A Comparison of Different Hybrid Direct Current Circuit Breakers for Application in HVDC System

Similar documents
Modelling of Hybrid DC Circuit Breaker Based on Phase-Control Thyristors

A low loss mechanical HVDC breaker for HVDC Grid applications THOMAS ERIKSSON, MAGNUS BACKMAN, STEFAN HALÉN ABB AB, CORPORATE RESEARCH SWEDEN

ABB s hybrid HVDC breaker, an innovation breakthrough enabling reliable HVDC grids

ECE 421 Project 1, Group 3 HVDC. Brian Beilstein, Robert Germick, James Haney, Alexander Joss, Matt Murphy, Shutang You

Comparative Analysis of Hybrid DC Breaker and Assembly HVDC Breaker

DC Arc-Free Circuit Breaker for Utility-Grid Battery Storage System

POWER TRANSMISSION OF LOW FREQUENCY WIND FIRMS

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

A Transient Free Novel Control Technique for Reactive Power Compensation using Thyristor Switched Capacitor

Fully Regenerative braking and Improved Acceleration for Electrical Vehicles

5 kw Multilevel DC-DC Converter for Hybrid Electric and Fuel Cell Automotive Applications

Electrical Test of STATCOM Valves

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC

Soft Switching of Two Quadrant Forward Boost and Reverse Buck DC- DC Converters Sarath Chandran P C 1

A Novel DC-DC Converter Based Integration of Renewable Energy Sources for Residential Micro Grid Applications

Offshore Wind Connections HVDC for Offshore Grids

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

Dynamic Modelling of Hybrid System for Efficient Power Transfer under Different Condition

A novel synthetic test system for thyristor level in the converter valve of HVDC power transmission

837. Dynamics of hybrid PM/EM electromagnetic valve in SI engines

Adaptive Power Flow Method for Distribution Systems With Dispersed Generation

Protection of Power Electronic Multi Converter Systems in AC and DC Applications

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

Design of Active and Reactive Power Control of Grid Tied Photovoltaics

Cigre SC B4 Activities Towards HVDC Grids. HVDC Grid Workshop Belgium

High Voltage Direct Current and Alternating Current Transmission Systems Conference. August Nari Hingorani

Implementation of FC-TCR for Reactive Power Control

Rural electrification using overhead HVDC transmission lines

6545(Print), ISSN (Online) Volume 4, Issue 2, March April (2013), IAEME & TECHNOLOGY (IJEET)

Low Voltage Prototype Design, Fabrication and Testing of Ultra-Fast Disconnector (UFD) for Hybrid DC CB

Performance Analysis of Bidirectional DC-DC Converter for Electric Vehicle Application

International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering. (An ISO 3297: 2007 Certified Organization)

A Method for Determining the Generators Share in a Consumer Load

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

A Review on Reactive Power Compensation Technologies

Power Flow Control in Meshed DC Grids. 29_03_17 Dr Jun Liang Cardiff University

Rotor Position Detection of CPPM Belt Starter Generator with Trapezoidal Back EMF using Six Hall Sensors

Master Thesis Proposal: Real-time and off-line simulation of DC Grids

Soft Start for 3-Phase-Induction Motor

Design of Four Input Buck-Boost DC-DC Converter for Renewable Energy Application

Faults Mitigation Control Design for Grid Integration of Offshore Wind Farms and Oil & Gas Installations Using VSC HVDC

Design of Integrated Power Module for Electric Scooter

A study of the power capacity of regenerative inverters in a DC electric railway system

International Journal Of Global Innovations -Vol.2, Issue.I Paper Id: SP-V2-I1-048 ISSN Online:

Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor

ICEC The 27 th International Conference on Electrical Contacts. presented by Peter Meckler

ABB POWER SYSTEMS CONSULTING

China. Fig. 1 Chain SVG Electrical Diagram

Driving Performance Improvement of Independently Operated Electric Vehicle

Comparison of Braking Performance by Electro-Hydraulic ABS and Motor Torque Control for In-wheel Electric Vehicle

Benefits of HVDC and FACTS Devices Applied in Power Systems

Wind-Turbine Asynchronous Generator Synchronous Condenser with Excitation in Isolated Network

A New Synthetic Test Circuit For the Operational Tests of HVDC Thyristor Modules

/12/$ IEEE. M. Bashir M.Sc student, Student Member, IEEE Ferdowsi University of Mashhad Mashhad, Iran

INVESTIGATION AND PERFORMANCE ANALYSIS OF MULTI INPUT CONVERTER FOR THREE PHASE NON CONVENTIONAL ENERGY SOURCES FOR A THREE PHASE INDUCTION MOTOR

Dual power flow Interface for EV, HEV, and PHEV Applications

Dynamic Modeling and Simulation of a Series Motor Driven Battery Electric Vehicle Integrated With an Ultra Capacitor

Analysis and Design of Improved Isolated Bidirectional Fullbridge DC-DC Converter for Hybrid Electric Vehicle

Reducing Train Weight and Simplifying Train Design by Using Active Redundancy of Static Inverters for the Onboard Supply of Rolling Stock

Behaviour of battery energy storage system with PV

A PARALLEL SNUBBER CAPACITOR BASED HIGH STEP UP ISOLATED BIDIRECTIONAL FULL BRIDGE DC TO DC CONVERTER

Active Damping of Ultra-fast Mechanical Switches for Hybrid AC and DC Circuit Breakers

Study on Flow Characteristic of Gear Pumps by Gear Tooth Shapes

DYNAMIC BEHAVIOUR OF SINGLE-PHASE INDUCTION GENERATORS DURING DISCONNECTION AND RECONNECTION TO THE GRID

New Power Electronic Devices and Technologies for the Energy Sector

Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM

IEEE Transactions on Applied Superconductivity, 2012, v. 22 n. 3, p :1-5

Innovative technologies ready for the Supergrid

Original. M. Pang-Ngam 1, N. Soponpongpipat 1. Keywords: Optimum pipe diameter, Total cost, Engineering economic

DESIGN AND ANALYSIS OF PRE- INSERTION RESISTOR MECHANISM

Exercise 6. Three-Phase AC Power Control EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to three-phase ac power control

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

Power Conditioning of Microgrids and Co-Generation Systems

IMPROVEMENT IN DOUBLY FED INDUCTON GENERATOR UNDER FAULT USING INDUCTOR

An Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks

Research Paper MULTIPLE INPUT BIDIRECTIONAL DC-DC CONVERTER Gomathi.S 1, Ragavendiran T.A. S 2

Analysis on natural characteristics of four-stage main transmission system in three-engine helicopter

Electric Mobility and Smart Grids: Cost-effective Integration of Electric Vehicles with the Power Grid

Reactive Power Management Using TSC-TCR

Safe, fast HV circuit breaker testing with DualGround technology

A Novel Technique for Energy & Cost Effective Drives for AC & DC Motors

Protective firing in LCC HVDC: Purposes and present principles. Settings and behaviour. V. F. LESCALE* P. KARLSSON

Next Generation of UHVDC System. R. Montaño, D Wu, L. Arevalo, B. Jacobson ABB - HVDC Sweden

Enhancement of Reliability Analysis for a 6-Bus Composite Power System using the Combination of TCSC & UPFC

Circuits for Protecting and Triggering SCRs in High Power Converters

Grouped and Segmented Equalization Strategy of Serially Connected Battery Cells

Intelligent Power Management of Electric Vehicle with Li-Ion Battery Sheng Chen 1,a, Chih-Chen Chen 2,b

Analysis of Fuel Economy and Battery Life depending on the Types of HEV using Dynamic Programming

Aggregation of plug-in electric vehicles in electric power systems for primary frequency control

Future Trends for Power Systems

Increasing the Battery Life of the PMSG Wind Turbine by Improving Performance of the Hybrid Energy Storage System

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System

A Comparative Analysis of Speed Control Techniques of Dc Motor Based on Thyristors

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 02, 2016 ISSN (online):

NORDAC 2014 Topic and no NORDAC

Improvement the Possibilities of Capacitive Energy Storage in Metro Railcar by Simulation

Design and Implementation of Non-Isolated Three- Port DC/DC Converter for Stand-Alone Renewable Power System Applications

Combination control for photovoltaic-battery-diesel hybrid micro grid system

Transcription:

, pp. 381-394 http://dx.doi.org/10.14257/ijca.2016.9.4.37 A Comparison of Different Hybrid Direct Current Circuit Breakers for Application in HVDC System Anh-Duc Nguyen, Thai-Thanh Nguyen and Hak-Man Kim * Incheon National University hmkim@inu.ac.kr Abstract This paper presents the comparison between two topologies of hybrid direct current circuit breaker (HDCCB) that are designed by ABB and Alstom Grid. The main difference between two topologies is the use of the semiconductor in each topology. ABB used IGBT cells whereas Alstom Grid used IGBT cells and thyristors. The working principles of each topology are presented and their advantages and disadvantages are shown in this study. Two HDCCB topologies are implemented in MATLAB / Simulink to clarify the comparison. The effect of the time delay in the topology of Alstom Grid is also discussed in this study. Keywords: Hybrid direct current circuit breaker (HDCCB), high voltage direct current (HVDC), ABB DCCB, Alstom Grid DCCB, modeling & analysis 1. Introduction The high voltage direct current (HVDC) system uses direct current (DC) for high power transmission. Unlike the high voltage alternative current (HVAC) system, the transmitted current in HVDC system does not change the direction. Besides, a longdistance HVDC transmission system introduces lower investment cost and lower losses than an equivalent HVAC system [1, 2]. Hence, the HVDC system has become realized and interested as new technology. Nonetheless, the constant DC current, which is one of the advantages of the HVDC transmission system, is an inevitable challenge for fault current interruption. Alternative current circuit breakers (ACCBs) operate basing on the zero-crossing principle but there is no natural zero crossings obtained in the DC current. The issue of identifying suitable circuit breaker topologies for HVDC grid remains controversial. For decades, a variety of topologies of DC circuit breakers have been proposed [3-5]. Among of them, the hybrid DC circuit breaker (HDCCB) that consists of the mechanical switch and the semiconductors has become the leading technology. In general, HDCCB consists of three essential branches: a main branch with a mechanical switch, an auxiliary branch with semiconductor devices and a metal oxide varistor () [6-8]. The fault current interruption in the HDCCB includes three steps in general. First of all, the load current flows through the main branch in normal condition. When the fault occurs, the open command is delivered to the mechanical switch and fault current is commutated into the auxiliary branch. Later, this branch carries the fault current until the mechanical switch completely opens. Finally, the semiconductors in the auxiliary branch turn off and commutate the fault current here into the surge arrester whose function is to force the current to zero. For enhancement, a power electronic switch formed by a stack of semiconductors is added in series with the mechanical switch to support the switch during commutation [9]. As an improvement, ABB and Alstom Grid introduced their new HDCCB topologies * Corresponding Author ISSN: 2005-4297 IJCA Copyrightc 2016 SERSC

with same working principles but different components included [10, 11]. It is noticed that these two HDCCB schemes both interrupt fault currents very quickly and there is low energy loss during normal operation. Each topology has its own advantages and disadvantages. However, the comparison between two topologies still has not been explored. This paper provides an overview and test results of their performance in order to consider the application of the HDCCB topologies of ABB and Alstom Grid. The paper is divided into four sections as follows. In Section 2, two HDDCB topologies of ABB and Alstom Grid are theoretically investigated according to their working principles. The simulation results of the two topologies are presented in Section 3. Section 4 presents the comparison between the ABB and Alstom Grid HDCCB topologies. Finally, the conclusions and future works are summarized in Section 5. 2. Operation Principle of the Hybrid DC Circuit-Breakers 2.1. The ABB s Hybrid DC Circuit Breaker The scheme in Figure 1 introduces the simplified ABB s HDCCB topology which consists of three branches as follows: Main branch or load current path includes an ultra-fast mechanical disconnector () and a load commutation switch () connected in series. These two components together build the low-loss load current path of the HDCCB. The contains a small number of IGBTs adequate to commutate fault current to the auxiliary branch. These IGBTs should be installed anti-series in order for bidirectional interruption. Auxiliary branch contains IGBT cells installed parallel with a surge arrester [12]. Each cell includes IGBTs modules connected in anti-series. The number of cells increases when the voltage level is higher. The function of this branch is to carry the large fault current while the mechanical switch is in opening process. The surge arrester not only reduces fault current to zero by eliminating energy, but also serves as over-voltage protection of the IGBTs in the auxiliary branch. Total protective level of the arresters is selected to be approximately 1.5 times of the rated DC voltage. Residual DC Current Breaker (RCD) Ultrafast Disconnector () Main Branch Load Commutation Switch () Auxiliary Branch Surge Arrester () Figure 1. Structure of the ABB s HDCCB 382 Copyrightc 2016 SERSC

RCD i DC i main RCD i DC i aux i aux RCD i DC a) Step 1: 0 < t < t 2 b) Step 2: t 2 < t < t 3 i RCD DC i aux c) Step 3: t 2 < t < t 3 d) Step 4: t 3 < t < t 4 RCD i I peak I trip I normal Main Branch Aux. Branch e) Fault Completely Cleared i Figure 2. Working Principle of ABB s HDCCB i main i aux i Auxiliary Branch Main Branch Fault occurs Fault cleared 0 t 1 t 2 t 3 t 4 t Figure 3. Fault Current Interruption of ABB s HDCCB The working principle of the ABB s HDCCB described in Figure 2 includes four steps as follows: Copyright c2016 SERSC 383

Step 1: During normal operation of the system, most of load current passes through the main branch because of the low impedance of the IGBT-based. Meantime, a relatively low amount of current flows in the auxiliary branch due to high impedance of the IGBT cells, as shown in Figure 2a. Step 2: When a fault occurs, the current increases extremely quickly to a certain fault current level which is called tripping value. When this value is reached, the turn-off signal will be sent to the IGBTs in. This leads to the commutation of fault current from the load current path into the auxiliary branch, as shown in Figure 2b. Step 3: At time of tripping value, the opens in less than 2 ms. Thus, the function of IGBT cells in auxiliary branch is to withstand the large amount of fault current which is still increasing during the 2 ms period. The IGBT cells in auxiliary branch is provided self-protection in case fault current exceeding the maximum breaking current limit of the IGBTs so that damage from this event can be avoided. Figure 2c describes the current behavior during this step. After the is completely opened, the turn-off command will be sent to the IGBT cells and the fault current commutates into the arrester path. Step 4: After the IGBT cells in auxiliary branch turn off, fault current is forced to commutate into the nonlinear resistor path with a surge arrester, as shown in Figure 2d. The fault current reduces to zero because of the energy elimination caused by the arrester. After fault clearance, the RCD shall open in 1 s to protect the surge arrester from thermal overload caused by residual current, as in Figure 2e. Consequently, the current performances during the four time intervals together form the fault current interruption procedure, as illustrated in Figure 3. There are generally three stages included in the procedure. The first one is fault detection and next is the current commutation stage. The final stage is fault clearance. 2.2. Alstom Grid s Hybrid DC Circuit Breaker The fast turning-off speed of IGBT cells in ABB s topology is undeniable for fault interruption. However, this characteristic is unsuitable in several situations. For example, the mechanical switch opens too slowly compared to the IGBTs or a longer duration is needed for system protection. Therefore, Alstom Grid introduced their HDCCB topology to overcome this problem. The Alstom Grid s HDCCB topology generally contains three branches with functions similar to the ABB s HDCCB. Nevertheless, the auxiliary branch structure of Alstom Grid s HDCCB is significantly different from ABB s one. While the IGBT cells with high turning-off speed are utilized in the ABB s HDCCB, Alstom Grid alternatively applies series stacks of pulse-power thyristors (PPTs) in the auxiliary branch for time-extension purpose [13], as shown in Figure 4. The auxiliary branch of Alstom Grid s HDCCB consists of two time-delaying branches and one arming branch. Each branch includes thyristor stacks connected in series. These thyristors are extremely difficult to turn off as IGBTs due to their characteristics. As a result, a capacitor bank is installed in series with each stack of thyristors in order to interrupt fault current. There are at least two time-delaying paths in the auxiliary branch of this HDCCB. The first time-delaying branch contains a large capacitor bank and a surge arrester with low voltage protection level in parallel. This protection level should not be higher than the voltage rating of the in the main branch. The second one operates similarly but includes a surge arrester with higher voltage rating. The arming branch structure is not different from the two branches as mentioned above. However, the capacitor of this branch is selected appropriate to the main surge arrester. 384 Copyrightc 2016 SERSC

Residual DC Current Breaker (RCD) Ultrafast Disconnector () Main Branch Auxiliary Branch Load Commutation Switch () Time-delaying Branches "Arming" Branch Surge Arrester () Figure 4. Structure of The Alstom Grid s HDCCB Figure 5 shows the working principle of the Alstom Grid s HDCCB. There are five steps to be illustrated as follows: Step 1: During normal operation, all thyristor stacks in auxiliary branch are at turn-off state and load current flows through main branch. This step is described in Figure 5a. When there is a fault occur, the IGBTs in the receive turn-off command and at the same time the thyristor stack in the first time-delaying branch is fired. Step 2: The fault current commutates into the first time-delaying branch and the capacitor here begins to be charged, as shown in Figure 5b. Additionally, at turningoff event, the mechanical switch begins opening. Step 3 includes two minor steps as follows: Step 3.1: When the contacts of the are apart but remain not fully open, the thyristor stack in second time-delaying branch is turned on. The fault current commutates from the first time-delaying branch into the second one. Therefore, there shall be two parallel current paths, as illustrated in Figure 5c Step 3.1. Step 3.2: Once fully charged, the capacitor in the first time-delaying branch discharge immediately to the surge arrester in parallel. Thus, the capacitor voltage becomes constant and the fault current in this branch reduces to zero. Consequently, the thyristor stack in the first time-delaying branch is automatically turned off according to the characteristics of the thyristor. For that reason, the fault current is completely transferred into the second time-delaying branch. When the contacts of the are entirely separated, the thyristor stack in the arming branch is triggered so that the fault current starts commutating into this branch, as shown in Figure 5c Step 3.2. Step 4: The capacitor in the second time-delaying branch operates similarly to the one in the first branch. This leads to the thyristor turning-off event in the whole timedelaying branch. Hence, the arming branch carries the fault current, as illustrated in Figure 5d. Step 5: The arming branch operates with the task to transfer the fault current into the nonlinear resistor path containing the main surge arrester. Ultimately, the fault current is interrupted by the arrester bank and the RCD opens to finish the current breaking process, as illustrated in Figures 5e and 5f, respectively. Copyright c2016 SERSC 385

As a result, the fault current breaking procedure throughout the five time intervals is represented in Figure 6. In general, the stages presented here are similar to those of the ABB s HDCCB topology. i DC i main RCD RCD i DC i time_delaying RCD RCD i DC i DC a) Step 1: 0 < t < t 2 b) Step 2: t 2 < t < t 3 RCD i DC i time_delaying i arming itime_delaying_1 itime_delaying_2 i time_delaying i arming itime_delaying_2 Step 3.1 Step 3.2 c) Step 3: t 2 < t < t 3 RCD i DC d) Step 4: t 3 < t < t 4 e) Step 5: t 4 < t < t 5 RCD f) Fault Completely Cleared Figure 5. Working Principle of the Alstom Grid s HDCCB i 386 Copyrightc 2016 SERSC

i I peak I trip i time_delaying i arming i i main I normal Main Branch Fault occurs Auxiliary Branch 0 t 1 t 2 t 3 t 4 t 5 t Fault cleared Figure 6. Fault Current Interruption of The Alstom Grid s HDCCB 3. Simulation Results In order to examine the performances and differences of ABB and Alstom Grid HDCCB topologies, two simulation models have been made. The implementation was executed by MATLAB / Simulink. Figures 7 and 9 illustrate the models of ABB and Alstom Grid HDCCB, respectively. Figure 7. Simulation Model of The ABB s HDCCB Copyright c2016 SERSC 387

For clear comparison between two models, the interruption procedure is observed during 0.15 s with fault occurring at 0.05 s. Furthermore, the basic parameters of the components in their main branches are selected to be the same so that the main branches operate similarly to each other. Additionally, for simplified testing, the auxiliary branch model of ABB includes only one IGBT cell with two anti-series IGBTs instead of several cells as real application. The Alstom Grid model also consists of single thyristors in each subsidiary branch. The fault clearance test of the ABB s HDCCB is shown in Figure 8. The performance of the currents i_main in the main branch, i_aux in the auxiliary branch, i_ through the surge arrester are examined, as shown in Figure 8a. At tripping value of 3000 A, i_main reduces to zero whereas i_aux increases to 3000 A and continue rising. After the mechanical switch opens completely, the current i_aux becomes zero and i_ rises, indicating the current commutation from the auxiliary branch into the surge arrester. The testing result of the fault current interruption procedure is shown in Figure 8b. Current (A) 4000 3500 3000 2500 2000 1500 1000 500 0 0.000 0.025 0.050 0.075 0.100 0.125 0.150 Time (s) a) Current in each Branch I_main I_aux I_ Idc (A) 4000 3500 3000 2500 2000 1500 1000 500 0 0.000 0.025 0.050 0.075 0.100 0.125 0.150 Time (s) b) Current passing through HDCCB Figure 8. Fault Current Interruption of The ABB s HDCCB Figure 9. Simulation Model of The Alstom Grid s HDCCB 388 Copyrightc 2016 SERSC

4000 3500 3000 2500 I_main I_time_delaying I_arming I_ 4000 3500 3000 2500 Current (A) 2000 1500 1000 Idc (A) 2000 1500 1000 500 500 0 0.000 0.025 0.050 0.075 0.100 0.125 0.150 Time (s) a) Current in each Branch 0 0.000 0.025 0.050 0.075 0.100 0.125 0.150 Time (s) b) Current passing through HDCCB Figure 10. Fault Current Interruption of the Alstom Grid s HDCCB Figure 10 represents the test of the fault current in the Alstom Grid s HDCCB with the currents i_main in the main branch, i_time_delaying in the time-delaying branch, i_arming in the arming branch and i_ through the main surge arrester. Although there are four currents to be observed in Figure 10a, the fault current performance in this simulation model is similar to that of ABB design, as shown in Figure 10b. It is observed that the auxiliary branch of Alstom Grid s HDCCB model carries the fault current for a longer period of time than the ABB one. Furthermore, the fault current interruption procedure in the ABB model finishes sooner than that of the Alstom Grid. Figure 11 describes in detail the zero-crossing points of these two HDCCB designs. It is observed that current zero of the ABB s HDCCB occurs at 0.093 s while this number is approximately 0.095 s in the Alstom Grid s HDCCB, 2 ms later than the former. For examining the case in which longer duration is needed for system protection, a delay time period of 3 ms is selected for the mechanical switch and the implementation is executed again. The zero-crossing point of this model in the new case is nearly 0.1 s, as shown in the dash-dot blue line in Figure 11. It is also observed that for the longer time of interruption, there is higher fault current of nearly 4000 A passing through the auxiliary branch of Alstom Grid s HDCCB. If the IGBT cells of ABB s HDCCB are used in this case, the very high value of the fault current can be a challenge for them. Hence, with the capability of safely withstanding very high fault currents, the thyristors used in Alstom Grid s HDCCB are preferred when the system requires more interruption time. In addition, in case the mechanical switch acts slowly compared to the IGBTs, thyristors are also more interested for application. Idc (A) 5000 4500 4000 3500 3000 2500 2000 1500 1000 500 0 ABB Model Alstom Model with no time delay applied Alstom Model with 3ms delay applied 0.000 0.025 0.050 0.075 0.100 0.125 0.150 Time (s) Figure 11. Zero-Crossing Points of Two HDCCB Models Copyright c2016 SERSC 389

4. Comparison between HDCCB Topologies of ABB and Alstom Grid As the previous parts introduced and implemented two HDCCB schemes of ABB and Alstom Grid, it can be seen that they have same working principles in general with three substantial branches. The main branch consists of one main mechanical disconnector in series with one power electronic switch whose function is to commutate fault current into auxiliary branch at time of fault detection. Consequently, the auxiliary branch of the two HDCCB schemes carries the fault current not only to postpone for some time, but also to reduce the very high current burden on the mechanical switch while it is opening. The main surge arrester absorbs energy after fault current commutates from the auxiliary branch into this nonlinear resistor path. Table 1 describes the comparison of ABB and Alstom Grid topologies in different aspects. First of all, the similarities of these two topologies are considered. ABB and Alstom Grid both apply the current commutation method with three significant branches for their own design. The main branch in each topology equivalently consists of one mechanical switch and at least a pair of anti-series IGBTs. In addition, the is used in the third branch of the two topologies with equivalent voltage rating for energy dissipation. Secondly, the main difference of ABB and Alstom Grid topologies locates in the auxiliary branch. ABB uses IGBT cells in series whereas thyristor stacks are preferred by Alstom Grid. There are some advantages and disadvantages of each semiconductor device mentioned above to be considered. The switching speed of the IGBTs is extremely high, which is either the benefit or the drawback of ABB s HDCCB. It is pointed out that if the mechanical switch is slow or if a longer time is needed for the DC protection, IGBTs can meet the challenge when carrying the very high fault current which is increasing continuously. Accordingly, Alstom Grid uses thyristor stacks to fulfill this problem because they can safely withstand very high fault currents. However, the thyristors in this topology require a capacitor connected in series in order for fault current interruption. When the two HDCCB topologies are compared with each other, according to the characteristics of the semiconductor devices, it can be noticed that ABB scheme interrupts the fault current more quickly whereas the design of Alstom Grid carries the high fault current more safely than each other. In practice, IGBTs with capability of switching on and off easily are more commercially favored so they might be more high priced than thyristor. Furthermore, in ABB topology, higher voltage level requires higher number of IGBT cells in series, leading to high component cost demand in HVDC system. Nevertheless, each thyristor stack is connected in series with one appropriate capacitor whose price increases depending on its size and voltage rating. Thus, the higher voltage level of the system leads to the higher component price for the Alstom Grid scheme. Another difference between the two topologies locates in the power losses during normal operation. Because the IGBT cells in the auxiliary branch of ABB s HDDCB remain turning on at steady state, there is a very small amount of losses when the load current passes through the HDCCB. The transfer losses of ABB s HDCCB are only a percentage of the losses incurred by a pure semiconductor breaker, for example 0.01% of the transmitted power [10]. The utilization of IGBT cells makes the operation of the ABB s HDCCB still include higher losses than the Alstom Grid s HDCCB which uses thyristors. However, the losses in the capacitor banks in the Alstom Grid topology are also increased in case of the high voltage level. Finally, the application of each topology in HVDC system is also considered. The voltage-source converter (VSC) HVDC system uses semiconductors which can pass current in either directions and can be controlled to turn on or off, for example IGBTbased switches. Meantime, the line-commutated converter (LCC) HVDC system consists of semiconductors which can carry voltage in either polarities and can be controlled to turn on only, for instance thyristor-based devices. Moreover, one of the disadvantages of 390 Copyrightc 2016 SERSC

the IGBT when compared to the thyristor is that the former has lower power capability and weaker overload capability than the latter. Accordingly, the thyristor-based LCC HVDC system can carry greater power and withstand overload more effectively than the IGBT-based VSC one. Hence, the applications of ABB s HDCCB should be included in VSC-HVDC system rather than LCC ones. On the contrary, the LCC-HVDC system is relatively more suitable for Alstom Grid s HDCCB. Furthermore, with economical consideration, the medium voltage DC (MVDC) system is more appropriate for ABB s HDCCB application rather than Alstom Grid one because the IGBT cost is not as high as the capacitor cost in MVDC system. However, the IGBT price increases significantly when IGBTs are applied in HVDC system. It is eventually higher than the capacitor price despite the increasing size and cost of the capacitor bank used in Alstom Grid s HDDCB. Thus, the price of ABB s HDCCB including IGBT cells is quite fairly higher than that of Alstom Grid one consisting of thyristor stacks and capacitors. Consequently, for HVDC system application, it is certain that Alstom Grid s HDCCB is preferred in systems which require longer time delay for system protection and ABB s HDCCB is more appropriate for systems in which fast current interruption is necessary. Table 1. Comparison between ABB and Alstom Grid HDCCB Topologies ABB HDCCB Alstom Grid HDCCB Current breaking method Current commutation method. Current commutation method. One mechanical disconnector in One mechanical disconnector in series with Main branch series with at least two IGBTs at least two IGBTs connected anti-series. components connected anti-series. Auxiliary branch components Uses IGBT cells in series. Uses Thyristor stacks in series with an appropriate capacitor. Surge arrester + Depends on the number of IGBT + Depends on the number of thyristor stacks cells. and capacitor size. Component cost + The higher voltage level of the + The higher voltage level of the system, demand system, the more IGBT cells the larger size of capacitor required. required. + The IGBTs are able to switch on The thyristors can withstand very high fault Advantages and off very quickly. currents safely. + IGBTs can be controlled to turn on or off easily. In case of longer time needed for Thyristors cannot be turned off easily as Disadvantages system protection, IGBTs struggles IGBTs. They require a capacitor connected in withstanding high peak current. in series to reduce fault current to zero in order for automatically turning off. + Low losses in the range of several + Low on-state losses. On-state losses tens of kw only. + Low enough for the use of liquid coolants + Higher losses than Alstom Grid HDCCB. + Significantly high. High although the system protection require Fault current + A few milliseconds higher than long time delay. interruption speed Alstom Grid topology. Application 5. Conclusions Preferred in MVDC system and HVDC system in which the fast fault current interruption is required. Preferred in HVDC system which requires the more time delay for system protection. In this paper, the HDCCB topologies of ABB and Alstom Grid were compared. The differences between the two topologies locate in the semiconductor components in their auxiliary branch. In ABB topology, the special IGBT is used leading to an increasing total cost of its topology, and the losses in HDCCB is mainly due to the losses in IGBT cells. By comparison, in the Alstom Grid topology, thyristor stacks are used instead of IGBT cells, which require the capacitor banks to interrupt the fault current. Therefore its total Copyright c2016 SERSC 391

cost can be increased due to the size of the capacitor banks. The fault current interruption speeds of both designs were examined and compared to each other. The results showed that the ABB model breaks the fault current more rapidly than the Alstom Grid one. It was also noticed that in case of longer time required for system protection, the Alstom Grid design with thyristor stacks in auxiliary branch can carry the very high fault current safely. Acknowledgment This work was supported by Incheon National University Research Grant in 2014. References [1] M. M. Rahman, M. F. Rabbi, M. K. Islam, and F. M. Mahafugur Rahman, HVDC over HVAC Power Transmission System: Fault Current Analysis and Effect Comparison, In Proceeding of the International Conference on Electrical Engineering and Information & Communication Technology (ICEEICT), Dhaka, (2014) April 10-12, pp. 1-6. [2] G. F. Reed, H. A. Al Hassan, M. J. Korytowski, P. T. Lewis, and B. M. Grainger, Comparison of HVAC and HVDC Solutions for Offshore Wind Farms with A Procedure for System Economic Evaluation, In Proceeding of the IEEE Conference on Energytech, Cleveland, OH, (2013) May 21-23, pp. 1-7. [3] T. Senda, T. Tamagawa, K. Higuchi, T. Horiuchi, and S. Yanabu, Development of HVDC Circuit Breaker Based on Hybrid Interruption Scheme, IEEE Trans. Power Apparatus and Systems, vol. PAS- 103, no. 3, (1984) March, pp. 545-552. [4] G. Ge, M. Liao, X. Duan, and J. Zou, HVDC Hybrid Circuit Breaker Based on SF6 Interrupter and Vacuum Interrupter in Series, In Proceeding of the 2nd International Conference on Electric Power Equipment Switching Technology (ICEPE-ST), Matsue, (2013) October 20-23, pp. 1-4. [5] C. Peng, A. Q. Huang, and X. Song, Current Commutation in A Medium Voltage Hybrid DC Circuit Breaker Using 15 kv Vacuum Switch and SiC Devices, In Proceeding of the Applied Power Electronics Conference and Exposition (APEC), Charlotte, NC, (2015) March 15-19, pp. 2244-2250. [6] W. Zhou, X. Wei, S. Zhang, G. Tang, Z. He, J. Zheng, Y. Dan, and C. Gao, Development and Test of A 200kV Full-Bridge Based Hybrid HVDC Breaker In Proceeding of the IEEE 17th European Conference on Power Electronics and Applications (EPE'15 ECCE-Europe), Geneva, (2015) September 8-10, pp. 1-7. [7] O. Cwikowski, M. Barnes, R. Shuttleworth, and B. Chang Analysis and Simulation of the Proactive Hybrid Circuit Breaker, In Proceeding of the IEEE 11th International Conference on Power Electronics and Drive Systems (PEDS), Sydney, NSW, (2015) June 9-12, pp. 4-11. [8] U. Amir Khan, J-G. Lee, F. Amir, and B-W. Lee, A Novel Model of HVDC Hybrid-Type Superconducting Circuit Breaker and Its Performance Analysis for Limiting and Breaking DC Fault Currents, IEEE Trans. Applied Superconductivity, vol. 25, no. 6, (2015) December. [9] A. Hassanpoor, J. Hafner, and B. Jacobson, Technical Assessment of Load Commutation Switch in Hybrid HVDC Breaker, IEEE Trans. Power Electronics, vol. 30, no. 10, (2015) October, pp. 5393-5400. [10] M. Callavik, A. Blomberg, J. Hafner, and B. Jacobson, The Hybrid HVDC Breaker - An Innovation Breakthrough Enabling Reliable HVDC Grids, ABB Grid Systems, Technical Paper, (2012) November. [11] W. Grieshaber, J-P. Dupraz, D-L. Penache, and L.Violleau, Development and Test of A 120kV Direct Current Circuit Breaker, CIGRÉ Session, Paris, (2014), Paper B4-301. [12] R. Derakhshanfar, T.U. Jonsson, U. Steiger, and M. Habert, Hybrid HVDC Breaker Technology and Applications in Point-to-Point Connections and DC Grids, CIGRÉ Session, Paris, (2014), pp. 1-11. [13] C. C. Davidson, R. S. Whitehouse, C. D. Barker, J-P. Dupraz, and W. Grieshaber, A New Ultra-Fast HVDC Circuit Breaker for Meshed DC Networks, In Proceeding of the IEEE 11th International Conference on AC and DC Power Transmission, Birmingham, (2015) February 10-12, pp. 1-7. [14] B-C. Kim, Y-H. Chung, H-D. Hwang, and H-S Mok, Development of HVDC Circuit Breaker with Fast Interruption Speed, In Proceeding of the IEEE 9th International Conference on Power Electronics and ECCE Asia (ICPE-ECCE Asia), Seoul, (2015) June 1-5, pp. 2844-2848. [15] A. Raza, X. Diangou, S. Xunwen, and L. Weixing, Appraisal of VSC Based MTDC System Topologies for Offshore Wind Farms, In Proceeding of the IEEE 9th International Conference on Power Electronics and ECCE Asia (ICPE-ECCE Asia), Seoul, (2015) June 1-5, pp. 2141-2147. 392 Copyrightc 2016 SERSC

Authors Anh-Duc Nguyen, he received B.S. degree in Electrical Engineering from Hanoi University of Science and Technology, Vietnam in 2014. Currently, he is a combined Master and Ph.D. student in the Department of Electrical Engineering, Incheon National University, Korea. His research interests include HVDC protection and HVDC applications. Thai-Thanh Nguyen, he received B.S. degree in Electrical Engineering from Hanoi University of Science and Technology, Vietnam in 2013. Currently, he is a combined Master and Ph.D. student in the Department of Electrical Engineering, Incheon National University, Korea. His research interests include power system analysis and FACTS & HVDC modeling and analysis. Hak-Man Kim, he received his first Ph.D. degree in Electrical Engineering from Sungkyunkwan University, Korea in 1998 and received his second Ph.D. degree in Information Sciences from Tohoku University, Japan, in 2011, respectively. He worked for Korea Electrotechnology Research Institute (KERI), Korea from Oct. 1996 to Feb. 2008. Currently, he is a professor in the Department of Electrical Engineering, Incheon National University. His research interests include Microgrids and DC power systems. Copyright c2016 SERSC 393

394 Copyrightc 2016 SERSC