Circuit breaker interlocking and operation requirements SIEMENS

Similar documents
The X, Y, and Z of Circuit Breaker Control

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General

Typical Specification

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Pretest Module 29 High Voltage Unit 1

Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear rated up to 15kV, 25 and 40kA UPPER TERMINAL SET VERSION

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Solid Dielectric, Single Phase Recloser

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Vacuum Circuit Breaker Type VAD-3

AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism

Type 38-3AH3 38 kv vacuum circuit breaker instruction manual. Installation operation maintenance E50001-F710-A238-V1-4A00. Answers for energy.

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

Solid Dielectric, Single Phase Reclosers

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

Vacuum Circuit Breakers (Vehicle)

Instruction manual. Types GMSG and GMSG-GCB 5 kv to 15 kv vacuum circuit breakers.

Cobra-S. Catalog Cobra-S

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

Learning Module 6: Medium Voltage Power Circuit Breakers. 101 Basic Series

Close-Open (Short-Circuit) Time Results Interpretation

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Single Pole Circuit Protectors 55. Multi-Pole Circuit Protectors 56. Configurations 58. Operating Characteristics 59.

Contents. Page INTRODUCTION Power/Vac GUIDE FORM SPECIFICATION thru

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9968

solutions RUS accepted

The safest, most reliable Switchgear in the market today

SafeGear TM Motor Control Center Arc resistant metal-clad construction

www. ElectricalPartManuals. com

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

University of Houston Master Construction Specifications Insert Project Name

SWITCHGEAR OPERATING PERSONNEL SAFETY UPGRADE SOLUTIONS FOR AGED INSTALLED BASE

Vacuum Circuit Breakers (Vehicle)

1. Safety practices General Introduction Standards...3

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Vacuum Circuit Breakers (Vehicle)

Not all Low Voltage Switchgear is created equal

HGA. Hinged Armature Auxiliary. Hinged armature auxiliary relay to perform auxiliary functions in AC and DC circuits.

Exercise 4-1. Friction Brakes EXERCISE OBJECTIVE DISCUSSION. Understand the construction and operation of friction brakes.

Powered by Safety 01.4IB.77000B PowlVac-ND Vacuum Circuit Breaker

AP/UP, AP/MIL Series Magnetic Circuit Protectors

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

Solid Dielectric, Independent Pole Operated Reclosers Catalog O-vst16

Air-insulated switchgear UniGear type ZS1

Solid Dielectric, Three Phase Reclosers Catalog O-vs18

B kv T&D GAS INSULATED SWITCHGEAR

Fuses still the best form of overload protection

Medium Voltage. ANSI C37.20 and NEMA SG-5

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

Switchgear. Low Voltage

AP1000 European 7. Instrumentation and Controls Design Control Document

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

Power/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers

B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

SIEMENS-ALLIS. Medium Voltage. Metalclad Switchgear. www. ElectricalPartManuals. com

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

Solid Dielectric, Triple Option Reclosers Catalog O-vst14

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

Series A Construction

33KV INDOOR SWITCHGEAR

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Vacuum Circuit Breakers (Vehicle) Type MSV 5kV. Instructions Installation Operation Maintenance SGIM-9988

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

IB PowlVac ITE-HK Remote Racking Device

Vacuum Circuit Breakers kv

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

Medium voltage vacuum circuit breaker. E-VAC series

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

505 Size 5 Series A Construction

BREAKER FAILURE PROTECTION

7. SERVICES OVER 600 VOLTS

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

POWERCON CORPORATION

AF series contactors (9 2650)

ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy

RUS accepted Catalog O-vst18

Horizontal Circuit Switchers

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC

MOTOR TERMINAL CONNECTIONS

Transcription:

Circuit breaker interlocking and operation requirements SIEMENS

When manufacturers and specifiers discuss circuit breaker operational and interlocking requirements, several terms are used repeatedly. Despite the common use of these terms, it seems clear that many persons do not understand what these terms imply or require. This issue of Tech Topics is intended to discuss several of the frequently used but often misunderstood terms. First, the terms that apply to all medium-voltage circuit breakers will be discussed, whether stationary mounted (as in outdoor distribution type circuit breakers) or drawout mounted (as in metal-clad switchgear).

Trip-free IEEE C37.04 for medium-voltage circuit breakers requires that they be tripfree, which is a condition in which the mechanism is designed such that the tripping or opening function takes precedence over the closing function. The requirements as elaborated in the standard are: If a closing operation is in progress, and a tripping signal (either mechanical or electrical) is received, the circuit breaker shall react as follows: If the closing signal and the tripping signal are initiated simultaneously, the circuit breaker contacts are permitted to close or touch momentarily before opening.

If the closing signal is initiated before the tripping signal is initiated, the circuit breaker contacts are permitted to close or touch momentarily before opening. If the trip circuit uses circuit breaker auxiliary switch contacts (52a contacts, closed when the circuit breaker is closed) or other equivalent contacts, the trip coil of the circuit breaker cannot be energized until these contacts in the trip circuit are made. Therefore, the circuit breaker main contacts are permitted to close or touch momentarily before opening.

If the tripping command is initiated mechanically (manually) and held in the actuated position before a closing signal (whether electrical or mechanical) is applied, the circuit breaker main contacts are not permitted to close, even momentarily. If the mechanism design requires, the circuit breaker may discharge stored energy but the main contacts are not permitted to move more that 10 percent of the open gap distance. The dielectric withstand capability of the open gap shall not be reduced, and the main contacts shall assume the fully open position.

Trip-free is a requirement of all medium-voltage circuit breakers, whether stationary mounted or draw out mounted. Trip-free is an important safety feature, as it assures that the decision to open a circuit breaker dominates over the command to close. Further, and probably most important, if there were no trip-free functional requirement, it would not be possible to lock a circuit breaker open (fundamental to lockout-tagout procedures) when performing maintenance.

Anti-pump IEEE C37.11 for circuit breaker control circuits requires the anti-pump function. This requires that when an electrical closing command is issued, only a single closing operation results. This is normally accomplished by incorporating an anti-pump relay in the close circuit. The anti-pump relay is energized at the same time that the close signal is applied. The anti-pump relay is connected so that it seals in as long as the close signal is maintained. The anti-pump relay, when sealed in, opens a contact in the close circuit. Thus, the circuit breaker closes, but if the close signal is maintained, the close circuit has an open contact in the circuit, preventing further close operations as long as the close signal is maintained.

The anti-pump function is a very important feature of control circuits. Without the anti-pump function, if the user connected a maintained contact in the close circuit, and the circuit breaker were closed into a fault current, the protective relays would cause an immediate trip action, but the maintained contact in the close circuit would initiate closing (again) into the fault. This process is called pumping, and would lead to ultimate catastrophic failure of some element in the system, perhaps the conductors leading to the fault, perhaps the circuit breaker, or elsewhere in the system. Therefore, anti-pump is one of the fundamental requirements for every medium-voltage circuit breaker.

Note that the anti-pump function is reset if the control power supply is removed for some reason. When this happens, the anti-pump relay contact in the close circuit closes to complete the close circuit. Then, if a maintained contact in the user s control circuit is closed, and the control power is restored, the circuit breaker will close. However, after this initial close operation, the anti-pump relay will be sealed in, and further closing operations will be prevented until the maintained contact is opened or the control power supply is interrupted. This illustrates that a maintained contact should never be used in a close circuit.

Draw out circuit breaker interlocks Draw out circuit breakers must have interlocks for the following: To prevent moving the circuit breaker between the TEST position and the CONNECTED position while the circuit breaker is closed. To prevent closing of the circuit breaker while the circuit breaker is at a position between the TEST position and the CONNECTED position. To positively secure the circuit breaker in the TEST position and in the CONNECTED position, as well as in the DISCONNECTED position. While this requirement applies to the three defined positions, most modern designs positively secure the circuit breaker both in these three positions, and also between these positions.

The mechanism must prevent closing of the circuit breaker unless the mechanism has full energy (stored energy) to complete the closing operation. This applies whether the energy stored is in a spring system, or is in a magnetic actuator type of operating mechanism. The mechanism shall provide protection against accidental discharge of stored energy during maintenance activities. This may be accomplished in any of several ways:

The mechanism may be designed to prevent withdrawal of the circuit breaker from the circuit breaker compartment with the stored-energy (spring) mechanism charged. Typically, with a design of this type, the user must initiate a closing operation manually in the DISCONNECT position in the circuit breaker cell (as control power is not connected in the disconnect position), followed by a manual trip operation to open the circuit breaker. This discharges the closing energy prior to withdrawing the circuit breaker from the circuit breaker compartment.

The mechanism may be designed such that closing cannot be performed when the circuit breaker is removed from the circuit breaker compartment. This is usually described as a blocked closing condition. The mechanism may be designed such that, before the circuit breaker is removed from the compartment, the closing energy is automatically discharged from the stored-energy mechanism.

This latter item is most commonly referred to as the spring dump function. Of the three allowable methods of preventing accidental discharge of stored-energy (prevent withdrawal, block closing, and spring dump), only the last (spring dump) is automatic. The others require that the operator either perform actions in a particular sequence (for the prevent withdrawal type), or apply special tools or procedures when performing maintenance (for the block closing type). The other interlocks required for draw out type circuit breakers are relatively simple to understand, so are not discussed in detail. We hope this discussion of the interlocks required for circuit breakers is useful. For those wishing further knowledge, the reader should consult the relevant standards, including:

IEEE C37.04-1999, Standard Rating Structure for AC High-Voltage Circuit Breakers (clause 6.9). IEEE C37.11-1997, Standard Requirements for Electrical Control for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis (clause 3). IEEE C37.20.2-1999, Standard for Metal-Clad Switchgear (clause 7.10). It should be noted that all three of these standards are in the process of revision, and the next edition of C37.11 is expected to be approved by the IEEE-SA Standards Board in 2013. Thus, the reader should always consult the latest approved revision of any standard.