COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

Similar documents
COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

Effective November 2016 Supersedes September 1998 (S )

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

Effective June 2016 New Issue

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

Effective November 2016 Supersedes February 2012 (S )

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

Effective March 2015 Supersedes S August 2012

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

High-voltage primary bushings installation instructions

COOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

Type NR oil switch installation and operation instructions

Effective May 2017 Supersedes December 2004 (S )

Effective May 2017 Supersedes January 2003 (S )

COOPER POWER SERIES. KA146W5 single pole-mounting hanger; KA146W2 tank lifting windlass assembly and installation instructions. Reclosers MN280039EN

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

S Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards

Figure 1. Kearney Type HX cutout.

COOPER POWER SERIES. Types D and DV recloser installation instructions. Reclosers MN280030EN

COOPER POWER SERIES. Manually-Operated M-Force Switch Installation and Operation Instructions. Switches and Disconnects MN008003EN

Factory Authorized Mechanism Enhancement (FAME)

COOPER POWER SERIES. Metal-enclosed capacitor banks installation instructions. Power Capacitors MN230010EN

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

COOPER POWER SERIES. Instructions for oil-filled, single-phase overhead distribution transformers. Distribution Transformers MN201003EN

COOPER POWER SERIES. Metal-enclosed, pad-mounted capacitor banks installation instructions. Power Capacitors MN230009EN

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage

3-way multi-family drawout cable interlock kit - type 32 - RF

CCP2-FLR1-21_ flange-rod operating mechanism

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

Two-way cable interlock kit for Magnum drawout circuit breakers

Two-way cable interlock kit for Magnum fixed circuit breakers

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers.

Instruction Booklet IB E. Contents

Edison modular fuse, vault application products

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004

600 A 28 kv class Cleer loadbreak connector system

600 A 15 and 25 kv class Cleer grounding elbow

COOPER POWER SERIES. Externally fused block banks installation instructions. Capacitors MN230004EN

COOPER POWER SERIES. Type MOST Fluid-Insulated Switchgear; Installation, Operation, and Maintenance Instructions

COOPER POWER SERIES. RVAC Fluid-insulated Vacuum Switchgear; Installation, Operation, and Maintenance Instructions. Switchgear MN285005EN

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

Installation Instructions LINK---C

25 kv class fused loadbreak elbow connector

600 A 15 kv class Cleer loadbreak connector system

COOPER POWER SERIES. Types VWE, VWVE27, VWVE38X, WE, WVE27, and WVE38X; threephase electronically controlled; installation and operation instructions

COOPER POWER SERIES. VFI tester operating instructions. Underground Distribution Switchgear MN285001EN

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

O & M Manual for the EATON Generator Ready Loadcenter

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit

ELB ELB

600 A 15 kv class T-OP II deadbreak connector

Two-position sidewall (horizontal) and cover (vertical) mounted loadbreak switches

600 A 25 kv class BT-TAP deadbreak connector

600 A 35 kv class separable splices

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

Installation Instructions For Motor Control Center (MCC) Units

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

CM52 Network Protector with Arc Flash Reduction Module

100 A externally operated one-, twoand three-phase tap-changer switch

Effective October 2016 Supersedes January 2014 (S )

600 A 35 kv class BT-TAP deadbreak connector

KFE10010-E. Reclosers. Contents. Type KFVE and KFVME (27kV) Bus Bar Kit KRK710-1 Installation Instructions. Cooper Power Systems

Type DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

Technical specifications for 10 ka, heavy-duty class 1, 3 kv and 3.33 kv VariSTAR MOV disks

Technical specifications for 10 ka, heavy-duty class 1, 4.5 kv and 5 kv VariSTAR MOV disks

Installation Instructions 15/25/35kV, 600/900 AMPERE

Transcription:

Fault Indicators MN320011EN Effective March 2017 Supersedes August 2004 (S320-80-1) COOPER POWER S.T.A.R. Hot line voltage indicator installation instructions SERIES Indicator boot Internal sleeve Pulling eye Led indicator

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. i

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... i Safety for life... iii Safety information... iii Safety instructions... iii Product Information.... 1 Installation Procedures.... 1 For RTE 15, 25, and 35 kv Loadbreak Elbows and GE-Chardon 15 and 35 kv Elbows...1 For all Cooper Power Systems 200 a, 250 a and 400 a Deadbreak Elbows, Elastimold 15, 25 and 35 kv (PCE) Elbows and New Design Blackburn 15 kv Elbows...1 For Old Design* 15 and 25 kv Blackburn Elbows Elastimold 15, 25 and 35 kv (not PCE) Elbows Joslyn 15 kv Elbows and GE-Chardon 25 kv Elbows...2 ii

! SAFETY FOR LIFE Safety for life Eaton s Cooper Power series products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high-voltage lines and equipment and support our Safety For Life mission.! SAFETY FOR LIFE Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians, who are familiar with this equipment should install, operate and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high- and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, could result In death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with high voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury and equipment damage. Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install, or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. iii

S.T.A.R. Hot line voltage indicator installation instructions CAUTION The Eaton Cooper Power series S.T.A.R. Type HL Voltage Indicator is designed to be operated in accordance with normal safe operating procedures. These instructions are not intended to supersede or replace existing safety and operating procedures. Read all the instructions before installing the voltage indicator. Voltage indicators should be installed and serviced only by personnel familiar with good safety practice and the handling of high-voltage electrical equipment. Improper operation, handling, or maintenance can result in death, severe personal injury, and equipment damage. Product information The Eaton Cooper Power series S.T.A.R. Hot Line (HL) Voltage Indicators are used on both 200 A separable connectors and 600 A terminators with voltage test points. They are easily installed with a shotgun stick using the pulling eye. The indicator displays the presence of voltage by showing a flashing LED in the window of the display. When the system is de-energized, the indicator LED will not flash. The voltage indicator is weatherproof, submersible, and meets or exceeds applicable portions of ANSI /IEEE 495-1986 Testing Guide. Do not use this device as the only indication that the circuit is energized or de-energized. A dirty, wet or otherwise faulty test point or indicator could cause a false reading indicating a dead circuit. Always use an approved means to be certain the circuit is de-energized before operating associated equipment designed for deadbreak operation. Internal sleeve Indicator boot Pulling eye Led indicator Figure 1. S.T.A.R. Hot line voltage indicator with internal sleeve NNote: At least 2.4 kv line-to-ground must be present to operate the device. Installation procedures The Hot Line voltage indicator can be installed on most manufacturers elbows. Instructions are included herein for RTE, Elastimold, Blackburn, Joslyn and GE-Chardon elbows. Where an adapter is required, a kit must be ordered separately. For RTE 15, 25, and 35 kv loadbreak elbows and GE-Chardon 15 and 35 kv elbows 1. The voltage indicator can be installed on live elbows. As an alternative, de-energize the circuit and elbow terminator and ground the terminator according to approved procedures. 2. Remove the cap from the elbow test point using a shotgun stick. 3. Be sure the test point area is clean and dry. 4. Discard the internal sleeve. 5. Lightly lubricate the inside of the indicator boot using a silicone lubricant. 6. Attach the pulling eye of the indicator to the shotgun stick. 7. Using steady pressure, push the boot over the test point while rotating the boot. 8. Align the pulling eye on the indicator with the elbow pulling eye. 9. Re-energize the circuit if necessary. The LED will pulse indicating the circuit is energized. For all Eaton Cooper Power series 200 A, 250 A and 400 A deadbreak elbows, Elastimold 15, 25 and 35 kv (pce) elbows and new design* Blackburn 15 kv elbows 1. The voltage indicator can be installed on live Elastimold (PCE) or new design Blackburn elbows. As an alternative, de-energize the circuit and elbow terminator and ground the terminator according to approved procedures. 2. Remove the cap from the elbow test point using a shotgun stick. 3. Be sure the test point area is clean and dry. 4. Insert the internal sleeve into the indicator boot. 5. Lightly lubricate the inside of the internal sleeve using a silicone lubricant. 6. Attach the pulling eye of the indicator to the shotgun stick. These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide directions for meeting every contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user s purpose, contact your Eaton representative. 1

S.T.A.R. Hot line voltage indicator installation instructions 7. Using steady pressure, push the boot over the test point while rotating the boot. 8. Align the pulling eye on the indicator with the elbow pulling eye. 9. Re-energize the circuit if necessary. The LED will pulse indicating the circuit is energized. For old design* 15 and 25 kv blackburn elbows, elastimold 15, 25 and 35 kv (not pce) elbows, joslyn 15 kv elbows and ge-chardon 25 kv elbows 1. A separate adapter (Catalog # STAK) is required for the old design 15 and 25 kv Blackburn, Elastimold 15, 25 and 35 kv (not PCE), Joslyn 15 kv and GE-Chardon 25 kv elbows. It is not included with the voltage indicator and must be ordered separately. Because an adapter is needed, a slotted screwdriver and hex head driver mounted on a shotgun stick with tool holder is also required. Table 1. Adapter screw and thread sizes** Elbow manufacturer Screw & thread size 15 and 25 kv Blackburn Old Design 3/8 in. 24 15 kv Joslyn, Elastimold 15, 25 and 35 kv (Not PCE) 5/16 in. 24 25 kv GE-Chardon 1/4 in. 20 ** Consult your Eaton representative for other available screw sizes. 2. De-energize the circuit and elbow terminator and ground the terminator according to approved procedures. 3. Remove the cap from the elbow test point. 4. Remove and discard the screw and steel washer from the center of the test point. From the referenced adapter kit, select the proper adapter screw and thread size from Table 1. 5. Be sure the test point is clean and dry. 6. Using the 7/64 inch hex wrench provided, screw the adapter and plastic washer into the test point using the shotgun stick with tool holder. 7. Discard the internal sleeve. 8. Lightly lubricate the inside of the indicator boot using a silicone lubricant. 9. Attach the pulling eye of the indicator to the shotgun stick. 10. Using steady pressure, push the boot over the test point while rotating the boot. 11. Align the pulling eye on the indicator with the elbow pulling eye. 12. Re-energize the circuit if necessary. The LED will pulse indicating the circuit is energized. * Blackburn completed an elbow design change around July 1992. Any Blackburn elbow sold and/or shipped prior to July 1992 could be of either the old or new design. After determining the design, follow the appropriate instructions for installing the indicator. 2

S.T.A.R. Hot line voltage indicator installation instructions This page intentionally left blank. 3

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No. MN320011EN March 2017 #5000038078 Rev. 04 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton's Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.