LUNERA BALLASTLED TM TECHNOLOGY AND POWER FACTOR

Similar documents
LUNERA BALLASTLED TECHNOLOGY AND POWER FACTOR

Electrical Power Electric power electrical electric power Electric power electric electric

LANCE-KASHIAN & COMPANY River Park Plaza Parking Lot Lighting Retrofit Fresno, CA May 21, 2013

Constant wattage for high intensity discharge (HID) lamps

Understanding Electronic UltraMax HID Ballasts

Pump ED 101. Power Factor (Part 2) - - Electricity Behaving Better

Working Principle of Power Saver as per Manufacture:

Alternator as a voltage Generating source and its response to the leading power factor loads

Lighting Tables for New Equipment 7/16/2008

Lighting Tables for New Equipment 3/9/2016

Power Quality Luis Vargas Research Engineer 9/18/2008

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

DS-1 (Residential) Customer Charge Per electric service account $ 8.23 $ 8.23 $ 8.23 Meter Charge Per electric service account $ 6.06 $ 6.06 $ 6.

2001 TMT Associates 1

Emerging Lighting Technologies IEEE - March 21, 2001

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

GECAP24400V0 Capacitor For 400W MH BLST

TECHNICAL TERMS AND ABBREVIATIONS

Lucalox XO High Pressure Sodium Lamps with improved reliability Lucalox TM XO Tubular Clear 50W, 70W, 100W, 150W, 250W, 400W & 600W

Understanding Electronic UltraMax HID Ballasts

The simplest way to convert to LED

Lighting Tables for New Equipment 2/24/2015

Power Factor Correction

Lighting Tables for New Equipment 1/1/2018

Lighting Tables for Existing/Base Equipment 4/15/2011

GE Lighting DATA SHEET. Product information. Features. Applications

Is Uncorrected Power Factor Costing You Money?

Lighting Tables for Existing/Base Equipment 4/15/2011

Lighting Tables for Existing/Base Equipment 1/1/2014

Eskisehir Light Train- Correcting Capacitive

ELECTRICAL FUNDAMENTALS

Lucalox PSL. GE Lighting DATASHEET. Lucalox PSL Tubular Clear 230V 250W, 400W, 600W and 750W Lucalox PSL Tubular Clear 400V 600W and 750W

FROM YE OLDEN DAYS OF EFFICIENT LIGHTING TO TODAY S STANDARDS FOR EFFICIENCY. WE LL DISCUSS WHY EACH TECHNOLOGY WAS

Installation Planning (or what I didn t learn at meter school)

Power Factor Correction

DC CIRCUITS ELECTROMAGNETISM

Chapter 3.1: Electrical System

Non-Summer, First 800 kwh $ $ $ Non-Summer, Over 800 kwh $ $ $

Product Selection Card

Lunera T-LED Lamp Family: Engineered for Quality & Reliability

Volume 2 Charts, Formulas, and Other Useful Information

ELECTRONIC HID BALLASTS

White Paper. Application of Resistive/Reactive Load Banks for kva Testing

DESCRIPTION & APPLICATION

Power Quality and Energy Management

Technical Information Guide

Lucalox Standard. GE Lighting. Product information. Applications areas

Be Off The Grid com Inc.

T5 versus T8 Fluorescent Lamps. The good, the bad, & the ugly about T8 and T5 lamps

Arcstream Double Ended

Steve Sindoni Commercial Engineer OSRAM Sylvania

Microcontroller Based Power Factor Correction Using SCR

HSI-HX / HSI-THX SA HSI-THX 400W 4K E40 SLV PRODUCT OVERVIEW DATA TABLE. Optical data

ELECTRONIC HID BALLASTS

Mandatory Fluorescent Changes For 2012

Electrical Design/Build Guide

ELECTRONIC HID BALLASTS

TVA Distributor Retail Rates and Comprehensive Services Program Power Factor Case Studies. Gerald Johns, P.E. Power Utilization Engineer, TVA

UNIT 2. INTRODUCTION TO DC GENERATOR (Part 1) OBJECTIVES. General Objective

POWER METER. my2010 (c)

TABLE OF CONTENTS CHAPTER 1 ELECTRICAL THEORY About This Textbook...xi. Passing Your Exam...xiv. How to Use the National Electrical Code...

kvah Billing - Frequently Asked Questions (FAQs)

GE ConstantColor CMH StreetWise

Philips-Advance High Efficiency Ballasts & Energy-Saving Ballast Strategies

Single-Phase Meter Components

ABB n.v Power Quality in LV installations

Customer and Utility Energy Management Fundamentals 101

UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1. UNIT 2 ELECTRICAL CIRCUITS...49 Introduction...49

Table of Contents. CHAPTER 1 ElECTRiCAl THEoRY Mike Holt enterprises, inc neC.Code ( )

The Provincial Energy Goals. BC Provincial Energy Commitments: A Practical Solution. The Municipal Challenges

Lunera Product Catalog

Other Devices. Installation Contactors Z-SCH. Connection diagrams Z-SCH NO 3 NO / 1 NC. Permitted Installation Positions

ConstantColor CMH Supermini Ultra

inductors Inductors Power Inductors/Chokes Precision Wound Heavy Duty Toroidal Inductors 120 Volts... I2-I3 240 Volts... I3

Energy Saving Options for Small ISDs. Presented by Casey Stone, PE, CEM

MIPSYCON 2014 Can a Grid be Smart without Communications? A Look at an Integrated Volt Var Control (IVVC) Implementation

CUSTOMER / ACCOUNT INFORMATION Electric Utility Customer Information (As shown on utility bill)

Technical Report 2: Electrical Systems Existing Conditions + Building Load Summary Report

General Purpose Buck - Boost Wiring Diagrams... 86

LED Lighting Initiative. Presentation for Sales February 14, Time to catch the wave!

Southern California Edison Revised Cal. PUC Sheet No E Rosemead, California (U 338-E) Cancelling Revised Cal. PUC Sheet No.

NHPUC No. 3 - Electricity Delivery Thirtieth Revised Page 4 Unitil Energy Systems, Inc. Superseding Twenty-Ninth Revised Page 4

High Performance LED High Bays

LUNERA T8 LED RETROFIT KITS 1/2/3/4-Lamp Replacement Kits for 2FT or 4FT T8 Fluorescent Lamps

Power Systems Trainer

GE Ballast HID Electromagnetic nomenclature

Lucalox Standard Tubular Clear Product Code * * 11678* LU150/100/ HO/T/E40 LU150 /100/40

HOKKIM. Control & Protection Relays. giving you control. Utilization: Power Factor Regulator : 14-STEP CYCLIC POWER FACTOR REGULATOR.

CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION

50 Hz Mini/Micro Computer Regulator (MCR) Series Installation and Operation Manual

Number 9 January SECTION 1 Dimming of T12 Fluorescent lamps 2. SECTION 2 Dimming of T8 Fluorescent lamps 4. SECTION 3 Do's and Don'ts 6

SILICONES GLOBAL SOLUTIONS

Electric Utility Contact Information Indiana Michigan Power

EFFICIENCY IMPROVEMENT OPPORTUNITIES IN OUTDOOR LIGHTING

TED 5000 USER MANUAL

Table of Contents. CHAPTER 1 BASIC ELECTRICAL THEORY (Essential for Journeyman and Master s Licensing Exams)... 1

ORTRONIC System GREEN PLANET COMPANY.

ADF. Restoring the perfect wave

International Journal of Advance Research in Engineering, Science & Technology

TABLE OF CONTENTS. About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1

Transcription:

LUNERA BALLASTLED TM TECHNOLOGY AND POWER FACTOR Replacing metal halide lamps in magnetic ballast-driven fi xtures with the Lunera Susan Lamp, a LED plug-and-play replacement, causes the ballast to have a leading (capacitive) power factor. In most large facilities, this leading power factor can used to offset other lagging (inductive) devices such as motors and pumps resulting in an improvement of the building s overall power architecture and fi nancial savings to the user. What is Power Factor (PF) Power factor (PF) is a measurement of the alignment of the voltage and current waveforms in an AC system, a number from 1.0 (perfect aligned) to 0.0 (90 out of phase). What causes voltage and current to be misaligned are reactive loads which can either be lagging (inductive such as motors, pumps and most power converters) or leading (capacitive), as opposed to resistive loads. Neutral (Resistive) Load Voltage and Current Aligned PF=1.0 Lagging (Inductive) Load Current Lags Voltage PF < 1.0 Leading (Capacitive) Load Current Lags Voltage PF < 1.0 Fig. 1 Power factor for a neutral (resistive) load vs. lagging (inductive) or leading (capacitive) loads. Loads seen in buildings are typically a combination of resistive and inductive loads driven by electric motors, magnetic ballasts and mixed plug loads. + = Lagging (Inductive) Load Leading (Capacitive) Load Neutral (Resistive) Load Fig. 2 When lagging and leading loads are added together, they have the helpful effect of canceling each other out as can be seen in Fig. 2. For example a 10A load with a lagging 0.6PF and a 10A load with a leading 0.7PF when added together create a combined load of 13A with a lagging PF of 0.99. Watts are a measure of the power delivered to a device. In an AC system it is: Watts = Voltage (V rms) Current (A rms) Power factor As opposed to Volt-Amps (VA) which is simply a measure of Voltage x Current Voltage-Amps = Voltage (V rms) Current (A rms) 1 of 6

2 of 6 Why do Utilities Care about Power Factor? Utilities charge for watts consumed; however their infrastructure of switching yards, transformers and distribution lines must be sized to the amount of current delivered. The effect of power factor on current can be quite dramatic: 10kW load driven at 277V with a PF of 0.95 draws a current of 38A 10kW load driven at 277V with a PF of 0.65 draws a current of 56A (46% more) As we saw earlier, lagging loads can be compensated by adding leading loads to them, or practically by applying capacitors; this is typically done at key stages in the distribution process such as the switching yard in order to compensate the lagging load and minimize the distribution losses and infrastructure requirements as shown in fi g. 3. Fig. 3 Utilities use large adjustable capacitor banks at various stages in the electrical distribution grid in order to compensate for lagging (inductive) loads and minimize the distribution losses and infrastructure requirements of supporting lagging loads. Fig. 4 Compensating capacitors perform power factor compensation at a utility switching yard.

3 of 6 Magnetic Ballasts, Compensation and Power Factor Arc lamps, such as fluorescent and HID lamps, require a high voltage to initially strike them. But once operating, they require a stable current flow in order to maintain the arc and light output. Magnetic ballasts use large magnetics (inductors) to accomplish this stable current flow. However, inductors have the downside of delivering a low power factor load so compensating capacitors are embedded in the ballast to compensate the load. The capacitor is sized to the delivered lamp load as shown in Fig. 5. Constant Wattage Autotransformer (CWA) Ballast 120V Power Switch Ballast Coil 120 Volt Power Cord BLACK WHITE BLACK 120V COM Primary Secondary BROWN GROUND TO LAMP COM Capacitor NBL Ignitor BLACK WHITE Lamp Cord (To Lamp) LAMP COM GROUND Fig. 5 Simplified magnetic ballast architecture with compensating capacitor. An inductor is used to limit power and control current to the amp while a capacitor is used to compensate for the lagging (inductive) load and generate a high power factor. The capacitor is sized to the relative load of the lamp. BallastLED Lamps and Magnetic Ballasts When a legacy arc lamp, driven by a magnetic ballast, is replaced with a Lunera BallastLED lamp which consumes 50% to 90% less power, the resulting ballast is now over-compensated for the reduced load it is driving. Simply put, after installing the Lunera BallastLED lamp, the capacitor installed in the ballast is larger than what is needed to compensate for the lagging power factor of the inductors in the ballast. This causes the ballast to have a leading (capacitive) power factor. In most large facilities this leading power factor can used to offset other lagging (inductive) devices such as motors and pumps resulting in an improvement of the building s overall power architecture and financial savings to the user. The following case studies explore the scenario of replacing a 400W metal halide lamp with a Susan Pro 400 LED lamp.

4 of 6 Case Study #1 Replacing a 400W Metal Halide Lamp with a Susan Pro 400 LAMP The Gen1 Susan Pro 400 lamp consumes 162W and delivers the same mean lumens as the 400W metal halide lamp it replaces. However, as the ballast is over-compensated, the load presented to the circuit is more complex. 400 300 400W Metal Halide v. Susan Pro 400 400W Metal Halide vs. 400W Susan Pro 4.0 4.0 3.0 3.0 Input Voltage (V) Input Voltage (V) 200 100 - - (100) (100) (200) (200) (300) (300) (400) (400) 2.0 2.0 1.0 1.0 0.0 0.0-3.0-4.0 Input Current (A) (-1.0) - 1.0 (-2.0) - 2.0 (-3.0) (-4.0) Input Current (A) Fig. 6 Input Volt-Amps of Metal Halide v. Lunera Susan Lamp Pro Susan Lamp creates a substantial reduction in both consumed power (watts) as well as volt-amps (VA). However, even more valuable, it creates a leading power factor load that can be used to offset other lagging power factor loads in the facility. For example, California utility company, PG&E, charges large customers (over 400kW) adjusts their kw rate based on the power factor of their load: A 0.06% premium is added for each point that a customer s power factor (PF) falls below 0.85 A 0.06% discount is applied for each point that a customer s power factor (PF) rises above 0.85 Table 1 Power Savings an VA Reduction of the Susan Lamps 400W HID Susan Pro 400 Susan Junior 400 400 162 100 W Ballast Power 45 45 45 W Total Power 445 207 145 W Current Phase Angle 26 (55) (66) Degress Ballast VA 494 363 354 VA Input Voltage 277 277 277 V rms Input Current 1.78 1.31 1.28 A rms Power Savings -53% -67% VA Reduction -27% -28% Learn more at: http://bit.ly/pgedocs

AND 5 of 6 Case Study #2 Building-Level Retrofit Implications of Replacing Metal Halide Lamps with the Lunera Susan Lamp Assumptions 100,000 sq. ft. building lit with 400W Metal Halide (MH) lamps on a 20 x20 spacing Building is operated 4,370 hours per year Lighting represents 35% of building electrical load; HVAC represents 35% of the building electrical load, and plug loads represent the remaining 30% Metal halide lamps and HVAC have a lagging power factor of 0.9; plug loads have a lagging power factor of 0.7 Comparing Metal Halide and Susan Lamp Solutions in the Building Before the Susan Lamp Retrofit After the Susan Lamp Retrofit W/sq. ft. Total Power Total Load W/sq. ft. Total Power Total Load Lighting 1.1 111kW 123kVA (lagging 0.90 PF) 0.50 52kW 91kVA (lagging 0.57 PF) HVAC 1.2 120kW 133kVA (lagging 0.90 PF) 1.20 120kW 133kVA (lagging 0.90 PF) Plug Load 1.0 100kW 142kVA (lagging 0.70 PF) 1.00 100kW 142kVA (lagging 0.70 PF) Aggregate 3.3 313kW 394kVA (lagging 0.84 PF) 2.70 271kW 284kVA (lagging 0.95 PF) Table 2 Comparing the building s power envelope before and after a Susan Lamp retrofit. Before the Susan Lamp Retrofit After the Susan Lamp Retrofit Energy Consumed 1.53M kwh 1.27M kwh Base Rate Charge $230, 155 $191,064 PF Surcharge +$924 (PF of 0.84 is below 0.85) -$11,553 (PF of 0.95 is above 0.85) Electric Bill $230,419 $179,510 (22.4% savings) Table 3 Comparing the building s cost of energy before and after a Susan Lamp retrofit using a PG&E PR calculation at a nominal rate of $0.15/kWh adjusted for power factor. Bottom Line Lighting power was reduced by 54%, including the ballast load from the HID fixtures. Total power was reduced by 18%. However total VA was reduced by 28% as the leading current going into the lighting fixtures now compensates for the lagging current inside the building. The result is a substantial improvement in the load presented to the utility, and a reduction in building load (VA) that is nearly twice as large as the power (watts) reduction enabled by the lamps.

6 of 6 Conclusion Retrofitting from legacy HID lamps to Lunera s BallastLED technology provides a building owner not only 50-90% energy savings and substantial maintenance savings, but also unlocks value in the magnetic ballasts to provide capacitive compensation for inductive loads in the building. These cost saving pillars justify the investment in your Susan Lamp retrofit: Energy Savings of 50-90% Up to a 5x extension in maintenance cycles for lamp replacement Improvement in light levels and light quality Building Level power factor Improvement of up to 11 basis points Potential for substantial rebates from your utility partner 2015 Lunera Lighting, Inc. All Rights Reserved. Lunera and the Lunera logo are registered trademarks; Lunera TruColor is trademark of Lunera Lighting, Inc. All other trademarks are the property of their respective owners. This document is for informational purposes only.