Using an SMC-50 Solid-State Smart Motor Controller for Pump Protection

Similar documents
Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

When to use a Soft Starter or an AC Variable Frequency Drive

Working Principle of Power Saver as per Manufacture:

SMC -50 Technology and Control Advances

Pump ED 101. Power Factor (Part 2) - - Electricity Behaving Better

Alternator as a voltage Generating source and its response to the leading power factor loads

825-P Modular Protection System for motors Specification Guide

Is Uncorrected Power Factor Costing You Money?

ABB Softstarter Benefits Charnchanok Thongprad

Is Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics

RVS-DN Digital Reduced Voltage Motor Starter

CTi Automation - Phone: Fax: Web:

Power Factor Correction

CSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date:

Blower Drive Checkout for 3GIBC1 Systems

Variable Speed Drives Controlling Centrifugal Pumps Energy Savings

Hp V AC Current Rating [A] 230V AC 60 Hz

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

Application Description

150 B180 N B D A 8L. Enclosure Type. Input Line Voltage Open Type V AC, 3-phase, 50 and 60 Hz V AC, 3-phase, 50 and 60 Hz

Variable Speed Pumping

RVS-DX Digital Reduced Voltage Motor Starter

Pump Panel Specifications

Principles of iers (intelligent

A softstarter beyond the ordinary

Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80

RVS-AX Instruction Manual

Exercise 6. Three-Phase AC Power Control EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to three-phase ac power control

Unit Protection System for Pumped-Storage Power Stations

MODEL 422 Submersible Pump Controller

Selection Guide for SMC-Delta and SMC-3. A New Dimension in Motor Control

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Unit-II Synchronous Motor

Starts, stops and protects. Emotron TSA Softstarter

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

ECH 4224L Unit Operations Lab I Fluid Flow FLUID FLOW. Introduction. General Description

PowerFlex AC Drives Portfolio

UPS Ratings-Not so Apparent

Overcurrent protection

SECTION MOTOR CONTROL

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Electrical Power Electric power electrical electric power Electric power electric electric

CENTRIFEEDER ELECTRONICS

Variable speed application guidelines

Power Switching Principles

Best Practice Variable Speed Pump Systems

General Issues of Line Leak Detection

Dual Power. Protection. Protection

Understand how soft starters operate.

Motor Protection Fundamentals. Motor Protection - Agenda

DRAFT 1400HP 1000HP 100HP. Reduced Voltage Solid State Starters. Softstarters SOFT. PF Controller PCS Controller PDS Controller V 1...

ADVANCED PID TROUBLESHOOTING

American Traction Systems. DC Bus Capacitorss. Total. Dual Chopper Module. Dual. Inverter. 750kW. 750kW Generator Module. Module

Magellan Utility Scale Energy Storage

Components of Hydronic Systems

Single-Phase Meter Components

Legat-65. Voltage Stabilizer Technical Certificate. NOVATEK-ELECTRO LTD Research-and-Manufacture Company

White Paper. Application of Resistive/Reactive Load Banks for kva Testing

The purpose of this lab is to explore the timing and termination of a phase for the cross street approach of an isolated intersection.

BLACKBIRD OWNER S MANUAL

Product Instruction. Door Control Board: Board 1Ø4 for PM/SSC (R3)

VASCO. Variable Speed Controller ENGLISH

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

Size for Size Best Value in the Industry

Synchronous Generators I. Spring 2013

Benefits of a Cooling Tower VFD Retrofit

Fisher CAV4 Control Valve

Selective Coordination

Introduction to hmtechnology

ECE 480 Design Team 3: Designing Low Voltage, Low Current Battery Chargers

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

1 Low-voltage Power-factor Correction capacitors KNK APPLICATION DESIGN

Series Motor Protection

VERTICAL MULTI-STAGE CENTRIFUGAL PUMPS

DC CIRCUITS ELECTROMAGNETISM

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications

KD LV Motor Protection Relay

Synchronous Generators I. EE 340 Spring 2011

Signature Series. Duplex Softener Service Manual

Welcome to the SEI presentation on the basics of electricity

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

IMPROVING MOTOR SYSTEM EFFICIENCY WITH HIGH EFFICIENCY BELT DRIVE SYSTEMS

Inverter control of low speed Linear Induction Motors

T-Line Generator Control, Protection and Monitoring

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

NOVATEK-ELECTRO LTD Research-and-Manufacture Company Voltage Stabilizer Legat-35

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech

TRIPS AND FAULT FINDING

APPLICATION GUIDE. Pure easiness for a wide range of applications ACS580 general purpose drives

three different ways, so it is important to be aware of how flow is to be specified

Dealing with customer concerns related to electronic throttle bodies By: Bernie Thompson

Use these modules to gain valuable knowledge about STIHL policies, procedures and products that will be a benefit to you on the job immediately.

NOVATEK-ELECTRO LTD Research-and-Manufacture Company. Legat-5M. Voltage Stabilizer. Technical Certificate.

Features IN THIS CHAPTER

VERTICAL MULTI-STAGES CENTRIFUGAL PUMPS

The Discussion of this exercise covers the following points:

CENTERLINE 2500 Low Voltage Motor Control Centers and Switchgear Assemblies

Fuseology. Dual-Element, Time-Delay Fuse Operation

Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module.

SPECIFICATIONS NB SKILLS TRADE 19 AUTOMATION AND CONTROL

Transcription:

Using an SMC-50 Solid-State Smart Motor Controller for Pump Protection William Bernhardt and Richard Anderson, Rockwell Automation Pump system protection comes in many methods, from preventing water hammer to detecting potential pump blockage. You need this protection to help prevent further damage or to keep damage from occurring at all. The damage in a pumping application can cause a critical operation to stop and cause flooding or no water supply. Prevention of water hammer during starting and stopping of a pump motor can easily be fixed by controlling the ramp and deceleration of the motor. The use of a properly set soft starter or a variable frequency drive can assist greatly with water hammer. But what about damage to pumps caused by partial blockage or absence of fluid? Partial or complete blockage is costly and time consuming to repair. Some of the damage can cause immediate erosion of parts such as pump impellers. Other damage could take time and lead to costly repairs and downtime in the future. Without some form of detection, a maintenance person, seeing the system is not working properly, has to go out and see what the issue is. Trying to figure out what is going on may also mean taking the system apart. This paper discusses the use of technology to warn of damage or to stop a process from damage. Pump Issues A by-product of partial blockage on the inlet side of a pump is cavitation. Cavitation could be very damaging to a pump and other components in a system. Cavitation and flashing (see page 2) can cause pitting or erosion of metal parts within a pump, or other metal components in the system. Blockage frequently adds vibration and noise to the pumping system. Cavitation is typically a result of restriction of liquid flow (oil, water, etc) in the pump system. From Bernoulli's principle, a decrease in area will have an increase in velocity, which will in turn have a decrease in pressure. The arrows in Figure 1 show the direction of water flow in a pump system.

2 Figure 1 - Bernoulli s Principle Illustration Less Area Higher Velocity Lower Pressure More Area Slower Velocity Higher Pressure More Area Slower Velocity Higher Pressure When the pressure in the line feed drops due to a restriction or a partially closed valve, the velocity of the fluid increases and vaporization occurs if the pressure drops below the vapor point, forming bubbles. If the pressure continues to drop downstream from the vena contracta (narrowest point or diameter of the flow restriction), the bubbles get bigger. When the bubbles flow to a larger volume area, the velocity slows and the pressure increases. The bubbles have an internal pressure less than the surrounding volume pressure at this point. The bubbles now collapse and the surge of energy causes pressure waves with possible levels as high as 60,000 100,000 psi. There is noise and possible vibration associated with the collapse back to liquid. This collapse of bubbles and the resulting pressure surge, along with the associated noise and vibration, is called cavitation. Damage from cavitation can be very quick, very destructive, and very costly. Flashing occurs when the pressure of a fluid falls below its vapor pressure. At this point, the fluid begins to change from a liquid to a vapor that may still have small droplets of fluid in it, both of which have the same chemical makeup. Flashing damage is slower and results in smoother damage to components like smooth river rocks. The damage from flashing takes longer to occur than the damage caused by cavitation. Graphically, if pressure falls below the vapor pressure curve, and temperature stays the same, there is the possibility of reaching the vapor state of the liquid. The same thing happens in the opposite direction if you raise the temperature and the pressure stays the same as in commonly seen in boiling water.

3 Figure 2 - Cavitation Curve Liquid High Pressure Vapor Low Temperature Signs of Cavitation in the Power System From a motor performance perspective, a drop in current, low power factor (PF), and drop in real power could all be warning signs of cavitation. Current measurement by itself is not necessarily the most accurate method as explained further in this paper. The more power information a device can collect, the better its ability to indicate signs of cavitation. Vibration is another byproduct of cavitation as the vapor returns to a solid and the pressure expands. In most cases, you can clearly hear the vibration caused by cavitation. Dry Runs Similar to and possibly partly caused by cavitation, a dry run is a situation in which a pump is run without liquid. It could be caused by a closed suction valve or other blockage in the suction line. Running dry can cause thermal and mechanical failures within the pumping system. Low or No Flow Discharge Blockage or partial blockage on the discharge side can cause vibration and may reduce the minimum required flow rate of a given pump. The reduction in flow rate may cause damage thermally and mechanically to the system, because most pumps have recommended operational range. Operating outside of the range may cause damage to the pump.

4 Overload Conditions Jammed impellers, oversized impeller, improper fitting of system components, bearing failures, and improper head pressure for the pump size are just a few examples of situations that can cause overload conditions on a pump. An overload can cause thermal and mechanical damage. What are some available preventive options? Some options available are relays marketed as being suitable to detect cavitation and prevent dry running. Some of these only monitor a single phase and have to work in conjunction with an externally mounted Current Transformer (CT). In some cases, a toroid is also used in conjunction with a CT to bring current feedback in the case of larger motors. Other components, such as resistors, may also be needed. These add up to extra components and wiring needed to do the job of measuring the current. While it appears most devices use current to help diagnose cavitation and prevent a dry running pump, some use power measurements. You can use power measurements such as power factor and real power. Figure 3 shows the motor performance from no load to approximately ¼ load; the current rise is very slight, almost flat. At this load, using current only as a monitoring metric has very limited usefulness, outside of monitoring for overload. Above ¼ load, the current begins to increase substantially. Properly sizing the motor for the application benefits the protection of the pump system. Oversizing the motor too much will reduce the range of opportunity to detect an issue with the system. For example if the motor is 50% loaded nominally, current has barely changed in Figure 3. Power factor and horsepower rise significantly for the same duration starting at no load. The combination of the power factor and horsepower may be a better indication of cavitation or some other issue going on with a pump application. Figure 3 - Motor Load Performance 250 150 Hp Motor Loading Performance 200 150 100 50 0 0 No Load 1/4 Load 1/2 Load 3/4 Load 4/4 Load 5/4 Load Hp Current % Power Factor Horsepower (or Watts) would range from zero, where no work is done, to the rating of the motor, or slightly higher, depending on the load. This would appear as almost a straight line.

5 The equations for 3-phase power are as follows: kw = Volts x Amperes x Power Factor x 3 Volts x Amperes x Efficiency x Power Factor x 3 Hp = 1000 746 Current level is the amount drawn on the given portion of work performed from the motor. Many factors are taken into account to produce the no-load current, including the number of poles of the motor and reactive power. Maintaining the magnetic field of the motor is the main reason why current does not drop to zero with no load. Power Factor ranges from 0.0 to 1.0. A 1.0 power factor is a purely resistive load. 0.0 is usually inductive. The lower the PF, the lower the efficiency of the system. Real power (kw) performs the actual work of the motor. In the case of a PF value of 0, no real power is present. Reactive power (kvar) is the power that is needed to magnetize the motors Apparent Power x sin Θ = VIsin Θ Apparent power (kva) is the combination of real and reactive power. For typical loads with reactance, the equation is: (Real Power 2 + Reactive Power 2 ) Power Factor is the ratio of real power to apparent power. PF = Real Power Apparent Power = cos Θ Figure 4 illustrates this graphically and geometrically in the power triangle. Figure 4 - Power Triangle Apparent Power Reactive Power θ = Power Factor Real Power For overload conditions, different types of standalone devices are used based mainly on an increase in current. Devices like soft starters may have the overload functionality built in. Rockwell Automation Solution The SMC -50 solid-state smart motor controller is a solid-state soft starter that has vast starting, stopping and power measuring capabilities with the ability to add more functionality with option cards for communication and

6 expansion I/O. The ability to smoothly start or stop a pump without water hammer using a linear acceleration, pump start, or soft start (or soft stop) is only a matter of a parameter setting. What enhances and sets the SMC-50 soft starter apart from competitors is the ability to actively monitor valuable power information that can be used to assist in detect damaging cavitation and assist in preventing dry runs in pumping applications. Easily programmable alarm and fault levels assist in indicating the system issues. The SMC-50 soft starter has the ability to monitor power factor in all three phases in addition to providing a total average. With the ability to monitor over and under power factor, also comes the ability to monitor whether it is leading or lagging. A lagging PF is when load current lags voltage. Lagging PF is indicative of an inductive (motor) load. Leading PF indicates a capacitive load when load current leads voltage. To assist with eliminating false trips, you can program delays from 0.1 to 99 seconds before an enunciation of the fault is performed. As the power factor drops below a settable value, that value could be used to indicate cavitation and provide feedback (alarm) or stop the soft starter (fault). Any time the SMC-50 soft starter faults, a snap shot is taken of the following parameters. Phase Voltage (A-B, B-C and C-A) Phase Current (A,B and C) Power Factor Motor Thermal Usage Motor Speed THD Voltage Average THD Current Average Product Status Board Temp Line Frequency This aids in the troubleshooting of the issue with the system. Real, reactive, and apparent power for each phase with alarms and faults for each is part of the SMC-50 parameter structure. Since reactive power doesn t change much when changing loads to the motor, real power is a better method of detecting cavitation or low loading conditions. Remembering Figure 3, the best indication of an issue with underload conditions is monitoring and using these values, especially when cavitation or a dry run is possible. Using current alone is not accurate enough. With the pump application detection methods inherent to the SMC-50 soft starter, it may be possible to use the slow speed reversing function to unclog a blockage when something has been pulled into the pipes, for example, a blockage in a sewage influent pump. Once the blockage is detected by the appropriate power parameters, the slow speed function could be used to reverse the flow for a short period of time with the hope of unplugging the intake and not requiring manual intervention. Additionally, using option cards such as the 150-SM3 Analog I/O Module would allow feedback from a flow meter to the SMC-50. You could possibly use the analog data with the included DeviceLogix capabilities programming for control. You can download free Connected Components Workbench software to create the DeviceLogix program in addition to programming the SMC-50 soft starter. Overload protection is also standard with the SMC-50 soft starter, which covers the overloading issues the pump may have. An adjustable overload trip class is used to dial in the appropriate setting for the given pump system, potentially preventing further damage to the motor, pump and system.

Conclusion Pumping applications can be very dynamic and, being so, using dynamic protection is the best way to protect the system. Proper protection could prevent, or at least limit, damage to equipment such as impellers and pumps themselves. Proper protection can include notification of changes in the system. After something is damaged, not only is there the cost of the item itself, but down time, troubleshooting, uninstalling, and reinstalling the new part. Prevention is much more cost effective. The SMC-50 soft starter successfully starts the pump system with a choice of starting options, and offers broad power monitoring capability to monitor how the pump system performs. It also has the ability to indicate if an issue is beginning to take place. Allen-Bradley, LISTEN. THINK. SOLVE. SMC, and Rockwell Software are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Publication 150-AT003A-EN-P - December 2015 Copyright 2015 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.