitors

CITY DRIVING ELEMENT COMBINATION INFLUENCE ON CAR TRACTION ENERGY REQUIREMENTS

Application Note 103 January LTM4600 DC/DC µmodule Regulator Thermal Performance Eddie Beville, Jian Yin AN103-1

Analysis of the use of thermoelectric generator and heat pipe for waste heat utilization

Thermal Unit Operation (ChEg3113)

The Traveler Series: Adventurer

TO-220. Symbol Description Max Units VIN Input Voltage 15 V IOUT DC Output Current PD/(VIN-VO) ma. -40 to 125 (* in case of IL

Aluminum Capacitors Standard - 85 C Snap-In

High Current Thermal Fuse

IceLED Ultra VS Cree XLamp modular active Star LED Cooler ø99mm Cree XLamp Active Star LED Cooler ø99mm

IMPROVEMENT ON MOUNTING THERMAL RESISTANCE BETWEEN A CIRCUIT BOARD WITH MANY COMPONENTS AND A LIQUID-COOLED COLD PLATE

Power Quality and Energy Management

NOT RECOMMENDED FOR NEW DESIGNS

Application Note Thermal Mass Flow Sensor FS7

Analysis of Fuel Economy and Battery Life depending on the Types of HEV using Dynamic Programming

LIFE CYCLE COSTING FOR BATTERIES IN STANDBY APPLICATIONS

AMS Amp LOW DROPOUT VOLTAGE REGULATOR. General Description. Applications. Typical Application V CONTROL V OUT V POWER +

Sensorless Brushless DC-Servomotors

APPLICATION NOTE Calculating temperature rise when mounting remote access units into Oberon s Model 1074 Ceiling Zone enclosures

Internal Bracing Design Program Background Information

Stefan van Sterkenburg Stefan.van.sterken

Components of Hydronic Systems

Advanced Monolithic Systems

Chapter 7: DC Motors and Transmissions. 7.1: Basic Definitions and Concepts

Variable speed application guidelines

Technical Guide No. 7. Dimensioning of a Drive system

THERMOELECTRIC SAMPLE CONDITIONER SYSTEM (TESC)

Heat Pipe Selection Guide Heat Pipe Introduction

Cooling Enhancement of Electric Motors

Consideration of Snubber Capacitors for Fast Switching with an Optimized DC Link. May 3, 2016

Pump Control Ball Valve for Energy Savings

CAPT JT Elder Commanding Officer NSWC Crane

Transcription:

Optimising Thermoelectric Cooler Modules in a System Introduction The aim of this document is to provide better understanding of the data provided in the datasheet for thermoelectric cooler (TEC) or Peltier devices and how it may be used to understand and optimise a TEC in a system. Example graphs are presented from ET-127-10-13-RS, but the explanations are applicable to all single stage TECs. The datasheets present equivalent data at three different fixed hot side temperatures (T h = 25, 50 and 75 o C) to illustrate the impact this has on performance: over this range, higher hot side temperatures normally lead to improved performance. This document will focus on examples at 25 o C hot side. Heat Flow P c max I max T max Figure 1: Heat removed (Pc) vs Temperature difference at T h = 25 o C Figure 1 shows the heat removed, P c, against the temperature difference across the module at a range of different currents. This graph is important to use in determining the performance in your system. It is clear that the larger temperature difference that the module has to work against, the smaller the quantity of the heat removed from the cold side. For example, if a full system results in a

30 o C temperature difference across the module, the maximum cooling power can be read off the graph as a maximum of 21 W at a current of 3.9 A. It is important to estimate the temperature difference expected across the module, as the actual P c in use can be significantly less than P c max. The heat removed must compensate for any heat sources on the module cold side, and any thermal losses through contact with ambient air or insulation, or through clamping bolts etc. In addition the heat removed must be sufficient to provide an adequate transient response. Figure 2: Waste heat (Q h) vs Temperature difference Figure 2 shows the waste heat, Q h, against the temperature difference across the module at a range of different currents. This graph shows the amount of heat that must be dissipated from the hot side of the module. The waste heat is approximately given by the sum of the heat removed (Pc) and the electrical power into the module (IV): QQ h = PP cc + IIII. Therefore the waste heat is always higher than the heat removed, and can be significantly higher, especially at higher temperature differences and higher currents. For example, at a 30 o C temperature difference, at I = I max = 3.9 A, 79W of heat energy is dissipated from the hot side, significantly more than the 21 W of cooling provided by the cold side under these conditions. The quantity of waste heat can therefore serve as a guide to select a suitable heat sink or other heat transfer means on the hot side. Since the heat flow on the hot side is always higher than on the cold side, issues with a system can often be due to unintended additional thermal resistances added on the hot side. This data can be used more quantitatively, to estimate the temperature difference seen by the module in a system. For example if other components such as a heat sink add a thermal resistance R h on the hot side, they will result in an additional temperature loss T h - T amb in the system, as shown in Figure 3.

T amb R h TEC module Q h T h P c or Q c Figure 3: TEC diagram including hot side thermal resistance. Using approximate knowledge of the heat out of the TEC, Q h, can aid in estimating this temperature loss by using the equation: T c TT h TT aaaaaa = QQ h RR h. Continuing the example of using the TEC at 30 o C across the module and at a current Imax, a forced convection heat sink with a thermal resistance R h = 0.25 o C/W is used. The additional system temperature drop T h - T amb = R h * Q h = 0.25 * 79 = 20 o C. Therefore, even though the module is generating a 30 o C temperature difference, the temperature drop between the cold side of the module and the ambient air (T amb) is only T amb T c = T (T h T amb) = 30 20 = 10 o C. The heat flow out of the module has a significant impact on the overall system performance as it has reduced the overall system temperature difference from 30 o C at the module level to 10 o C at the system level. Therefore it is usual to run the module at a current less than I max, e.g. ~70% of I max. This reduction in I max only results in a small reduction in the cooling power (P c) and the achievable module temperature differences, but produces a much larger reduction in the waste heat (Q h). This reduction in Q h results in a better system performance. Note that there is an optimum, as if the current is reduced too much, the loss in module cooling power dominates, reducing system performance. The exact optimum current point depends on the module and system. The variation of the cooling power and waste heat with current can be seen more quantitatively in Figure 4 and Figure 5 (not published in standard datasheets).

I max Figure 4: Heat removed (P c) vs current Figure 5: Waste heat (Q h) vs current Note that this non-linearity in the heat pumped vs current means that pulse width modulation (PWM) control may need additional smoothing before its input into the TEC, or it may reduce the TEC performance. This occurs as for example the average heat pumped and average waste heat is different if the module is run at I max for half the time or I max/2 all the time.

Electrical Characteristics TEC voltage vs current characteristics are shown in Figure 6. The characteristics are dependent on the temperature difference as well as the mean module temperature. Therefore, for example, driving the module at a constant voltage from an initial zero temperature difference will result in a drop in current as a temperature difference across the module develops. This temperature difference dependence can be also be useful to troubleshoot a system. If, with a set voltage the current drawn is much smaller than expected (or equivalently the voltage is much higher than expected with a fixed current system), this suggests that the temperature difference across the module is much higher than expected, suggesting problems with thermal interfaces or other system issues. This can be separated from module issues by checking the AC resistance of the module in the off state. Reversing a module Figure 6: TEC voltage vs TEC current A thermoelectric single stage module can be electrically driven in reverse to reverse the heat flow direction. The performance will be almost completely identical apart from a small loss due to additional heat losses down the wires. Note that the temperature rating of either side of the module may be different in some cases. A high number of thermal cycles of the module can degrade device lifetime unless the module has been specifically designed for cycling applications (e.g. ETC or APHC in the part number). A thermoelectric module may also be used as a heater when it pumps heat (i.e. using Q h). Since it is a heat pump it can even achieve higher heat flow into the hot side than the inputted electrical energy. Heating is generally easier than cooling with a thermoelectric module. Typically a thermoelectric module is used instead of a resistive heater when fast ramp rates and stable temperatures are required, sue to the low thermal mass of the thermoelectric and its ability to actively heat and cool.

A thermoelectric module however has a lower maximum temperature rating than electrical resistance heaters so is not suitable for high temperatures or very high heat flows into large thermal masses. Coefficient of Performance (COP) The final graph (Figure 7) in the datasheet shows the coefficient of performance (COP). This is defined for cooling applications, as: CCCCCC = HHHHHHHH pppppppppppp EEEEEEEEttrrrrrrrrrr iiiiiiiiii pppppppppp = PP cc II VV It can be seen that the COP is maximised at low temperature differences and low to medium currents provided that the current is sufficient to achieve the required temperature difference. Figure 1 also shows what current (and associated P c) the maximum COP occurs at when you have fixed the temperature difference. It does not show the value of the COP at that maximum. A high COP is desirable to reduce electricity usage and reduce the waste heat produced, but there is often a balance between efficiency and achievable pumping power or temperature difference. Figure 7: Coefficient of performance vs current.