Temperature Controller (Heat Pumps)

Similar documents
Differential Pressure Sensors

Differential Pressure Sensors

Air damper actuators

GDB..3..1A GLB..3..1A

Air damper actuators

Actuators for Fire Protection Dampers

SAV Electronic Valve Actuator

Use. Functions. OpenAir TM. Rotary version, modulating, with spring return, AC 24 V

Actuators for Fire and Smoke Protection Dampers

Flowrite 599 Series SAX Electronic Valve Actuator Non-spring Return, 24 Vac, 3-Position Control

Differential Temperature Controller

2-position electric actuators with Ball valves VBZ ½...11/4

Electromotoric actuators

Actuators for air dampers and control valves of oil burners

Actuators for air dampers and control valves of oil burners

Differential pressure sensor

SAX Electronic Valve Actuator

MWF+ Application. Types Available. Average temperature sensor. Datasheet

Actuators for air dampers and control valves of oil burners

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

Electromotoric Actuators

Actuators for Fire and Smoke Protection Dampers

Electromotoric Actuators

Electromotoric Actuators

AKF10+ Application. Types Available. Duct-/Immersion temperature sensor. Datasheet

AKF10+ Application. Types Available. Duct-/Immersion temperature sensor. Datasheet

Condensation monitor

Switching DC Power Supply

Cable Temperature QAP... Sensor. Use

Commercial Actuator Selection Chart Non-Spring Return

Pressure Sensors. for liquid and gaseous media

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

Actuators for Fire and Smoke Protection Dampers

Modulating control valves with magnetic actuators, PN 16

Actuators for Air and Gas Dampers

Polygyr -Compact Exhaust Air Temperature Controller

Electronic Ignition Module

Controllers & Transmitters

Electromotoric Actuators

VLF45... Hot Air Valves. Siemens Building Technologies HVAC Products

DuraDrive MF /MS Series Non-spring Return Rotary Electronic Damper Actuators 24 Vac Three-position/Modulating

Electro-hydraulic actuators for valves

2-Port and 3-Port Zone Valves, PN16

Electromotoric Actuators

Electromotoric actuators

Differential Pressure Sensors

For air / gas dampers and control valves of oil or gas burners

RE48AML12MW time delay relay 2 functions s..300 h V AC - 2 OC

JUMO ecotrans Lf 01/02

MF /MS Series

Actuators for Air and Gas Dampers

Electrical data Nominal voltage AC/DC 24V Nominal voltage frequency 50/60Hz

See «Overview of types»

Electrical Actuators

Differential Pressure Switch QBM81-

Actuators. Building Technologies Division

Actuators for small valves

Power consumption In operation At rest For wire sizing. Connection Motor. Auxiliary switch

Differential Pressure Switch QBM81-

Modulating control valve with magnetic actuator PN16

Electromotoric Actuators. for zone valves VVI46.., VXI46.., VVS46.. and VXS46..

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

M A N U A L. Field Current Controller F2.2

Immersion temperature sensor QAE26.9.

Boiler Management Unit (BMU)

For air dampers and control valves of oil or gas burners

YCCS Zone/Bypass Damper Assembly

Model DS1000/DT20 System

Electronic Ballast EVG 2000-T

Technical Documentation

YCCS Zone/Bypass Damper Assembly

Commerical Comfort System (CCS) Variable Air Volume (VAV) Zone Pressure Independent Damper Controller

SMT-150 Installer Manual

Electromagnetic Flow Monitor magphant

RE48AML12MW time delay relay 2 functions s..300 h V AC - 2 OC

Dusty / Dusty Ex. Low-Cost Broken Bag Detection. Operating Instructions. SWR engineering Messtechnik GmbH

Metasys Zoning Package Installation

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN. Rev.

JUMO MIDAS S05 Pressure transmitter Type

ISO-TECH IPS1810H and IPS1603D DC power supply ISO-TECH IPS 1810H et IPS 1603D Alimentation électrique c.c.

Variable speed drives

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return Rotary 24 Vac 3-position Control

Operating instructions Flow monitors SI / / 2010

Output signal active note. Measuring range rel. pressure. Electrical Data Power supply DC V, ±10%, 1.1 W

Operating instructions Flow monitors SI5000 SI / / 2007

Control Solutions Biofloor

Micro-differential Pressure High-precision Digital Pressure Sensor For Gas DP-M SERIES

Application Support. Product Information. Omron STI. Support Engineers are available at our USA headquarters from

Differential Pressure Sensors

Power consumption In operation At rest For wire sizing. Cable 1 m, 2 x 0.75 mm 2 Cable 1 m, 6 x 0.75 mm 2 Functional data Torque Motor Spring return

Power consumption In operation At rest For wire sizing

DEVICE STATE/BYPASSED FAILURE OVERLOAD

Defining a timer in simple terms. Which actions are executed? Which market are they used frequently? Benefits and Advantages

STRA-24 for chilled beams

Technical data. Safety notes. Power consumption In operation At rest For wire sizing. 1.5 nominal torque 0.2 W 4 VA Auxiliary switch

ExBin-P Pressure switches 5 Pa Pa

Direct Coupled Damper Actuator Model MY6050A1001

EUROTHERM ONTROLS. Two phase thyristor power switches. Product data

MX4X-6XXX Series MX4X-7XXX Series. Selection Guide. Applications. DuraDrive Series Actuators and Accessories

Technical Instructions Document No EA GQD May 6, OpenAir GQD Series. Spring Return, 20 lb-in (2 Nm), Rotary Electronic Damper Actuators

Transcription:

3 345 Temperature Controller (Heat Pumps) For comfort control in HVAC systems RWD31 RWD41 Stand-alone electronic temperature controller Four 2-position (On/Off) outputs Easy adjustment of parameters via potentiometers LED indicators for heating and cooling demand DIN rail or panel mount Use The RWD31 and RWD41 controllers are intended for Heating, Ventilating and Airconditioning systems including Heat Pumps. Control equipment Single or dual compressor Heat Pumps Single or dual stage heating and cooling equipment Functions summary Stand-alone controller with four 2-position(On/Off) outputs One main temperature sensor (Ni 1000) input One auxiliary input for remote setpoint adjustment One digital input D1 for standby (On/Off) mode CE2N3345en 15.01.2003 Siemens Building Technologies HVAC Products

Output Type summary Input Output Supply Voltage Type Analog Digital 2-position 2 1 4 AC 230 V RWD31 2 1 4 AC 24 V RWD41 Accessories Name Protective single enclosure for wall mounting Protective multiple enclosure for wall mounting Time Clock Transformer (30VA) Type ARG62.21 ARG62.22 SEH62.1 SEM62.1 & SEM62.2 Equipment combinations The following units can be connected to RWD31 and RWD41 controllers. Units Data sheet no. Sensors with Ni1000 temperature sensing element 17... to 18 Room temperature sensor with setpoint adjuster QAA25 1721 / 1748 or QAA25/AP Remote setting unit FZA21.11 1981 Siemens actuators with 2-position input 45 / 46 Other equipment with 2-position input Examples: compressors, electric heaters, Other combinations with third party units are possible, provided input and output specifications match the RWD31 and RWD41. Functions Main function The input B1 detects the actual temperature and compares it with the setpoint. Depending on the deviation, the controller acts accordingly with its outputs to achieve the desired setpoint. The RWD31 and RWD41 controllers have the following output configuration. on2 2 x SD_H 2 x SD_C off_z Q1 on1 off2 off2 on1 Q2 Q3 off1 off1 on2 SP SD_H SD_C Off_Z Setpoint Switching Differential for Heating Switching Differential for Cooling Off Zone SD_H SP SD_C T C Q1 = Heating stage 2 (Reverse acting) Q2 = Heating stage 1 (Reverse acting) Q3 = Cooling stage 1 (Direct acting) = Cooling stage 2 (Direct acting) Input B1 Input R1 Digital input D1 The input B1 is used for Ni 1000 temperature sensor. The input R1 is used for passive remote setpoint adjuster (0 1000 Ω : 0 50 C). Digital input D1 is used to implement the standby (On/Off) mode. Changeover occurs via potential-free contact between D1-GND. 2/8 Siemens Building Technologies Data sheet CE2N3345en

Delay times The outputs have fixed delay times to protect equipment from switching On/Off too frequently. Set delay switch to ON position Changeover delay (heating demand cooling demand) Inter-stage delay from stage 1 stage 2 (cooling & heating) Minimum off time for stage 1 & stage 2 (cooling & heating) Delay 120s 120s 120s Operating and setting elements The RWD31 and RWD41 parameters are adjusted via potentiometers. 6 5 9 8 4 3 2 1 7 Range 1. Off Zone 0 8K 2. Setpoint 15 30 C 3. Switching differential for cooling 0.5 4K 4. Switching differential for heating 0.5 4K 5. Re-calibration sensor adjuster -5 +5K 6. Delay switch On/Off LED indicators 7. Orange LED for power ON and standby mode (LED flashes) 8. Green LED for cooling demand 9. Red LED for heating demand Applications Example Air conditioning plant with temperature control. Dual compressor heat pump. + B1 = Space temperature Q2 = Heating stage 1 Q1 = Heating stage 2 Q3 = Cooling stage 1 = Cooling stage 2 3345s01 - Q1 Q2 Q3 Q1 Q2 Q3 B1 Temp. Siemens Building Technologies Data sheet CE2N3345en 3/8

Remote setpoint adjustment A remote setting unit (FZA21.11) or an integrated sensor with setpoint (QAA25/AP, QAA25), connected to terminals R1-M, enables remote adjustment. In this case, the controller s setpoint adjuster must be set to Ext. position. Passive measurement from 0 1000 Ω corresponding range from 0 50 C. + - 3345s02 Q1 Q2 Q3 Q1 Q2 Q3 R1 B1 Temp. Standby A switch contact (via time clock, thermostat) between digital input D1-GND is used to enable the standby mode. During standby mode, all Q outputs are OFF. + - 3345s03 Q1 Q2 Q3 D1B1 Q1 Q2 Q3 Temp. Mechanical Design Housing Protective housing ARG62.21/ARG62.22 Terminals The RWD31 & the RWD41 temperature controllers are as per DIN 43 880 Gr. 1 requirements. A protective housing is used to protect the controller when mounted outside a control panel, such as on ducts, walls and in plant rooms. Furthermore, the protective housing prevents inadvertent contact with voltage supplying parts such as the connecting terminals. The RWD31 or RWD41 clips into the protective housing. The cable entries are located at the top and the bottom of the protective housing. The front has an opening for the adjustment potentiometers. Screw terminals Installation notes The RWD31 and RWD41 controllers can be mounted as follows: Observe all local installation and mounting regulations. A B C D On a DIN rail (EN 50 022-35 x 7.5) at least 120 mm long Wall mounted with 2 screws Front mounted using standard elements. e.g. 1x DIN rail 150 mm long, 2x hexagonal placeholders 50 mm, washers and screws In the ARG62.21/ARG62.22 protective housing A B C D 4/8 Siemens Building Technologies Data sheet CE2N3345en

Electrical installation Standard cables can be used for the controller. However, when mounting in an environment greatly exposed to EMC, use only shielded cables. The RWD31 is designed for AC 230 V operating voltage. The RWD41 is designed for AC 24 V operating voltage. The low voltage must comply with the requirements for safety extra-low voltage (SELV) as per EN 60730. Use safety insulating transformers with double insulation as per EN 60742; they must be designed for 100 % on-time. When using several transformers in one system, the connection terminals must be galvanically connected. Supplying voltages above AC 24 V to low voltage connections may damage or destroy the controller or any other connected devices. Additionally, connections to voltages exceeding AC 42 V endanger personnel safety. Engineering notes The sections marked with a warning symbol contain technical safety requirements and restrictions. Observe all of these warnings as they directly relate to the protection of personnel and equipment. Technical data General data Power supply Power consumption Operating voltage RWD31 Operating voltage RWD41 Safety extra-low voltage (SELV) as per Frequency RWD31 Frequency RWD41 RWD31 RWD41 AC 230 V +10 % -15% AC 24 V ±20 % EN 60730 50 Hz/60 Hz 50 Hz/60 Hz 4.5 VA 3 VA Environmental conditions Environmental conditions IP code Transport Climatic conditions Temperature Humidity Mechanical conditions Operation Climatic conditions Temperature Humidity Housing Front Front and with ARG62.2.. IEC721-3-2 Class 2K3 25...+70 C <95 % r.h. Class 2M2 IEC721-3-3 Class 3K5 0...+50 C <95 % r.h. IP 20 as per EN 60529 IP 20 as per EN 60529 IP 30 as per EN 60529 Product standards Automatic electrical controls for household and similar use EN 60730 conformity In accordance with European Union directives Electromagnetic compatibility EMC Low voltage directive 89/336 EEC 73/23 EEC Siemens Building Technologies Data sheet CE2N3345en 5/8

Other international approval Terminals Weight without packaging Emissions Immunity Safety C tick compliance Screw terminals for cables with RWD31 RWD41 EN 50081-1 EN 50082-1 EN 60730 N474 min. 0.5 mm dia. max. 2 x 1.5 mm 2 or 2.5 mm 2 0.410 kg 0.320 kg Analog input B1 Ni 1000 Ω at 0 C Remote setpoint R1 Digital input D1 Digital outputs Q s Controller setpoint range Max. cable length for dia. 0.6 mm Range Max. cable length for dia. 0.6 mm Polling voltage for control commands (D GND) Current consumption Relay contacts (potential-free) Voltage Maximum rating Minimum rating 15 30 C max. 300 m 0...1000 Ω corresponding to adjustable range from 0 50 C max. 300 m DC 24V <5 ma AC 24...230 V AC 230 V, 4 A resistive, 3 A ind. (per relay terminal) DC 30 V, 4 A AC 19.2 V, 20 ma DC 5 V, 100 ma Diagrams Internal diagrams L D1 GND B1 M R1 M Q1 Q2 RWD31 Q3 N 14 11 22 24 21 32 34 31 44 41 G D1 GND B1 M R1 M Q1 Q2 RWD41 Q3 3345g01 14 11 22 24 21 32 34 31 44 41 D1 Digital input L, N AC 230 V supply (For RWD31) G, AC 24 V supply (For RWD41) ( SELV AC 24 V Power supply) M Ground () for signal inputs Q... Digital output, various voltages permissible AC 24...230 V B1 Signal input (Main input: Ni 1000) R1 Signal input (Aux. input: 0 1000 Ω remote setting unit, QAA25/AP, QAA25) Note: M, GND, are internally connected 6/8 Siemens Building Technologies Data sheet CE2N3345en

Connection diagrams Single compressor Heat Pump + remote setting unit + switch B M 3345g02 B1 R1 S1 L N G B1 M R1 M D1 GND Q 11 21 31 41 14 22 24 32 34 44 RVC RVH CR1 Dual compressor Heat Pump + remote setting unit + switch B M 3345g03 B1 R1 S1 L N G B1 M R1 M D1 GND Q 11 21 31 41 14 22 24 32 34 44 RVC RVH CR1 CR2 Two-stage of heating and cooling 3345g04 B M B1 L N G B1 M R1 M D1 GND Q 11 21 31 41 14 22 24 32 34 44 H2 H1 C1 C2 CR1 Compressor 1 CR2 Compressor 2 RVC Reversing valve in cooling demand RVH Reversing valve in heating demand H1 Heat 1 H2 Heat 2 C1 Cool 1 C2 Cool 2 B1 Main temperature sensor R1 Remote setting unit (optional) S1 Time clock or switch (optional) Note: The reversing valve for the heat pump can be energised in heating or cooling demand. It depends on the heat pump equipment internal circuitry. Siemens Building Technologies Data sheet CE2N3345en 7/8

200 200 106 89 Dimensions 130 111 56.5 47.9 31 148 61.2 ARG62.21 344 61.2 ARG62.22 8/8 Siemens Building Technologies Data sheet CE2N3345en