Printed Date: 10/7/2014 Mark: EF-R04 Model: G-143-VG Direct Drive Centrifugal Roof Exhaust Fan Standard Construction Features: Model G Centrifugal Roof Exhaust Fans are direct drive. These fans are specifically designed for roof mounted applications exhausting relatively clean air. Fan wheels are centrifugal, backward inclined, and constructed of aluminum. Options & Accessories: Motor - Vari-Green EC motor w/mounted Potentiometer Dial UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-1, Toggle, Junction Box Mounted & Wired Roof Curb-Galv., GPI-22-G14, Under Sized 1.5 in. Total Unit Warranty: 1 Yr (Standard) CAPS 4.15.1679 Z:\Carl\winjobs\Alley 111.gfcj Page 6 of 18
Printed Date: 10/7/2014 Mark: EF-R04 Disconnect Switch Enclosure Rating: NEMA-1 Standard Construction Features: Enclosure constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment and to provide a degree of protection against falling dust. This enclosure meets the rod entry and the indoor corrosion protection design tests. The rod entry test is intended to simulate incidental contact with enclosure equipment. Disconnect Switch Configuration Type: Toggle Motor Size: 3/4 hp Voltage: 115 UL Listed: Yes Manufacturer: Pass and Seymour Cycle: 60 Amperage: 20 CSA Approved: Yes Overload Protection: None Phase: 1 Switch Pole(s): 1 Rating: 1 hp Mounting: Mounted and Wired RPM: 1300 Wiring (Exp. Resist.): None Electrical Drawing Details Ø0.28 (4 HOLES) Wiring Schematic 4.35 1.06 1.65 0.72 1.06 2.50 2.00 Notes: All dimensions shown are in units of in. CAPS 4.15.1679 Z:\Carl\winjobs\Alley 111.gfcj Page 7 of 18
Printed Date: 10/7/2014 Mark: EF-R04 Assembly Drawing Type: Direct Drive Centrifugal Roof Exhaust Fan Exhaust Duct Suggested Roof Opening 16.0 SQ 18.5 SQ TOP VIEW 28.4 23.8 4.0 37.7 22.0 1.8 14.0 Flat Roof Curb FRONT VIEW Notes: All dimensions shown are in units of in.. CAPS 4.15.1679 Z:\Carl\winjobs\Alley 111.gfcj Page 8 of 18
Vari-Green Motor & Control Options Printed Date: 10/7/2014 Mark: EF-R04 An EC motor that uses AC input power and internally converts it to DC power. Potentiometer (dial) mounted on the motor enclosure adjusts the speed (RPM) down 80%. Motor Type: Dial on Motor Wiring Diagram CAPS 4.15.1679 Z:\Carl\winjobs\Alley 111.gfcj Page 9 of 18
Roof Curb Model: GPI Material: Galvanized Printed Date: 10/7/2014 Mark: EF-R04 Standard Construction Features: - Roof Curb fits between the building roof and the fan mounted directly to the roof support structure - Constructed of either 18 ga galvanized steel or 0.064 in. aluminum - Straight Sided without a cant - 2 in. mounting flange - 3 lb density insulation - Height - Available from 8 in. to 42 in. as specified in 0.5 in. increments. Notes: - The maximum roof opening dimension should not be greater than the "Actual" top outside dimension minus 2 in.. - The minimum roof opening dimension should be at least 2.5 in. more than the damper dimension or recommended duct size. - The Roof Opening Dimension may NOT be the Structural Opening Dimension. - Damper Tray is optional and must be specified. Tray size is same as damper size. - Security bars are optional and must be specified. Frames and gridwork are all 10 ga steel. Gridwork is welded to the frame and the frame is welded to the curb. To prevent corrosion, they are coated with Greenheck s high performance Permatector coating. 20.5 20.5 14.0 24.5 24.5 ISOMETRIC VIEW Notes: All dimensions shown are in units of in. CAPS 4.15.1679 Z:\Carl\winjobs\Alley 111.gfcj Page 10 of 18
Printed Date: 10/7/2014 Mark: EF-R04 G-143-VG Min/Max Fan Curve Performance Requested Volume (CFM) Actual Volume (CFM) External SP (in. wg) Total SP (in. wg) Fan RPM Operating Power (hp) 1,900 1,900 0.6 0.6 1282 0.44 CAPS 4.15.1679 Z:\Carl\winjobs\Alley 111.gfcj Page 11 of 18
Printed Date: 10/7/2014 Mark: EF-R05 Model: G-143HP-VG Direct Drive Centrifugal Roof Exhaust Fan Standard Construction Features: Model G Centrifugal Roof Exhaust Fans are direct drive. These fans are specifically designed for roof mounted applications exhausting relatively clean air. Fan wheels are centrifugal, backward inclined, and constructed of aluminum. Options & Accessories: Motor - Vari-Green EC motor w/mounted Potentiometer Dial UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-1, Toggle, Ship Separate, Field Mounted Roof Curb-Galv., GPI-22-G14, Under Sized 1.5 in. Total Unit Warranty: 1 Yr (Standard) CAPS 4.15.1679 Z:\Carl\winjobs\Alley 111.gfcj Page 13 of 18
Printed Date: 10/7/2014 Mark: EF-R05 Disconnect Switch Enclosure Rating: NEMA-1 Standard Construction Features: Enclosure constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment and to provide a degree of protection against falling dust. This enclosure meets the rod entry and the indoor corrosion protection design tests. The rod entry test is intended to simulate incidental contact with enclosure equipment. Enclosure is equipped with provision to lockout in the off position with customer supplied lock. Disconnect Switch Configuration Type: Toggle Motor Size: 1/2 hp Voltage: 115 UL Listed: Yes Manufacturer: Pass and Seymour Cycle: 60 Amperage: 15 CSA Approved: Yes Overload Protection: None Phase: 1 Switch Pole(s): 1 Rating: 1/2 hp Mounting: Ship Separate RPM: 1725 Wiring (Exp. Resist.): None Electrical Drawing Details Ø0.28 (4 HOLES) Wiring Schematic 4.35 1.06 1.65 0.72 1.06 2.50 2.00 Notes: All dimensions shown are in units of in. CAPS 4.15.1679 Z:\Carl\winjobs\Alley 111.gfcj Page 14 of 18
Printed Date: 10/7/2014 Mark: EF-R05 Assembly Drawing Type: Direct Drive Centrifugal Roof Exhaust Fan Exhaust Duct Suggested Roof Opening 16.0 SQ 18.5 SQ TOP VIEW 28.4 23.8 4.0 37.7 22.0 1.8 14.0 Flat Roof Curb FRONT VIEW Notes: All dimensions shown are in units of in.. CAPS 4.15.1679 Z:\Carl\winjobs\Alley 111.gfcj Page 15 of 18
Vari-Green Motor & Control Options Printed Date: 10/7/2014 Mark: EF-R05 An EC motor that uses AC input power and internally converts it to DC power. Potentiometer (dial) mounted on the motor enclosure adjusts the speed (RPM) down 80%. Motor Type: Dial on Motor Wiring Diagram CAPS 4.15.1679 Z:\Carl\winjobs\Alley 111.gfcj Page 16 of 18
Roof Curb Model: GPI Material: Galvanized Printed Date: 10/7/2014 Mark: EF-R05 Standard Construction Features: - Roof Curb fits between the building roof and the fan mounted directly to the roof support structure - Constructed of either 18 ga galvanized steel or 0.064 in. aluminum - Straight Sided without a cant - 2 in. mounting flange - 3 lb density insulation - Height - Available from 8 in. to 42 in. as specified in 0.5 in. increments. Notes: - The maximum roof opening dimension should not be greater than the "Actual" top outside dimension minus 2 in.. - The minimum roof opening dimension should be at least 2.5 in. more than the damper dimension or recommended duct size. - The Roof Opening Dimension may NOT be the Structural Opening Dimension. - Damper Tray is optional and must be specified. Tray size is same as damper size. - Security bars are optional and must be specified. Frames and gridwork are all 10 ga steel. Gridwork is welded to the frame and the frame is welded to the curb. To prevent corrosion, they are coated with Greenheck s high performance Permatector coating. 20.5 20.5 14.0 24.5 24.5 ISOMETRIC VIEW Notes: All dimensions shown are in units of in. CAPS 4.15.1679 Z:\Carl\winjobs\Alley 111.gfcj Page 17 of 18
Printed Date: 10/7/2014 Mark: EF-R05 G-143HP-VG Min/Max Fan Curve Performance Requested Volume (CFM) Actual Volume (CFM) External SP (in. wg) Total SP (in. wg) Fan RPM Operating Power (hp) 650 650 0.6 0.6 1160 0.14 CAPS 4.15.1679 Z:\Carl\winjobs\Alley 111.gfcj Page 18 of 18
PERFORMANCE RATINGS QTR / QTRE SERIES FANS HVI PERFORMANCE Static Fan Model Pressure (Ps) CFM Sones Watts QTR050F 0.10 50 0.4 0.25 28 QTR080 0.10 80 1.0 0.25 66 QTR110 0.10 110 1.5 0.25 98 QTRE080 0.10 80 0.8 28.2 QTRE080R 0.25 55 QTRE110 0.10 110 1.3 36.3 0.25 89 AMPS Model Amps QTR050F 0.2 QTR080 0.7 QTR110 0.3 QTRE080 QTRE080R 0.3 QTRE110 0.3 Models QTRE080, QTRE080R & QTRE110 only HVI-2100 CERTIFIED RATINGS comply with new testing technologies and procedures prescribed by the Home Ventilating Institute, for off-the-shelf products, as they are available to consumers. Product performance is rated at 0.1 in. static pressure, based on tests conducted in a state-of-the-art test laboratory. Sones are a measure of humanly-perceived loudness, based on laboratory measurements. AIR FLOW PERFORMANCE MODEL QTR050F 0.5 0.4 WEIGHT Model QTR050F QTR080 QTR110 QTRE080 QTRE080R QTRE110 Shipping Weight 6.6 lbs. 12.4 lbs. 12.4 lbs. 12.4 lbs. 13.0 lbs AIR FLOW PERFORMANCE Ps (in. w.g.) Ps (in. w.g.) Ps (in. w.g.) 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 0.6 0.5 0.4 0.3 0.2 0.1 0.0 0.7 0.6 MODEL QTR080 0 10 20 30 40 50 60 70 80 90 100 Airflow (cfm) MODEL QTR110 0 10 20 30 40 50 60 70 80 90 100 110 120 Airflow (cfm) MODELS QTRE080 & QTRE080R 0 10 20 30 40 50 60 70 80 90 100 Airflow (cfm) MODEL QTRE110 Ps (in. w.g.) 0.3 0.2 0.1 Ps (in. w.g.) 0.5 0.4 0.3 0.2 0.0 0 10 20 30 40 50 60 70 Airflo w (cfm ) Broan-NuTone LLC Hartford, Wisconsin www.broan.com 800-558-1711 0.1 0.0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 Airflow (cfm)
Roof Curb Model: GPI Material: Galvanized Printed Date: 10/7/2014 Mark: EF-R01,02 Standard Construction Features: - Roof Curb fits between the building roof and the fan mounted directly to the roof support structure - Constructed of either 18 ga galvanized steel or 0.064 in. aluminum - Straight Sided without a cant - 2 in. mounting flange - 3 lb density insulation - Height - Available from 8 in. to 42 in. as specified in 0.5 in. increments. Notes: - The maximum roof opening dimension should not be greater than the "Actual" top outside dimension minus 2 in.. - The minimum roof opening dimension should be at least 2.5 in. more than the damper dimension or recommended duct size. - The Roof Opening Dimension may NOT be the Structural Opening Dimension. - Damper Tray is optional and must be specified. Tray size is same as damper size. - Security bars are optional and must be specified. Frames and gridwork are all 10 ga steel. Gridwork is welded to the frame and the frame is welded to the curb. To prevent corrosion, they are coated with Greenheck s high performance Permatector coating. 13.5 13.5 12.0 17.5 17.5 ISOMETRIC VIEW Notes: All dimensions shown are in units of in. CAPS 4.15.1679 Z:\Carl\winjobs\Alley 111.gfcj Page 2 of 18
Printed Date: 10/7/2014 Mark: EF-R01,02 Discharge Accessory Type: Roof Cap Curb Standard Construction Features: - Weathertight aluminum construction - Integral birdscreen - Built-in curb cap - Requires roof curb 12 7 6.375 10 15 1.5 Notes: All dimensions shown are in units of in. CAPS 4.15.1679 Z:\Carl\winjobs\Alley 111.gfcj Page 3 of 18
Printed Date: 10/7/2014 Mark: EF-R01,02 SP-A125 Min/Max Fan Curve Performance Requested Volume (CFM) Actual Volume (CFM) External SP (in. wg) Total SP (in. wg) Fan RPM Operating Power (hp) 100 108 0.2 0.233 1100 0 CAPS 4.15.1679 Z:\Carl\winjobs\Alley 111.gfcj Page 4 of 18