G600 Series Replacement Intermittent Pilot Ignition Controls

Similar documents
G76x Direct Spark Ignition Controls

G72x Series Direct Spark Ignition Controls

G861 Series Integrated Function. Direct Spark Ignition Control

G821L/G822L Series Integrated Function Direct Spark Ignition Controls

BG1600M Intermittent Pilot Ignition Control

E Series CE Approved Intermittent Pilot Ignition Control

Q35 Series Automatic Vent Damper System

BGH2UNCNTRLHT-01 Universal Hot Surface Ignition Control

ORDERING INFORMATION SPECIFICATIONS APPLICATION

SERIES VAC Microprocessor Based Direct Spark Ignition Control FEATURES DESCRIPTION APPLICATIONS THE TOTAL SOLUTION FOR GAS IGNITION CONTROL

B21 Series BASOTROL Gas Valve

INSTALLATION DATA 712 Series Pilot

J Series Pilot Burners/Y90 Series Inlet Fittings

Troubleshooting Manual

S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K Intermittent Pilot Gas Ignition Control

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

Hayward error codes and troubleshooting

VA-8020 Floating Valve Actuator

A419ABG-3C Electronic Temperature Control

Y75 and D Series Sensing Probes

P445 Series Electronic Lube Oil Control

Modulating Furnace Information. Warning on Meter Setting - Read First!

G96 Series BASOTROL Dual Operator Valve

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin LowNOx Commercial Gas Electronic Spark Ignition Sequence

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

Y75 Series Sensing Probes

AV-8020 Series Floating Control Actuated Valve

X4 Installation and Operation Manual - POWER FLAME INCORPORATED

SERIES VAC Microprocessor Based Direct Spark Ignition Control with Combustion Blower Relay FEATURES DESCRIPTION

System 350 P352AB Electronic Pressure Control Series

RESIDENTIAL ELECTRONIC IGNITION SYSTEMS

Q345A, Q3451, Q3481, Q348A, Q348B, Q362A, Q373A, Q381A and Q3452 Intermittent Pilot Burner/Igniter-Sensors

BLOWER VACUUM SWITCH FAILED OPEN

A25 Series Warm Air Control with Manual Reset

36H Gas Control Product Information

GEMINI GAS CONTROL PRODUCT INFORMATION

f i r e - p a r t s. c o m

BGD278 Series BASOTROL CE Approved Gas Valve

BGD258 Series BASOTROL CE Approved Class A Gas Valve

Installation, Operation and Maintenance Manual

BG1600M51EF-1AA Universal Intermittent Pilot Ignition Control

Installation, Operation and Maintenance Manual

User s Manual. Automatic Switch-Mode Battery Charger

H15 Series BASO Automatic Shutoff Pilot Gas Valve

burners with or without fan. It conforms to EN C). APPROVAL EU type test approval as per EU Gas Appliance Directive.

DPT-2015 Differential Pressure Transmitter for VAV Box Applications

R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators

SYSTEM CONTROL KIT. Model: CK-41F ITEMS INCLUDED IN KIT:

H15 Series BASO Automatic Shutoff Pilot Gas Valve

ZIP Economizer Fault Detection and Diagnostics (FDD) Table

ELECTRONIC FIREPLACE DAMPER

CIRCLE SEAL CONTROLS

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

The Combustex Pilot Pro 800 Pilot Burner Assembly with Ignition & Flame Failure Monitor

36C and 36D Gas Control Product Information

Y99AB-4 BASO Test Kit

P66 Series Electronic Fan Speed Controls

This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used by those not properly qualified.

S4562C 1085 COMBI BOARD APPLICATION. Contents PRODUCT HANDBOOK. General

GeniSys 24V. Model Advanced 24 Vdc Burner Control. Description / Applications

INSTALLATION MANUAL ACL 5500 COMBUSTION SAFETY CONTROLLER

VA-4233-GGx Series Electric Valve Actuators

This document describes the commissioning checklist procedures for the Capstone MicroTurbine systems.

System 350 S350P Proportional Plus Integral Temperature Stage Module

M100F Incremental Motor Actuator R81F Interface Board

Applies to: Models F, B, FE, and BE with spark pilot

CAUTION WARNING WARNING PROFLAME 2 UPGRADE KIT RX RX 300 NG/LP. Installation & Maintenance Manual

INSTALLER MANUAL USER MANUAL. Contents

Damper Actuator Installation

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Start-up Instructions

First Correlating Revision No. 1-NFPA [ Section No ]

SERVICE MANUAL (INTERNATIONAL)

PROFIRE 1100i IGNITION FLAME SAFETY CONTROLLER

Series 20 Installation Instructions

SEN and SEN Outdoor Air Temperature Sensors

CIRCLE SEAL CONTROLS

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators

M9216 Series Electric Spring Return Actuators

HI-POT/CONTINUITY TESTER Model PLEP01

VA-715x Electric Valve Actuator

M x Series Valve Linkage Kits

ROBERT H. PETERSON CO. AUTOMATIC REMOTE LIGHTING SAFETY PILOT SYSTEM WITH VARIABLE FLAME-HEIGHT REMOTE FOR NATURAL OR PROPANE GAS. Model APK-17(M)(P)

SAVANNAH EI & DELUXE SYSTEM TROUBLE SHOOTING GUIDE

Series 44 Installation Instructions

F61 Series Standard Flow Switches

SERVICE INSTRUCTIONS KEATING keatingofchicago.com

INSTALLATION INSTRUCTIONS

P0441-EVAP PURGE SYSTEM PERFO... P0441-EVAP PURGE SYSTEM PERFORMANCE

SYSTEM CONTROL KIT. Model: CK-41F. Designed for use with the SWG Series Power Venter for controlling Natural Gas or L.P. Gas appliances.

INSTALLATION INSTRUCTIONS

MODEL 422 Submersible Pump Controller

General Description. Product Specification. Document Digital Temperature Interlock

Troubleshooting Electronic Ignition

AUTOMATIC REMOTE CAPABLE SAFETY PILOT SYSTEM

R & D SPECIALTIES ROTROL I USER'S MANUAL

Art. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2

HVF110, 210, 310, 410HD

GRD502-B Flow Chart 02/05/09

Specifications of MAXON VALUPAK burners for 50 Hz operation

Transcription:

Installation Instructions G600 Issue Date 0601 G600 Series ment Intermittent Pilot Ignition Controls Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing or servicing Johnson Controls products. Carefully follow all instructions in this document and all instructions on the appliance. Limit repairs, adjustments, and servicing to the operations listed in this document or on the appliance. WARNING: Shock Hazard. Avoid electrical shock and equipment damage. Disconnect electrical power and turn off the gas before wiring the control into the circuit. CAUTION: Equipment Damage Hazard. Label all wires prior to disconnection when replacing the control. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. Perform the following procedure to remove the existing ignition control: 1. Shut off power to the appliance. 2. Turn off gas at the manual shutoff valve adjacent to the appliance. (If the manual shutoff valve services more than one appliance, be sure to light the other pilots before leaving the installation.) 3. Label each wire with the correct terminal designation prior to disconnection. 4. Disconnect the power supply (transformer) and the thermostat lead wire at the ignition control. 5. Disconnect the sensing probe lead wire from Terminal 4 on the ignition control. 6. Disconnect the high-voltage cable from the spark transformer on the ignition control. 7. Disconnect the Pilot Valve 1 and Main Valve 3 lead wires from the terminal board or 5-end plug-in Heyco terminals on the ignition control. 8. Disconnect the Y79 lockout module lead wire (if a Y79 is used) from the ignition control. te: The Y79 lockout module is no longer necessary as the replacement G600 ignition control (100% lockout models only) has a built-in lockout function. 9. Disconnect the vent damper plug/cable (if used) from the ignition control. 10. Remove the two screws holding the ignition control to the valve (if direct valve-mount model) or remove the screws holding the control to the appliance chassis (if foot-mount model). 11. Remove the old ignition control and discard. Mounting WARNING: Fire or Explosion Hazard. If the control is installed in an area that is exposed to water (dripping, spraying, rain, etc.), it must be protected. If the control has been exposed to water in any way, do not use it. CAUTION: Equipment Damage Hazard. Do not mount the control where it will be exposed to direct infrared radiation from the main burner or to temperatures in excess of the maximum product temperature rating. 2001 Johnson Controls, Inc. 1 Part. 24-8143-138, Rev. B www.johnsoncontrols.com

Perform the following procedure to mount the new G600: 1. Choose a location that provides the shortest, direct-cable route to the spark electrode/flame sensor assembly. Easy access to the terminals is desired for wiring and servicing. The G600 may be mounted in any position. 2. Mount the control on a grounded metal surface. te: The G600 is packaged with a mounting plate and two hex head screws. Use the two screws to secure the new ignition control to the valve assembly or to the back mounting plate. Refer to Table 1 for mounting instructions. Table 1: Mounting Instructions Original Ignition Control Mounting Instructions G60, G66, CSA Use same holes as old ignition. G65 Cannot mount G600 on valve. Mount on flat surface and wire to valve. Refer to Figures 1 through 3 for wiring diagrams. All wiring should be in accordance with the NEC and all other local codes and regulations. The high-voltage spark transformer cable must not be in continuous contact with a metal surface. Use standoff insulators. Ensure that the flame sensor wire and the high voltage spark transformer cable are separated from one another a minimum of 6.35 mm (1/4 in.) and are not wrapped around any pipe, other wiring, or accessories. Pilot Valve Other Controls High Limit 1 2 3 4 5 6 GR GR THS 2 Transformer Main Valve Power Supply See te 1. See te 2. Wiring Flame Sensor Damper Plug (See te 3.) CAUTION: Equipment Damage Hazard. Connect the high voltage cable to the spark transformer terminal and spark electrode (pilot burner assembly) before applying power to the control. Be certain the ground wire is attached to the pilot burner and control ground terminal strip. CAUTION: Equipment Damage Hazard. Locate all limit and operating controls in series with the thermostat terminal (THS 2) on the ignition control. Check the voltage rating marked on the control and make sure it is suited to the application. Use a National Electrical Code (NEC) Class 2 transformer to provide 24 VAC under maximum load, including valves. A transformer having excessive primary impedance due to poor coupling will affect the ignition potential. Spark Connection tes: 1. This un-switched 24 VAC line must be used as shown if: a. It is already available on the system. b. A vent damper is to be installed on the system. Otherwise, omit the 24 VAC line and connect Terminal 5 to 6 with the jumper provided. 2. If the G600 is mounted directly to a valve having two leads numbered 1 and 3, it is internally grounded and does not require the ground connection shown. 3. Damper plug installation instructions: a. If the original control was not connected to an external control (e.g., M35) through the 6-pin receptacle, the damper plug must be inserted. b. If the original control was connected to an external control through the 6-pin receptacle, reconnect as found and discard the damper plug. Figure 1: Wiring Diagram for n-100% Lockout G600 with Terminal Board Connections 2 G600 Series ment Intermittent Pilot Ignition Controls Installation Instructions

Transformer Transformer Other Controls High Limit THS 2 Other Controls High Limit THS 2 Power Supply See te 1. MV Power Supply Pilot Valve 1 2 3 4 5 6 Main Valve PV 1 3 5 GR GR See te 2. 2 6 GRD See te 1. Flame Sensor Damper Plug (See te 3.) See te 2. Top View Spark Connection tes: 1. This un-switched 24 VAC line must be used as shown if a vent damper is to be installed in the system. 4 Flame Sensor 2. If the G600 is mounted directly to a valve having two leads numbered 1 and 3, it is internally grounded and does not require the ground connection shown. 3. Damper plug installation instructions: a. If the original control was not connected to an external control (e.g., M35) through the 6-pin receptacle, the damper plug must be inserted. b. If the original control was connected to an external control through the 6-pin receptacle, reconnect as found and discard the damper plug. Figure 2: Wiring Diagram for 100% Lockout G600 with Terminal Board Connections Spark Transformer Bottom View tes: 1. This un-switched 24 VAC line must be used as shown if it is already available on the system. Otherwise, omit the 24 VAC line and connect Terminals 5 and 6 with the jumper provided. 2. If the G600 is mounted directly to a valve having two leads numbered 1 and 3, it is internally grounded and does not require the ground connections shown. te: Figure 3: Wiring Diagram for n-100% Lockout G600 with 5-end Heyco Connections n-lockout and lockout models are provided in both terminal board and Heyco wiring connection styles. Refer to the wiring connection information supplied in the Technical Data section. G600 Series ment Intermittent Pilot Ignition Controls Installation Instructions 3

Setup and Adjustments Commissioning The anticipator setting is normally equal to the ignition system current draw, plus that of the pilot and main valve. Due to variations in appliance wiring and valves, it is advisable to measure the actual current draw of the heating system at the thermostat location. Measuring this current can be accomplished by opening the thermostat contacts (lowering the setpoint) and installing an AC ammeter across the terminals, or by using a clamp-on ammeter with a ten turn multiplier attached to the terminals. See Figure 4. IMPORTANT: Measuring the current with an ammeter energizes the system. Wait until the appliance is in the run condition before taking a current draw measurement. Ten Turns W W To Heating System AC Ammeter Low Scale Setting To Heating System R R Checkout WARNING: Fire or Explosion Hazard. Avoid personal injury or property damage by making sure the control functions properly and there are no gas leaks. Follow this checkout procedure before leaving the installation. Make sure all components are functioning properly by performing the following shutoff test: 1. Turn on power to the appliance with the gas and the thermostat off, 2. Turn the thermostat to the highest setting and verify that the control goes through the operating sequence to a lockout condition. (n-lockout models will not lockout, but spark indefinitely.) te: The burner will not light because the gas is off. 3. Turn off the thermostat. 4. Turn on the gas and purge gas lines of all air. 5. Test for leaks on all pipe joints and connections upstream of the gas valve with a soap solution. 6. Turn the thermostat to the highest setting and verify successful ignition and a normal run condition for at least 3 minutes. If the appliance fails to run, see the Troubleshooting section. 7. Test for leaks on all pipe joints and connections downstream of the gas valve with a soap solution. 8. Turn the thermostat down for at least 30 seconds and then back up again. Verify successful ignition at least three times. 9. Return the thermostat to a normal temperature setting before leaving the installation. Clamp-on Ammeter (Divide reading by ten.) Figure 4: Measuring Thermostat CurrentCheckout 4 G600 Series ment Intermittent Pilot Ignition Controls Installation Instructions

Operation Operating Mode Definitions The following definitions describe the G600 operating conditions: Prepurge: Initial time delay between thermostat contact closure and trial for ignition. Trial-for-Ignition: Period during which the pilot valve and spark are activated, attempting to ignite gas at the pilot burner. The control attempts to prove flame at the pilot burner within the trial-for-ignition time. Once flame is proven, the main valve is energized. Run: Main gas valve and pilot valve remain energized and spark is turned off after successful ignition. Lockout: Pilot gas did not ignite within the trial-for-ignition time. Open the thermostat contacts for 30 seconds, then close to restart the sequence of operation. Flameout: Loss of proven flame. Sequence of Operation Figure 5 illustrates the sequence of operation of the G600 controls. When the G600 is used to replace an original control, the system sequence of operation does not change. Following is the sequence of operation for all G600s: 1. Call for Heat: The thermostat contacts close, powering Terminal 2 on the G600. 2. Pilot Flame Checking: If the G600 detects the presence of pilot flame (from the flame sensor) when there should not be (i.e., before the call for heat), the G600 will not operate. 4. Prepurge: The appliance prepurge fan or relay is energized through the thermostat contacts. The control delays for the 4-second prepurge before simultaneously opening the pilot valve and supplying a continual spark at the pilot burner (models with prepurge only). 5. Trial for Ignition: During the trial for ignition, the G600 energizes Terminal 1 and the spark transformer, which opens the pilot valve and activates the spark in an attempt to light the pilot burner. If the G600 detects the presence of the pilot flame within the trial-for-ignition time, it proceeds to the run state. If the G600 does not detect the presence of the pilot flame within the trial-for-ignition time, it de-energizes all outputs (locks out) and remains in this condition until the thermostat is recycled. The G600AX and G600AY have infinite trials for ignition and spark indefinitely. 6. Run: If pilot flame is detected within the trial for ignition, Terminal 3 is energized and the spark transformer is de-energized, which opens the main valve and shuts off the spark. The pilot valve and main valve are kept open throughout the run state. The control remains in the run condition until the call for heat ends or until a flameout occurs. 7. Flameout: If, during the run state, the control detects the loss of pilot flame, it de-energizes the main valve within 0.8 second (flame failure response time). The pilot valve is kept open, the spark is re-established, and another trial for ignition begins. 3. Vent Damper Actuation: On models electrically interlinked with a vent damper, the G600 powers the vent damper motor. Once the vent damper reaches its open position, the motor stops, and the G600 is allowed to begin the prepurge (prepurge models only) or trial for ignition. G600 Series ment Intermittent Pilot Ignition Controls Installation Instructions 5

Start Thermostat call for heat Flame present for 30 seconds? Lockout End Prepurge te: Models with prepure only. Trial for ignition Flame sensed? Energize main valve. Run Flameout? Thermostat calling for heat? Is control a G600AX or AY? Is control a G600KX, LX, LY, MX, NX, or RX? Fifth flameout? Lockout De-energize control and valve. End Figure 5: G600 Sequence of Operation 6 G600 Series ment Intermittent Pilot Ignition Controls Installation Instructions

Troubleshooting If the system does not function properly, determine the cause using the procedures in this section. Before proceeding with troubleshooting the system, check the following: Are all mechanical and electrical connections tight? Is the system wired correctly? Is gas inlet pressure per the manufacturer s specifications? Is the system powered? Is the thermostat calling for heat? There are three potential system failure conditions: spark, and system does not work. Spark present, but pilot does not light. Pilot lights, but main burner does not come on. Determine the failure condition, then use the respective flowchart on the following pages to troubleshoot the system. Perform the procedures in the Checkout section after any servicing. Repairs and ment CAUTION: Equipment Damage Hazard. Label all wires prior to disconnection when replacing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. The G600 controls are not field repairable. Do not attempt field repairs. Use only an exact or factory-recommended replacement control. All other accessories, such as flame sensors, electrode assembles, pilot assemblies, and leads can be obtained through the original equipment manufacturer or a Johnson Controls distributor. G600 Series ment Intermittent Pilot Ignition Controls Installation Instructions 7

Start Is 24 VAC present between Terminal 2 and ground? Check for defective transformer, thermostat, or faulty wiring. Open thermostat contacts for 30 seconds and then close. Is spark present now? System was in lockout (if control is 100% lockout). Causes include flameout or an internal fault. Did pilot remain lit from previous cycle? gas valve. Turn off supply voltage. Is spark cable securely connected to the ignition control? Correct Is spark cable brittle, burnt, or cracked? cable. Is spark electrode ceramic cracked? pilot burner. Is spark gap per manufacturer s specifications and located in pilot gas stream? Correct or replace pilot burner. control. End Figure 6: Spark, and System Does t Work 8 G600 Series ment Intermittent Pilot Ignition Controls Installation Instructions

Start Are pilot valve connections correct and secure? Connect pilot valve securely between Terminal 1 and ground. Is 24 VAC between Terminal 1 and ground? control. Is inlet gas pressure per manufacturer s specifications? Correct gas pressure. Is gas at pilot burner? Make sure pilot line is not obstructed. Check for clean orifice. Correct or replace pilot burner. Is spark gap per manufacturer s specifications and located in pilot stream? If OK, replace pilot valve. Shield from drafts. End Figure 7: Spark Present, but Pilot Does t Light G600 Series ment Intermittent Pilot Ignition Controls Installation Instructions 9

Start Does spark stay on after pilot lights? Is 24 VAC between Terminal 3 and ground? control. Make sure sensor cable and spark cable are separated and not wrapped around any pipes or accessories. Is gas inlet pressure per manufacturer s specifications? Correct Correct Is sensor cable securely connected to Terminal 4 and flame sensor? Is main valve wiring securely connected to Terminal 3 and ground? Correct flame sensor. Is sensor ceramic cracked? main valve. Correct Is sensor cable grounded out? Does sensor cable lack continuity or good insulation? cable. If the system still fails, clean the pilot assembly and flame sensor with steel wool, verify a good ground path exists between the pilot burner bracket and the ignition control, or replace the flame sensor, orifice, or control. End Figure 8: Pilot Lights, but Main Burner Does t Come On 10 G600 Series ment Intermittent Pilot Ignition Controls Installation Instructions

Technical Data Product Ignition Type Ignition Source High Voltage Cable Maximum Length Flame Sense Cable Maximum Length Flame Detection Means Flame Detection Type Minimum Flame Current Flame Failure Response Time Spark Gap Prepurge Time Trial-for-Ignition Time Wiring Connections Spark Transformer Connection Power Requirements Contact Rating G600 Series ment Intermittent Pilot Ignition Controls Indirect High voltage spark, capacitive discharge 1,220 mm (48 in.) 1,220 mm (48 in.) Flame rectification Remote G600AX and AY G600KX, LX, LY, MX, NX, and RX 0.8 second maximum 2.5 mm (0.1 in.) nominal G600AX and AY G600KX, LX, LY, MX, NX, and RX Model G600AX, AY G600KX G600LX, LY G600MX G600NX G600RX Trial Time Infinite 8 seconds 25 seconds 50 seconds 120 seconds 85 seconds G600AY and LY G600AX, KX, LX, MX, NX, and RX Rajah Control Operation Current Main Valve Pilot Valve 24 VAC at 60 Hz 0.15 A nominal +valves 2 A continuous, 5 A inrush 2 A continuous, 5 A inrush 0.2 microamperes DC 0.15 Microamperes DC ne 4 seconds* Recycle/Lockout n-100% Lockout 100% Lockout 100% Lockout 100% Lockout 100% Lockout 100% Lockout 5-end Heyco Terminal Board Maximum Firing Rate 117 kw (400,000 Btu/hr) Ambient Storage -40 to 66 C (-40 to 150 F) Conditions Humidity Rating 95% RH non-condensing Type of Gas Natural, Liquefied Petroleum (LP), manufactured, mixed, or LP gas-air mixture Agency Listings CSA (AGA/CGA) Certificate Number 164933-1064436 Specification Standards ANSI Standard Z21.20 * Timings listed are for 60 Hz operations. Timings increase by 20% under 50 Hz operation. The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 Printed in U.S.A. www.johnsoncontrols.com G600 Series ment Intermittent Pilot Ignition Controls Installation Instructions 11