CONTROL UNITS VEHICLE EXHAUST GASES. Pure advantages

Similar documents
CONTROL UNITS LOCAL EXTRACTORS LOCAL EXTRACTORS. Pure advantage

T: +44 (0) F: +44 (0) E:

AUTOMATICS. GEOVENT offers a wide range of options for ventilation and extraction controls.

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.

EXHAUST EXTRACTOR Pure advantage. Exhaust rails for rescue vehicles

DPC300 FUME CUPBOARD CONTROLLER

Electric Furnace KF/KFS Series

LOCAL EXTRACTION Pure advantages. The ideal extractor for light industry and laboratory environments.

IEC Utilization Categories (Explanation)

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

Single-inlet centrifugal fans

ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters (2 of 2) Lecture 6 Contactors and Motor Starters

RVS-AX Instruction Manual

Components for EEx e Panels

Control Power V AC, 50/60 Hz 150-C30NBD 150-C30FHD

IRRIGATION 810-3T-PLUS TRANSMITTER GUIDE

MAGNETIC MOTOR STARTERS

R820 REV2 SERIES SCR POWER CONTROLS NOVEMBER 2017

AXICIAT VA. Axial fans. Smoke extraction F200/120 and F400/120. High available pressure

KV sileo 100 M. Circular duct fans. Circular duct fans

THT/HATCH THT/HATCH. Order code THT/HATCH 40 2T 1 N 1 G

Dimensions WxHxD [mm] Weight [kg]

Industrial Variable Speed A-C Motors B-4511

Gate & Door Controller with LCD and Intelligent Technology

Instructions for the BCEA Rotary heat exchanger

Coil Data Nominal Current MA Nominal VA Sealed Single Pole Normally Open (SPNO) White Rodgers Q

Coil Data Nominal Current MA Nominal VA Sealed. Coil Data Nominal Current MA Nominal VA Sealed. Single Pole Double Throw (SPDT)

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

TSAT: Single inlet, belt-driven centrifugal fans fitted with electric motors. CJTSA: Ventilation units with a forward-curved impeller.

Safety Relay Unit. Ordering Information. Ideal for Safety Door and Emergency Stop Switch Circuits for Machines in European Countries

Type SOQ Negative Sequence Time Overcurrent Relay

FDR - Fire Damper for Rectangular and Circular Ducts. Halton FDR. Fire Damper for Rectangular and Circular Ducts

AA4006 Speed Sensitive Trip Unit. User Manual

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology

1 Phase electronic contactor (SC 1)

IN-LINE DUCT FANS MIXVENT-TD Fan Systems

SN1010 NATURAL VENTILATION CONTROLLER SET POINT

Safety Interlock Switches

ELECTRIC POWER REGULATION TEMPERATURE CONTROLLERS. room C

DTV, DTH and VVR Roof- and wall fans DTV Roof fan DTH Roof fan VVR Wall fan

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

Timer Relays - Fixed & Adjustable

ErP POWERBOX EC FANS - ESTOC EC FEATURES ELECTRICAL SUPPLY TEMPERATURE RANGE SIZES FEATURES AND CONSTRUCTION PRODUCT CODE IMPELLER MOTOR

Q Range Watertight Single-Phase Electric Quarter-turn Actuators for part-turn valves and dampers

Shipping volume [ft 3 ] 3 SQF-2 47 * 2.9 1" NPT Dimensions [in] L B S 3 SQF-3 49 * 2.9 1" NPT

amp ramp Operators Manual Page 1 Saftronics 2S Ltd Turnbridge Mills Quay Street Huddersfield West Yorkshire HD1 6QT

HIGH-POWERED VENTILATORS

SINGLE DUCT TERMINAL UNITS

Single or Double 240VAC motor control for domestic and industrial gates and doors.

FILTER Pure advantage. A flexible modular filter for particles and gas

GLM SERIES CONTROL Users Manual Rev:

CWK Circular duct coolers for cooled water

Application Engineering

RVP-R- VAV controller. In explosion-proof version

TD-ECOWATT AND DECOR-ECOWATT Series

Output signal active note. Measuring range rel. pressure. Electrical Data Power supply DC V, ±10%, 1.1 W

High efficiency low noise Speed-controllable Integral thermal contacts Can be installed in any position Maintenance-free and reliable

SP600 AC Drives MODIFIED STANDARD V*S DRIVES SP600 Drives: 480 VAC (3)

EDM Series EDM-80N EDM-80L EDM-100 EDM-200 AXIAL BATHROOM FANS. Bathroom extract fans EDM

Application Engineering

Sabre Plate Mounted Sickle Fans (VSP)

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

Installation, Operation and Maintenance Manual

HYDROPLUS. BOOSTER PUMPS Range of booster pumps fitted MULTi V, MULTi VS or MULTi-H pumps: Small institutions and industrial use 2 pole - 50 Hz

Motor. Document # Vari-Green Motor and Controls. Table of Contents. Features, Operation, Wiring and Troubleshooting

access

MCC Automatic Start-Stop Microcomputer Charger Control

Products for Indoor Air Quality and Control

7/S5 FIRE DAMPER FD40. v 2.9 (en)

HOW TO SPECIFY SDV UNITS

825-P Modular Protection System for motors Specification Guide

7/S6 FIRE DAMPER FDC40. v 2.9 (en)

Time scale: from 0.05 s to 100 h Multi-function Plug-in for use with 96 series sockets. Relay + socket. Wiring diagram (without control signal)

Swing Gate Kits AUTOMATIC GATE KITS & ACCESSORIES SECURING GATES SINCE Control Cards. Accessories 2017 / Gate & Door Controls Catalogue

Power consumption In operation At rest For wire sizing. Torque Inhibiting torque. 150 s / C Sound power level Motor

EDM-80N EDM-80L EDM-100 EDM-200. Installation examples. Extract ventilation through short duc

INSTRUCTION MANUAL MODEL PS VDC POWER SUPPLY

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

SDL Single-Duct, Low-Height, VAV Terminals

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

* With I-Option card only (C. T. connection) Basic connections with isolated contacts

Daikin McQuay. VAV Air Terminal Unit MQ FCI6, FVI5, THI5. Replacement Parts List No Revision J 07/2017

Typical applications are the control of barriers/booms in the parking and access control environments.

Combined Ventilation Controller RVWS-T-224HA

DC Variable Speed Drive Panel

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide

Power controlled LPU system

Model 340i / 680i / 1220i DC drive product manual HG iss 8 1

TECHNICAL DATA SHEET LAD/CYCLER16KW

Essential equipment for all your requirements

MaxPak Plus Analog DC V S Drive

SECTION MOTOR CONTROL

Installation Instructions

ExBin-P Pressure switches 5 Pa Pa

SOLSTART Instruction Manual

ADJUSTABLE FREQUENCY CRANE CONTROLS

UTK/UTT - Multi-blade Damper. Halton UTK, UTT. Multi-blade Damper

Varispeed E7. Varispeed E7. Varispeed. Varispeed E7. Varispeed E7. Varispeed E7 INVERTER SERIES

Code: FPT F32AM1A MECC-ALTE ECP 28-VL / 4. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP) 400/ ,8 30,0/24,0 32,5/26,0 46,97 ESPAÑA

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

Transcription:

CONTROL UNITS VEHICLE EXHAUST GASES Movex s control s offers a good working environment, adapted to all types of facilities. The right choice of control s is energy-saving and provides the lowest possible noise levels. automation encompasses specially adapted and proven components, as well as recommendations for appropriate system selections. In the installation examples on pages 2 through 5, there are suggestions for various solutions to help finding systems to comply with most needs. Exhaust extraction products are presented in various system solutions in the examples. For control of local extractors installations, see the control automation for local extractors. For help in installation or to calculate energy savings, please contact Movex. Movex also offers a range of local extractors, fans, accessories, and filters VEHICLE EXHAUST GASES Pure advantages

Start and stop of fan, with or without speed control System 1:11 Manual start and stop of fan The fan is started and stopped manually with protective motor switch SMB. The protective motor switch has termic magnetic release and a phase failure protection. SMB Protective motor switch 1X115 / 3X208 / 3X VAC System 1:12 Manual speed control of fan started and stopped with an external signal 3-phase motor only. The signal to start and stop fan with an external signal from for example a central monitoring system. The SFC POT potentiometer manually regulates the fan speed control according to your requirements. SFC POT Potentiometer SFC Frequency converter 1X VAC/ 3X VAC System 1:13 Manual start and stop of fan two speeds 3-phase motor only The fan is started and stopped manually with the rotary switch SFC VSS. With the rotary switch the fan speed can be switched between 2 preset speeds programmed on the frequency converters SFC VSS display. Rotary SFC Frequency converter 1X VAC/ 3X VAC System 1:14 Manual start and stop of fan as well as demand control of fan speed 3-phase motor only. The fan is started and stopped manually with the switch SFC SB. The frequency converter maintains the negative pressure in the collecting duct using the pressure sensor. ST 300 Pressure sensor SFC SFC SB Frequency converter 1X VAC/ 3X VAC 1x/ 3x VAC Signal cable Hose

Start and stop of fan with contactor. Automatic control, with time delay. System 2:11 Automatic start and stop of fan. Automatic start and stop with a switch placed on the hose reel or balancing block. S 400 is equipped with an adjustable time delay of 0-15 minutes. Contactor Transformer S 400 S 400 1X VAC/ 3X VAC 1X115 VAC Automatic control, radio transmitted with a time delay. System 2:12 Automatic start and stop of fan. Automatic start and stop with a radio switch placed on the balancing block. S400 is equipped with an adjustable time delay 0-15 minutes. Contactor Transformer Relay R S 400 S 400 Relay T R T 1X VAC/ 3X VAC 1X115 VAC R - Receiver T - Transmitter 1x/ 3x VAC Signal cable Hose

Individual damper control, start and stop of fan through a contactor. Automatic control of fan and damper, with time delay. System 3:11 Automatic start and stop of fan. Start and stop of fan as well as opening and closing of damper is automatic with a switch placed on the hose reel or balancing block. S 400 is equipped with an adjustable time delay 0-15 minutes. Contactor 1X VAC/ 3X VAC Transformer 1X115 VAC S 400 S 400 Automatic control of fan and damper, radio transmitter with time delay. System 3:12 Automatic start and stop of fan. Start and stop of fan as well as opening and closing of damper is automatic with a radio transmitted switch placed on the balancing block. S 400 is equipped with an adustable time delay 0-15 minutes. Contactor Transformer Relay R S 400 S 400 T Relay R T 1X VAC/ 3X VAC 1X115 VAC R - Receiver T - Transmitter 1x/ 3x VAC Signal cable Hose

Individual damper control and control of the fan through a pressure sensor and frequency converter. Automatic control of the frequency converter and damper, with time delay. System 4:11 Manual control of damper and need-adapted control and start and stop of fan 3-phase motor only. Start and stop of fan as well as opening and closing of dampers is automatic with a switch placed on the hose reel or balancing block. The frequency converter maintains a constant negative pressure in the main duct via the pressure sensor. S 400 is equipped with an adjustable time delay 0-15 minutes. ST 300 Pressure sensor SFC Frequency converter 1X VAC/ 3X VAC Transformer 1X115 VAC S 400 S 400 Automatic control of frequency converters and damper, radio transmitter with time delay System 4:12 Automatic control of damper and needadapted control and start and stop of fan 3-phase motor only. Start and stop of fan as well as opening and closing of damper is automatic with a radio transmitted switch placed on the balancing block. The frequency converter maintains a constant negative pressure in the main duct via the pressure sensor. S 400 is equipped with an adjustable time delay 0-15 minutes. ST 300 Pressure sensor SFC Frequency converter S 400 S 400 Transformer Relay R T Unit Relay R T 1X VAC/ 3X VAC 1X115 VAC R - Receiver T - Transmitter 1x208/ 3x VAC Signal cable Hose

SFC FREQUENCY CONVERTER Designed for process ventilation ENCLOSURE CLASS IP 21 Designation SFC 037/21-1 SFC 037/21-3 SFC 055/21-1 SFC 055/21-3 SFC 075/21-1 SFC 075/21-3 SFC 110/21-1 SFC 110/21-3 SFC 150/21-1 SFC 150/21-3 SFC 220/21-1 SFC 220/21-3 Rated power kw / HP 0.37 / 0.5 0.37 / 0.5 0.55 / 0.75 0.55 / 0.75 0.75 / 1 0.75 / 1 1.1 / 1.5 1.1 / 1.5 1.5 / 2 1.5 / 2 2.2 / 3 2.2 / 3 Rated current A 3.3 1.5 3.7 1.9 4.8 2.3 6.9 3 8 4.1 11 5.5 Input Voltage V 1-phase 3-phase Ouput Voltage V 3 phase The SFC frequency converter is designed for variable speed control of e.g. fans. This provides optimal operating economy and the lowest possible noise level. Depending on the number of work stations in operation, the SFC (along with the ST 300 pressure sensor) varies the fan speed and thus evacuates the correct amount of air. Alternatively, manual variable control can be used with the SFC POT potentiometer. The SFC VSS is used if a 2-step control is preferred. Interference filters are included. The enclosure class is IP 21 for built-in applications, alternatively IP 55 for dust- and water protection. Movex can supply SFC PROG pre-programmed frequency converters to make it easier to put systems in operation. For alternative voltages, etc., please contact Movex. Weight lb 3.3 3.3 3.3 6.8 6.8 Width inch Height inch Depth inch 2 13/16 5 1/8 5 11/16 5 5/8 5 1/2 5 7/8 2 13/16 5 11/16 5 1/2 5 1/8 5 5/8 5 7/8 2 13/16 5 11/16 5 1/2 5 1/8 5 5/8 5 7/8 5 1/8 5 5/8 5 7/8 5 1/8 5 5/8 5 7/8 5 1/8 5 5/8 5 7/8 5 1/8 5 5/8 5 7/8 5 1/2 7 1/4 5 7/8 5 1/2 7 1/4 5 7/8 SFC 400/21-3 4 / 5.5 9.5 6.8 5 1/2 7 1/4 5 7/8 SFC 750/21-3 7.5 / 10 17 14.3 7 1/16 9 1/8 6 11/16 ENCLOSURE CLASS IP 55 Designation Rated power kw / HP SFC 037/55-1 SFC 037/55-3 SFC 055/55-1 SFC 055/55-3 SFC 075/55-1 SFC 075/55-3 SFC 110/55-1 SFC 110/55-3 SFC 150/55-1 SFC 150/55-3 SFC 220/55-1 SFC 220/55-3 0.37 / 0.5 0.37 / 0.5 0.55 / 0.75 0.55 / 0.75 0.75 / 1 0.75 / 1 1.1 / 1.5 1.1 / 1.5 1.5 / 2 1.5 / 2 2.2 / 3 2.2 / 3 Rated current A 3.3 1.5 3.7 1.9 4.8 2.3 6.9 3 8 4.1 11 5.5 Input Voltage V 1-phase 3-phase Ouput Voltage V 3 phase Weight lb 13.8 13.8 13.8 23.5 23.5 Width inch Height inch Depth inch 8 1/4 8 7/16 9 7/6 11 11/16 6 7/16 7 9/16 8 1/4 9 7/6 6 7/16 8 7/16 11 11/16 7 9/16 8 1/4 9 7/6 6 7/16 8 7/16 11 11/16 7 9/16 8 7/16 11 11/16 7 9/16 8 7/16 11 11/16 7 9/16 8 7/16 11 11/16 7 9/16 8 7/16 11 11/16 7 9/16 9 1/16 13 3/8 8 3/16 9 1/16 13 3/8 8 3/16 SFC 400/55-3 4 / 5.5 9.5 23.5 9 1/16 13 3/8 8 3/16 SFC 750/55-3 7.5 / 10 17 52 12 5/8 16 3/4 11 7/16

SFC POT/VSS/SB SFC POT POTENTIOMETER The SFC POT is a potentiometer for a variable regulation of fan speed via frequency converters. Dimensions Resistance 3 15/16 x3 15/16 x2 5/8 inches. 10 k SFC VSS ROTARY SWITCH The SFC POT is a rotary switch for 2-step regulation of fan speeds via frequency converters. SFC POT Dimensions Increments 0-1-2 3 15/16 x3 15/16 x2 5/8 inches. SFC SB SWITCH SFC VSS The SFC SB is a switch for start/stop of fans via frequency converters. SFC SB Dimensions 2 3/8 x3 1/8 x2 3/16 inches. Enclosure class IP 54 Power supply Max 250 V, 16 A ST 300 ST 300 PRESSURE SENSOR The ST 300 maintains constant negative pressure in the discharge duct via a frequency converter that controls fan speeds. The ST 300 always provides the correct flow, regardless of the number of open and closed dampers. Dimensions 3 9/16x3 3/4x1 7/16 inches. Enclosure class IP 54 Operating range 2, 4, 8, 12 IN/WG Power supply 24 VDC Output signal 0-10 V (alt. 4-20 ma) Included accessories Measurement output and 7 feet hose

S 400 S 400 CONTROL UNIT The S 400 is used for automatic control of damper motor SAS 24 at terminals 1 4. Fans are normally controlled via the transformer s. The after-run time for evacuation of remaining gases is built into the control. The time is set between 0 15 min. The S 400 is supplied with 24 VAC from the transformer. Dimensions 5 1/8x3 1/8x3 1/16 inches Enclosure class IP 54 Primary side 24 VAC Secondary side 24 VAC ACCESSORIES for hose reel mounted on a hose reel, opens when the hose is pulled down and closes when the hose is fully rolled upp S 400 for balancing block, Single pole switch mounted on a balancing block. is opened when the hose is pulled down and closed when the hose is fully drawn up. Supplemented with an electrical cable attached on the trolley on the profile rail. with radio transmitter for profile rail Micro switch mounted on the balancing block. When the hose is pulled down the switch opens and a radiotransmitter sends a signal to a receiver that opens a relay. The switch is closed when the hose is fully drawn up. SMT 60 Mechanical timer switch, 1 h The SMT mechanical timer switch is a manual timer, adjustable from 0 to 60 minutes. It can replace a PR T / KHT push-button. The SMT 60 is wall-mounted close to the extractor. Dimensions 315/16x 315/16x 25/8 Timeset 0-60 min. SMT 60 S 400 Terminals 1-4 24 V~ For damper. 5-7 Potential-free VX-switch. 8-9 24 V~ supply from. 10-14 Connection sensor (15 V). SMT 60 1 2 3 4 5 6 7 8 9 10 11 12 1314 SAS

TRANSFORMER UNIT The is used to supply 24 VAC to the S 400 control. of fan is made via external contactor 115 VAC, via signal from terminals 1 & 2. Frequency converter is controlled via the potential-free outputs, terminals 3 and 4. The can also be used in a custom system with the SKD connection box. The SKD distributes power to dampers and to the switch for automatic start/stop of fans, as well as automatic opening of SAS dampers. Dimensions 5 1/8 x7 1/6 x4 1/16 inches. Enclosure class IP 54 Primary side 115 VAC Secondary side 24 VAC (60 VA) Terminals L1-N 115 V~ Main connection. 1-2 115 V~ Connection. 3-4 Potential-free VX-switch. 5-6 24 V~ Votage (SKD). 7-8 connection (SKD). L1 PE N 1 2 3 4 5 6 7 8 S 400 SFC

S 200/115 S 200/115-24 S 200/115 CONTROL UNIT S 200/115-24 CONTROL UNIT The S 200/115 is used for start/stop of fan. The after-run time for evacuation of remaining gases is built into the pliers sensor (~30 sec.). For longer after-run times, there is an adjustable timer card (0 15 min. and 0 240 min.) available as an accessory. Single-phase fans (max. 1 HP) can be directly controlled via an integrated relay. Other fans are controlled with an external contactor via the same integrated relay, terminals 1 5. Frequency converters are controlled via the potential-free output, terminals 6 8. Dimensions 7 1/16 x5 1/8 x3 1/16 inches Enclosure class IP 54 Primary side 115 VAC Secondary side 115 VAC (Max 10A) ACCESSORIES SMT 60 STK 15 STK 240 Mechanical timer switch, 1 h Timer card 0-15 min Timer card 0-240 min for hose reel for balancing block with radio transmitter for profile rail The S 200/24 is used for automatic control of damper motor SAS 24 and/or a fan. For longer after-run times, there is an adjustable timer card (0 15 min. and 0 240 min.) available as an accessory. Fans are controlled with external contactors via the integrated relay, terminals 1 5. Frequency converters are controlled via the potential-free output, terminals 6 8. Dimensions 7 1/16 x5 1/8 x3 1/16 inches Enclosure class IP 54 Primary side 115 VAC Secondary side 24 VAC ACCESSORIES SMT 60 STK 15 STK 240 Mechanical timer switch, 1 h Timer card 0-15 min Timer card 0-240 min for hose reel for balancing block with radio transmitter for profile rail S 200/115 S 200/115-24 STK 15 STK 240 S 200/115 S 200/115-24 1 2 3 4 5 6 7 8 9 1011 121314 1 2 3 4 5 6 7 8 9 1011 121314 SAS SAS Terminals 1-5 115 V~. 6-8 Potential-free VX switch. 9-11 115 V~ Main connection. 12-14 Connection sensor (15 V). SMT 60 Terminals 1-5 24 V~ For damper. 6-8 Potential-free VX-switch. 9-11 115 V~ Main connection. SMT 60 12-14 Connection sensor (15 V).

SMB SMB PROTECTIVE MOTOR SWITCH The SMB is a 3-pole protective motor switch with thermal-magnetic release and equipped with phase failure protection. The SMB is designed for control and protection of fan motors. Dimensions 3 11/16 x5 13/16 x3 5/16 inches Enclosure class IP 55 Product Current 3-phase range ~ V (A) (HP) SMB 10* 0,63-1,0 0.37 SMB 16* 1,0-1,6 0.5/0.75 SMB 25* 1,6-2,5 1 SMB 40* 2,5-4,0 1.5 / 2.0 SMB 63* 4,0-6,3 3.0 SMB 100* 6,0-10,0 5.5 SMB 140** 9,0-14,0 7.5 SMB 180** 13,0-18, 10 *Self-protecting, pre-fusing not required **Max. pre-fusing when Ik>Icu is 63 A. CONTACTOR The is a 3-pole contactor with an overcurrent relay for manual resetting. The overcurrent relay has phase failure protection. It is used with external switches or control. Dimensions 4 1/16 x7 7/8 x6 inches Enclosure class IP 55 Product Current 3-phase range ~ V (A) (HP) 10/* 0,63-1,0 0.37 17/* 1,0-1,6 0.5/0,75 25/* 1,6-2,5 1 40/* 2,5-4,0 1.5/2.0 60/* 4,0-6,3 3.0 80/* 6,0-10,0 5.5 130/** 9,0-14,0 7.5 180/** 13,0-18, 10 * Maximum power is 4 HP. **Maximum power is 13 HP.

SAS 20150924 ~ 24 V SAS AUTOMATIC DAMPER The SAS is an automatic single-leaf damper for applications where short operating times are necessary. The extremely fast motor opens the damper blade in 7.5 seconds. This entails 95% extraction capacity after 3 seconds. The damper is supplied for air tightness class 1. For other air tightness classes, please contact Movex. Dimensions (motor) 5 1/2 x3 15/16 x3 3/8 Material (cowling) PA Material (damper housing) Galvanised sheet metal Opening time, 90º 7,5 s Torque 3 Nm Power consumption (24 V) 2 VA in operation/ 0 VA not in operation Power consumption ( V) 5 VA in operation/ 0 VA not in operation Product Diameter Voltage (inch) (V) SAS-100/24 Ø3 15/16 24 SAS-125/24 Ø4 15/16 24 SAS-160/24 Ø6 5/16 24 SAS-200/24 Ø7 7/8 24 SAS-250/24 Ø9 13/16 24 SAS-315/24 Ø12 3/8 24 104 Commerce Drive, Northampton, PA 18067, USA Phone: 610 440-0478, Fax: 610 440-0480 www.movexinc.com info@movexinc.com