Technical Information THYRISTORS T-PH from 5A to 700A Specifications Universal Phase Thyristor Unit 55-77-03-63, March 0 GENERAL DESCRIPTION THYRISTORS T-PH is a full digital and universal Thyristor unit based on a very powerful dedicated micro configurable via serial communication port for all inputs, firing modes, control modes and loads types. Suitable to drive resistive, inductive, transformer with normal resistor. Two legs switching three wires loads STAR or DELTA connection. Frontal Key Pad standard to configure all the internal functions and parameters. Four Analog output configuirable. Six Digital input. Four realay output. Universal Input signal with automatic zero/span calibration. Universal Firing modes, customer configurable via Key Pad or communication port as Burst Firing or Delayed Triggering. Universal Feed back modes. Unbalanced load and Heater Break Alarm. RS 85 port. Modbus protocol. Comply with EMC and * up to 500A. IP0 Protection. * cul approval up to 600A included.
TECHNICAL SPECIFICATION Operating Temperature 0+0 C over this temperature see derating curve. Voltage Power supply 80V standard, 600V or 690V on request. Auxiliary Voltage Supply 90 65V, 0VA power consumption. Fan voltage supply: 30V ±5% as a standard and 0V on request. Analog Input Main reference, 0mA, 0 0V, 0KPOT, RS85 port. Analog Input Secondary reference, 0 0V, 0KPot. Analog Ouput Digital Input Relay Output Universal Firing Control Mode Heater Break Alarm Unbalanced load Communication Thermal protection Four Analog output (0 0mA or 0mA)for retransmission of Voltage or Power and current for each Phase. Six optoisalated digital intput (/Vdc), for START, STOP, ENABLE, CALIBRATION, RESET ALARM and EXTERNAL ALARM. Three configurable relay output and one critical alarm. One of these firing modes can be configured Burst Firing BF, Delayed Triggering. Voltage (V), Power (VxI) and External feedback. Circuit microprocessor based to diagnose partial or total load failure and short circuit on Thyristors. This protection allow to have Multidrive working up to 0% of unbalance on one phase. RS85 Port. Modbus communication protocol 9600 or 900 bauds. Available on forced ventilated units. 0.8 0.6 0. 0. Derating curve
HEATER BREAK ALARM HB ON FRONT CABINET = FEW MINUTES TO SET AND CALIBRATE ALL THE UNITS The Heather Break circuit diagnostic partial or total load failure. It reads load resistance with an internal voltage transducer and current transformer to calcolate the resitance value V/I. The Heather Break circuit is compensated for voltage fluctuation,infact a voltage variation has no influence on resistance value because V/I ratio remain constant. On this unit is possible to set the nominal resistance and the alarm sensitivity. HB alarm in addition diagnostic the thyristor in short circuit. A normaly open contact gives the alarm condition and an indication of the alarm type appears on display. BURST FIRING BF This firing is performed digitally within the thyristor unit at zero volts, producing no EMC interference. Analogue input is necessary for BF and the number of complete cycles must be specified for 50% power demand. This value can be between and 55 complete cycles, determining the speed of firing. When is specified, the firing mode becomes Single Cycle (SC). DELAYED TRIGGERING DT CD EASY Used to switch the primary coil of transformers when coupled with normal resistive loads (not cold resistance) on the secondary, DT prevents the inrush current when zero voltage (ON-OFF) is used to switch the primary. The thyristor unit switches OFF when the load voltage is negative and switches ON only when positive with a pre-set delay for the first half cycle. This is a memory support tool that can be used by mantenance personnel on shop floor. The user can copy the configuration of one unit and paste it into another.cd EASY is very simple with one push button to upload the configuration (Read and another to down load the stored configuration (Write) This tool can be used with our Remote service to mail the working configuration via internet. CD-KP FIELD BUS MODULE The CD-KP is designed mounted on front cabinet and to be connected with all cd automation s Thyristor units via RS85. On front unit is possible to read parameters, power, current, reference and alarms. One of these variables can be selected and retransmitted via an isolated output ( 0mA or 0 0V) On front unit is available a connector to comunicate with PC. In addition are available Local/Remote, up and down and function command. CD-RS Used to convert RS3 to RS. TU-RS85-PDP Used to convert RS85 Modbus to Profibus DP. TU-RS85-ETH Used to convert RS85 Modbus to Ethernet. For more informations see "Field Bus Module" bulletin. POWER SCALING APPLICATIONS AND FOCUS ON: It's a scaling factor of the input command signal and limit the output of Thyristor unit. This parameter can be adjusted from to 99% via RS85 or by the front of the unit If this parameter is setted at 50% and the input signal is 00% the output become 50% This feature is very useful to reduce the power when a zone has been oversized or when a temperature controller gives same reference to more unit along a furnace. Imagine 3 zones with left and right one close to the doar where in acontinuos furnace the material come into and flow out.the profile of temperature along furnace is higher in central zone because there is less dispersion but if we scale its input we can have a flat profile. Infrared lamp Autoclaves Fournaces Chemical Petrochemical Climatic chambers Pharmaceutical 3
WIRING CONNECTION THYRISTORS T-PH from 35A to 700A THYRISTORS T-PH THYRISTORS LOAD TYPE LOAD TYPE NOTE Delta Star () The user must provide for protection external electromagnetic circuit breaker or fuse isolator. () Use an appropriate external transformer to supply of the electronic board (see the identification label). (3) The coil contactor, the relays and other inductive loads must be equipped with proper RC filter. () Before give the Start command supply the input of auxiliary voltage. DIMENSION AND FIXING HOLES H H W D W D S3 W 6 mm. - H 0 mm. - D 70 mm. - kg. 8 5A 5A S W 6 mm. - H 50 mm. - D 70 mm. - kg.,5 300A 850A S6 PH H 580 x W 00 x D 35-5kg. (000A) S7 PH H 780 x W 00 x D 35-65kg. (00/500A) S3 PH H 780 x W 55 x D 533-96kg. (850/000A) S PH H 890 x W 55 x D 58-6kg. (00/700A)
OUTPUT FEATURES (POWER DEVICE) Current A Voltage range (V) Ripetitive peak reverse voltage (600V) (690V) Latching current (maeff) Max peak one cycle (0msec.) Leakage current (maeff) IT value for fusing tp=0msec. Frequency range (Hz) Power loss I=Inom (W) Isolation Voltage Vac 5A 330 690V 600 800 50 000 5 750 7 70 99 500 75A 330 690V 600 800 50 350 5 8830 7 70 80 500 00A 330 690V 600 800 50 50 5 300 7 70 0 500 5A 330 690V 600 800 50 000 5 Fre900eF 7 70 300 500 50A 330 690V 600 800 50 000 5 900 7 70 360 500 5A 330 690V 600 800 300 800 5 900 7 70 50 500 75A 330 690V 600 800 300 800 5 08000 7 70 660 500 00A 330 690V 600 800 00 7800 5 08000 7 70 960 500 50A 330 690V 600 800 00 7800 5 300000 7 70 080 500 500A 330 690V 600 800 00 8000 5 306000 7 70 00 500 600A 330 690V 600 800 000 7800 5 07000 7 70 0 500 700A 330 690V 600 800 000 7800 5 07000 7 70 50 500 850A 330 690V 600 800 000 7800 5 07000 7 70 680 500 000A 330 600V 600 N.A. 700 500 300 78000 7 70 00 500 00A 330 690V 600 800 700 600 300 306xE3 7 70 3080 700 500A 330 600V 600 N.A. 700 600 300 306xE3 7 70 3750 700 850A 330 690V 600 800 700 36000 300 680xE3 7 70 070 500 000A 330 600V 800 N.A. 700 36000 300 680xE3 7 70 00 500 00A 330 690V 800 800 700 60000 300 80000xE3 7 70 533 500 700A 330 600V 00 N.A. 700 60000 300 80000xE3 7 70 6750 500 ORDERING CODES 3 5 6 7 7 8 9 0 3 5 6 THYRISTORS T-PH T - Note, 5, 6 Current 7 Max Voltage Control Mode Approvals 35A 0 0 3 5 5A 75A 00A 5A 50A 5A 80A 00A 50A 500A 600A 700A 850A 000A 00A 500A 850A 000A 00A 700A 0 0 5 0 0 7 5 0 0 0 0 5 0 5 0 0 5 0 8 0 0 0 0 0 5 0 0 5 0 0 0 6 0 0 0 7 0 0 0 8 5 0 0 0 0 () 0 0 5 0 0 () 8 5 0 0 0 0 () 0 0 7 0 0 () 80V 600V 690V 6 7 8 Aux. Voltage supply 0V 30V 9 Input SSR 3:30V dc 0:0V :0mA 0KPot RS85 S V A K R 0 Firing Burst Firing BF B Delayed Triggering + Burst Firing DT+BF D Open Loop Voltage Feed Back V Power Feed Back VxI Current Feed-back I 0 U W I Option :0mA Retransmission Load Current and Control Mode A (3) 0:0V Retransmission Load Current V (3) and Control Mode 3 Fan Voltage Fan Voltage equal to Aux. Voltage 3 CE EMC For European Market cul For American Market up to 700A 0 L () 5 Manual None Italian Manual English Manual German Manual French Manual 0 3 6 Load type/connection Resistive Load/ Delta Connection Resistive Load/ Star Connection Transformer Load/ Delta Connection 3 Transformer Load/ Star Connection Note (): After 6th digit write current and voltage of load inside brackets Ex. (90A- 00V). this is to receive the Thyristor unit already tuned from Honeywell. Note (): Rating not available at 690V. Note (3): In total are available Analog output. One dedicated to control mode and the other 3 for current on phases --3. Note (): cul Approval up to 700A included. 5
SALES AND SERVICE For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one of the offices below. ASIA PACIFIC EMEA NORTH AMERICA SOUTH AMERICA hfs-tac-support@honeywell.com Australia Honeywell Limited Phone: +(6) 7-386 55 Fax: +(6) 7-380 68 Toll Free: 300-36-39-36 Toll Free Fax: 300-36-0-70 China - PRC - Shanghai Honeywell China Inc. Phone: (86-) 557-568 Fax: (86-) 637-86 Honeywell Process Solutions Phone: + 8000655 or + (0)065583 Fax: + (0) 3 65555 Email: (Sales) sc-cp-apps-salespa6@honeywell.com or hfs-tac-support@honeywell.com Honeywell Process Solutions Phone: -800-3-9883 or -800-33-08 Email: (Sales) ask-ssc@honeywell.com or hfs-tac support@honeywell.com Honeywell do Brasil & Cia Phone: +(55-) 766-900 Fax: +(55-) 766-905 Email: (Sales) ask-ssc@honeywell.com or hfs-tac-support@honeywell.com Singapore Honeywell Pte Ltd. Phone: +(65) 6580 378 Fax: +(65) 65-3033 South Korea Honeywell Korea Co Ltd. Phone: +(8) 799 6 Fax: +(8) 79 905 Specifications are subject to change without notice. For More Information Learn more about how Honeywell s THYRISTORS T-PH and how it can help improve plant performance. Visit our website www.honeywellprocess.com/ or contact your Honeywell account manager. Honeywell Process Solutions 860 West Rose Garden Lane Phoenix, Arizona 8507 Phone: -800-3-9883 or -800-33-08 www.honeywellprocess.com/ 55-77-03-63 March 0 0 Honeywell International Inc. 6