Element D Services Heating, Ventilating, and Air Conditioning

Similar documents
Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating Ventilating and Air Conditioning ODG010107

Element D Services Heating Ventilating and Air Conditioning ODG010107

Design Standard - Fume Hoods & Fume Hood Exhausts

January, 2014 Page 1 of 6

UNIVERSITY OF ROCHESTER DESIGN STANDARDS JANUARY 2012 SECTION FUME HOODS AND LOCAL EXHAUST SYSTEMS

STATE UNIVERSITY CONSTRUCTION FUND

Fume Hood Standard. The appropriate maintenance/engineering division on each campus or other business unit operating on UofT property shall:

3.5 Exposure Control Measures

DEPAUL UNIVERSITY. Fume Hoods Manual. Environmental Health & Safety. April 2017

TABLE OF CONTENTS STANDARDS FOR THE DESIGN, CONSTRUCTION, MAINTENANCE AND USE OF LABORATORY FUME HOODS. Effective August 2010

Fume Hood Program. Program originated: 08/2008 Updated: 06/2016. Gordon Krueger Environmental Safety Specialist

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume

UNR Ventilation Policy

How to Use a Chemical Fume Hood Safely

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

Lab Safety & Energy Optimization. Introduction & Agenda

Laboratory Exhaust Systems

Underutilized Technologies

---:...-- Environmental Health & Safety RADIATION PROCEDURES MANUAL. Procedure Cover Sheet. Procedure Number: EHS REV 2

Ductless Nanoparticle Containment Enclosures

.1 Special Building Areas 8. Laboratories..3 Laboratory Casework (section ).4 Chemical storage cabinets (section )

LABORATORY HOOD MANUAL

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

Model ND-2 Specification

VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD

University of Delaware

new fume hoods providing performance and protection

Laboratory Exhaust Systems

Fume hood construction details. VANGUARD FUME HOODS Listed by Intertek to UL 1805 standard page 1. Features

Fume hood construction details VANGUARD FUME HOODS. Listed by Intertek to UL 1805 standard. page 1. Features

2. Backward inclined / backward curved centrifugal wheel fans. 3. Axial / backward curved mixed flow impeller bifurcated fans.

Fixed Range Exhaust Flow Canopies for NU 540 (Series 1 ), NU 543 (Series 1 ) Class II, Type A2, Biological Safety Cabinets

Product Data. 35J Single-Duct Retrofit Terminal Units for Variable Air Volume Systems. 40 to 3700 cfm

Application. Tek-Air Systems, Inc. 41 Eagle Road Danbury, CT (203) FAX: (203) SALES FAX: (203)

FVC2100/2200 TEK-AIR TECHNICAL PRODUCT DATA SHEET FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER. Application. General Description

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules

Demand Based Static Pressure Reset Control for Laboratories

AUDIO-VISUAL EQUIPMENT

SECTION AXIAL HVAC FANS

FUME HOOD SELECTION GUIDE

General. Technical Bulletin: ACCESSORY INFORMATION

AUDIO-VISUAL EQUIPMENT

Energy Recovery Laboratory Exhaust

BULLETIN 456. July 1997 VANEAXIAL FANS. Type W Direct Drive/Belt Driven. Model VW Direct Drive. Model VWBD Belt Driven

OVERVIEW Combination Supply/Return Diffuser (SARM)

Tubular Centrifugal Fans

Completing Your Fume Removal System

HOWORTH EXFLOW 28 PREVENTS AIRBORNE INFECTION TECHNICAL SPECIFICATION. Exflow 28 Technical Specification. Page 1 of 7

Polypropylene Total Exhaust Fume Hoods

Direct Gas-Fired Heating

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System

SECTION AIR TERMINAL UNITS

Proposed Addendum ag to Standard , Ventilation for Acceptable Indoor Air Quality

NEBBinar: A TAB Professional s Wish List: Equipment Procedures & Issues. March 27, 2014

FXV/CXV & FXV3/CXV3 Layout Guidelines

INSTALLATION INSTRUCTIONS K-SERIES UNDER CABINET HOOD

Ductless Nanoparticle Containment Enclosures

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc.

FAN POWERED TERMINAL UNITS

BAC, BAF, BAH Central Station Air Handlers

Class II biological safety cabinets

AMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers

High Performance Ductless Balance Enclosures

INSTALLATION INSTRUCTIONS K SERIES LINER INSERT

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD

USER'S GUIDE TO FUME HOODS. Procedures for Increasing the Effectiveness of Laboratory Hoods. Revised December, Hood Basics

D2-2. Table of Contents RETROFIT/BYPASS TERMINAL UNITS

SECTION HVAC AIR CLEANING DEVICES

Laboratory Exhaust Systems

Energy Recovery Laboratory Exhaust

SECTION COMPRESSED-AIR PIPING FOR LABORATORY FACILITIES

Accessories Standard Service Fixture Kits

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society

INSTALLATION INSTRUCTIONS ISLAND LINER INSERT

Ductless Nanoparticle Containment Enclosures

Central Station Air-Handling Units

FILTRATION FUME CABINET MODELS T800 T1800 OPERATING AND MAINTENANCE MANUAL

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society

CORPORATION DURALAB CORPORA

CENTAXIAL TUBULAR CENTRIFUGAL FANS. BIA Airfoil Blade Design Direct Drive & Belt Driven Model CBD / CDD (Class I, II & III) Model CBD Belt Driven

Ventilated Balance Enclosures

Protector XStream Laboratory Hoods

VAV terminal units. Type TVM. For dual duct systems PD TVM 1

Centrifugal Cabinet Fans Model BCF Belt Drive Low-Profile

KWT GALLEY WATER WASH HOOD GALLEY WATER WASH HOOD KWT. With supply air and Capture Jet technology

SLIM LINE FUME HOOD MONITOR

SECTION DUCTWORK ACCESSORIES

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD

Metasys Zoning Package Installation

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Dual Duct Variable Air Volume Terminal (Model TDS)

LABORATORY FUME HOODS

KVL-P with Plate Shelf

ADVANCED SAFETY ENGINEERING FOR EFFECTIVE HANDLING OF HAZARDOUS PARTICULATE DRUGS AND POWDERS IN A CLASS II, TYPE A2 BIOLOGICAL SAFETY CABINET

CLAIRE TOTAL SAFETY CABINET TYPE B2 Safe for chemicals due to Total Exhaust

Guideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society

INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD

Transcription:

Laboratory Exhaust and PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3042 on exhaust and ventilation with additional criteria for projects involving design of laboratory exhaust and ventilation systems. B. Refer to Design Guideline Element D3042 for the following: 1. General design criteria related to exhaust and ventilation systems. 2. Special Contract Document requirements and products applicable to the Project. PART 2 - DESIGN CRITERIA 2.01 GENERAL A. In general, laboratory exhaust systems shall comply with procedure and support room ventilation air requirements of NFPA 45, 90A, NIH, CDC, OSHA Regulation 29 CFR, Part 1910, ACGIH a Manual for Recommended Practice for Design 27 th Edition, and ANSI/AIHA Z9.5-2003. B. Special exhaust systems as noted below and where determined to be hazardous, shall not be housed in the same chase that contains environmental supply, return, and exhaust ducts. Special exhaust systems shall be labeled "hazardous" consistent with specification requirements. 1. Laboratory hood exhaust systems. 2. Biological laboratory exhaust. 3. Radioactive hot lab exhaust. 4. LN 2 freezer room exhaust system. Refer to Design Guideline Element Z4050. C. Where laboratory classification is BSL-1 or BSL-2 and laboratory protocol does not allow for hazardous exhaust as a portion of the laboratory exhaust system, combined environmental/laboratory exhaust systems may be used and may be located in the same chase as environmental supply and return ductwork. The combination environmental/laboratory exhaust ductwork should still be labeled "hazardous" to be consistent with specification requirements. D. All other ductwork carrying make-up air that is connected to special exhaust systems may be installed in the same chase that carries environmental supply and/or return ducts. E. Exhaust fans serving laboratory hoods shall be connected to an emergency power source. Refer also to Design Guideline Element D3000 for additional emergency power requirements. F. Evaluate recirculation of air in non-laboratory areas. G. Evaluate sensible cooling in low hazard, high heat load areas. ODG061412 1 OF 6

Laboratory Exhaust and 2.02 LABORATORY HOOD EXHAUST FANS A. While the type of exhaust system depends on hood characteristics, incorporate the following features into the design to avoid excessive noise levels and ensure accurate air balancing. 1. Exhaust shall be continuously monitored and an alarm system (local audible and visible alarm and an alarm at s central monitoring services, shall be provided for each hood and biological safety cabinet). 2. Select exhaust fans to operate at low tip speed (approximately at 50 percent of the maximum permissible tip speed) and maximum static efficiency. 3. Furnish to the Owner for review during the Design Phase, fan selection data on a performance curve and ensure that the fan discharge is directed vertically upward. 4. Size ductwork to maintain velocity in the ductwork between 1500 and 2000 fpm to prevent condensed fumes or particulate from adhering to the walls of the ducts or settling out onto horizontal surfaces and to address acoustical issues. 5. Perform a sound analysis for each exhaust fan and provide sound attenuation, if required. 6. To ensure that design airflow is achieved on manifolded and shared exhaust systems, specify pressure independent, factory-set, field-adjustable automatic airflow controls for each fume hood and biological safety cabinet. 7. An independent flow monitor shall be provided with provisions to alarm locally and also to alarm to the building automation system (BAS). Provisions must be incorporated in the design to allow access to the independent flow monitor. B. Each laboratory exhaust air system shall have a corresponding supply air system to comply with laboratory, hood exhaust air, and laboratory ventilation exhaust air change (AC/hr) requirements listed below: Room Description Occupied 3 AC/hr (minimum) Unoccupied AC/hr (minimum) Vacant 4 AC/hr (minimum) Fume Hood Rooms 6 6 4 Radio Chemistry 10 6 4 Laboratories 4 6 4 4 Equipment Room 4 6 6 4 Tissue Culture Room 3 6 6 4 Dark Room 10 10 4 Storage Room 4 4 4 Glass Wash Room 10 6 4 Cold Room 4 4 4 Notes: 1. Occupied defined as space with personnel present during specific time. 2. Vacant defined as space that is not assigned to a lab user and that does not have equipment that generates chemicals. 3. BSL3 and Tissue Culture Rooms are exempt from the occupied and unoccupied air change rate. 4. Room shall have override capability for changing from unoccupied to occupied modes. ODG061412 2 OF 6

Laboratory Exhaust and C. Actual air change rates may exceed the above stated rates to maintain temperatures in the laboratory or prevent a hazardous environment. By definition, one AC/hr is the total of supply air and infiltration air from the surrounding space provided in one hour divided by the total room volume. D. Laboratory exhaust fans shall be an N+1 redundant system capable of maintaining constant volume with the capacity to exhaust listed rooms at the required minimum ventilation design air change rates. E. Exhaust fans shall be direct drive. Where exhaust air filters require or merit such, exhaust fans shall be powered through the use of variable frequency drives that vary fan speeds to maintain exhaust air conditions during exhaust air filter loading. Fan speed is determined by maintaining an airflow measurement or static pressure setpoint (adjustable) from the BAS. F. The design exhaust rate through standard fume hoods, standard radioisotope fume hoods, and biological safety cabinets (BSCs) will be determined based on maintaining full containment at the maximum possible sash opening. 1. Laboratory chemical hood operation: Face velocities should be between 80 and 125 fpm at the maximum sash height with an optimum level of 100 fpm during occupied periods for standard fume hoods. Face velocity may be reduced to 60 fpm during unoccupied periods (via zone presence sensors at the hoods or room occupancy sensors). 2. Non-traditional chemical fume hoods (e.g. high performance fume hoods, application specific installations, etc.) are excluded from the above statements 2.02 F. and F.1. G. Either variable or constant volume bypass type hoods will be utilized. For substantial organic chemistry areas, variable volume type hoods with restricted bypasses will be utilized for those spaces. In addition to fume hoods, the BSCs, flammable storage cabinets, and acid storage cabinets will be served as follows: 1. Typical fume hoods and Class II Type B1 cabinets should be combined into a single laboratory exhaust system. 2. Radioisotope hoods should have a dedicated exhaust system. 3. Organic chemistry hoods may also require a dedicated exhaust air system. 4. Acid storage cabinets will be ventilated utilizing a 2-inch galvanized pipe directly connected from the cabinet to the fume exhaust ductwork. An exhaust air valve will not be utilized for the cabinet. 5. Some Class II Type B2 BSCs will utilize bag-in/bag-out 99.97 percent HEPA filters located on top of the BSC cabinet with supply air filters contained within the BSCs. H. The type of filtration components that will be placed in the laboratory exhaust shall be evaluated during Schematic Design based on the work being performed in each of the laboratories and exhaust hoods. I. Instruments that control air valves shall be capable of changing the state of room pressurization, which will be dependent on current and future use of the laboratory. ODG061412 3 OF 6

Laboratory Exhaust and J. Storage rooms that contain laboratory specialty gases or liquid nitrogen stored in dewars shall be ventilated and shall have the appropriate gas detection monitoring and alarm systems per OSHA requirements to protect personnel from accidental asphyxiation. 2.03 LABORATORY EXHAUST DUCTWORK A. Specify welded stainless steel Type 316L ductwork, 18 gage minimum, for exhaust air ductwork from BSCs, laboratory glassware washers, and chemical fume hoods where corrosive chemicals may be used. For hoods that use radioactive isotopes, specify Type 316 polished welded, stainless steel ductwork. Exhaust ductwork from synthesis labs should be Type 316L stainless or other suitably rugged/ inert material due to the corrosive and toxic exhaust. B. Galvanized steel can be used on general exhaust system ductwork. C. Specify exhaust ductwork used to transport air from BSC s where radioisotopes are used to be labeled with the standard Caution Radiation Symbol magenta on yellow background at 20 foot intervals. Equip BSC s with proper filtration components to capture potential contaminates. D. Route exhaust ductwork through the building roof at a distance of 25 feet and downwind from any outside air ventilation air intake. The final location and orientation of the laboratory exhaust or outside air intake will be determined from wind tunnel results. E. The allowable exhaust air stack height shall be minimum 12 feet above centerline height of air intake or roofline. The stack discharge air velocity shall be equal to or greater than 3000 fpm (3600 fpm for an NIH funded project). F. Locate exhaust discharge stacks where exhaust air cannot be easily reintroduced into building outside air intakes. Owner prefers to locate outside ventilation air intakes on the side of the building; not on the roof. Refer to Design Guideline Element D3041 for additional criteria on outside air intakes. 2.04 AIR DEVICES A. Refer to Sound Criteria in Design Guideline Element D3002. B. Specify exhaust square panel face diffusers similar to Titus Omni directional diffusers with round necks in open laboratory areas. Increase neck sizes for the diffuser since they are being used for exhaust air purposes. C. Air valves shall be used to control the exhaust airflow rates from rooms, hoods, and BSCs via feedback signals from stand alone controllers and setpoints (adjustable) from the BAS. PART 3 - SPECIAL CONTRACT DOCUMENT REQUIREMENTS 3.01 GENERAL A. Include a single line riser drawing of the general exhaust ventilation exhaust systems in the Contract Documents. This shall be initially provided in the Schematic Design Submittal. ODG061412 4 OF 6

Laboratory Exhaust and B. When high plume exhaust fans are being considered in the design of a laboratory exhaust system, note plume heights, design airflow rates, static pressure requirement, and maximum brake horsepower requirements on the equipment schedule on the Drawings. 1. A/E shall consider wind velocities as listed in the Appendix of the Climatic Design Information chapter of ASHRAE Handbook of Fundamentals or airport weather data. PART 4 - PRODUCTS 4.01 GENERAL A. Refer to Owner s Master Construction Specifications. These are available on the Owner s Design Guidelines website: http://www2.mdanderson.org/depts/cpm/standards/specs.html B. Evaluate energy recovery units as appropriate to the application in accordance with the latest edition of ANSI/ASHRAE/IESNA 90.1. Refer to Design Guideline Element D3041 for energy recovery requirements. C. Evaluate the use of proximity occupant sensors when there is less than 800 square feet of floor space per hood to reduce the open sash face velocity to 60 fpm when the workspace in front of the fume hood is not occupied (typical for VAV fume hoods in support space rooms or alcoves with dedicated supply paired with the fume hood exhaust and not required in open labs unless there is a high density of hoods). D. Specify high efficiency / low exhaust volume design for constant volume fume hoods installed in rooms smaller than 1500 square feet of floor space per hood (typical for radioisotope fume hood installations) or variable volume rooms where fume hood density dictates minimum airflow rates. E. Specify high plume, dilution mixed flow fans with direct drives for laboratory exhaust where feasible. F. Evaluate and provide test data for manufacturers of HVAC airflow tracking equipment proposed on the Project that are not currently specified in Owner s Master Construction Specifications, Proposed products should operate with BACnet open protocol and should also be compatible with the building automation system. G. Evaluate an exhaust ductwork material that is capable of withstanding the corrosion products from a synthesis laboratory. PART 5 - DOCUMENT REVISION HISTORY Issue Date Revision Description Reviser 01-01-07 Initial Adoption of Element ODG061412 5 OF 6

Laboratory Exhaust and Issue Date Revision Description Reviser Rev. 1 02-27-07 Part 2 Laboratory Exhaust Hoods added Titus; Part 2.1 revised Table for Tissue Culture Room AC rate from 8 to 12 for unoccupied mode; revised to exception on AC rates lab temp, and prevent hazardous environment; revised 150 to 125 fpm; deleted B3 and Class III BSCs; revised 10 ft to12 ft on exhaust stacks; revised Air Devices; added criteria that A/E to evaluate use of duct material serving synthesis labs; deleted additional exhaust requirement for RI room. PDN Rev. 2 11-15-07 Revised AC/hr values in the table of 2.02 B. including the additions of notes and editorial format changes. Rev. 3 03-04-08 Added 2.01B.4, added AC/hr value in the table of 2.02 B. for LN 2 Freezer Room, revised 2.02. J. and added 2.02 K. Rev. 4 12-09-08 Included sustainability requirements throughout document based upon TGCE's evaluation. (Paragraphs 2.01 B; 2.01 B 4; 2.01 D; 2.02 D; 2.02 E; 2.02 F; 2.02 G; 2.02 H; 4.01 B & 4.01C) PDN / CC PDN JCD Rev. 5 01-08-09 Revised AC/hr values and note 2 in the table of 2.02 B. PDN / CC Rev. 6 07-08-10 Revised 2.02 A. 5. B., D, and G.1.: Deleted 2.02 G.2. entirely. AC/hr values and notes in the table. Relocated statement about high plume exhaust fans from Paragraph 2.03A to 3.01B. Revised 4.01E. SAK / DAB / GSN Rev. 7 09-16-10 Added new guidelines under 2.01A; revised ductwork velocity requirement under 2.02A, 4. Rev. 8 05-17-12 Added reference to Z4050 in paragraph 2.01 B.4, deleted LN2 requirements from table 2.02 B. and deleted paragraph 2.03 D. Rev. 9 06-14-12 This revision was made to update this guideline in accordance with MS 11 53 13 Rev 2.02 F. added descriptive word standard for radioisotopes revised the 100 fpm sash velocity requirement to read as the full Rev. 8containment maximum possible sash opening. 4.01C. added direction to the engineer to consider proximity sensor when floor space is less than 800 square feet. KTB / SK PDN GN / CHL / PDN END OF ELEMENT ODG061412 6 OF 6