Orifice Flow Meters POP-S (E5720 rev /03/2013)

Similar documents
Burners. Pilot Heads BTC & BTSA (E3121 rev /09/2010)

Valves. Slow opening and rapid closing solenoid valves VM-L (E1111 rev /11/2012)

Valves. Rapid opening and closing solenoid valves VMR (E1110 rev /11/2012)

Burners. Pilot Heads BTC & BTSA (E3121 rev /04/2018)

Burners. Metallic free flame burners. EMB (E3004 rev /02/2010)

Burners. Ribbon linear flame burners AB & ABM (E3010 rev /11/2017)

Free flame burners EMB (E3004 rev /02/2015)

Burners. Self-recuperative burners high speed free flame REKO-SIK-FF (E3901FF rev /05/2009)

OIL REGULATORS RFG SERIES FEATURES APPLICATIONS DESCRIPTION INSTALLATION. Bulletin E5301 rev03 02/04/03. Body and valve seat: Shutter seat:

Radiant tube burners RT (E3900 rev /01/2018)

Burners. High velocity LOW NOx combustion air burners EMB-SIK-NxT (E3507 rev /11/2016)

Burners. Self-recuperative burners high speed with flat flame REKO-SIK-SW (E3903 rev /06/2015)

Valves. Double stage and modulant motorized butterfly valves MRBV & MRBV-CMAP (E1302 rev /04/2011)

Electronics. Permanent operation microprocessor burner control device ESA GENIO-S (E7021 rev /05/2015)

Electronics. Permanent operation microprocessor burner control device ESA GENIO-PRS (E7022 rev /05/2015)

Electronics. Permanent Operation Microprocessor Burner Control ESA ESTRO-PO (E7014PO rev /05/2013)

Installation, Operation, and Maintenance Manual

TECHNICAL CATALOGUE BLOCK CHECK AND FOOT VALVES

TECHNICAL CATALOGUE EUROPA CHECK AND FOOT VALVES

VF VFH. elektrogas.com. Butterfly valves DN40 DN150 EE155-11/11

VGD20... VGD40... Double Gas Valves. Siemens Building Technologies Landis & Staefa Division

INSTALLATION, OPERATION AND MAINTENANCE TECHNICAL MANUAL

User Guide IM/TORBAR-EN Rev. D. Averaging pitot tubes

ONE STAGE GAS BURNERS RDBS SERIES

RS SERIES. Two Stage Progressive Gas Burners FIRING RATES

INDUSTRIAL MICRODIFFUSION DUAL-FUEL BURNERS

RS/M SERIES. Modulating Gas Burners FIRING RATES

TECHNICAL CATALOGUE BALL VALVES: IDEAL

TWO STAGE PROGRESSIVE AND MODULATING GAS BURNERS RIELLO 40 GS/M SERIES GS 10/M 22/ kw GS 20/M 43/ kw

CONDOR CLASSIC STEAM FIRE TUBE. Design pressure up to 21 bar Steam production from to Kg/h

VLF45... Hot Air Valves. Building Technologies Division

RS/1 SERIES. One Stage Gas Burners RS 34/1 MZ RS 44/1 MZ kw kw GAS

VLF45... Hot Air Valves. Siemens Building Technologies HVAC Products

SENSOR MUT2300. Electromagnetic flowmeter. The electromagnetic flowmeter designed for the toughest applications DS401-1-ENG

Automatic concealed bollards 275 H600 and 275 H800 with pit

TECHNICAL CATALOGUE GAS BALL VALVES: BERLIN

Sheet n 1 of 20 Doc. n WDMM/02/E MOD. WDMM INSTALLATION, USE AND SERVICE MANUAL. PETROL INSTRUMENTS S.r.l APRILIA (LT) - ITALY

TECHNICAL CATALOGUE BALL VALVES: VIENNA

Installation and Operating Instructions DDM-DS11 DDM-DS11-MS1 DDM-DS11-MS2

Specifications of STICKTITE and PILOTPAK Nozzles

TECHNICAL CATALOGUE BALL VALVES: VIENNA

TECHNICAL CATALOGUE BALL VALVES: PARIS

ECONOMATIC REX/REXF REX/REXF DUAL STR

PNEUMATIC PUMP Series

Field proven low emissions. State-of-the-art low NOx firing - adjustable for application flexibility

LVDT/HC PILOT BURNER. External raw gas pilot burner

OPERATING INSTRUCTIONS

Installation and Maintenance Manual MRW-01. Radial Winch 20 ST

Instructions for installation, operation and maintenance of: GATE VALVE

TRANSMITTER ATTACHES TO THIS SURFACE

TECHNICAL CATALOGUE BALL VALVES: IDEAL

HANDBOOK SOLENOID VALVES. Ed SOLENOID VALVES VS-ED 01/ ENG 1

INSTRUCTIONS FOR INSTALLATION, OPERATION AND MAINTENANCE OF

POMPE AUTOADESCANTI SELF-PRIMING ELECTRO PUMP ACM DISASSEMBLY AND ASSEMBLY INSTRUCTIONS FOR MULTISTAGE SELF-PRIMING PUMPS

INSTALLATION AND MAINTENANCE

JUMO flowtrans DP R. Meter run R01 and orifice plate R02. Applications. Brief description. Special features. Customer benefits.

RS/E-EV MZ SERIES. Modulating Gas Burners FIRING RATES

SENSOR MUT2300. Electromagnetic flowmeter. The electromagnetic flowmeter designed for the toughest applications DS401-1-USA

Specifications of LVDT/HC-pilot burner. Materials of construction. Duct burners - LVDT/HC-pilot burner. combustion systems for industry

SARGON S - M - L. All rights reserved INSTALLATION MANUAL

VML. elektrogas.com. Safety solenoid valves for gas Slow opening and fast closing type DN10 DN80 EE

Installation, Operation, and Maintenance Manual

G72x Series Direct Spark Ignition Controls

Orifice Flange Union Assembly and Orifice Run Installation and Operation Manual

TECHNICAL MANUAL MT064

VMH. www. delta-elektrogas.com. Safety shut off valves for gas with hydraulic actuator DN65 DN200 EE

Butterfly valves Figure 56 Installation & Maintenance Instructions

Bevel gearboxes. Catalogue

E Series CE Approved Intermittent Pilot Ignition Control

Flow Meter Terminal Boxes

DOUBLE ECCENTRIC DOUBLE FLANGED BUTTERFLY VALVES. TIS asia

Plunger Heads Use and Maintenance Manual

Orifice plate flowmeters Series PR By-pass flowmeter for liquids, gases and steam

Installation and Maintenance Manual MRW-02. Radial Winch 20 ST

Valves with a difference. Thin Wafer. Check Valves DVC INTERNATIONAL

PCS. Proof of closure switch for safety gas valves. delta-elektrogas.com EE

PETROL. Double Case PD Flowmeters. Trust in us Our Quality Counts. Technical Bulletin. PETROL Instruments S.r.l.

These installation and maintenance instructions must be read in full and completely understood before the installation!

MidFlow _ 135. Sliding Vane Meters DN (1-2 ) Model PT / Fuel Oil Flowmeters135. Product Bulletin

GREENOx BT LOW RETURN TEMPERATURE DUAL BT WITH TILED BOILERS. GREENOx BT COND LOW RETURN TEMPERATURE WITH CONDENSER

Performa Winch 80.3 STP

NEOTECHA NTB-NTC BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

ProFlow TO BE REALLY SURE. Vane Meters. Experience in flow measurement. Introduction

Specifications of STICKTITE and PILOTPAK Nozzles

A Member of the. Integrated Metering Technologies

US - UP2/OIL 12V US - UP2/OIL 24V

26 Series Stainless Steel 2-way Ball Valves

Installation and Maintenance Manual MRW-01. Radial Winch 40.2 ST

Operating Instructions

Performa Winch 50.2 STP

Pressure Reducing Valve Type 2114/2415

Heavy duty slurry pumps

W801S (Downflow) SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] (80% A.F.U.E. )

LOW PRESSURE BALANCED VALVE DIAPHRAGM BALANCED

Kimray reserves the right to modify or improve the designs or specifications of such products at any time without prior notice Kimray Inc.

The information in this instruction manual is subject to modifications without prior notice and is the exclusive property of Zorzini.

L-SEALER MACHINES UNEXPECTED IDEAS

G76x Direct Spark Ignition Controls

INSTALLATION, OPERATION and MAINTENANCE MANUAL for FLOTEC SENSOR

VALIADIS S.A. HELLENIC MOTORS

Transcription:

Accessories Orifice Flow Meters POP-S (E5720 rev. 05-20/03/2013)

GENERAL WARNINGS: DISPOSAL: ¾ All installation, maintenance, ignition and setting must be performed by qualified staff, respecting the norms present at the time and place of the installation. ¾ To avoid damage to people and things, it is essential to observe all the points indicated in this handbook. The reported indications do not exonerate the Client/User from observing general or specific laws concerning accidents and environmental safeguarding. ¾ The operator must wear proper DPI clothing (shoes, helmets...) and respect the general safety, prevention and precaution norms. ¾ To avoid the risks of burns or high voltage electrocutaion, the operator must avoid all contact with the burner and its control devices during the ignition phase and while it is running at high temperatures. ¾ All ordinary and extraordinary maintenance must be performed when the system is stopped. ¾ To assure correct and safe use of the combustion plant, it is of extreme importance that the contents of this document be brought to the attention of and be meticulously observed by all personnel in charge of controlling and working the devices. ¾ The functioning of a combustion plant can be dangerous and cause injuries to persons or damage to equipment. Every burner must be provided with certified combustion safety and supervision devices. ¾ The burner must be installed correctly to prevent any type of accidental/undesired heat transmission from the flame to the operator or the equipment. ¾ The performances indicated in this technical document regarding the range of products are a result of experimental tests carried out at ESA-PYRONICS. The tests have been performed using ignition systems, flame detectors and supervisors developed by ESA-PYRO- NICS. The respect of the above mentioned functioning conditions cannot be guaranteed if equipment, which is not present in the ESA-PYRONICS catalogue, is used. To dispose of the product, abide by the local legislations regarding it. UNI ISO 7/1 GENERAL NOTES: ¾ In accordance to the internal policy of constant quality improvement, ESA-PYRONICS reserves the right to modify the technical characteristics of the present document at any time and without warning. ¾ It is possible to download technical sheets which have been updated to the latest revision from the www.esapyronics.com website. EN746-2 Headquarters: Esa S.p.A. Via Enrico Fermi 40 24035 Curno (BG) - Italy Tel +39.035.6227411 Fax +39.035.6227499 esa@esacombustion.it CERTIFICATIONS: The products manufactured by ESA-PYRONICS have been created in conformity to the UNI EN 746-2:2010 Norms: Equipment for industrial thermal process - Part 2: Safety requirements for combustion and the movement and treatment of combustible elements. This norm is in harmony with the Machine Directive 2006/42/CE. It is certified that the products in question respect all the requirements prescribed by the above mentioned Norms and Directives. These have been designed, produced, controlled and tested in accordance to the company s internal procedures for quality control, certified in conformity with the UNI EN ISO 9001:2008 Norm by DNV Italia s.r.l. Pipe threads for coupling with seals on threads. Size, tolerances and designation. The products conform to the Russian market requirements according to the GOST and GOSGORTEKHNADZOR certification. CONTACTS / SERVICE: International Sales: Pyronics International s.a. Zoning Industriel, 4ème rue B-6040 Jumet - Belgium Tel +32.71.256970 Fax +32.71.256979 marketing@pyronics.be www.esapyronics.com www.esapyronics.com 2

The POP-S calibrated orifice flow meters are accessories designed for indirect air or gas flow measurement via the reading of charts, tables or instruments. The orifice ports are accurately machined for precision measurements. Each orifice flange has its serial number and orifice diameter printed on tab for easy identification and selection. APPLICATIONS ¾ Flow measurements. ¾ Differential pressure reference for burner calibration. ¾ Flow direction control coupled with pressure switches. ¾ Combustion chamber prepurge control or burner ignition at minimum potential (according to the EN764/2 Norm). F5720I03 CHARACTERISTICS Primary measuring element: ¾Threaded flanges (according to UNI ISO 7/1) G25 ¾Welding flanges: Fe 360 ¾Orifice port: galvanized Fe 360/ AISI304 ¾Maximum operating temperature: 400 C ¾Maximum operating pressure: 400 mbar ¾Gasket: AFM-34 / X-Plus Impulse line kit (optional): ¾Pressure outlet: OT58 ¾Fittings: nickel-plated brass/aisi321 ¾Connecting pipes (by customer): copper F5720I04 www.esapyronics.com 3

DESCRIPTION The POP-S plates are simple flow measuring orifices for measuring fluid flow through differential pressure devices. The flow measurement principle is based on the installation of a calibrated orifice inside the piping. The presence of this orifice causes a static pressure difference between the upstream and downstream sections of the orifice. Measuring takes place via a secondary element, consisting mainly of a differential pressure gauge or a pressure transmitter. In combustion plants, calibrated flanges are the ideal instrument for measuring and controlling air and gas flow. The AIR/GAS ratio regulation in burners is simplified when the precise combustion air and fuel gas flow volumes are known. MIN. LENGTH 100mm BY CLIENT MIN. LENGTH 100mm BY CLIENT D5720I01 INFORMATION FOR SIZING To be able to correctly size the port of the orifice found inside the POP-S calibrated flanges, the following project data must be known: ¾ Fluid type ¾ Nominal flow rate of the pipeline ¾ Differential pressure on the calibrated flange ¾ Operating pressure and temperature ¾ Nominal diameter of the pipeline (DN) ¾ Internal diameter of the pipeline (if not standard) POSITION OF THE MEASURING ORGAN Seen as the POP-S calibrated flanges are not manufactured according to the UNI EN5167-2 Norm, they do not need to have lengthy parts upstream or downstream. Correct installation entails a rectilinear part of at least 100mm upstream and downstream. The POP-S calibrated flange must have a constant inlet pressure. This is why it must be installed immediately after the interception valve or however, upstream any regulation or flow organ. D5720I02 www.esapyronics.com 4

FLOW SWITCH The 2010 version of the EN746/2 Norm updated the part for the check that must be done regarding the purging of the combustion chamber during furnace start-up and burner ignition with nominal power higher than 120kW, which must necessarily take place below 33% of the power. Following this update, it is not sufficient to use a minimum air pressure switch on the piping that ensures the correct blower ignition, but a differential pressure switch must also be used (that in this case becomes a minimum air flow switch) that can read the Dp (differential pressure) of a calibrated flange and that allows chamber purge to be activated as soon as the measured air flow rises above 80% of the maximum nominal flow of the plant. In the same way, it is not possible to switch the burners on at minimum potential relying exclusively on the servomotor limit switch. But a differential pressure switch is used (that in this case becomes a maximum air flow switch) which gives burner ignition consent below 33% of the nominal power of each burner. For the above mentioned applications, it is advisable to use a POP-S calibrated flange that is correctly connected to a pair of differential pressure switches as indicated in the diagram. A special kit for mounting the pressure switches can be supplied. 62 Nr.2 holes n 7 THE FLOW SWITCH ASSEMBLY MUST BE FIXED IN POSITION BY CLIENT, USING THE SPECIAL HOLES ON THE PLATE. D5720I03 FLOW SWITCH ASSEMBLY FOR ORIFICE FLOWMETER MOD. POP-S UPSTREAM ORIFICE FLOWMETER PRESSURE INLET Copper pipe Ø8 (+) (-) FLOW OUTLET DOWNSTREAM ORIFICE FLOWMETER PRESSURE INLET Copper pipe Ø8 FLOW INLET THE IMPULSE LINE ARE INCLUDED IN THE ORIFICE FLOWMETER ASSEMBLY D5720I04 www.esapyronics.com 5

WARNINGS ¾The POP-S flanges are suitable for strict flow measurements such as readings for electronic ratio regulation or consumption measures (fiscal and non). ¾Make sure that the operating pressure and the fluid temperature are lower than the maximum values allowed. ¾Check the correct installation according to the indications given in the appropriate paragraph of this data sheet. ¾Any type of alteration or repair carried out by third parties may compromise the application safety and automatically invalidates the warranty conditions. INSTALLATION Maintenance and installation must be performed by qualified staff respecting the norms in force. After installation it is always advisable to check the tightness of the threads or flanged connections. MOUNTING OF THREADED FLANGES 1 - Disassemble the flange. 2 - Using thread sealing paste, screw the flanges (pos. 01) one by one onto the piping (pos. 02), guaranteeing adequate thread tightness (pos. 03). 3 - Make sure that there are no foreign objects inside the flange (pos. 01) or in the pipes (pos. 02) before assembling. If necessary, remove any impurities. 4 - Check the correct alignment of the connecting pipes (pos. 02) and check that the distance between the pipes and assembly is correct (flanges pos. 01 / gaskets pos. 04 / orifice pos. 05), to avoid exerting tension on the piping during the tightening phase. 5 - Position the gaskets (pos. 04 selected according to the type of fluid) and insert the bolts (pos. 06). 6 - Position the calibrated orifice (pos. 07), keeping the printed information facing downwards. 7 - Using suitable tools, progressively screw on the bolts (pos. 06) crosswise, avoiding excessive tightening. 8 - Check the tightness of the threaded connections (pos. 03) with a leak detection product by pressurizing the pipe. MOUNTING OF WELDING FLANGES 1 - Disassemble the flange. 2 - Make sure that there are no foreign objects inside the flange (pos. 08) or in the pipes (pos. 09) before assembling. If necessary, remove any impurities. 3 - Check the correct alignment of the connecting pipes (pos. 09) and check that the distance between the pipes and assembly is correct (flanges pos. 08 / gaskets pos. 10 / orifice pos. 11), to avoid exerting tension on the piping during the tightening phase. 4 - Weld the flanges (pos. 08) at the ends of the piping (pos. 09), eliminating any remaining welding burrs. 5 - Position the gaskets (pos. 10 selected according to the type of fluid) and insert the bolts (pos. 12). 6 - Position the calibrated orifice (pos. 11), keeping the printed information facing downwards. 7 - Using suitable tools, progressively screw on the bolts (pos. 12) crosswise, avoiding excessive tightening. 8 - Check the tightness of the flanged connections with a leak detection product by pressurizing the pipe. 01 04 01 02 03 06 02 03 09 09 05 12 08 08 10 11 D5720I05 www.esapyronics.com 6

GENERAL MAINTENANCE PLAN Operation Type (*) Advised time Gasket integrity O annually Bolt tightening S annually Notes Check that there are no gas leaks towards the outside. Reduce to half-yearly in applications with vibrations. NOTES: Key: O=ordinary / E=extraordinary (*) it is advisable to replace the gaskets each time the flanges are disassembled. EXTRAORDINARY MAINTENANCE For correct maintenance of the POP-S flanges, scrupulously follow the instructions below that are to be carried out with the plant off. BOLT TIGHTENING 1 - Bolt tightening check must take place with the plant off. GASKET REPLACEMENT 2 -Progressively unscrew the screws that hold the valve in a criss-cross way. Extract the orifice and replace the gaskets. 3 - Clean the inside of the orifice with a clean cloth and compressed air. Do not use any tools that could damage the internal parts. www.esapyronics.com 7

OVERALL DIMENSIONS OF THREADED MODEL Ø"C" Ø"A" "D" "B" "E" "E" "F" D5720I06 Threaded connections ø A [mm] [mm] [mm] [mm] [mm] [Kg] B ø C D E ø F Mass Model 3 POP-S G - 3/8 60 60,3 79 21 48 1.0 4 POP-S G - 1/2 60 60,3 79 21 48 0,9 6 POP-S G - 3/4 60 60,3 79 21 48 0,8 8 POP-S G - 1 60 60,3 79 21 48 0,8 10 POP-S G - 1.1/4 76,2 81 95 30,5 67 1,3 12 POP-S G - 1.1/2 76,2 81 95 30,5 67 1,1 16 POP-S G - 2 87,3 96,8 107 30,5 67 1,5 OVERALL DIMENSIONS OF FLANGED MODEL Ø 81 3 Ø"D" Ø"E" "B" Ø "A" 18 18 42 D5720I07 Model Pipe connections ø ø A [mm] B [mm] ø C [mm] ø D [mm] ø E [mm] 20 POP-S 2.1/2 100 122 111,1 77 68 2.0 24 POP-S 3 110 130 123,8 90 80 2,4 32 POP-S 4 150 172 168,1 115 106 4,4 40 POP-S 5 200 222 235 142 133 8,0 48 POP-S 6 200 222 235 170 157 6,5 Mass [Kg] www.esapyronics.com 8

ORDERING CODE - COMPLETE FLANGE WITH CALIBRATED OFRIFICE 01 - POP - S MODEL 01 3 4 6 8 10 12 16... 3 4 6 8 10 12 16... see table pg. 8 ORDERING CODE - ONLY CALIBRATED OFRIFICE 01 - OP - S MODEL 01 3 4 6 8 10 12 16... 3 4 6 8 10 12 16... see table pg. 8 www.esapyronics.com 9

ESA worldwide distribution AUTHORIZED DISTRIBUTION STAMP If you have any doubt about the qualifi cation or identity of the distributor, please check that they appear on our website www.esapyronics.com in the Sales Contacts section, or contact us directly at esa@esacombustion.it 2012 ESA S.p.A. Company under the management and coordination of SIAD S.p.A. All rights reserved. The information contained herein is offered for use by technically qualifi ed personnel at their discretion and risk without warranty of any kind. We regularly update our data, for updated data please visit our web site www.esapyronics.com Printed in Italy CATukR00/12 Head Office and Factory ESA S.p.A. Company under the management and coordination of SIAD S.p.A. Via E. Fermi, 40 I-24035 Curno (Bergamo) ITALY esa@esacombustion.it www.esapyronics.com Tel. +39 035 6227411 Fax +39 035 6227499 Share Capital euro 153.111,00 paid up - Fiscal Nr.: 03428410157 - V.A.T. Nr.: (IT) 00793030164 Reg. Impr. Bg Nr.: 03428410157 - R.E.A. BG-173124 - Export: BG0061150 www.esapyronics.com Pyronics International s.a. Zoning Industriel, 4ème rue B-6040 Jumet BELGIUM marketing@pyronics.be www.esapyronics.com Tel. +32 71 256970 Fax +32 71 256979