Fixed-Mounted Circuit-Breaker Switchgear up to 36 kv, SF 6 -Insulated

Similar documents

Benefits, typical uses

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated

Switchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

NXPLUS C Single busbar. Maintenance-free for lifetime

Power Transmission and Distribution. NXPLUS C double busbar. The economical solution when replacing old systems

Types. Fixed-mounted circuitbreaker. NXPLUS C is a factoryassembled,

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kv, SF 6 -Insulated. Medium-Voltage Switchgear Catalog HA 35.

NXAirS Withdrawable Medium-Voltage Switchgear up to 24kV Air-Insulated

Air-Insulated Medium-Voltage Switchgear NXAIR, up to 24 kv

Catalog HA Edition up to 24 kv, Air-Insulated, Extendable. Medium-Voltage Switchgear. siemens.com/simosec

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

Vacuum Circuit Breaker

8DJ. Maintenance-free for lifetime

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated

Catalog HA Edition Medium-Voltage Switchgear. siemens.com/nxair

Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

Gas Insulated Metal-clad Switchgear, HMGS!

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

Air Insulated Switchgear NXAirS, 40.5kV Answers for infrastructure and cities.

Switchgear Type 8DJH 36 for Secondary

ZX-Family Gas-insulated medium voltage switchgear

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

Reliable medium-voltage switchgear for fail-safe operation, up to 24 kv siemens.com/simoprime-partner

Features. 2 Siemens HA Page. 8DJ10 switchgear is a factoryassembled,

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

HB1 and VB1 Generator Circuit-Breaker Switchgear. Medium-Voltage Switchgear. siemens.com/generatorswitchgear. Catalog HB1 and VB1 Edition 2017

Medium-Voltage Switchgear

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

DIRECT CONTACT. Switchgear Sales Team TEL : ~9 CHANGWON PLANT Switchgear Design Team TEL : ~9

CPG.0 Single busbar gas-insulated cubicles

VB1-D Generator Circuit-Breaker Switchgear

Air-insulated switchgear UniGear type ZS1

Gas-insulated medium-voltage switchgear. For the metal industry. Answers for energy.

voltage switchgear ZX ABB ZX Family 1

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment

Gas-insulated medium-voltage switchgear. For the mining industry. Answers for energy.

Metal Clad Air Insulated Switchgear

Switchgear Type 8DH10 up to 24 kv, Gas-Insulated, Extendable

ZX2.2 Gas-insulated medium voltage switchgear

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

Medium-Voltage Switchgear OPERATING INSTRUCTIONS

SWITCHCRAFT. Switchcraft Europe GmbH SWITCHCRAFT

Cost-Efficient Solution for Power Distribution. Gas-Insulated Medium-Voltage Switchgear: Safe, Compact and Reliable

HIGS Highly Integrated Generator Circuit-Breaker Switchgear

Vacuum Circuit-Breaker Modules

ZX2 Gas-insulated medium voltage switchgear

Air-insulated medium voltage switchgear metal-enclosed type-tested factory-assembled withdrawable-unit design 12 kv / 24 kv

Gas-insulated medium-voltage switchgear. For marine and offshore applications. Answers for energy.

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

HB3 Generator Circuit-Breaker Switchgear

with Vacuum Circuit Breaker HAF

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.

Distributing Power Economically. Totally Integrated Power. Gas-insulated medium-voltage switchgear: safe, compact, and reliable

ZX-Family Gas-insulated medium voltage switchgear

Medium voltage products UniSec DY800 New 24 kv air-insulated medium voltage switchgear to e-distribuzione specifications

Gas-Insulated Switchgear. Type 8VN1 blue GIS up to 145 kv, 40 ka, 3150 A

Gas-insulated switchgear up to 420 kv, 63 ka, 5000 A Type 8DQ1. siemens.com/energy. Answers for energy.

ZX1.5-R. Gas-insulated medium voltage for railway application DISTRIBUTION SOLUTIONS. Gas-insulated medium voltage for railway application ZX1.

Medium-Voltage Switchgear Type 8DH10 up to 24 kv, Gas-Insulated, Extendable

SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kv, ANSI, Air-Insulated, Extendable

B kv Gas-insulated Substations

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

UniGear. Technical Guide

Medium Voltage Distribution PIX. Air Insulated Switchgear up to 24 kv PARS TABLEAU

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

UniSafe 36. Medium voltage, arc-proof, air-insulated, metal-clad switchboard

Medium voltage switchgear type W 12. rated voltage 12 kv rated current 630 A

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

Metal Clad Switchgears

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

PT Guna Era Manufaktura. Catalogue GAE TPS \ Medium Voltage Switchgear 12kV - 24kV \ M GAE TPS. Medium Voltage Switchgear 12kV - 24kV

HIS Highly Integrated Switchgear up to 550 kv, 63 ka, 5000 A Type 8DQ1

Innovac SVS/08 - SVS/ kv modular switchgear

HB3-80 Generator Circuit-Breaker Switchgear. Medium-Voltage Switchgear. Totally Integrated Power HB3-80. Catalog HB3-80.

B kv T&D GAS INSULATED SWITCHGEAR

the safe, reliable, and efficient choice for MV switchgear

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

EMC 24 SERIES METAL CLAD SWITCHGEAR. We engineer, we assure. Up to 24 kv - 25 ka With Withdrawable, Air-Insulated, Medium Voltage Distribution Panel

M-RING 24. SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A)

Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

Totally Integrated Power. A reliable all-rounder. Gas-insulated medium-voltage switchgear 8DJH 36.

Medium-Voltage Switchgear Medium-voltage switchgear type 8DJH, block versions Up to 24 kv, gas-insulated

GMA. Medium-voltage switchgear

COMPACT AND EXTENSIBLE RING MAIN UNIT. insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker

W 12 ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH. DRIESCHER - Air-Insulated Medium-Voltage Switchgears

SWITCHGEAR DIVISION PRODUCT PROFILES

Reliable Solution for Power Distribution. Air-Insulated Medium-Voltage Switchgear: Cost-Efficient, Sustainable and Safe

UP TO 17,5 kv LSC 2B PM (METAL-CLAD) WITHDRAWABLE VACUUM CIRCUIT BREAKER MEDIUM VOLTAGE CUBICLES

MESG 12 / 17.5 / 24 / 36 KV

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel

Transcription:

Medium- Switchgear Catalog HA 35.51 2000 Supersedes: Catalog HA 35.51 1998

Contents General Infmation Page Application, features, requirements General Infmation Application, features, 2 requirements Technical Data Electrical data 3 View of a switchgear Product Range Circuit-breaker panel 4 and 5 Disconnect panel 6 and 7 Sectionalizer panel 8 Design Panel construction 8 and 9 Dimensions 10 Module coupling Solid-state HMI 11 Mechanical control board Standards Standards, specifications, 12 guidelines Appendix Catalog index 13 Conditions of sale and delivery, 15 expt regulations, trademarks, dimensions fixed-mounted circuit-breaker switchgear is of the three-pole, metal-enclosed, metal-clad, SF 6 -insulated type f indo installation, f single busbar. Typical uses Transfmer stations and substations operated by: Power supply utilities Power stations Cement industry Automobile industry Iron and steel wks Rolling mills Mining industry Textile, paper and food industries Chemical industry Petroleum industry Pipeline installations Offshe installations Electrochemical plants Petrochemical plants Traction power supplies Shipbuilding industry Diesel power plants Emergency power supply installations Lignite open-cast mines Technical characteristics Three-pole primary enclosure SF 6 -insulated Vacuum circuit-breakers Three-position switch as busbar disconnect and feeder earthing switch Make-proof earthing with vacuum circuit-breaker Panel width 600 mm (with busbar sectionalizer panel < 2000 A: 900 mm > 2000 A: 1200 mm) f all voltages up to 36 kv Hermetically sealed, welded stainless steel switchgear container Single-pole, solid-insulated, screened, bolted-type module coupling Cable connection with inside outside cone plug-in systems Siemens AG 2000 2 Siemens HA 35.51 2000

R-HA35-060a eps Technical Data Electrical data Operat safety Safe-to-touch and hermetically sealed primary enclosure All high-voltage parts, including the cable sealing ends, busbars and voltage transfmers, are surrounded by earthed layers metal enclosures Capacitive voltage detection system f verification of safe isolation from supply Operating mechanisms and auxiliary switches safely accessible outside the primary enclosure (switchgear container) Protective system interlock to prevent operation when enclosure is open Type-tested enclosures and interrogative interlocks provide high degree of internal arcing protection Rated voltage up to 24 kv 36 kv (40.5 kv *) Rated frequency 50/60 Hz 50/60 Hz Rated sht-duration power-frequency withstand voltage Rated lightning impulse withstand voltage Rated sht-circuit breaking current and rated sht-time withstand current, 3 s 50 kv 70 kv (85 kv *) 125 kv 170 kv (185 kv *) max. 31.5 ka 31.5 ka Rated sht-circuit making current max. 80 ka 80 ka Rated nmal current of busbar max. 2500 A 2500 A Rated nmal current of feeder max. 2500 A 2500 A * On request Operational reliability Hermetically sealed primary enclosure f protection against environmental effects (dirt, moisture and small animals) Operating mechanism components maintenancefree in indo environment (DIN VDE 0670 Part 1000) Breaker operating mechanisms accessible outside the switchgear container (primary enclosure) Inductive voltage transfmers metal-enclosed f plug-in, mounting outside the main circuit Ring-ce current transfmers located outside the primary enclosure Complete interrogative interlocking system Welded switchgear container, sealed f life Minimum fire load fixed-mounted circuit-breaker switchgear Siemens HA 35.51 2000 3

Product Range Overview Circuit-breaker panel with cable connection as inside cone f: Rated voltage up to 36 kv Rated sht-circuit breaking current up to 31.5 ka Rated nmal currents of busbars and feeders up to 2500 A Busbar fittings 1 ) Panel connection versions Fittings befe circuit-breaker module Fittings after circuit-breaker module 4 ) Panel connection fittings Capacitive voltage detection system 1 x plug-in cable, sizes 23 transfmer, Current transfmer 2 ) 1 x plug-in cable, size 2 2 x plug-in cable, sizes 23 2 ) transfmer, 3 x plug-in cable, sizes 23 2 ) Surge arrester, 4 x plug-in cable, size 2 HA35-2368b eps and 3 ) Busbar current transfmer Solidinsulated bar (e.g. Duresca bar) Surge arrester, 1) Capacitive voltage detection system accding to LRM IVDS system. 2) Not possible with rated nmal current of feeder of 2500 A. 3) Not possible with busbar voltage transfmer. 4) Requires cable connection with container f separate inside cone. 4 Siemens HA 35.51 2000

Product Range Overview Circuit-breaker panel with cable connection as outside cone f: Rated voltage up to 24 kv Rated sht-circuit breaking current up to 25 ka Rated nmal currents of busbars up to 2500 A and feeders up to 1250 A Busbar fittings 1 ) Panel connection versions Fittings befe circuit-breaker module Fittings after circuit-breaker module Panel connection fittings Capacitive voltage detection system 1 x plug-in cable transfmer, disconnectable Current transfmer 1 x plug-in cable, size 2 2 x plug-in cable transfmer, 3 x plug-in cable Surge arrester, HA35-2369b eps and 2 ) Busbar current transfmer Surge arrester limiter, 1) Capacitive voltage detection system accding to LRM IVDS system. 2) Not possible with busbar voltage transfmer. Siemens HA 35.51 2000 5

Product Range Overview Disconnect panel with cable connection as inside cone f: Rated voltage up to 36 kv Rated sht-circuit breaking current up to 31.5 ka Rated nmal currents of busbars and feeders up to 2500 A Busbar fittings 1 ) Panel connection versions Fittings befe cable connection module Panel connection fittings Capacitive voltage detection system 1 x plug-in cable, sizes 23 transfmer, Current transfmer 2 ) 1 x plug-in cable, size 2 2 x plug-in cable, sizes 23 2 ) transfmer, 3 x plug-in cable, sizes 23 2 ) Surge arrester, 4 x plug-in cable, size 2 HA35-2370c eps and 3 ) Busbar current transfmer Solidinsulated bar (e.g. Duresca bar) Surge arrester, 1) Capacitive voltage detection system accding to LRM IVDS system. 2) Not possible with rated nmal current of feeder of 2500 A. 3) Not possible with busbar voltage transfmer. 6 Siemens HA 35.51 2000

Product Range Overview Disconnect panel with cable connection as outside cone f: Rated voltage up to 24 kv Rated sht-circuit breaking current up to 25 ka Rated nmal currents of busbars up to 2500 A and feeders up to 1250 A Busbar fittings 1 ) Panel connection versions Fittings befe cable connection module Fittings after cable connection module Panel connection fittings Capacitive voltage detection system 1 x plug-in cable transfmer, disconnectable Current transfmer 1 x plug-in cable, size 2 2 x plug-in cable transfmer, 3 x plug-in cable Surge arrester, HA35-2371b eps and 2 ) Busbar current transfmer Surge arrester limiter, 1) Capacitive voltage detection system accding to LRM IVDS system. 2) Not possible with busbar voltage transfmer. Siemens HA 35.51 2000 7

Product Range Overview Panel construction Sectionalizer panel f: Rated voltage up to 36 kv Rated sht-circuit breaking current up to 31.5 ka Rated nmal current of busbars up to 2500 A Busbar fittings Fittings befe circuit-breaker module Panel with integrated inside cone Features Rated voltage up to 36 kv Rated sht-circuit breaking current up to 31.5 ka Rated nmal currents of busbars and feeders up to 2500 A HA35-2372d eps 1 ) Capacitive voltage detection system Current transfmer Panel with separate inside cone Features Rated voltage up to 36 kv Rated sht-circuit breaking current up to 31.5 ka Rated nmal currents of busbars and feeders up to 2500 A Panel with outside cone Features Rated voltage up to 24 kv Rated sht-circuit breaking current up to 25 ka Rated nmal currents of busbars up to 2500 A and feeders up to 1250 A 1) Not possible with rated nmal current of busbar of 2500 A. 8 Siemens HA 35.51 2000

Design Legend 1 Do of low-voltage compartment 7 16 2 SIPROTEC 4 bay controller, type 7SJ63, f control and protection 1 2 3 4 5 6 NXPLUS HA35-2374d eps 8 30 9 10 11 12 13 30 14 15 30 24 18 25 30 26 23 30 12 Panel with integrated inside cone Panel with separate inside cone (lower part of panel shown) 17 18 19 20 21 22 23 22 3 detection system CAPDIS 4 EMERGENCY-OFF pushbutton, mechanical 5 Do to mechanical control board 6 Cover of cable connection compartment 7 Busbar cover 8 Busbar module, welded, SF 6 -insulated 9 Three-pole busbar system 10 Three-position switch, SF 6 -insulated, with the three positions: ON OFF EARTHING PREPARED 11 Module coupling between busbar module and circuit-breaker module 12 Circuit-breaker module, welded, SF 6 -insulated, with integrated cable connection 13 Vacuum interrupter of circuit-breaker 14 Pressure-relief duct 15 Integrated cable connection as inside cone 16 Optional low-voltage compartment 935 mm high 17 Standard low-voltage compartment 735 mm high 18 Ring-ce current transfmer 19 Manual and mot operating mechanism of three-position switch 20 Mechanical control board 21 Manual and mot operating mechanism of circuit-breaker 22 transfmer connection socket as inside cone 23 Cable connection compartment 24 Module coupling between circuitbreaker and cable connection module 25 Cable connection module, welded, SF 6 -insulated, with separate cable connection 26 Separate cable connection as inside cone 27 transfmer connection socket as outside cone 28 Cable connection as outside cone 29 Connection cables 30 Rupture diaphragm 18 27 28 23 29 Panel with outside cone (lower part of panel shown) Siemens HA 35.51 2000 9

R-HA35-061 eps Design Panel construction Dimensions * Width of the sectionalizer panel < 2000 A: 900 mm, > 2000 A: 1200 mm **Useful depth of the low-voltage compartment Dimensions 1 6 2 3 280 280 7 8 9 350** 3 4 2250 2450 5 HA35-2375f eps 80 600* 1600 1 Module coupling 2 Busbar module 3 Current transfmer 4 Circuit-breaker module 5 End wall 6 Bushing in adjacent panel 7 Busbars 8 Low-voltage compartment, 735 mm high 9 Option: low-voltage compartment, 935 mm high Module coupling Module coupling Connects panels with each other, as well as containers within a panel Single-pole, bolted-type Consisting of round copper with cast-resin insulation Bolted busbar joint with silicon rubber insulation Stress control by means of electrically conductive layers of insulation (inside and outside) Screened by earthing outer layers with switchgear container Switchgear installation, extension panel replacement without any wk on the SF 6 -gas system 1 10 2 3 4 9 8 7 5 6 HA35-2376b eps 1 Busbar conduct 2 Silicon sleeve 3 Conductive layer 4 High-quality joint 5 Cast-resin bushing 6 Container wall 7 Screening elements 8 Cast-resin insulation 9 Bolted busbar joint 10 Pressure ring Busbar module (SF 6 -insulated) Module coupling (solid-insulated) Busbar module (SF 6 -insulated) 10 Siemens HA 35.51 2000

R-HA35-064 eps R-HA35-062a eps R-HA35-071 eps Design Panel construction Solid-state HMI (humanmachine interface) SIPROTEC 4 bay controller, type 7SJ63, Profibus capable, f control, protection, signalling, communication and measurement f stand-alone master operation. 5 1 2 Features LCD f process and equipment data, graphically as feeder mimic control diagram and as text Four programmable function keys f frequently perfmed actions Fourteen programmable LEDs f indicating any desired data Two key-operated switches f changeover between local and remote control and interlocked and non-interlocked position detection system CAPDIS Features detection system accding to VDE 0682, Part 415 Indication of state Dead state (active zero indication) Err Integrated signalling relay Self-testing, therefe repeated testing, demanded in the standards, is not required Additional test sockets f phase comparison with an LRM phase comparat Mechanical control board Features Arranged behind panel do Opening of do switches off the SIPROTEC 4 bay controller, type 7SJ63, automatically (protective function is maintained) Three-position switch interlocked with circuit-breaker Cancelling of feeder earthing can be blocked mechanically Solid-state HMI with panel do closed with SIPROTEC 4 bay controller and CAPDIS voltage detection system 1 2 3 4 Mechanical control board with panel do open 5 6 7 8 9 10 11 12 13 14 15 6 9 SIPROTEC 4 bay controller, type 7SJ63 *) and voltage detection system CAPDIS *) The basic unit f this is in the low-voltage compartment 1 LCD SIPROTEC 4 2 Keys f navigation 3 Control keys 4 Function keys 5 LEDs 6 Key-operated switches 7 LCD CAPDIS 8 Test sockets 9 Signalling relay (accessible from the rear) 1 ON/OFF position indication f three-position switch 2 ON/OFF operating shaft f three-position switch 3 OFF/EARTHING PREPARED operating shaft f three-position switch 4 OFF/EARTHING PREPARED position indication f three-position switch 5 Mimic diagram 6 Ready indication f busbar module (gas compartment moniting) 7 Ready indication f circuit-breaker module (gas compartment moniting) 8 Interlocking f preselection f 2 and 3 9 ON/OFF position indication f circuit-breaker 10 Manual spring charging f circuit-breaker 11 ON pushbutton f circuit-breaker with sealable cap, mechanical 12 Locking device f feeder earthed 13 OFF pushbutton f circuit-breaker, mechanical 14 Spring charged indication f circuit-breaker 15 Operating cycle counter f circuit-breaker 3 4 7 8 Siemens HA 35.51 2000 11

Standards Standards, specifications, guidelines Standards The switchgear complies with the standards and specifications listed below: VDE 0670, Part 1000 VDE 0670, Part 6 VDE 0670, Part 101 et seq. VDE 0670, Part 2 IEC 60 694 IEC 60 298 IEC 60 056 IEC 60 129 In accdance with the obligaty harmonization in the European Community, the national standards of the member countries confm to IEC 60 298. Type of service location switchgear can be used as an indo installation in accdance with VDE 0101: Outside closed electrical operating areas in locations not accessible to the general public. Tools are required to remove switchgear enclosures. In closed electrical operating areas. A closed electrical operating area is a room area which is used solely f the operation of electrical installations. This type of area is locked at all times and accessible only to authized trained personnel and other skilled staff. Untrained unskilled persons must be accompanied by authized personnel. Internal arc test, resistance to internal arcs Internal arc test Tests have been carried out with switchgear, in der to verify its behaviour under conditions of internal arcing. The resistance to internal arcing complies with the requirements of VDE 0670, Part 6, Appendix AA IEC 60 298, Appendix AA Resistance to internal arcs The possibility of faults in the fixed-mounted circuit-breaker switchgear is much less than in previous types, due to the single-pole enclosure of external components and the SF 6 insulation of the switchgear: All external fault-causing facts have been eliminated, such as: Pollution deposits Moisture Small animals and feign bodies Maloperations are prevented by the clear, logical layout of the operating elements The three-position switch and the vacuum circuitbreaker provide sht-circuitproof earthing of the feeder Should arcing occur in spite of this, the pressure is relieved towards the rear into a duct. In the improbable event of a fault inside the module container, the SF 6 insulation restricts the arc energy to only about 1 / 3 of that f air. The pressurerelief facility in the rear panel of the module container is designed to operate in an overpressure range of 2 to 3.5 bar. The gases are discharged towards the rear into a duct. The pressure-relief duct diverts the gases upwards. Protection against electric shock, the ingress of water and solid feign bodies The fixed-mounted circuit-breaker switchgear is fully enclosed and entirely unaffected by climatic influences. All medium-voltage switching devices are enclosed in stainless steel containers, which are welded gas-tight and filled with SF 6 gas. Live parts outside the switchgear container are single-pole insulated and screened. There are no points at which leakage currents of highvoltage potential are able to flow off to earth. All essential components of the operating mechanism are made of non-croding materials. Climate and ambient conditions The fixed-mounted circuit-breaker switchgear offers the following degrees of protection: IP3XD f external enclosure IP65 f parts under high voltage in accdance with: DIN VDE 0670, Part 6 IEC 60 298 with IEC 60 529 12 Siemens HA 35.51 2000

Appendix Power Transmission and Distribution Group Catalog Index of the Medium- Division (please contact your Siemens Representative) Designation Title Order No. High- and Medium- Equipment High- Equipment (Above 52 kv) HG 21.4 Surge Counting Devices f Surge Arresters E50001-K1521-A401-A1-7600 Medium- Equipment (High- Equipment up to 52 kv) HG 11.11 3AH Vacuum Circuit-Breakers E50001-K1511-A111-A4-7600 HG 11.15 3AY2 Components up to 36 kv f 3AH Vacuum Circuit-Breakers E50001-K1511-A151-A1-7600 HG 11.21 3TL Vacuum Contacts E50001-K1511-A211-A1-7600 HG 11.31 Disconnects and Earthing Switches E50001-K1511-A311-A1-7600 HG 11.51 NXACT Vacuum Circuit-Breaker Modules E50001-K1511-A511-A1-7600 HG 12 Vacuum Switches, Switch-Disconnects, HV HRC Fuse E50001-K1512-A101-A4-7600 HG 13 Switchgear Interlock Units, Control Valves, Compressed Air Systems E86010-K1513-A101-A1-7600 HG 21 Overvoltage Protection E50001-K1521-A101-A1-7600 HG 21.2.5 3EH2 Surge Arresters E50001-K1521-A251-A3-7600 HG 21.2.7 2EE2 Special-Purpose Surge Arresters f the Protection of Mots, Generats and Furnace Transfmers E50001-K1521-A271-A3-7600 HG 22 Insulats of Cast Resin (Excerpt) E50001-K1522-A111-A1-7600 HG 24 Current and Transfmers E50001-K1524-A101-A2-7600 HG 25 Air-Ced Reacts, High- Capacits E86010-K1525-A101-A4-7600 Medium- Switchgear Medium- Switchgear HA 25.21 Type 8BK20 Switchgear up to 24 kv with Withdrawable Circuit-Breakers (Metal-Clad) E50001-K1425-A311-A6-7600 HA 25.31 Type 8BK40 Switchgear up to 17.5 kv/63 ka with Withdrawable Circuit-Breakers E50001-K1425-A411-A3-7600 HA 25.71 NXAIR Withdrawable Circuit-Breaker Module Switchgear up to 12 kv, Air-Insulated E50001-K1425-A811-A1-7600 NXAIR M Withdrawable Circuit-Breaker Module Switchgear up to 24 kv, Air-Insulated E50001-K1425-E811-A1-7600 HA 27.11 Type 8BK30 Switchgear up to 12 kv with Withdrawable Vacuum Contacts E50001-K1427-A111-A3-7600 HA 35.11 Panels up to 36 kv with s,, Types 8DA10 and 8DB10, Single-Pole, Metal-Enclosed, Metal-Clad, Single-Busbar Switchgear, Duplicate-Busbar Switchgear E50001-K1535-A101-A6-7600 HA 35.41 Type 8DC11 Panels up to 24 kv, Fixed-Mounted Vacuum Circuit-Breaker Switchgear, E50001-K1435-A401-A4-7600 HA 35.51 NXPLUS E50001-K1435-A511-A2-7600 HA 40.1 Switchgear f Secondary Distribution Systems up to 24 kv,, Types 8DJ and 8DH: General Part E50001-K1440-A111-A2-7600 HA 41.11 Fixed-Mounted Ring-Main Units up to 24 kv,, Type 8DH10 E50001-K1441-A101-A2-7600 HA 45.11 Secondary Distribution Switchgear up to 24 kv,, Type 8DJ10 E50001-K1445-A111-A7-7600 HA 45.31 Secondary Distribution Switchgear up to 24 kv,, Type 8DJ20 E50001-K1445-A311-A3-7600 HA 51.1 Type 8FB1 Compact Transfmer Substations up to 24 kv E50001-K1451-A111-A2-7600 Siemens HA 35.51 2000 13

Appendix Notes 14 Siemens HA 35.51 2000

Appendix Conditions of Sale and Delivery Expt Regulations Trademarks Subject to the General Conditions of Supply and Delivery f Products and Services of the Electrical and Electronic Industry and to any other conditions agreed upon with the recipients of catalogs. The technical data, dimensions and weights are subject to change unless otherwise stated on the individual pages of this catalog. The illustrations are f reference only. We reserve the right to adjust the prices and shall charge the prices applying on the date of delivery. In accdance with the present provisions of the German Expt List and the US Commercial Control List, expt licences are not required f the products listed in this catalog. An expt licence may however be required due to countryspecific application and final destination of the products. Relevant are the expt criteria stated in the delivery note and the invoice regarding a possible expt and reexpt licence. Subject to change without notice. All product designations used are trademarks product names of Siemens AG of other suppliers. Dimensions All dimensions in this catalog are given in mm. Responsible f: Technical contents: Stephan Werner, Siemens AG, Dept. EV MS1 VM Erlangen General editing: Gabriele Pollok, Siemens AG, Dept. EV BK T Erlangen Printed in Germany KGK 03.00 8.0 VO/- 16 En 101620 6101/D6048 Siemens HA 35.51 2000 15