Duct System for a Server or Switch Cabinet Mounted Cisco 4900M (CNLTD21B2)

Similar documents
INLET DUCT FOR CISCO 6880 Part Number(s) DIRLC25S23W

INLET DUCT FOR CISCO 9513 SWITCH Part Number: DIBBC2314S21W

Installing the Switch Chassis

GT-Series GlobalFrame Gen 2 Cabinet System

Mass Exports- 2/368 B, Irugur Road, Chinniampalayam, Coimbatore , Tamil Nadu, India

GF-SERIES GLOBALFRAME CABINET SYSTEM

Space Saving Cable Management Rack Systems

DIGITAL AlphaServer 1000 and DIGITAL AlphaStation 600 Rackmount Installation Information

Space Saving Cable Management Rack Systems

HAW-EIBU Rack Installation Guide. Version 1.0

HP BladeSystem c7000 Carrier-Grade Options Installation Guide

THE NEW TS IT RACK 8

6U Vertical Server Cabinet - 30 in. depth

Chapter 3. Installing Equipment

Panduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF and ZDF

19 Server Cabinets SOHO/SMB Networking

2-Post Rack Mount Kit Installation Instructions

Service Bulletin No. 2994

Installation Instructions In-bottom/Out-back Cooling Kit for E4h Drives VLT FC Series FC 102, FC 103, FC 202, and FC 302

Data sheet. Server Rack ( heavy duty rack cabinet ) W:800 = D:1000

Vertical Cable Organizer with Finger Ducts - 0U - 3 ft.

Instruction Sheet SRSR SERIES. Rotating Sliding Rail System

Ortronics. Mighty Mo. GX Cabinets. Designed to Perform, Configured to Fit

Opticom Rack Mount Fiber Enclosures

Van Rack Installation Manual Ford Transit Connect

MAZDASPEED3 Intercooler Instructions

NEMA Enclosures Installation Instructions

4 Post Adapter Kit for Dell 1U Equipment

PANZONE Overhead Distribution Racks

Universal Network Zone System Part Numbers: Z23U-****

Installing the ONS M6 Shelf

Installing the Air Flow Regulator

MIGHTY MO CABLE MANAGEMENT SYSTEM

Network Zone System Part Numbers: Z23N-***** Z23R-****

Please take time to read and understand these installation instructions.

Cabinet and Rack Installation

ILL. 1. Horizontal. supply air cover panel shipped on HVAC unit. Access door/ panel

CABINETS, RACKS, AND CABLE MANAGEMENT SOLUTIONS

Merry-go-round Building Instructions

Frequently Asked Questions

Wall-Mount Server Rack with Built-in Shelf - Solid Steel - 8U

TL REPAIR MANUAL. Telma model FV61-00 (FU831310) replacement on Dana 19060S axle. Page 1 of 8 30jun10

Exhaust System Installation Corvette C6

Z22C-** Preconfigured Network Zone System

42U Server Rack Cabinet - 37 in. Deep Enclosure

483 mm (19 ) Server Cabinet Unique Series. Abstract. Features. 1.5 mm strong steel sheet. Load capacity up to 1000 kg. Standard colors grey and black

Modular Enclosure Solutions RACK IQ - ENTERPRISE & HYPERSCALE DATA CENTER CABINETS

Van Rack Installation Manual Dodge ProMaster

Installation Instructions

Network Zone System. Part Numbers: Z22N-****** Z22R-****

Tailcone Alignment Work aid, Using T (Laser Fixture), T (Target)

varioflex 19 network & server cabinets, 600, 800 mm width - 600, 800, 1000 mm depth

SHIMLESS INDUSTRIAL LINEAR BEARINGS

SHIMLESS INDUSTRIAL LINEAR BEARINGS - PATENT PENDING

18SP597 Series 60 Right-Side EGR Bolt-Together System to a Spherical Joint Tube-and-Shell Cooler with Pneumatic Actuator Valve

Tyler - Cargo Rack For Eurocopter AS-350 & AS-355 Series Helicopters FAA STC # SR01449LA

Installation Instructions : Huracan : Page 1

18SP596 Series 60 Right-Side EGR Bolt-Together System to a Spherical Joint Tube-and-Shell Cooler with Hydraulic Actuator Valve

Telecommunication rack systems Harju Elekter Teletehnika

ATLAS TRANSFER CASES CABLE SHIFTER units built before 4/30/12

SCHÄFER IT-Systems The specialists for IT infrastructure

Raidtec Rack Mount Guide Version 2.1

19 floor rack with steel door

W156.W158.W1510. W 15U Cabinet. 15U Rackmount Server Cabinet. 22U Rackmount Server Cabinet INTRODUCTION FEATURES FEATURES

INSTALLATION INSTRUCTIONS

Installation Instructions - D-Series Warming Cabinet Instruction Door for Hinge UseReversal (Glass and Stainless Steel Doors)

Vane pump upgrade kit 180F4161 isave 21 ERD Disassembling and assembling

INSTALLATION INSTRUCTIONS BUILT-IN KIT MODEL RK-12S30 PROVIDED PARTS

FLEX-6000 Rack Mounting Bracket Installation Guide

Cabinet and Rack Installation

Recommended Installation Procedure (11 DEC 09) ATech Timing Belt Tensioner (979847/901) VW 1.6/2.0L L4 EA189 CR Engine

AMP NETCONNECT 19 NETWORK AND SERVER RACK SYSTEM.

Product Cut Sheet N-SERIES TERAFRAME GEN 3 NETWORK CABINET SYSTEM SERVICE PARTS

NETWORK AND SERVER CABINETS

Cabinet and Rack Installation

Installation Instructions : Huracan : Page 1

42U Server Rack Cabinet - 30 in. Extra Wide - 37 in. Deep Enclosure

AMP NETCONNECT 19 NETWORK AND SERVER RACK SYSTEM.

Ref Qty Part Description Part Number -1- Kit ( ) Contents:

Cabinet and Rack Installation

Bulletin 1494V Variable Depth, Flange Operated Disconnect Switch Kits for 400 and 600 Amperes (Series A) Switches

SYSTEM # Installation Instructions for: CAMARO SS WITH 6.2L ENGINE REV. 12/13/17. Page 1 of 6

Assist Step Kit Installation (Side Assist Step)

50A Dual-Feed 5/5 GMT Total Front Access Fuse Panel

Suggested Installation Instructions for: , , Corvette C6 - Corsa Performance Exhaust System

INSTALLATION MANUAL. Melink Corporation (513) Revision

LP-R705XX 7000 Series ServerRack Cabinets.

P/N Rev 01 04/14-1- NOTE: If you are ordering hinges for your rear doors, order and/or

Piston Cooling Nozzle, Replacement

INSTALLATION MANUAL MULTI DECK HOT MERCHANDISERS MD PREMIUM. Versions. Solid back level Pass through level

LK4000 MOTOR CITY LIFT KING

Access rack system (ARS)

Caution: Wear protective goggles danger of chipped pieces! 01733AXX

Product Cut Sheet F-SERIES TERAFRAME GEN 3 CABINET SYSTEM SERVICE PARTS

Cisco Nexus 7700 Switches Environment

Competitor. Ultra Light Plus, Semi Electric Bed. Item # Owner s Assembly And Operating Manual

ClimateCab Cabinets and Accessories

Owner s Manual. 10U Wall-Mounted SmartRack Enclosure. Model: SRW10US W. 35th Street, Chicago, IL USA

IMPORTANT OWNER-OPERATOR INSTALLATION INSTRUCTIONS. A Hidden Power

Bill of Materials: Please take time to read and understand these installation instructions.

Transcription:

Duct System for a Server or Switch Cabinet Mounted Cisco 4900M (CNLTD21B2) Panduit Corp. 2012 INSTALLATION INSTRUCTIONS 4900M Duct (Installed in Net-Access Cabinet.) Switch Cabinet Application Server Cabinet Application Component Guide Ducting Server Adjustment Brackets Duct Box Right Hand Bracket Switch Adjustment Brackets Page 1 of 9

Table of Contents 4900M Ducting Section 1 SERVER APPLICATION Page Determine Location of 4900M Duct..... 1 Cage Nut Installation 2 Left and Right Hand Bracket Installation..... 3 Ducting Installation 4 Duct Box Installation.. 5 Section 2 SWITCH APPLICATION Page Determine Location of 4900M Duct 6 Left and Right Hand Bracket Installation... 7 Ducting Installation.. 8 Duct Box Installation 9 Page 2 of 9

SECTION 1 - Server Cabinet Application - Ports Facing Hot Aisle (Cabinet Part Numbers CS*** or S***) Determine Location of 4900M Duct Ducting requires (2) rack spaces for installation. Duct components are to be installed prior to switch installation and are designed not to support the switch. NOTE: Front-to-back equipment rail depth must be set to between 28.0 and 29.0. Intended Mounting Locations (2 rack spaces) Intended Mounting Locations (2 rack spaces) Note: Duct must be installed below or above Middle Front to Back Beam. Duct box Right Hand Bracket Install Cage Nuts Insert (2) cage nuts per equipment rail at 4900M component mounting locations (8 total cage nuts are to be installed). (1) grounding cage nut (green) must be installed in each equipment rail. The view below depicts cage nut locations for (1) intended mounting location. Intended Mounting Location (2 rack spaces) Cage Nuts (installed) Page 3 of 9

Installation Loosen the two nuts for the server adjustment bracket and adjust the bracket to match the distance between the front and rear rails of the Server Cabinet. Align the with the desired rack space, fasten the bracket using (2) #12-24 screws in the front rail and (2) in the rear rail. Tighten nuts on adjustment bracket to lock in place. -Repeat previous steps for Right Hand Bracket. Server Adjustment Brackets Right hand bracket Server Adjustment Brackets Note: Green Grounding Screw must go in Green Grounding Cage Nut. Page 4 of 9

Ducting Installation Install (1) Ducting Assembly to using (3) #10-32 nuts. Align Duct with pem studs in Left Hand bracket and secure with (3) #10-32 nuts. Front of cabinet Rear of cabinet Ducting Assembly (3) #10-32 Nuts Duct Box Installation Insert Duct Box into and Right Hand Bracket by sliding duct box along the lower flange. Push in until stop is reached, secure box with (2) #12-24 screws, and (2) #12 star washers. Rear of cabinet Front of cabinet (2) #12-24 Screws and (2) #12 Star Washers Duct Box Page 5 of 9

SECTION 2 - Switch Cabinet Application - Ports Facing Cold Aisle (Cabinet Part Numbers N*** or CN***) Determine Location of Duct Ducting requires (2) rack spaces for installation. 4900M Duct components are to be installed prior to switch installation and are designed not to support the switch. NOTE: Front-to-back equipment rail depth must be set to between 24.5 and 26.0 Intended Mounting Locations (2 rack spaces) Intended Mounting Locations (2 rack spaces) Right Hand Bracket Duct box Note: Duct must be installed below or above Middle Front to Back Beam. Page 6 of 9

Installation Loosen the two nuts for the switch adjustment bracket and adjust the bracket to match the distance between the front and rear rails of the Switch Cabinet. Align the with the desired rack space, fasten the bracket using (2) #12-24 screws in the front rail and (2) #12-24 screws in the rear rail. Tighten nuts on adjustment bracket to lock in place. -Repeat previous steps for Right Hand Bracket. Switch Adjustment Brackets Right hand bracket Switch Adjustment Brackets Page 7 of 9

Ducting Installation Install (1) Ducting Assembly to Right Hand Bracket using (3) #10-32 nuts. Align Duct with pem studs in Right Hand bracket and secure with (3) #10-32 nuts. Right Hand Bracket (3) #10-32 Nuts Rear of cabinet Front of cabinet Ducting Assembly Page 8 of 9

Duct Box Installation Insert Duct Box into and Right Hand Bracket by sliding duct box along the lower flange. Push in until stop is reached, secure box with (2) #12-24 screws, and (2) #12 star washer. Once duct box is installed, remove the Panduit label and rotate it 180 degrees then re-apply the label. Front of cabinet Rear of cabinet (2) #12-24 Screws and (2) #12 Star Washers Duct Box Note: Orientation of Duct Box Page 9 of 9