FORM 150.67-EG1(1017) MODEL YCAL AIR-COOLED SCROLL CHILLERS WITH BRAZED PLATE HEAT EXCHANGERS STYLE E 15 65 TON 53 218 kw 50 and 60 Hz R-410A
Nomenclature Y C A L 033 E E 46 X E DESIGN SERIES FOUR DIGIT UNIT NUMBER X = ACROSS THE LINE A = AIR COOLED A = AMERICAS L = SCROLL COMPRESSOR VOLTAGE CODE: 17 = 200-3-60 28 = 230-3-60 40 = 380-3-60 46 = 460-3-60 58 = 575-3-60 REFRIGERANT = R-410a Y = YORK CHILLER E = HIGH EFFICIENCY Approvals ASME Boiler and Pressure Vessel Code Section Vlll Division 1. AHRI Standard 550/590 and 551/591. UL 1995 Heating and Cooling Equipment ASHRAE 15 Safety Code for Mechanical Refrigeration ASHRAE Guideline 3 Reducing Emission of Halogenated Refrigerants in Refrigeration and Air-Conditioning Equipment and Systems N.E.C. National Electrical Code OSHA Occupational Safety and Health Act 2 JOHNSON CONTROLS
Table Of Contents FORM 150.67-EG1 (1017) INTRODUCTION... 5 MICROCOMPUTER CONTROL CENTER... 7 ACCESSORIES AND OPTIONS... 10 SELECTION DATA... 13 DESIGN PARAMETERS... 17 WATER PRESSURE DROP... 18 RATINGS... 20 PHYSICAL DATA AND NOMINAL RATINGS... 40 PART LOAD RATINGS... 42 UNIT DIMENSIONS... 44 ISOLATOR DETAILS... 80 ELECTRICAL DATA - 50 & 60HZ... 84 ELECTRICAL NOTES... 87 CIRCUIT BREAKER CALCULATIONS... 89 POWER WIRING - SINGLE CIRCUIT... 90 CONTROL WIRING... 94 APPLICATION DATA... 95 GUIDE SPECIFICATIONS... 98 Performance data provided in this document was created in accordance with Johnson Controls software: YORKworks version 13.02 and DXCHILL version 6.04 JOHNSON CONTROLS 3
THIS PAGE INTENTIONALLY LEFT BLANK. 4 JOHNSON CONTROLS
Introduction FORM 150.67-EG1 (1017) YORK Air-Cooled Scroll Chillers provide chilled water for all air conditioning applications using central station air handling or terminal units. They are completely self-contained and are designed for outdoor (roof or ground level) installation. Each unit includes hermetic scroll compressors, a liquid cooler, air cooled condenser, a charge of refrigerant R-410A, and a weather resistant microprocessor control center, all mounted on a rugged, formedsteel base. GENERAL The 15-65 Ton (53-218 kw) YCAL models are shipped complete from the factory ready for installation and use. The unit is pressure-tested, evacuated, and fully charged with R-410A and includes an initial oil charge. After assembly, a complete operational test is performed with water flowing through the cooler to assure that the refrigeration circuit operates correctly. The unit structure is heavy-gauge, galvanized steel. The steel is coated with baked-on powder paint, which, when subjected to ASTM B117 1000 hour, salt spray testing, yields a minimum ASTM 1654 rating of 6. Corrosion resistant wire mesh panels are added to protect the condenser coil from incidental damage and restrict unauthorized access to internal components. Unit also includes service isolation valves as standard. Units are designed in accordance with NFPA 70 (National Electric Code), ASHRAE/ANSI 15 Safety code for mechanical refrigeration, ASME, Listed and labeled with Intertek Testing Services (ETL) and rated in accordance with the latest version of ARI Standard 550/590. COMPRESSORS The chiller has suction-gas cooled, hermetic, scroll compressors. The compressors incorporate a scroll design that is compliant in both the axial and radial direction. All rotating parts are statically and dynamically balanced. A large internal volume and oil reservoir provides greater liquid tolerance. Compressor crankcase heaters are also included for extra protection against liquid migration. COOLER Brazed plate heat exchangers are UL (Underwriters Laboratories) listed. Installing contractor must include accommodations in the chilled water piping to allow proper drainage and venting of the heat exchanger. Water inlet and outlet connections are grooved for compatibility with factory supplied ANSI/AWWA C-606 connections. The cooler is equipped with a heater controlled by a separate thermostat. The heater provides freeze protection for the cooler down to -20 F (-29 C) ambient. The cooler is covered with 3/4 (19mm) flexible, closed-cell, foam insulation (K 0.25). A 40 mesh strainer (0.5 and 1.5 mm) is recommended upstream of the heat exchanger to prevent clogging. JOHNSON CONTROLS 5
Introduction (Cont'd) CONDENSER Coils Fin and tube condenser coils of seamless, internally-enhanced, high-condensingcoefficient, corrosion resistant copper tubes are arranged in staggered rows, mechanically expanded into aluminum fins. Integral subcooling is included. The design working pressure of the coil is 650 PSIG (45 barg). Low Sound Fans The condenser fans are composed of corrosion resistant aluminum hub and composite blades molded into a low noise airfoil section. They are designed for maximum efficiency and are statically and dynamically balanced for vibration-free operation. They are directly driven, and positioned for vertical air discharge. The fan guards are constructed of heavy-gauge, rust-resistant, PVC (polyvinyl chloride)-coated steel wire. Motors The fan motors are Totally Enclosed Air-Over, squirrel-cage type, current protected. They feature ball bearings that are double-sealed and permanently lubricated. AHRI CERTIFICATION PROGRAM YORK YCAL chillers have been tested and certified by Air-Conditioning, Heating and Refrigeration Institute (AHRI) in accordance with the latest edition of AHRI Standard 550/590 (I-P). Under this Certification Program, chillers are regularly tested in strict compliance with this Standard. This provides an independent, third-party verification of chiller performance. Refer to the AHRI site at: http://www.ahrinet.org/ for complete Program Scope, Inclusions, and Exclusions as some options listed herein fall outside the scope of the AHRI certification program. For verification of certification, go to the AHRI Directory at www.ahridirectory.org. Rated in accordance with the latest issuance of AHRI Standard 550/590 and 551/591. 6 JOHNSON CONTROLS
MicroComputer Control Center FORM 150.67-EG1 (1017) All controls are contained in a NEMA 3R powder painted steel cabinet with a gasketed door and include: Liquid Crystal Display (LCD) with Light Emitting Diode (LED) backlighting for outdoor viewing: Two display lines Twenty characters per line Color coded 12-button non-tactile keypad with sections for: DISPLAY/PRINT of typical information: Chilled liquid temperatures Ambient temperature System pressures (each circuit) Operating hours and starts (each compressor) Print calls up to the liquid crystal display: Operating data for the systems History of fault shutdown data for up to the last six fault shutdown conditions An RS-232 port, in conjunction with this press-to-print button, is provided to permit the capability of hard copy print-outs via a separate printer (by others). ENTRY section to ENTER setpoints or modify system values SETPOINTS updating can be performed to Chilled liquid temperature setpoint and range Remote reset temperature range Set daily schedule/holiday for start/stop Manual override for servicing Low and high ambient cutouts Number of compressors Low liquid temperature cutout Low suction pressure cutout JOHNSON CONTROLS 7
MicroComputer Control Center (Cont'd) High discharge pressure cutout Anti-recycle timer (compressor start cycle time) nti-coincident timer (delay compressor starts) UNIT section to: Set time Set unit options UNIT ON/OFF switch The microprocessor control center is capable of displaying the following: Return and leaving liquid temperature Low leaving liquid temperature cutout setting Low ambient temperature cutout setting Outdoor air temperature English or Metric data Suction pressure cutout setting Each system suction pressure Discharge pressure (optional) Liquid Temperature Reset via a Johnson Controls ISN DDC or Building Automation System (by others) via: a pulse width modulated (PWM) input as standard a 4-20 milliamp or 0-10 VDC input, or contact closure with the optional B.A.S. interface option Anti-recycle timer status for each system Anti-coincident system start timer condition Compressor run status No cooling load condition Day, date and time Daily start/stop times Holiday status Automatic or manual system lead/lag control Lead system definition 8 JOHNSON CONTROLS
MicroComputer Control Center (Cont'd) FORM 150.67-EG1 (1017) Compressor starts & operating hours (each compressor) Status of hot gas valves, evaporator heater and fan operation Run permissive status Number of compressors running Liquid solenoid valve status Load & unload timer status Water pump status JOHNSON CONTROLS 9
Accessories and Options All accessories and options are factory mounted unless otherwise noted. ELECTRICAL OPTIONS Single-Point Supply Terminal Block Standard. Includes enclosure, terminal-block and interconnecting wiring to the compressors. Separate external protection must be supplied, by others, in the incoming compressor-power wiring. (Do not include this option if either the SinglePoint NonFused Disconnect Switch or Single-Point Circuit Breaker options have been included.) Single-Point Non-Fused Disconnect Switch Unit-mounted disconnect switch with external, lockable handle (in compliance with Article 440-14 of N.E.C.), can be supplied to isolate the unit power voltage for servicing. Separate external fusing must be supplied, by others in the power wiring, which must comply with the National Electrical Code and/ or local codes. Single-Point Circuit Breaker A unit mounted circuit breaker with external, lockable handle (in compliance with N.E.C. Article 440-14), can be supplied to isolate the power voltage for servicing. (This option includes the Single-Point Power connection.) Control Transformer Converts unit power voltage to 115-1-60 or 115-1-50 if 50Hz is selected (0.5 or 1.0 KVA capacity). Factory mounting includes primary and secondary wiring between the transformer and the control panel. Power Factor Correction Capacitors Will correct unit compressor power factors to 0.90-0.95. CONTROL OPTIONS Ambient Kit (Low) Standard units will operate to 25 F (-4 C). This accessory includes all necessary components to permit chiller operation to 0 F (-18 C). (This option includes the Discharge Pressure Transducer/Readout Capability option.) For proper head pressure control in applications below 25 F (-4 C), where wind gusts may exceed five mph, it is recommended that Optional Condenser Louvered Enclosure Panels also be included. Ambient Kit (High) Required if units are to operate when the ambient temperature is above 110 F (43 C). Includes discharge pressure transducers. (This option includes the Discharge Pressure Transducer / ReadoutCapability option.) (Field-Mounted.) Language LCD And Keypad Display Spanish, French, and German unit LCD controls and keypad display available. Standard language is English. Discharge Pressure Transducers And Readout Capability The addition of pressure transducers allows models to sense and display discharge pressure. This is recommended for glycol chilling applications. (This option is included with either the low or high ambient kits.) Suction Pressure Transducers Permits unit to sense and display suction pressure. This capability is standard. 10 JOHNSON CONTROLS
Accessories and Options (Cont'd) FORM 150.67-EG1 (1017) Motor Current Module Capable of monitoring compressor motor current. Provides extra protection against compressor reverse rotation, phase-loss and phase imbalance. Option consists of one module per electrical system. COMPRESSOR, PIPING, EVAPORATOR OPTIONS Low Temperature Glycol Required for glycol chilling below 30 F (-1 C) leaving glycol temperature. Option includes resized thermal expansion valve. Chicago Code Relief Valves Unit will be provided with relief valves to meet Chicago code requirements. Service Isolation Valve Service isolation valves are standard to unit. This includes a system high pressure relief valve or internal compressor relief mechanism in compliance with ASHRAE 15. Hot Gas By-Pass Permits continuous, stable operation at capacities below the minimum step of compressor unloading to as low as 5% capacity (depending on both the unit and operating conditions) by introducing an artificial load on the cooler. Hot gas by-pass is installed on only refrigerant system #1 on two-circuit units. DX Cooler 300 PSIG (21 barg) Dwp Waterside The waterside will be rated to 300 PSIG (21 barg) instead of the standard 150 PSIG DWP. 300 PSIG R.F. flanges are included on the DX cooler nozzles. The companion flanges will be field-supplied by others. Flanges (ANSI/AWWA C-606 couplings Type) Consists of two (2) Flange adapters for grooved end pipe (standard 150 psi [10.5 barg] cooler). Flow Switch The flow switch or its equivalent must be furnished with each unit. 150 PSIG (10.5 barg) DWP For standard units. Johnson Controls model F61MG-1C vaporproof SPDT, NEMA 4X switch (150 PSIG [10.5 barg] DWP), -20 F to 250 F (-29 C to 121 C), with 1 NPT connection for upright mounting in horizontal pipe. (Field-mounted.) 300 PSIG (21 barg) DWP For units with optional 300 PSIG (21 barg) DX cooler. McDonnell & Miller model FS74W vaporproof SPDT, NEMA 4X switch (300 PSIG (21 barg) DWP), -20 F to 300 F (-29 C to 149 C), with 1¼ inch MPT connection for upright mounting in horizontal pipe. (Field-mounted.) Differential Pressure Switch Alternative to an above mentioned flow switch. Pretempco model DPS300AP40PF-82582-5 (300 PSIG [21 barg] max. working pressure), SPDT 5 amp 125/250VAC switch, Range 3-45 PSIG (0.2-3 barg), deadband 0.5-0.8 psi (0.003-0.005 barg), with 1/4 NPTE Pressure Connections. CONDENSER AND CABINET OPTIONS Condenser coil protection against corrosive environments is available by choosing any of the following options. For additional application recommendations, contact your local Johnson Controls office. Pre-Coated Fin Condenser Coils The unit's coils are constructed with epoxy coated aluminum fins. This can provide corrosion resistance comparable to copper-fin coils in typical seashore locations. Either these or the post-coated coils (below), are recommended for units being installed at the seashore or where salt spray may hit the unit. JOHNSON CONTROLS 11
Accessories and Options (Cont'd) Post-Coated Dipped Condenser Coils The unit's coils are constructed with dippedcured condenser coils. This is the choice for corrosive applications (with the exception of strong alkalies, oxidizers and wet bromine, chlorine and fluorine in concentrations greater than 100 ppm). Copper Fin Condenser Coils The unit coils are constructed with copper fins. (This is not recommended for units in areas where they may be exposed to acid rain.) Enclosure Panels (Unit) Tamperproof enclosure panels prevent unauthorized access to units. Enclosure panels can provide an aesthetically pleasing alternative to expensive fencing. Louvered Panels (Full Unit) Louvered panels surround the front, back, and sides of the unit. They prevent unauthorized access and visually screen unit components. Unrestricted air flow is permitted through generously sized louvered openings. This option is applicable for any outdoor design ambient temperature up to 115 F (46 C). Recommended for use with the Low Ambient kit where wind gusts may exceed five mph (eight kph). Sound Attenuation One or both of the following sound attenuation options are recommended for residential or other similar sound-sensitive locations. Compressor Acoustic Sound Blanket Each compressor is individually enclosed by an acoustic sound blanket. The sound blankets are made with one layer of acoustical absorbent textile fiber of 5/8 (15mm) thickness; one layer of anti-vibrating heavy material thickness of 1/8 (3mm). Both are closed by two sheets of welded PVC, reinforced for temperature and UV resistance. Ultra Quiet Fans Lower RPM, eight-pole fan motors are used with steeper-pitch fans. Vibration Isolators Level adjusting, spring type 1 (25.4mm) or 2" deflection or neoprene pad isolators for mounting under unit base rails. (Field-mounted.) 12 JOHNSON CONTROLS
Selection Data FORM 150.67-EG1 (1017) GUIDE TO SELECTION Capacity ratings for the YCAL Packaged Air-Cooled Liquid Chillers, shown on pages 16 through 48 cover the majority of design applications for these units. For unusual applications or uses beyond the scope of this catalog, please consult your nearest Johnson Controls Office or sales representative. SELECTION RULES 1. Ratings Ratings may be interpolated, but must not be extrapolated. The Ratings on page 20 and the Design Parameters on page 17 indicate the limits of application for these chillers. 2. Cooler Water Ratings are based upon 2.4 GPM per ton which is equal to a 10 F chilled water range and a 0.0001 fouling factor for the cooler at sea level. Tables on pages 20 through 28 give capacity, compressor kw required, cooler GPM and unit EER. 3. Condenser Ratings are given in terms of air on condenser in degrees Fahrenheit. 4. Copper Fin Condenser Ratings Since the thermal conductivity of copper is slightly higher than aluminum, apply the following corrections to the standard ratings. Tons x 0.97 and compressor kw x 0.99. 5. Performance Data Correction Factors Ratings are based on 0.0001 cooler fouling factor, 10 F chilled water range and at sea level. For operation at different conditions, apply the appropriate correction factor from the following table. ALTITUDE SEA LEVEL 2000 FT. 4000 FT. 6000 FT. TEMP SPLIT FOULING FACTOR 0.0001 0.0003 TONS COMPR KW TONS COMPR KW 8 0.990 0.998 0.979 0.996 10 1.000 1.000 0.991 0.998 12 1.012 1.003 1.002 1.001 14 1.021 1.005 1.012 1.003 8 0.987 1.005 0.978 1.003 10 0.997 1.008 0.988 1.006 12 1.009 1.010 1.000 1.008 14 1.018 1.012 1.009 1.010 8 0.983 1.014 0.975 1.012 10 0.994 1.016 0.985 1.014 12 1.005 1.019 1.111 1.017 14 1.014 1.021 1.006 1.019 8 0.980 1.023 0.971 1.021 10 0.990 1.025 0.982 1.023 12 1.002 1.028 0.993 1.026 14 1.011 1.030 1.002 1.028 JOHNSON CONTROLS 13
Selection Data (Cont'd) 6. Ethylene Glycol Correction Factors The following factors are to be applied to the standard ratings for units cooling ethylene glycol. ETHYLENE GLYCOL %WEIGHT TONS COMPR KW GPM PRESS FREEZE DROP POINT 10 0.996 0.999 24.300 1.014 26.2 20 0.991 0.998 25.100 1.104 17.9 30 0.984 0.997 25.900 1.234 6.7 40 0.976 0.995 26.900 1.399-8.1 50 0.968 0.994 28.000 1.599-28.9 7. Propylene Glycol Correction Factors the following factors are to be applied to the standard ratings for units cooling propylene glycol. PROPYLENE GLYCOL %WEIGHT TONS COMPR KW GPM PRESS FREEZE DROP POINT 10 0.995 0.999 24.000 1.049 26 20 0.984 0.997 24.300 1.124 19 30 0.973 0.994 24.900 1.258 9 40 0.960 0.992 25.600 1.430-6 50 0.943 0.989 26.600 1.650-28 METHOD OF SELECTION To select a YORK Packaged Air-Cooled Liquid Chiller, the following data must be known: 1. Design Capacity in tons refrigeration (TR). 2. Entering and Leaving Liquid Temperatures. 3. Outside ambient air temperature in F. 4. GPM of chilled liquid. Determine capacity requirements from the following formula: GPM = TR x 24 RANGE( F) EXAMPLE WATER CHILLING 1. Given: Provide a capacity of 50 tons at 42 F leaving water at 10 F range. 0.0001FF, 85 F air on the condenser, at sea level and 60 Hz. 2. Find: Unit Size, Compressor KW Output 3. From the ratings on page 18. 4. SELECT: YCAL0056(English Units) a. 54.4 Tons b. 51.8 Compressor KW c. 11.1 Unit EER 14 JOHNSON CONTROLS
Selection Data (Cont'd) FORM 150.67-EG1 (1017) 5. Calculate Compressor kw at 50 Tons: kw = 50 x 51.8kW =47.6kW 54.4 6. Calculate GPM: GPM = (50 Tons)x 24 =120GPM 10 F Range 7. From page 16, read 6 ft of water cooler pressure drop from GPM: 16 A YCAL0056 is suitable. EXAMPLE - BRINE CHILLING Example - Brine Chilling 1. Given: Provide a capacity of 34 tons cooling 30% by weight Ethylene Glycol from 50 F to 40 F, 0.00025FF, 95 F air on the condenser, 60 Hz and 4000 ft. altitude. 2. 2. Determine: a. Unit Size b. KW Input c. Ethylene Glycol GPM d. Cooler Pressure Drop 3. See Ethylene Glycol Correction Factors, for 30% by weight ethylene glycol. READ: 0.984 Tons Factor 0.997 Compr. KW factor 26.1 Gal/ F/Tons Factor 4. See Performance Data Correction Factors for 0.00025 fouling factor and 4,000 ft. altitude. READ: 0.975 Tons factor 1.012 kw factor 5. From RATINGS on page 16. SELECT: YCAL0046 (English Units) 35.3 Tons 41.1 Compressor kw 6. Determine YCAL0046 glycol cooling capacity and Compressor kw requirement from pg 18: a. ONS: = 35.3 x 0.984 x 0.975 = 33.87 b. Compr. KW = 41.1 x 0.997 x 1.012 = 41.77 JOHNSON CONTROLS 15
Selection Data (Cont'd) 7. Determine average full load Compressor kw at 34 tons: 34 Tons x (41.77) =41.93 Compressor kw 33.87 Tons 8. 8. Determine E.G. GPM: GPM = Tons x Gal F / min/ Ton Factor RANGE 9. Determine Cooler Pressure Drop: a. See Ethylene Glycol Correction Factors for 30% by weight ethylene glycol. READ: 1.258 Pressure Drop factor b. See page 14 at 88.7 GPM for YCAL0046 READ: 3.0 Water PD c. Cooler Pressure Drop = 3.0 x 1.258 or 3.77 ft. 10. A YCAL0046 is suitable. 16 JOHNSON CONTROLS
Design Parameters FORM 150.67-EG1 (1017) ENGLISH YCAL LEAVING WATER TEMPERATURE ( F) COOLER FLOW (GPM) AIR ON CONDENSER ( F) MIN MAX MIN MAX MIN MAX 0019EE 40 55 10 150 0 125 0022EE 40 55 10 150 0 125 0028EE 40 55 10 150 0 125 0033EE 40 55 10 150 0 125 0043EE 40 55 40 200 0 125 0046EE 40 55 40 200 0 125 0052EE 40 55 60 300 0 125 0056EE 40 55 60 300 0 125 0066EE 40 55 60 300 0 125 SI UNITS YCAL LEAVING WATER TEMPERATURE ( C) COOLER FLOW (L/S) AIR ON CONDENSER ( C) MIN MAX MIN MAX MIN MAX 0019EE 4.4 12.8 0.6 9.5-17.7 51.7 0022EE 4.4 12.8 0.6 9.5-17.7 51.7 0028EE 4.4 12.8 0.6 9.5-17.7 51.7 0033EE 4.4 12.8 0.6 9.5-17.7 51.7 0043EE 4.4 12.8 2.5 12.6-17.7 51.7 0046EE 4.4 12.8 2.5 12.6-17.7 51.7 0052EE 4.4 12.8 3.8 18.9-17.7 51.7 0056EE 4.4 12.8 3.8 18.9-17.7 51.7 0066EE 4.4 12.8 3.8 18.9-17.7 51.7 NOTES: 1. For leaving brine temperature below 40 F (4.4 C), contact your nearest Johnson Controls Office for application requirements. 2. For leaving water temperature higher than 55 F (12.8 C), contact the nearest Johnson Controls Office for application guidelines. 3. The evaporator is protected against freezing to -20 F (-28.8 C) with an electric heater as standard. 4. For operation at temperatures below 25 F (-3.9 C), the optional Low Ambient Kit will need to be installed on the system (for YCAL0043-0065 models only). 5. For operation at temperatures above 115 F (46.1 C), the optional High Ambient Kit will need to be installed on the system. JOHNSON CONTROLS 17
Water Pressure Drop 100 YCAL EVAPORATOR PRESSURE DROP CURVE WATER PRESSURE DROP (PSI) 10 A B C D E 1 0 50 100 150 200 250 WATER FLOW RATE (GPM) LD18667 EVAPORATOR CURVE A B B B C D C D E CHILLER MODEL YCAL0019EE YCAL0022EE YCAL0028EE YCAL0033EE YCAL0043EE YCAL0046EE YCAL0052EE YCAL0056EE YCAL0066EE 18 JOHNSON CONTROLS
Water Pressure Drop (Cont'd) FORM 150.67-EG1 (1017) YCAL EVAPORATOR PRESSURE DROP CURVE 100 WATER PRESSURE DROP (kpa) 10 A B C D E 1 0 2 4 6 8 10 12 14 16 WATER FLOW RATE (l/s) LD18668 EVAPORATOR CURVE A B B B C D C D E CHILLER MODEL YCAL0019EE YCAL0022EE YCAL0028EE YCAL0033EE YCAL0043EE YCAL0046EE YCAL0052EE YCAL0056EE YCAL0066EE JOHNSON CONTROLS 19
Ratings R-410A (60HZ) ENGLISH MODEL: YCAL0019EE IPLV = 14.6 AIR TEMPERATURE ON CONDENSER ( F) LCWT 75.0 80.0 85.0 90.0 95.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 16.2 13.6 13.3 15.8 14.4 12.3 15.3 15.3 11.3 14.9 16.3 10.3 14.4 17.3 9.5 42.0 16.7 13.7 13.6 16.3 14.6 12.6 15.9 15.5 11.6 15.4 16.4 10.6 14.9 17.4 9.7 44.0 17.3 13.9 14.0 16.8 14.7 12.9 16.4 15.6 11.9 15.9 16.6 10.9 15.4 17.6 10.0 45.0 17.6 13.9 14.1 17.1 14.8 13.0 16.7 15.7 12.0 16.2 16.6 11.0 15.7 17.6 10.1 46.0 17.8 14.0 14.3 17.4 14.8 13.2 16.9 15.7 12.1 16.5 16.7 11.2 16.0 17.7 10.2 48.0 18.4 14.1 14.6 18.0 15.0 13.5 17.5 15.9 12.4 17.0 16.8 11.4 16.5 17.9 10.5 50.0 19.0 14.3 14.9 18.5 15.1 13.8 18.0 16.0 12.7 17.5 17.0 11.7 17.0 18.0 10.7 MODEL: YCAL0022EE IPLV = 15.5 AIR TEMPERATURE ON CONDENSER ( F) LCWT 75.0 80.0 85.0 90.0 95.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 19.9 16.7 13.5 19.4 17.6 12.5 18.8 18.7 11.4 18.1 19.9 10.4 17.5 21.1 9.5 42.0 20.6 16.8 13.8 20.0 17.8 12.8 19.4 18.9 11.7 18.7 20.0 10.7 18.1 21.3 9.7 44.0 21.2 17.0 14.2 20.7 18.0 13.1 20.0 19.1 12.0 19.4 20.2 11.0 18.7 21.5 10.0 45.0 21.6 17.1 14.3 21.0 18.1 13.2 20.4 19.2 12.1 19.7 20.3 11.1 19.0 21.6 10.1 46.0 21.9 17.2 14.5 21.3 18.2 13.3 20.7 19.3 12.3 20.0 20.4 11.2 19.3 21.7 10.2 48.0 22.6 17.4 14.8 22.0 18.4 13.6 21.4 19.4 12.5 20.7 20.6 11.5 20.0 21.9 10.5 50.0 23.3 17.5 15.1 22.7 18.6 13.9 22.0 19.6 12.8 21.3 20.8 11.7 20.6 22.1 10.7 MODEL: YCAL0028EE IPLV = 13.4 AIR TEMPERATURE ON CONDENSER ( F) LCWT 75.0 80.0 85.0 90.0 95.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 26.5 22.0 12.8 25.9 23.1 11.9 25.3 24.3 11.1 24.6 25.6 10.3 23.9 27.1 9.5 42.0 27.4 22.2 13.1 26.8 23.3 12.2 26.1 24.5 11.4 25.5 25.8 10.6 24.7 27.3 9.8 44.0 28.4 22.4 13.4 27.7 23.5 12.5 27.0 24.7 11.7 26.3 26.1 10.9 25.6 27.5 10.1 45.0 28.8 22.5 13.6 28.2 23.6 12.7 27.5 24.9 11.8 26.8 26.2 11.0 26.0 27.6 10.2 46.0 29.3 22.6 13.7 28.6 23.7 12.9 27.9 25.0 12.0 27.2 26.3 11.1 26.4 27.7 10.3 48.0 30.3 22.8 14.1 29.6 24.0 13.2 28.8 25.2 12.3 28.1 26.5 11.4 27.3 27.9 10.6 50.0 31.3 23.1 14.4 30.5 24.2 13.5 29.8 25.4 12.6 29.0 26.8 11.7 28.2 28.2 10.9 NOTES: 1. kw = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kw) 3. LCWT = Leaving Chilled Water Temperature 4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with the latest version of ARI Standard 550/590 6. The shaded points are certified in accordance with the latest version of ARI Standard 550/590 20 JOHNSON CONTROLS
Ratings (Cont'd) FORM 150.67-EG1 (1017) R-410A (60HZ) ENGLISH MODEL: YCAL0019EE IPLV = 14.6 AIR TEMPERATURE ON CONDENSER ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 14.0 18.4 8.6 13.5 19.6 7.8 13.0 20.9 7.1 12.4 22.2 6.4 6.6 10.2 7.0 6.3 10.9 6.4 42.0 14.5 18.5 8.9 13.9 19.7 8.1 13.4 21.0 7.3 12.9 22.3 6.6 6.8 10.2 7.3 6.5 10.9 6.6 44.0 14.9 18.7 9.1 14.4 19.9 8.3 13.9 21.1 7.5 13.3 22.4 6.8 7.1 10.3 7.6 6.8 10.9 6.8 45.0 15.2 18.7 9.2 14.7 19.9 8.4 14.1 21.2 7.6 13.5 22.5 6.9 7.2 10.3 7.7 6.9 10.9 7.0 46.0 15.4 18.8 9.4 14.9 20.0 8.5 14.3 21.2 7.7 13.8 22.6 7.0 7.3 10.3 7.8 7.0 10.9 7.1 48.0 15.9 19.0 9.6 15.4 20.1 8.7 14.8 21.4 8.0 7.9 9.7 8.9 7.6 10.3 8.1 7.3 11.0 7.3 50.0 16.5 19.1 9.8 15.9 20.3 9.0 15.3 21.5 8.2 8.2 9.7 9.2 7.9 10.4 8.3 7.6 11.0 7.6 MODEL: YCAL0022EE IPLV = 15.5 AIR TEMPERATURE ON CONDENSER ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 16.8 22.4 8.6 16.1 23.9 7.8 15.4 25.4 7.0 14.7 27.0 6.3 7.9 12.2 7.1 7.5 13.0 6.4 42.0 17.4 22.6 8.8 16.7 24.1 8.0 16.0 25.6 7.2 8.6 11.5 8.2 8.2 12.3 7.4 7.8 13.1 6.6 44.0 18.0 22.8 9.1 17.3 24.2 8.2 16.5 25.8 7.4 8.9 11.6 8.5 8.5 12.3 7.7 8.1 13.1 6.9 45.0 18.3 22.9 9.2 17.6 24.3 8.3 16.8 25.9 7.5 9.1 11.6 8.6 8.7 12.4 7.8 8.2 13.1 7.0 46.0 18.6 23.0 9.3 17.9 24.4 8.4 17.1 25.9 7.6 9.2 11.6 8.8 8.8 12.4 7.9 8.4 13.2 7.1 48.0 19.2 23.2 9.5 18.5 24.6 8.6 17.7 26.1 7.8 9.6 11.7 9.1 9.2 12.4 8.2 8.7 13.2 7.4 50.0 19.9 23.4 9.8 19.1 24.9 8.9 18.3 26.4 8.0 9.9 11.7 9.3 9.5 12.5 8.4 MODEL: YCAL0028EE IPLV = 13.4 AIR TEMPERATURE ON CONDENSER ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 23.2 28.6 8.8 22.4 30.2 8.1 21.6 31.9 7.4 20.8 33.7 6.8 19.9 35.7 6.2 11.0 18.5 6.1 42.0 24.0 28.8 9.1 23.2 30.4 8.3 22.4 32.1 7.7 21.5 33.9 7.0 20.6 35.9 6.4 11.5 18.6 6.4 44.0 24.8 29.0 9.3 24.0 30.6 8.6 23.1 32.3 7.9 22.3 34.1 7.2 21.3 36.1 6.6 11.9 18.7 6.6 45.0 25.2 29.1 9.4 24.4 30.7 8.7 23.5 32.4 8.0 22.6 34.2 7.3 21.7 36.2 6.7 12.1 18.7 6.7 46.0 25.6 29.2 9.6 24.8 30.8 8.8 23.9 32.5 8.1 23.0 34.3 7.4 22.1 36.3 6.7 12.3 18.8 6.8 48.0 26.5 29.4 9.8 25.6 31.0 9.0 24.7 32.7 8.3 23.8 34.6 7.6 22.8 36.5 6.9 12.8 18.9 7.0 50.0 27.4 29.7 10.0 26.5 31.3 9.3 25.6 33.0 8.5 24.6 34.8 7.8 23.6 36.7 7.1 13.2 19.0 7.2 NOTES: 1. kw = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kw) 3. LCWT = Leaving Chilled Water Temperature 4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with the latest version of ARI Standard 550/590 6. The shaded points are certified in accordance with the latest version of ARI Standard 550/590 JOHNSON CONTROLS 21
Ratings (Cont'd) R-410A (60HZ) ENGLISH MODEL: YCAL0033EE IPLV = 14.5 AIR TEMPERATURE ON CONDENSER ( F) LCWT 75.0 80.0 85.0 90.0 95.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 29.7 23.8 13.3 29.0 25.0 12.4 28.3 26.3 11.6 27.5 27.7 10.8 26.7 29.2 10.0 42.0 30.7 24.0 13.6 30.0 25.2 12.8 29.2 26.5 11.9 28.5 27.9 11.1 27.6 29.4 10.2 44.0 31.7 24.2 14.0 31.0 25.4 13.1 30.2 26.7 12.2 29.4 28.1 11.3 28.6 29.6 10.5 45.0 32.2 24.4 14.1 31.5 25.6 13.2 30.7 26.9 12.3 29.9 28.3 11.5 29.0 29.8 10.6 46.0 32.7 24.5 14.3 32.0 25.7 13.4 31.2 27.0 12.5 30.4 28.4 11.6 29.5 29.9 10.8 48.0 33.7 24.8 14.6 33.0 26.0 13.7 32.2 27.3 12.8 31.4 28.7 11.9 30.5 30.2 11.0 50.0 34.8 25.1 14.9 34.0 26.3 14.0 33.2 27.6 13.0 32.3 29.0 12.1 31.4 30.5 11.3 MODEL: YCAL0043EE IPLV = 14.5 AIR TEMPERATURE ON CONDENSER ( F) LCWT 75.0 80.0 85.0 90.0 95.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 38.7 30.8 12.8 37.8 32.3 11.9 36.8 34.1 11.1 35.7 36.2 10.3 34.6 38.4 9.4 42.0 40.0 31.0 13.1 39.1 32.5 12.3 38.1 34.3 11.5 37.1 36.4 10.6 35.9 38.6 9.8 44.0 41.4 31.1 13.5 40.5 32.7 12.7 39.5 34.6 11.8 38.4 36.6 10.9 37.2 38.8 10.1 45.0 42.1 31.2 13.7 41.1 32.8 12.8 40.1 34.7 12.0 39.1 36.7 11.1 37.9 38.9 10.2 46.0 42.7 31.3 13.9 41.8 32.9 13.0 40.8 34.8 12.1 39.7 36.8 11.3 38.6 39.0 10.4 48.0 44.1 31.5 14.3 43.2 33.2 13.4 42.2 35.0 12.5 41.1 37.0 11.6 39.9 39.3 10.7 50.0 45.6 31.7 14.6 44.7 33.4 13.8 43.6 35.2 12.8 42.5 37.3 11.9 41.3 39.5 11.0 MODEL: YCAL0046EE IPLV = 14.7 AIR TEMPERATURE ON CONDENSER ( F) LCWT 75.0 80.0 85.0 90.0 95.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 41.0 32.4 13.0 40.0 34.2 12.1 39.0 36.1 11.2 37.9 38.2 10.4 36.7 40.5 9.5 42.0 42.5 32.6 13.3 41.4 34.4 12.4 40.4 36.3 11.6 39.2 38.4 10.7 38.1 40.8 9.9 44.0 43.9 32.9 13.7 42.9 34.6 12.8 41.8 36.6 11.9 40.6 38.7 11.0 39.4 41.0 10.2 45.0 44.7 33.0 13.9 43.6 34.8 13.0 42.5 36.7 12.1 41.4 38.8 11.2 40.1 41.1 10.3 46.0 45.4 33.1 14.1 44.4 34.9 13.1 43.2 36.8 12.2 42.1 39.0 11.3 40.8 41.3 10.5 48.0 46.9 33.4 14.4 45.9 35.2 13.5 44.7 37.1 12.6 43.5 39.2 11.7 42.3 41.5 10.8 50.0 48.5 33.6 14.8 47.4 35.4 13.9 46.2 37.4 12.9 45.0 39.5 12.0 43.7 41.8 11.1 NOTES: 1. kw = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kw) 3. LCWT = Leaving Chilled Water Temperature 4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with the latest version of ARI Standard 550/590 6. The shaded points are certified in accordance with the latest version of ARI Standard 550/590 22 JOHNSON CONTROLS
Ratings (Cont'd) FORM 150.67-EG1 (1017) R-410A (60HZ) ENGLISH MODEL: YCAL0033EE IPLV= 14.5 AIR TEMPERATURE ON CONDENSER ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 25.9 30.8 9.2 25.0 32.5 8.5 24.1 34.3 7.8 23.2 36.2 7.1 22.2 38.3 6.4 11.6 18.3 6.5 42.0 26.8 31.0 9.5 25.9 32.7 8.7 24.9 34.5 8.0 24.0 36.5 7.3 23.0 38.5 6.6 12.1 18.4 6.8 44.0 27.7 31.2 9.7 26.8 33.0 8.9 25.8 34.8 8.2 24.8 36.7 7.5 23.8 38.8 6.8 12.5 18.4 7.0 45.0 28.1 31.4 9.8 27.2 33.1 9.0 26.2 34.9 8.3 25.2 36.8 7.6 24.2 38.9 6.9 12.7 18.5 7.1 46.0 28.6 31.5 9.9 27.7 33.2 9.2 26.7 35.0 8.4 25.7 37.0 7.7 24.6 39.0 7.0 13.0 18.5 7.2 48.0 29.5 31.8 10.2 28.6 33.5 9.4 27.6 35.3 8.6 26.5 37.2 7.9 25.4 39.3 7.2 13.4 18.6 7.5 50.0 30.5 32.1 10.4 29.5 33.8 9.6 28.5 35.6 8.9 27.4 37.5 8.1 14.5 17.8 8.4 13.9 18.7 7.7 MODEL: YCAL0043EE IPLV= 14.5 AIR TEMPERATURE ON CONDENSER ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 33.5 40.9 8.6 32.2 43.6 7.9 30.9 46.5 7.1 29.6 49.7 6.4 28.2 53.1 5.8 14.3 25.5 5.5 42.0 34.7 41.1 8.9 33.5 43.8 8.1 32.2 46.7 7.4 30.8 49.8 6.7 29.4 53.2 6.0 15.0 25.5 5.8 44.0 36.0 41.3 9.2 34.7 44.0 8.4 33.4 46.8 7.6 32.0 50.0 6.9 30.6 53.3 6.2 15.6 25.5 6.0 45.0 36.7 41.4 9.4 35.4 44.1 8.6 34.0 46.9 7.8 32.6 50.0 7.0 31.2 53.4 6.3 15.9 25.5 6.1 46.0 37.3 41.5 9.5 36.0 44.2 8.7 34.7 47.0 7.9 33.2 50.1 7.2 31.8 53.5 6.5 16.2 25.5 6.3 48.0 38.7 41.7 9.8 37.4 44.4 9.0 36.0 47.2 8.2 34.5 50.3 7.4 33.0 53.6 6.7 16.9 25.6 6.5 50.0 40.1 42.0 10.1 38.7 44.6 9.2 37.3 47.5 8.4 35.8 50.5 7.6 34.2 53.8 6.9 17.6 25.6 6.8 MODEL: YCAL0046EE IPLV= 14.7 AIR TEMPERATURE ON CONDENSER ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 35.4 43.0 8.7 34.2 45.7 8.0 32.8 48.6 7.3 31.4 51.7 6.6 30.0 55.1 5.9 15.2 26.4 5.7 42.0 36.8 43.2 9.0 35.5 45.9 8.3 34.1 48.8 7.5 32.7 51.9 6.8 31.2 55.2 6.2 15.9 26.4 5.9 44.0 38.2 43.5 9.3 36.8 46.2 8.5 35.4 49.1 7.8 34.0 52.1 7.1 32.4 55.4 6.4 16.5 26.5 6.2 45.0 38.9 43.6 9.5 37.5 46.3 8.7 36.1 49.2 7.9 34.6 52.3 7.2 33.1 55.6 6.5 16.9 26.5 6.3 46.0 39.5 43.8 9.6 38.2 46.4 8.8 36.8 49.3 8.0 35.3 52.4 7.3 33.7 55.7 6.6 17.2 26.5 6.4 48.0 40.9 44.0 9.9 39.6 46.7 9.1 38.1 49.6 8.3 36.6 52.6 7.5 35.0 55.9 6.8 17.9 26.6 6.7 50.0 42.4 44.3 10.2 41.0 47.0 9.3 39.5 49.8 8.5 37.9 52.9 7.8 36.3 56.2 7.1 18.6 26.7 6.9 NOTES: 1. kw = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kw) 3. LCWT = Leaving Chilled Water Temperature 4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with the latest version of ARI Standard 550/590 6. The shaded points are certified in accordance with the latest version of ARI Standard 550/590 JOHNSON CONTROLS 23
Ratings (Cont'd) R-410A (60HZ) ENGLISH MODEL: YCAL0052EE IPLV = 15.1 AIR TEMPERATURE ON CONDENSER ( F) LCWT 75.0 80.0 85.0 90.0 95.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 47.7 38.0 12.8 46.6 40.1 12.0 45.5 42.3 11.1 44.3 44.7 10.3 43.1 47.2 9.6 42.0 49.4 38.3 13.2 48.3 40.4 12.3 47.1 42.6 11.5 45.9 45.0 10.6 44.7 47.6 9.9 44.0 51.2 38.7 13.5 50.0 40.8 12.6 48.8 43.0 11.8 47.5 45.4 10.9 46.2 47.9 10.2 45.0 52.0 38.9 13.7 50.8 40.9 12.8 49.6 43.2 11.9 48.3 45.5 11.1 47.0 48.1 10.3 46.0 52.9 39.0 13.9 51.7 41.1 13.0 50.5 43.3 12.1 49.2 45.7 11.3 47.8 48.3 10.4 48.0 54.8 39.4 14.2 53.5 41.5 13.3 52.2 43.7 12.4 50.9 46.1 11.6 49.5 48.6 10.7 50.0 56.6 39.8 14.6 55.3 41.9 13.7 54.0 44.1 12.7 52.6 46.5 11.9 51.1 49.0 11.0 MODEL: YCAL0056EE IPLV = 14.7 AIR TEMPERATURE ON CONDENSER ( F) LCWT 75.0 80.0 85.0 90.0 95.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 58.2 48.2 12.7 56.9 50.7 11.9 55.5 53.3 11.1 54.1 56.2 10.3 52.5 59.3 9.5 42.0 60.2 48.7 13.0 58.9 51.2 12.2 57.5 53.8 11.4 55.9 56.7 10.6 54.3 59.8 9.8 44.0 62.3 49.2 13.4 60.9 51.7 12.5 59.4 54.4 11.7 57.9 57.2 10.9 56.2 60.3 10.1 45.0 63.3 49.5 13.5 61.9 52.0 12.7 60.4 54.6 11.8 58.8 57.5 11.0 57.2 60.6 10.2 46.0 64.4 49.7 13.7 62.9 52.2 12.8 61.4 54.9 12.0 59.8 57.8 11.1 58.1 60.9 10.3 48.0 66.5 50.3 14.0 65.0 52.8 13.1 63.5 55.5 12.2 61.8 58.3 11.4 60.0 61.4 10.6 50.0 68.6 50.9 14.3 67.1 53.4 13.4 65.5 56.1 12.5 63.8 58.9 11.7 62.0 62.0 10.8 MODEL: YCAL0066EE IPLV = 15.1 AIR TEMPERATURE ON CONDENSER ( F) LCWT 75.0 80.0 85.0 90.0 95.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 68.6 58.0 12.7 67.0 60.8 11.9 65.3 63.9 11.1 63.5 67.2 10.3 61.7 70.8 9.5 42.0 71.0 58.6 13.1 69.3 61.5 12.2 67.6 64.5 11.4 65.8 67.9 10.6 63.9 71.4 9.8 44.0 73.5 59.2 13.4 71.7 62.1 12.5 69.9 65.2 11.7 68.1 68.5 10.9 66.1 72.1 10.1 45.0 74.7 59.6 13.5 73.0 62.4 12.7 71.1 65.6 11.8 69.2 68.9 11.0 67.3 72.5 10.2 46.0 76.0 59.9 13.7 74.2 62.8 12.8 72.3 65.9 11.9 70.4 69.2 11.1 68.4 72.8 10.3 48.0 78.6 60.6 14.0 76.7 63.5 13.1 74.8 66.6 12.2 72.8 70.0 11.4 70.8 73.6 10.6 50.0 81.1 61.3 14.3 79.2 64.2 13.4 77.3 67.4 12.5 75.2 70.8 11.7 73.1 74.3 10.8 NOTES: 1. kw = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kw) 3. LCWT = Leaving Chilled Water Temperature 4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with the latest version of ARI Standard 550/590 6. The shaded points are certified in accordance with the latest version of ARI Standard 550/590 24 JOHNSON CONTROLS
Ratings (Cont'd) FORM 150.67-EG1 (1017) R-410A (60HZ) ENGLISH MODEL: YCAL0052EE IPLV= 15.1 AIR TEMPERATURE ON CONDENSER ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 41.9 49.9 8.9 40.5 52.8 8.2 39.1 55.8 7.5 37.6 59.1 6.9 36.1 62.5 6.3 18.5 30.1 6.0 42.0 43.4 50.3 9.1 42.0 53.1 8.4 40.5 56.2 7.7 39.0 59.4 7.1 37.4 62.9 6.4 19.3 30.2 6.3 44.0 44.9 50.6 9.4 43.5 53.5 8.7 42.0 56.5 8.0 40.4 59.8 7.3 38.7 63.2 6.6 20.0 30.4 6.5 45.0 45.6 50.8 9.5 44.2 53.7 8.8 42.7 56.7 8.1 41.1 60.0 7.4 39.4 63.4 6.7 20.4 30.4 6.6 46.0 46.4 51.0 9.7 45.0 53.8 8.9 43.4 56.9 8.2 41.8 60.1 7.5 40.1 63.6 6.8 20.8 30.5 6.7 48.0 48.0 51.3 9.9 46.5 54.2 9.2 44.9 57.3 8.4 43.3 60.5 7.7 41.5 64.0 7.0 21.5 30.6 6.9 50.0 49.6 51.7 10.2 48.1 54.6 9.4 46.5 57.7 8.7 44.7 60.9 7.9 42.9 64.4 7.2 22.3 30.7 7.2 MODEL: YCAL0056EE IPLV= 14.7 AIR TEMPERATURE ON CONDENSER ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 50.8 62.6 8.8 49.1 66.1 8.1 47.3 69.8 7.4 45.4 73.8 6.8 43.5 78.0 6.2 22.7 37.0 6.2 42.0 52.6 63.1 9.0 50.9 66.6 8.3 49.0 70.3 7.6 47.1 74.3 7.0 45.1 78.5 6.3 23.6 37.1 6.5 44.0 54.5 63.6 9.3 52.6 67.1 8.6 50.7 70.8 7.8 48.7 74.8 7.2 25.6 35.3 7.3 24.5 37.3 6.7 45.0 55.4 63.9 9.4 53.5 67.4 8.7 51.6 71.1 8.0 49.6 75.1 7.3 26.1 35.4 7.4 25.0 37.4 6.8 46.0 56.3 64.1 9.5 54.4 67.6 8.8 52.5 71.4 8.1 50.4 75.3 7.4 26.5 35.5 7.5 25.4 37.5 6.9 48.0 58.2 64.7 9.8 56.3 68.2 9.0 54.3 71.9 8.3 52.2 75.9 7.6 27.5 35.7 7.8 26.4 37.7 7.1 50.0 60.1 65.3 10.0 58.1 68.8 9.2 56.1 72.5 8.5 53.9 76.5 7.8 28.5 35.9 8.0 27.4 37.9 7.4 MODEL: YCAL0066EE IPLV= 15.1 AIR TEMPERATURE ON CONDENSER ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 59.8 74.7 8.8 57.8 78.8 8.1 55.8 83.3 7.4 53.8 88.2 6.8 51.6 93.5 6.2 26.6 44.3 6.3 42.0 61.9 75.3 9.1 59.9 79.5 8.3 57.9 84.0 7.7 55.7 88.8 7.0 40.1 63.8 6.8 27.7 44.5 6.5 44.0 64.1 76.0 9.3 62.1 80.2 8.6 59.9 84.6 7.9 57.7 89.5 7.2 30.0 42.2 7.3 28.8 44.7 6.7 45.0 65.2 76.3 9.4 63.1 80.5 8.7 61.0 85.0 8.0 58.8 89.8 7.3 30.5 42.4 7.5 29.3 44.8 6.8 46.0 66.4 76.7 9.5 64.2 80.9 8.8 62.0 85.4 8.1 59.8 90.2 7.4 31.1 42.5 7.6 29.9 44.9 6.9 48.0 68.6 77.5 9.8 66.5 81.6 9.0 64.2 86.1 8.3 61.9 90.9 7.6 32.3 42.8 7.8 31.0 45.2 7.2 50.0 71.0 78.2 10.0 68.7 82.4 9.3 66.4 86.9 8.5 64.0 91.7 7.8 33.5 43.0 8.1 32.2 45.5 7.4 NOTES: 1. kw = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kw) 3. LCWT = Leaving Chilled Water Temperature 4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with the latest version of ARI Standard 550/590 6. The shaded points are certified in accordance with the latest version of ARI Standard 550/590 JOHNSON CONTROLS 25
Ratings - (Cont'd) R-410A (60HZ) SI MODEL: YCAL0019EE AIR TEMPERATURE ON CONDENSER ( C) LCWT 25.0 30.0 35.0 40.0 45.0 50.0 ( C) KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP 5.0 57.3 14.0 3.8 54.6 15.6 3.3 51.7 17.4 2.8 48.6 19.4 2.4 45.2 21.7 2.0 23.2 10.5 2.0 6.0 59.0 14.1 3.9 56.2 15.7 3.4 53.2 17.5 2.9 50.1 19.5 2.4 46.6 21.8 2.0 24.0 10.5 2.1 7.0 60.7 14.2 4.0 57.9 15.8 3.4 54.8 17.6 3.0 51.6 19.7 2.5 48.1 21.9 2.1 24.8 10.5 2.2 8.0 62.5 14.3 4.1 59.6 15.9 3.5 56.5 17.7 3.0 53.1 19.8 2.6 49.6 22.0 2.2 25.6 10.5 2.2 9.0 64.3 14.5 4.2 61.3 16.1 3.6 58.1 17.9 3.1 54.7 19.9 2.6 51.1 22.2 2.2 26.4 10.6 2.3 10.0 66.2 14.6 4.2 63.1 16.2 3.7 59.8 18.0 3.2 56.3 20.0 2.7 52.6 22.3 2.3 27.3 10.6 2.4 11.0 68.0 14.7 4.3 64.9 16.3 3.7 61.5 18.1 3.2 58.0 20.2 2.7 54.2 22.4 2.3 28.2 10.6 2.4 MODEL: YCAL0022EE AIR TEMPERATURE ON CONDENSER ( C) LCWT 25.0 30.0 35.0 40.0 45.0 50.0 ( C) KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP 5.0 70.4 17.1 3.9 66.6 19.0 3.3 62.5 21.2 2.8 58.1 23.7 2.4 53.6 26.5 2.0 27.7 12.6 2.0 6.0 72.5 17.3 4.0 68.6 19.2 3.4 64.5 21.4 2.9 60.0 23.8 2.4 55.3 26.6 2.0 28.7 12.6 2.1 7.0 74.6 17.4 4.0 70.7 19.3 3.5 66.4 21.5 3.0 61.9 24.0 2.5 57.1 26.8 2.1 29.7 12.7 2.2 8.0 76.7 17.6 4.1 72.8 19.5 3.6 68.4 21.7 3.0 63.8 24.2 2.5 58.9 26.9 2.1 30.7 12.7 2.2 9.0 78.9 17.8 4.2 74.8 19.7 3.6 70.4 21.9 3.1 65.7 24.4 2.6 34.4 11.4 2.8 31.7 12.7 2.3 10.0 81.1 17.9 4.3 77.0 19.9 3.7 72.5 22.1 3.1 67.7 24.6 2.7 35.5 11.5 2.9 32.8 12.8 2.4 11.0 83.3 18.1 4.4 79.1 20.1 3.8 74.6 22.3 3.2 69.7 24.8 2.7 36.6 11.5 2.9 33.8 12.8 2.5 MODEL: YCAL0028EE AIR TEMPERATURE ON CONDENSER ( C) LCWT 25.0 30.0 35.0 40.0 45.0 50.0 ( C) KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP 5.0 94.0 22.5 3.7 89.9 24.7 3.3 85.5 27.2 2.8 80.7 29.9 2.5 75.6 33.1 2.1 69.9 36.6 1.8 6.0 96.9 22.7 3.8 92.7 24.9 3.3 88.1 27.3 2.9 83.2 30.1 2.5 77.9 33.3 2.2 72.2 36.8 1.8 7.0 99.8 22.9 3.9 95.5 25.1 3.4 90.8 27.5 3.0 85.8 30.3 2.6 80.4 33.4 2.2 74.5 36.9 1.9 8.0 102.8 23.1 3.9 98.3 25.3 3.5 93.6 27.7 3.0 88.4 30.5 2.6 82.8 33.6 2.3 76.8 37.1 1.9 9.0 105.8 23.3 4.0 101.2 25.5 3.6 96.3 27.9 3.1 91.0 30.7 2.7 85.3 33.9 2.3 46.2 18.3 2.2 10.0 108.9 23.5 4.1 104.2 25.7 3.6 99.1 28.2 3.2 93.7 30.9 2.8 87.9 34.1 2.4 47.7 18.4 2.2 11.0 112.0 23.8 4.2 107.2 25.9 3.7 102.0 28.4 3.3 96.4 31.2 2.8 90.5 34.3 2.4 49.2 18.5 2.3 NOTES: 1. kw = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kw) 3. LCWT = Leaving Chilled Water Temperature 4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with the latest version of ARI Standard 550/590 6. The shaded points are certified in accordance with the latest version of ARI Standard 550/590 26 JOHNSON CONTROLS
Ratings - (Cont'd) FORM 150.67-EG1 (1017) R-410A (60HZ) SI MODEL: YCAL0033EE AIR TEMPERATURE ON CONDENSER ( C) LCWT 25.0 30.0 35.0 40.0 45.0 50.0 ( C) KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP 5.0 105.1 24.3 3.8 100.6 26.6 3.4 95.6 29.3 3.0 90.1 32.2 2.6 84.2 35.6 2.2 42.7 17.7 2.1 6.0 108.3 24.6 3.9 103.6 26.9 3.5 98.5 29.5 3.0 92.9 32.5 2.6 86.9 35.8 2.2 44.2 17.8 2.1 7.0 111.5 24.8 4.0 106.7 27.1 3.6 101.4 29.7 3.1 95.7 32.7 2.7 89.6 36.0 2.3 45.6 17.9 2.2 8.0 114.7 25.0 4.1 109.8 27.3 3.6 104.4 30.0 3.2 98.6 32.9 2.7 92.3 36.2 2.4 47.1 18.0 2.3 9.0 118.0 25.3 4.2 113.0 27.6 3.7 107.5 30.2 3.2 101.5 33.2 2.8 95.0 36.5 2.4 48.6 18.0 2.3 10.0 121.3 25.5 4.3 116.2 27.8 3.8 110.5 30.5 3.3 104.4 33.4 2.9 97.8 36.7 2.5 50.2 18.1 2.4 11.0 124.7 25.8 4.3 119.4 28.1 3.8 113.7 30.7 3.4 107.4 33.7 2.9 100.7 37.0 2.5 51.8 18.2 2.4 MODEL: YCAL0043EE AIR TEMPERATURE ON CONDENSER ( C) LCWT 25.0 30.0 35.0 40.0 45.0 50.0 ( C) KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP 5.0 137.1 31.5 3.7 131.0 34.6 3.3 124.1 38.5 2.8 116.4 43.1 2.4 108.1 48.4 2.0 99.1 54.5 1.7 6.0 141.3 31.6 3.8 135.2 34.8 3.4 128.2 38.7 2.9 120.4 43.3 2.5 112.0 48.6 2.1 102.8 54.6 1.7 7.0 145.6 31.8 3.9 139.5 35.0 3.4 132.4 38.9 3.0 124.5 43.5 2.5 115.9 48.7 2.1 106.6 54.7 1.8 8.0 150.0 32.0 4.0 143.8 35.2 3.5 136.6 39.1 3.1 128.6 43.7 2.6 119.8 48.9 2.2 110.4 54.9 1.8 9.0 154.5 32.2 4.1 148.2 35.4 3.6 141.0 39.3 3.1 132.8 43.9 2.7 123.9 49.1 2.3 114.2 55.0 1.9 10.0 159.0 32.4 4.2 152.7 35.6 3.7 145.4 39.5 3.2 137.1 44.1 2.8 128.0 49.3 2.3 118.1 55.2 1.9 11.0 163.6 32.6 4.3 157.2 35.8 3.8 149.8 39.7 3.3 141.4 44.3 2.8 132.1 49.5 2.4 122.1 55.4 2.0 MODEL: YCAL0046EE AIR TEMPERATURE ON CONDENSER ( C) LCWT 25.0 30.0 35.0 40.0 45.0 50.0 ( C) KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP 5.0 145.4 33.2 3.8 138.7 36.6 3.3 131.4 40.6 2.8 123.4 45.3 2.4 114.7 50.6 2.0 105.4 56.5 1.7 6.0 149.9 33.4 3.8 143.2 36.8 3.4 135.8 40.9 2.9 127.6 45.5 2.5 118.8 50.7 2.1 109.3 56.7 1.8 7.0 154.5 33.6 3.9 147.7 37.1 3.5 140.1 41.1 3.0 131.9 45.7 2.6 122.9 51.0 2.2 113.2 56.9 1.8 8.0 159.3 33.9 4.0 152.3 37.3 3.6 144.6 41.3 3.1 136.2 45.9 2.6 127.1 51.2 2.2 117.2 57.1 1.9 9.0 164.0 34.1 4.1 157.0 37.5 3.6 149.1 41.6 3.2 140.6 46.2 2.7 131.3 51.4 2.3 91.7 40.6 2.0 10.0 168.9 34.3 4.2 161.7 37.8 3.7 153.7 41.8 3.2 145.0 46.4 2.8 135.6 51.6 2.4 94.9 40.7 2.1 11.0 173.8 34.6 4.3 166.5 38.0 3.8 158.4 42.1 3.3 149.5 46.7 2.9 139.9 51.9 2.4 98.1 40.9 2.1 NOTES: 1. kw = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kw) 3. LCWT = Leaving Chilled Water Temperature 4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with the latest version of ARI Standard 550/590 6. The shaded points are certified in accordance with the latest version of ARI Standard 550/590 JOHNSON CONTROLS 27
Ratings - (Cont'd) R-410A (60HZ) SI MODEL: YCAL0052EE AIR TEMPERATURE ON CONDENSER ( C) LCWT 25.0 30.0 35.0 40.0 45.0 50.0 ( C) KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP 5.0 169.2 39.0 3.7 162.0 42.9 3.3 154.3 47.4 2.9 146.0 52.4 2.5 136.9 57.9 2.1 126.8 64.1 1.8 6.0 174.6 39.3 3.8 167.2 43.2 3.4 159.2 47.7 2.9 150.7 52.7 2.5 141.3 58.2 2.2 131.0 64.4 1.8 7.0 180.1 39.6 3.9 172.4 43.6 3.4 164.2 48.0 3.0 155.4 53.0 2.6 145.8 58.6 2.2 135.2 64.8 1.9 8.0 185.7 39.9 4.0 177.8 43.9 3.5 169.3 48.3 3.1 160.2 53.3 2.7 150.4 58.9 2.3 139.5 65.1 1.9 9.0 191.5 40.3 4.1 183.3 44.2 3.6 174.5 48.7 3.2 165.2 53.7 2.7 155.0 59.2 2.4 143.9 65.4 2.0 10.0 197.3 40.6 4.2 188.8 44.6 3.7 179.8 49.0 3.2 170.2 54.0 2.8 159.8 59.6 2.4 148.3 65.8 2.1 11.0 203.3 41.0 4.3 194.5 44.9 3.8 185.3 49.4 3.3 175.3 54.4 2.9 164.6 59.9 2.5 83.2 29.9 2.3 MODEL: YCAL0056EE AIR TEMPERATURE ON CONDENSER ( C) LCWT 25.0 30.0 35.0 40.0 45.0 50.0 ( C) KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP 5.0 206.4 49.4 3.7 197.6 54.1 3.3 187.8 59.5 2.8 177.0 65.6 2.5 165.4 72.4 2.1 83.6 35.8 2.0 6.0 212.8 49.9 3.8 203.7 54.6 3.3 193.7 60.0 2.9 182.6 66.1 2.5 170.6 72.9 2.1 86.5 36.0 2.0 7.0 219.3 50.3 3.8 210.0 55.1 3.4 199.6 60.5 3.0 188.3 66.5 2.6 176.0 73.3 2.2 89.4 36.2 2.1 8.0 225.8 50.8 3.9 216.3 55.6 3.5 205.7 61.0 3.0 194.1 67.0 2.6 181.5 73.8 2.3 92.5 36.3 2.2 9.0 232.5 51.3 4.0 222.7 56.1 3.6 211.8 61.5 3.1 199.9 67.5 2.7 187.0 74.3 2.3 95.5 36.5 2.2 10.0 239.2 51.9 4.1 229.2 56.6 3.6 218.1 62.0 3.2 205.9 68.1 2.8 192.6 74.9 2.4 98.7 36.7 2.3 11.0 246.1 52.4 4.2 235.8 57.2 3.7 224.4 62.6 3.2 211.9 68.6 2.8 198.3 75.4 2.4 101.9 36.9 2.3 MODEL: YCAL0066EE AIR TEMPERATURE ON CONDENSER ( C) LCWT 25.0 30.0 35.0 40.0 45.0 50.0 ( C) KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP 5.0 243.2 59.4 3.7 232.3 64.9 3.2 220.7 71.1 2.8 208.4 78.3 2.5 195.5 86.5 2.1 97.9 42.9 2.0 6.0 250.8 60.0 3.8 239.6 65.5 3.3 227.7 71.7 2.9 215.2 78.9 2.5 201.9 87.1 2.2 101.3 43.1 2.0 7.0 258.6 60.6 3.8 247.1 66.1 3.4 234.9 72.3 3.0 222.0 79.5 2.6 208.3 87.7 2.2 104.9 43.3 2.1 8.0 266.5 61.2 3.9 254.7 66.7 3.5 242.2 73.0 3.0 228.9 80.2 2.6 214.9 88.4 2.3 108.5 43.5 2.2 9.0 274.5 61.8 4.0 262.4 67.4 3.5 249.6 73.6 3.1 236.0 80.8 2.7 221.7 89.0 2.3 112.2 43.7 2.2 10.0 282.7 62.4 4.1 270.3 68.0 3.6 257.2 74.3 3.2 243.2 81.5 2.8 228.5 89.7 2.4 116.0 44.0 2.3 11.0 291.0 63.1 4.2 278.3 68.7 3.7 264.8 75.1 3.2 250.5 82.3 2.8 235.4 90.4 2.4 119.9 44.2 2.4 NOTES: 1. kw = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kw) 3. LCWT = Leaving Chilled Water Temperature 4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with the latest version of ARI Standard 550/590 6. The shaded points are certified in accordance with the latest version of ARI Standard 550/590 28 JOHNSON CONTROLS
THIS PAGE INTENTIONALLY LEFT BLANK. JOHNSON CONTROLS 29
Ratings - (Cont'd) R-410A (50HZ) ENGLISH MODEL: YCAL0019EE IPLV = 15.5 AIR TEMPERATURE ON CONDENSER ( F) LCWT 75.0 80.0 85.0 90.0 95.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 13.7 11.0 14.2 13.3 11.6 13.1 12.9 12.3 12.0 12.5 13.1 11.0 12.1 13.9 10.0 42.0 14.1 11.1 14.6 13.7 11.7 13.4 13.4 12.4 12.3 13.0 13.2 11.3 12.5 14.0 10.3 44.0 14.6 11.2 14.9 14.2 11.8 13.7 13.8 12.6 12.6 13.4 13.3 11.6 13.0 14.2 10.6 45.0 14.8 11.2 15.1 14.4 11.9 13.9 14.0 12.6 12.8 13.6 13.4 11.7 13.2 14.2 10.7 46.0 15.1 11.3 15.2 14.7 12.0 14.0 14.3 12.7 12.9 13.8 13.4 11.8 13.4 14.3 10.8 48.0 15.6 11.4 15.6 15.1 12.1 14.3 14.7 12.8 13.2 14.3 13.6 12.1 13.8 14.4 11.1 50.0 16.0 11.5 15.9 15.6 12.2 14.6 15.2 12.9 13.5 14.7 13.7 12.4 14.3 14.5 11.3 MODEL: YCAL0022EE IPLV = 17.1 AIR TEMPERATURE ON CONDENSER ( F) LCWT 75.0 80.0 85.0 90.0 95.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 16.7 13.5 14.2 16.2 14.3 13.0 15.7 15.3 11.9 15.2 16.3 10.8 14.6 17.3 9.8 42.0 17.2 13.6 14.6 16.8 14.5 13.3 16.2 15.4 12.2 15.7 16.4 11.1 15.1 17.5 10.1 44.0 17.8 13.8 14.9 17.3 14.6 13.7 16.8 15.6 12.5 16.2 16.5 11.4 15.6 17.6 10.3 45.0 18.1 13.8 15.1 17.6 14.7 13.8 17.1 15.6 12.6 16.5 16.6 11.5 15.9 17.7 10.5 46.0 18.4 13.9 15.2 17.9 14.8 14.0 17.3 15.7 12.8 16.8 16.7 11.6 16.2 17.8 10.6 48.0 19.0 14.0 15.6 18.4 14.9 14.3 17.9 15.8 13.1 17.3 16.8 11.9 16.7 17.9 10.8 50.0 19.6 14.2 15.9 19.0 15.1 14.6 18.5 16.0 13.4 17.9 17.0 12.2 17.2 18.1 11.1 MODEL: YCAL0028EE IPLV = 14.7 AIR TEMPERATURE ON CONDENSER ( F) LCWT 75.0 80.0 85.0 90.0 95.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 22.1 17.3 14.0 21.6 18.3 13.0 21.1 19.3 12.0 20.6 20.5 11.1 20.0 21.8 10.2 42.0 22.9 17.4 14.4 22.4 18.4 13.3 21.8 19.5 12.4 21.3 20.6 11.4 20.7 21.9 10.5 44.0 23.6 17.5 14.7 23.1 18.5 13.7 22.6 19.6 12.7 22.0 20.8 11.7 21.4 22.0 10.8 45.0 24.0 17.6 14.9 23.5 18.6 13.9 23.0 19.7 12.9 22.4 20.8 11.9 21.8 22.1 11.0 46.0 24.4 17.7 15.1 23.9 18.7 14.1 23.3 19.7 13.1 22.8 20.9 12.1 22.1 22.1 11.1 48.0 25.2 17.8 15.5 24.7 18.8 14.4 24.1 19.9 13.4 23.5 21.0 12.4 22.9 22.3 11.4 50.0 26.0 18.0 15.8 25.5 19.0 14.8 24.9 20.0 13.7 24.3 21.2 12.7 23.6 22.4 11.7 NOTES: 1. kw = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kw) 3. LCWT = Leaving Chilled Water Temperature 4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with the latest version of ARI Standard 550/590 6. The shaded points are certified in accordance with the latest version of ARI Standard 550/590 30 JOHNSON CONTROLS