Installation and Start-up Guide. ACS-BRK Brake Units

Similar documents
vacon nx ac drives brake resistors user manual

ABB machinery drives. Application guide Common DC system for ACS380 drives

user's manual nx frequency converters brake resistors

HIB Enclosed Inverter User Guide

LV Capacitor CLMD03 Power Module Instruction manual

MODVAR Low voltage reactive power compensation modules Installation manual

Brake Chopper BC BC 4.1. Instruction and Operation Manual

Hardware manual Sine filters

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

34OSM_ rev. C / 1SCC311029M0203. Motorized switch fuses OSM_ Installation and operating instructions

DBR3, 4500W, 9R, TS - BRAKING RESISTOR

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

ACSM1. Hardware Manual ACSM1-04 Drive Modules (0.75 to 45 kw)

EDB6032_G/GB Antriebstechnik. Operating Instructions. Brake chopper 6032/6033/6034

Low voltage AC drives

ACS800. Hardware Manual ACS Drives (5.5 to 110 kw) ACS800-U31 Drives (7.5 to 125 HP)

Low voltage AC drives. ABB micro drives ACS to 3 hp/0.18 to 2.2 kw Catalog

ACS800. Hardware Manual ACS Drives (55 to 2500 kw / 75 to 2800 HP)

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

QS20.241, QS C1

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

amp ramp Operators Manual Page 1 Saftronics 2S Ltd Turnbridge Mills Quay Street Huddersfield West Yorkshire HD1 6QT

DYNACOMP. The top-class reactive power compensator

ACS800. Hardware Manual ACS Drives (0.55 to 110 kw) ACS800-U1 Drives (0.75 to 150 HP)

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

Quick guide. Plug-in fans GPPM with FC101_106 August 2014

Low voltage AC drives. ABB component drives ACS to 2.2 kw / 0.25 to 3 hp Catalog

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

APPLICATION NOTE AN-ODP March 2009

Protection and Connection Motorized and automatic transfer switches IEC Technical guide

ACS 800. Hardware Manual ACS Drives (90 to 500 kw) ACS800-U2 Drives (125 to 600 HP)

SmartVFD HVAC FEATURES APPLICATION SPECIFICATION DATA

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units

R5 ACS580-01, ACH580-01

ACS 800. Hardware Manual ACS Drives (0.55 to 110 kw) ACS800-U1 Drives (0.75 to 150 HP)

INDUSTRIAL POWER SUPPLIES SFL-SERIES

ABB industrial drives. Application guide ACS drives and ACS drive modules Common DC systems

ELECTRIC FENCE ENERGIZER SERVICE MANUAL MODEL 950 SERVICE MANUAL FOR OLLI 950 FENCE ENERGIZERS

4/3 proportional directional control valve, without position control, with on-board electronics (OBE)

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

8. Filter / Autoranging Rectifier Module (FARM )

Motorized switch-disconnectors OTM 40 to 125 Amperes

ELECTRICIAN S THEORY EXAMINATION 20 June 2015 QUESTION AND ANSWER BOOKLET

LDX-C120 Series is a 120 W integrated DIN Rail Battery Charger / DC UPS Power Supplies, suitable for wide variety of industrial applications.

LV Capacitor Bank APC

LV Capacitor Bank APC

PowerOhm Installation Manual for BM R Series Braking Modules

1332 TROUBLESHOOTING GUIDE. Remarks: If this function is not appropriate for the application, it can be eliminated by turning off DSWl, switch 3.

Power Electronics. POWERSWITCH Semiconductor Relay / - Contactor With Load Circuit Monitoring PH 9270

Operating Manual (Edition 04/2004) sinamics. Braking Module / Braking Resistor SINAMICS G130

Safety Working with LV Drives

Inverter System Accessories

Open Chassis Star-Delta Starter User Guide

RVS-AX Instruction Manual

SOLSTART Instruction Manual

ACS800. Hardware Manual ACS Drives (45 to 560 kw) ACS800-U7 Drives (50 to 600 HP)

Emotron FDU and VFX 2.0

Products Tde Macno. User s Manual BRAKING UNIT. Cod. MP00401E00 V_1.0

Parker AC10 Frequency Inverter (to 22kW) Easy Start Guide

ABB component drives ACS150, 0.5 to 5 Hp

VSD Series II Variable Speed Micro Drives

2.3. Adjustable Frequency Drives. Contents. Standards and Certifications

User s Manual. ACS550-PC/PD Packaged Drive with Disconnect Supplement to ACS550-01/U1 User s Manual

Brake Resistor Design Guide. How to Read this Design Guide 3 Abbreviations 4. Safety Precautions 5 CE Conformity and Labelling 5

Filtered PWM Speed Control for Permanent Magnet DC Motors

MOTORTRONICS Solid State AC Motor Control

Appendix: Safety and application notes for 19

SDS Enclosed Star-Delta Starter User Guide

VTZ variable speed Reciprocating compressors

Filters for Power Lines

Instructions 3A4793B EN. See page 3 for a complete list of model descriptions and part numbers.

Technical brochure. The Vector series The ABB comprehensive solution for automatic power factor correction

Design Guide. VLT Soft Start Controller MCD 100

APC03 capacitor bank series The ABB comprehensive solution for automatic power factor correction

Update notice. General safety. Type code key. Update notice 1

POWER FACTOR CORRECTION MOTOR LOAD (ML) FIXED CAPACITOR

LED Driver Linear / area dimming

Electronic Ballast EVG 2000-T

GRUNDFOS DATA BOOKLET. Grundfos RSI. Renewable solar inverter for pump control kw

WARRANTY INFORMATION...

ACS800. Hardware Manual ACS Drives (45 to 500 kw) ACS800-U2 Drives (60 to 600 HP)

SPX9000 FR10 FR12 Adjustable Frequency Drives

AeroVironment Universal Solar Pump Controllers

Devices Supported: KEB48220 KEB48221 KEB48300 KEB48301 KEB48400 KEB48401 KEB48600 KEB48601 KEB72330 EB KEB72450 KEB EB KEB72600 KEB

Instruction Manual. Harmonic Filter AHF 005/010. Drives Solutions

Application Engineering

Power Electronics. Motor brake relay GA 9031 ministop

Application example of a motor controlled by MCD100 and protected by a circuit breaker

AWZ 110. AWZ 13,8V/1A/7Ah/LM

CATALOG. ABB micro drives ACS55, 0.18 to 2.2 kw

For regenerative operation, the MOVIPRO is connected to an external braking resistor.

SINUS K 13. ACCESSORIES Braking resistors APPLICATION TABLES 78/160 INSTALLATION INSTRUCTIONS

LED Driver Linear / area fixed output

Capacitor reforming instructions Converter modules with electrolytic DC capacitors in the DC link

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

Application Engineering

ACS800. Hardware Manual ACS Drives (5.5 to 110 kw) ACS800-U11 Drives (7.5 to 125 HP)

SUPPLEMENT MANUAL IM250R03. AQUAVAR CPC SUPPLEMENT A - Variable Speed Drive SUPPLEMENT TO THE INSTALLATION AND OPERATION MANUAL (IM167)

P445 Series Electronic Lube Oil Control

Appendix: Safety and application notes for... 15

Transcription:

Installation and Start-up Guide ACS-BRK Brake Units

ACS-BRK Brake Units Installation and Start-up Guide 3AFY 61514309 REV C EN Effective: 16.09.2002 2002 ABB Oy.

Safety Warning! All electrical installation and maintenance work on the ACS- BRK brake units should be carried out by qualified electricians. Warning! Do not attempt any work on a powered ACS-BRK. After disconnecting the mains from the feeding frequency converter which brake unit is connected to, always wait 5 minutes to allow intermediate circuit capacitors to become discharged before working on the ACS-BRK brake unit. Always check (with voltage indicating instrument) that the ACS-BRK is unpowered before beginning the work. Warning! Never attempt to repair a broken unit; always contact the supplier for replacement. Warning! In normal heavy loading, maximum temperature of the wall attachment reaches +90 C. Temperature of the body and the cover may be higher. In heavy overloading cases, temperature of the wall attachment may be higher. Note! For more technical information, contact your local supplier. Because of the variety of uses for this equipment and because of the differences between this solid-state equipment and electromechanical equipment, the user of and those responsible for applying this equipment must satisfy themselves as to the acceptability of each application and use of the equipment. In no event will ABB be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. iii

iv

Table of Contents Safety.............................................. iii Chapter 1 - About This Manual.......................... 1 Chapter 2- Product Overview........................... 3 Chapter 3 - Technical Details........................... 5 Electrical Specifications.......................... 5 Environmental Specification....................... 5 Mounting...................................... 5 Ventilation..................................... 6 Mechanical Specification......................... 7 Chapter 4 - Electrical Installation......................... 9 Chapter 5 - Mandatory Installation Instructions According to the EMC Directive.......................... 13 Chapter 6 - Selection of Brake Unit....................... 15 A. Normal and Heavy Duty Use.................... 16 B. Choosing the Correct ACS-BRK for Repetitive Peak Load Duty..................... 17 C. Choosing the Correct ACS-BRK for Single Peak Duty............................. 20 v

vi

Chapter 1 About This Manual This manual provides you with the information necessary to select the correct ACS-BRK brake unit and to install it. Safety instructions are at the beginning of the manual. Read them carefully and exercise appropriate care when working with the unit. Manual Contents: Chapter 2 Product Overview Chapter 3 Technical Details Chapter 4 Electrical Installation Chapter 5 Mandatory Installation Instructions According to the EMC Directive Chapter 6 Selection of Brake Unit ABOUT THIS MANUAL 1

2

Chapter 2 Product Overview When the drive application requires rapid or accurate deceleration of the motor, an ACS-BRK braking unit is needed. The braking unit converts the kinetic energy of the motor into thermal energy. ACS-BRK braking units consist of a braking resistor and control electronics. These brake units can be used with the following ABB frequency converter series for both 200-240 V and 380-480 V line voltage. ACS 100 ACS 140 ACS 400 Each brake unit can be connected to any of the frequency converter listed above. The brake unit is selected according to the required braking power, not according to the rated power of the frequency converter. This guarantees the best price/performance ratio to the customer. Example: We have a 400 V drive application. The required continuous braking power is 100 W and the power rating of the frequency converter is 2.2 kw. The right selection is ACS-BRK-A. PRODUCT OVERVIEW 3

4

Chapter 3 Technical Details Electrical Specifications Table 1 Input ratings. Terminal name Terminal use Voltage U C+, U C- Power supply 200-850 V DC T1, T2 Overload indication (thermostat) 110-220 V AC, max 8 A, 50/60 Hz The operating voltage selection for the brake unit must be the same as the input voltage of the frequency converter. This selection is done using jumpers located on the control board of ACS-BRK, see Chapter 4 Electrical Installation. Table 2 Output ratings. Brake Unit Type Input voltage of the frequency converter Resistance P average P peak (20s) ACS-BRK-A ACS-BRK-B ACS-BRK-C ACS-BRK-D 200-240 V AC 380-480 V AC 200-240 V AC 380-480 V AC 200-240 V AC 380-480 V AC 200-240 V AC 380-480 V AC 400 Ω 150 W 350 W 1000 W 150 Ω 400 W 1000 W 2400 W 32 Ω 2000 W 4500 W 12000 W 10.5 Ω 7000 W 14000 W 42000 W TECHNICAL DETAILS ACS-BRK-E 200-240 V AC - 4 Ω 5000 W 30000 W ACS-BRK-F 200-240 V AC - 50 Ω 400 W 2400 W Environmental Specification Table 3 Environmental limits. Operating temperature 0-40 C Storage and transportation temperature -40 - +70 C Enclosure rating IP 21 Mounting ACS-BRK brake units must be mounted vertically on a solid non-inflammable vertical surface. The parts in contact with the mounting surface of the unit may reach +90 C and the rest of the metal parts may exceed +150 C. 5

Ventilation Maintain a minimum clearance to all directions to ensure efficient ventilation. The minimum clearance for models A, B and F is 150 mm, for model C 300 mm and for models D and E 500 mm. The ventilation of the mounting area must be efficient enough to carry away the power losses generated by the ACS-BRK. The power losses are listed in Table 2. Figure 1 ACS-BRK Dimensional drawing for types A, B and F. Figure 2 ACS-BRK Dimensional drawing for types C, D and E. 6

Mechanical Specification Table 4 ACS-BRK Dimensions. All dimensions are in millimetres Brake Unit Width Height Depth h1 w1 Weight (kg) Mounting ACS-BRK-A 90 240 180 196 67 1.2 4 mm screw ACS-BRK-B 90 300 285 230 67 1.5 4 mm screw ACS-BRK-C 150 500 347 486 136 7.5 5 mm screw ACS-BRK-D 270 600 450 582 252 20.5 6 mm screw ACS-BRK-E 270 600 450 582 252 18.5 6 mm screw ACS-BRK-F 90 300 285 230 67 1.5 4 mm screw TECHNICAL DETAILS 7

8

Chapter 4 Electrical Installation 1 Select the Right Voltage Range Voltage range is selected using jumpers located inside the brake unit. A Open the ACS-BRK unit according to the following pictures: Figure 3 Opening the ACS-BRK unit, models A, B and F. ELECTRICAL INSTALLATION Figure 4 Opening the ACS-BRK unit, models C, D and E. 9

B Select the voltage range using jumpers according to the nominal AC line voltage supplied to the frequency converter. Jumper settings according to line voltages are given in Figure 5 and Figure 6. The factory default setting is 440-480 V. Line voltage 440-480 V S1 S2 S3 415/480V 200/400V 200/400V Line voltage 380-415 V S1 S2 S3 415/480V 200/400V 200/400V Line voltage 200-240 V S1 S2 S3 415/480V 200/400V 200/400V Figure 5 Voltage range selection with jumpers, models A, B and F. Line voltage 440-480 V Line voltage 380-415 V Line voltage 200-240 V S1 S2 S1 S2 S1 S2 415/480V 200/400V 415/480V 200/400V 415/480V 200/400V Figure 6 Voltage range selection with jumpers, models C, D and E. C Put the cover lid back and tighten the screws. 2 Mount the unit ACS-BRK must be mounted vertically on a solid flat non-inflammable vertical surface. Leave free space to all directions, 150 mm for types A, B and F, 300 mm for type C and 500 mm for types D and E. See Chapter 3 Technical Details. NOTE! Maximum temperature of the parts in contact with the mounting surface is +90 C. Temperature of the body may be higher. NOTE! The heat radiating from the brake unit will raise the temperature of nearby objects. 10

3 Power cabling Warning! Before working on the frequency converter ensure isolation of the mains supply from the input terminals of the frequency converter. Wait at least 5 minutes and measure the DC-link voltage (voltage between U C- and U C+ ) before beginning the work. For power wiring in the Industrial Environment (Second Environment) refer to Figure 7. The length of the cable between the frequency converter and the brake unit must not exceed five metres, types A, B and F. The maximum length for types C, D and E is 100 m. No separate fuses in the braking circuit are required if the following conditions are met: the mains cable of the frequency converter is protected with fuses no mains cable or fuse overrating takes place in the braking circuit the specified cable is used, see Table 5 Recommended cable sizes. the cross sectional area of the Brake Unit cabling must always be larger or equal than the cross sectional area of the main cabling of the frequency converter For power wiring, using input RFI filter with the frequency converter, in the First Environment, see Chapter 5 Mandatory Installation Instructions According to the EMC Directive. NOTE! The contactor may not be installed between the braking unit and the frequency converter. ELECTRICAL INSTALLATION 11

4 Protection of the brake unit To prevent dangerous overtemperatures in a case of malfunction and overloading the input contactor of the frequency converter must be connected in series with the thermostat of the ACS-BRK unit, see Figure 7. L1 L2 L3 N PE U1 V1 W1 PE Frequency Coverter ACS-BRK U2 V2 W2 U C+ U C- PE U C+ U C- T + T - M 3~ Figure 7 Electrical connection. Table 5 Recommended cable sizes. Brake unit type ACS-BRK-A ACS-BRK-B Input voltage of the frequency converter 200-240 V AC 380-480 V AC 200-240 V AC 380-480 V AC ACS-BRK-C 200-240 V AC 380-480 V AC ACS-BRK-D 200-240 V AC 380-480 V AC ACS-BRK-E 200-240 V AC - ACS-BRK-F 200-240 V AC - P average P peak (20 s) 150 W 350 W 1000 W 400 W 1000 W 2400 W 2000 W 4500 W 12000 W 7000 W 14000 W 42000 W Power cable mm 2 (copper) 2 x 2,5 + 2,5 2 x 2,5 2 x 2,5 + 2,5 2 x 2,5 2 x 16 + 16 2 x 2,5 2 x 35 + 35 2 x 2,5 5000 W 30000 W 2 x 35 + 35 2 x 2,5 400 W 2400 W 2 x 2,5 + 2,5 2 x 2,5 Overload indicator cable mm 2 (copper) Note! ABB frequency converters have an internal overvoltage controller that must be disabled when the braking unit is used. Parameter numbers are given in the following table. Table 6 Disabling overvoltage controller. Frequency converter type Parameter number Set parameter value to ACS 100 308 0 ACS 140 2005 0 ACS 400 2005 0 12

Chapter 5 Mandatory Installation Instructions According to the EMC Directive Follow the instructions given in ACS 100, ACS 140 or ACS 400 EMC Instructions. In First Environment, defined in the product standard EN 61800-3, the brake unit supply cable must have an effective cable screen (braid or foil screen, e.g. Ölflex-110 SY-NR for 200...240 V units, Ölflex-Servo-FD 780 CP, Lappkabel or MCCMK, NK Cables, for 380...480 V units). In addition, with 200...240 V frequency converters the motor cable must be run through the output choke ACS-CHK-A. Route the control cables as far as possible from the mains, motor and chopper supply cables (at least 20 cm). Where control cables must cross power cables make sure they are at an angle as near 90 as possible. Also the cable routing must be done so that the distance from the sides of the converter is at least 20 cm to avoid excessive radiation to the cable. ACS-BRK U 2 V 2 W 2 U C+ U C- U C+ U C- max 50 cm ACS-CHK-A needed only with 200...240 V converter units in First Environment Figure 8 Cable connections between ACS-BRK and the frequency converter. WIRING INSTRUCTIONS 13

14

Chapter 6 Selection of Brake Unit Define the required actual average braking power. Note that the brake unit selection is based on the required braking power and not on the power rating of the frequency converter. Select the brake unit so that P average of the brake unit is equal or more than the required average braking power and momentary braking power is equal or less than P peak. See Table 7. Table 7 Selecting brake unit. Brake Unit Type Input voltage of the frequency converter P average P peak ACS-BRK-A ACS-BRK-B ACS-BRK-C ACS-BRK-D ACS-BRK-E ACS-BRK-F 200-240 V AC 380-480 V AC 200-240 V AC 380-480 V AC 200-240 V AC 380-480 V AC 200-240 V AC 380-480 V AC 200-240 V AC - 200-240 V AC - 150 W 350 W 1000 W 400 W 1000 W 2400 W 2000 W 4500 W 12000 W 7000 W 14000 W 42000 W 5000 W 30000 W 400 W 2400 W The easiest way to select the approriate brake unit is to use Table 8 and Table 9 in paragraph A. If more specific selection is needed, see paragraphs B and C. SELECTION 15

A. Normal and Heavy Duty Use If the actual braking power is not known, the following split into normal and heavy duty use can be used for selection of the braking unit. 1 Normal duty use Less than 60 % motor s nominal power is needed. Braking is required for less than 10 % of the 200 s cycle time (i.e. duty time is less than 20 s). 2 Heavy duty use 100 % motor s nominal power is needed. Braking is required for less than 10 % of the 200 s cycle time. Table 8 Brake unit selection table for voltage range 200 V. P shaft / [kw] Normal duty Heavy duty P shaft / [kw] Normal duty Heavy duty 0.37 ACS-BRK-A ACS-BRK-A 0.55 ACS-BRK-A ACS-BRK-B 0.75 ACS-BRK-B ACS-BRK-B 1.1 ACS-BRK-B ACS-BRK-F 1.5 ACS-BRK-B ACS-BRK-F 2.2 ACS-BRK-F ACS-BRK-F 3 ACS-BRK-F ACS-BRK-C 4 ACS-BRK-F ACS-BRK-C 5.5 ACS-BRK-C ACS-BRK-E 7.5 ACS-BRK-C ACS-BRK-E 11 ACS-BRK-E ACS-BRK-E 15 ACS-BRK-E ACS-BRK-E 18.5 ACS-BRK-E ACS-BRK-E 22 ACS-BRK-E ACS-BRK-E 30 ACS-BRK-E ACS-BRK-E Table 9 Brake unit selection table for voltage ranges 415 V and 480 V. P shaft / [kw] Normal duty Heavy duty 0.37 ACS-BRK-A ACS-BRK-A 0.55 ACS-BRK-A ACS-BRK-A 0.75 ACS-BRK-A ACS-BRK-A 1.1 ACS-BRK-A ACS-BRK-B 1.5 ACS-BRK-A ACS-BRK-B 2.2 ACS-BRK-B ACS-BRK-B 3 ACS-BRK-B ACS-BRK-C 4 ACS-BRK-B ACS-BRK-C P shaft / [kw] Normal duty Heavy duty 5.5 ACS-BRK-C ACS-BRK-C 7.5 ACS-BRK-C ACS-BRK-C 11 ACS-BRK-C ACS-BRK-C 15 ACS-BRK-C ACS-BRK-D 18.5 ACS-BRK-C ACS-BRK-D 22 ACS-BRK-C ACS-BRK-D 30 ACS-BRK-D ACS-BRK-D 37 ACS-BRK-D ACS-BRK-D 16

B. Choosing the Correct ACS-BRK for Repetitive Peak Load Duty Choose approriate brake unit for repetitive peak load duty by following the next 6 steps. 1 Calculate the maximum power P max generated by motor during braking. 2 Define the duty time t 1. 3 Define the cycle time t 2. P P max t 1 t 2 t t 1 = duty time t 2 = cycle time Figure 9 Defining the duty cycle. 4 Calculate the average braking power P ave, P ave = t 1 t2 P max 5 Calculate the energy during the peak E = t 1 P max SELECTION 17

6 Choose the brake unit from the figure so that the operating point is within safe operating area. See Figure 10 and Figure 11. 400 P average / W 300 ACS-BRK-B ACS-BRK-F 200 100 ACS-BRK-A 0 0 50 100 150 200 250 Energy / kj SOA for ACS-BRK-A SOA for ACS-BRK-B and F Figure 10 Safe operating area (SOA) for types ACS-BRK-A, -B and -F. Example 1, the resulting point. P average / kw 7 6 ACS-BRK-D 4 2 ACS-BRK-C ACS-BRK-E 0 0 500 1000 1500 2000 2500 3000 Energy / kj Figure 11 Safe operating area (SOA) for types ACS-BRK-C, -D and -E. 18

7 Check that at any time P peak value is not exceeded (refer to Table 7 on page 159). Example 1: A 30 s motor deceleration ramp is needed every three minutes. The nominal torque of the motor has to be available throughout the deceleration time. The motor is rated 1.5 kw and 240 V. P 30 average =. 180 1500 = 250 W E = 1500 W. 30 s = 45 kj Note! This is not the actual P average value during the motor deceleration ramp. The above calculation method is only used to simplify the selection of braking unit. The resulting point 250 W, 45 kj is out of the safe operating area of ACS- BRK-A but within that of ACS-BRK-B and -F, see Figure 10. Table 7 shows that with the line voltage of 240 V AC, ACS-BRK-F is the correct selection. SELECTION 19

C. Choosing the Correct ACS-BRK for Single Peak Duty The term single peak duty means that the motor has to be stopped once in a while with short or accurate ramp time. This is typical e.g. in a case of emergency stopping. The time between these single peaks must be more than 40 minutes, otherwise the brake unit must be selected as in chapter 6 B. 1 Calculate the maximum power P max generated by motor during braking. 2 Define the deceleration ramp time. 3 Choose the brake unit from the following diagram, so that the operating point is within the safe operating area, see Figure 12 and Figure 13. Power / W 2500 2000 1500 ACS-BRK-F 1000 ACS-BRK-B 500 ACS-BRK-A 0 0 200 400 600 800 1000 Time / s Figure 12 SOAs of the 200 V series converters. 2500 Power / W 2000 1500 ACS-BRK-B 1000 500 0 ACS-BRK-A 0 200 400 600 800 1000 Time / s Figure 13 SOAs of the 400 V series converters. 20

30 Power / kw 20 10 0 ACS-BRK-E ACS-BRK-D ACS-BRK-C 0 100 200 300 400 500 Time / s Figure 14 SOAs of the 200 V series converters. Example 2, the resulting point. Power / kw 40 30 ACS-BRK-D 20 10 ACS-BRK-C 0 0 100 200 300 400 500 Time / s Figure 15 SOAs of the 400 V series converters. Example 2: 200 V application maximum braking power during the cycle P max = 4 kw deceleration time is 10 s After checking from the Figure 14 that the resulting point is in SOA, the correct braking unit can be selected and it is ACS-BRK-C. SELECTION 21

22