FM 3. FM 3 with Bypass. Materials and Specifications. Fire Service Meter with Bypass Sizes 3, 4, 6, 8, 10. Features

Similar documents
Model Horizon. Horizon. Horizontal Turbine Meters Sizes 1-1/2" through 10" NOTICE OF DISCONTINUATION, Effective October 2011

500 Series DI. 500 Series DI. Materials and Specifications. Magnetic Drive Positive Displacement Disc Meters Sizes 1-1/2 and 2. Features.

400 Series IIS Magnetic Drive Positive Displacement Disc Meters Sizes 5/8-3/4-1

Model MVR. Model MVR. Materials and Specifications. Magnetic Drive Vertical Turbine Meters Sizes 3/4", 1", 1-1/2", 2", 3", 4" and 6" Features

Product Data Sheet. Recordall Fire Series Assemblies (FSAA) Cold Water Meter & Strainer with Disc Bypass DESCRIPTION

Product Data Sheet DESCRIPTION

Product Data Sheet. Recordall Fire Series Assembly (FSAA) Cold Water Meter & Strainer with Turbine Bypass DESCRIPTION

Product Data Sheet DESCRIPTION

OMNI Compound Water Meter

Product Data Sheet. Recordall Disc Meters. Lead-Free Bronze Alloy, Sizes 5/8, 5/8 x 3/4, 3/4 & 1 inch NSF/ANSI Standards 61 and 372 Certified

Product Data Sheet. Recordall Disc Meters. Lead-Free Bronze Alloy, Sizes 5/8", 5/8" x 3/4", 3/4" & 1" NSF/ANSI Standards 61 and 372 Certified

o-ring, testing port and a convenient integral strainer.

maincase using a high pressure o-ring, testing port and an AWWA compliant strainer.

sure o-ring, testing port and a convenient integral strainer. OMNI ELECTRONIC REGISTER

SECTION METERS AND GAGES FOR PLUMBING PIPING

Propeller Meters. Flow measurement solutions for water and wastewater

MADE IN THE USA BACKFLOW PREVENTERS

Series 756 FireLock Dry System Check Valve

Residential Metering Technologies. By: Ryan Fields TAUD Technical Conference Gatlinburg, TN March 2013

SECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING

4P-300 4V-500 CONTINUOUS PRESSURE THERMOPLASTIC DUAL. PRINCIPLE (U & Z Flow) DUAL CHECK VALVE. PRINCIPLE (Stn.Steel) REDUCED PRESSURE

TURBINE METERS - WP Series

SECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY

25 mm (1 in), 38 mm (1-1/2 in) & 50 mm (2 in) TYPE S FLOWMETERS WITH MODEL 157 AND 800 SERIES REGISTERS

Recordall Combo Meter Lead-Free Bronze Alloy, Size 8" (DN 200) NSF/ANSI Standards 61 and 372 Certified RCO-UM EN-02 (October 2013) User Manual

Self-Operating Temperature Regulators

35 Dealing with Type II and N Pattern Assemblies Pete Chapman

Model CV-1FR Grooved-End Riser Check Valves 2 Inch to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data

BM SERIES METERS PRECISION POSITIVE DISPLACEMENT METERS THE LEADER IN ACCURATE, LONG-LIFE, FUEL METERING INDUSTRY LEADING ACCURACY (+/-.

Series 758 FireLock Actuated System Valve

Sparling Propeller Meters

Cash Valve A SERIES PRESSURE REGULATORS. ISSUED - JANUARY 2001 CAVMC-0508-US-0208 ISO 9001 Certified

DOUBLE CHECK VALVES SERIES PRODUCT CODES OPERATION MEDIUM HAZARD RATING. 20mm - 50mm FEATURES APPLICATION SPECIFICATION STATEMENT DESCRIPTION

FireLock NXT Deluge Valve. With Deluge Trim Grooved x Grooved. System No. Submitted By Spec Sect Para Location Date Approved Date

Series 751 FireLock European Alarm Check Valve Stations

LUBE OIL PUMPS. Critical Lubrication Service for: Bearings Seals Gearboxes. on... Gas & Steam Turbines Compressors Engines Starting Packages

G. VULCANIZED SEAT Pressure sensitive seating with full disc overlap provides positive seating at high and low pressures.

BACKFLOW PREVENTION CATALOG

MODEL 106-PT / 106-PTC / S106-PT / S106-PTC DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

Suction Diffusers. Applications PROTECTION PUMP. Pressures to 790 PSIG Temperatures to 800ºF FEATURES MATERIALS END CONNECTIONS SIZE RANGES RATINGS

Flood Control Integrated System (FCIS)

30.85 FireLock NXT Actuated Valve with LPCB Approved Preaction Trim

Mark 5108 Series. Back Pressure Regulating Valves Mark 5108 Series. Back Pressure Regulating Valves. Valve Features. Operation

Series 769 FireLock NXT Deluge Valve

FLOOD PROTECTION SHUT DOWN VALVE (3 and smaller)

SECTION GENERAL-DUTY VALVES FOR HVAC PIPING. A. Contents of Division 23, HVAC and Division 01, General Requirements apply to this Section.

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Wafer Silent Check Valves

SECTION PLUMBING PIPING VALVES AND ACCESSORIES PART 1 - GENERAL

Direct-Operated Pressure & Temperature Regulating Valves


Double door, spring loaded, wafer check valve designed to protect your gas or liquid piping systems.

Backflow Preventers TABLE OF CONTENTS

Technical Data. Series Oval Flowmeter. Model 9400

Iron Check Valves Illustrated Index

AC 700 SERIES FUEL PUMPS Item code: FILLRITE-AC700

BUTTERFLY VALVES KENNEDY 140 YEARS AWWA C504 CLASS 150B & 250B CERTIFICATIONS ISO 9001 ISO BS OHSAS

CLOW CANADA - M-67 HERITAGE BRIGADIER FIRE HYDRANT SPECIFICATION

TYPE D50 PRESSURE REDUCING VALVE REDUCING VALVE D50 PRESSURE. PRESSURES to 300 PSIG at 420 F

Deep Well Pump Control Valve

PRESSURE REDUCING CONTROL VALVE

Series 800 AWWA Butterfly Valves

LEISTRITZ PUMPEN GMBH. Leistritz Screw Pumps & Systems L3MA 3 L. The new L3MA pump series according API 676 3rd. API 676 3rd. 6 3r

TYPE MP OSCILLATING PISTON FLOWMETER

TYPE PC Propeller Condensate Pumps

A Series General Purpose Pumps General Purpose Pumps for Pressure Lubrication, Hydraulic Service, Fuel Supply and General Transfer

BERMAD Waterworks. 800 Series. Technical Specifications Metric

Hydra-Cell T80 Series Pumps Design Advantages

BS 5163 Resilient Wedge Gate Valve

SC Swing Check Valves Product Data Sheet. Valve Availability. Body Material: Size Range: 3" through 8" Pressure: 100 psi (3") 70 psi (4" to 8")

DWS 41. Installation Data 44 Performance Specs DWS & DW-PRV Series

61W - Wafer style resilient seated butterfly valves 61L - Lugged style resilient seated butterfly valves

INDUSTRIAL DYNAMICS CO

MAINTENANCE MANUAL. Covering Models: Series (1/4-10 ) S Series (1/4-1 ) Series (3-10 )

TEMPERATURE REGULATORS W91/W94 Series

See Water Pressure Reducing Valves Catalog (PHBRWPRV) for more detailed information about the products in this section.

WCV Series Full Pattern Wafer Check Valves 2 TO 8 PVC AND CVPC

See Water Pressure Reducing Valves Catalog (PHBRWPRV) for more detailed information about the products in this section.

SECTION 8 Fire Protection

Innovative Products For Unique Applications. A Tradition of Excellence. Creative Engineering for Fluid Systems. Earthquake Proof Valves

F-Series Fire Fighting Pumps

of wet barrel hydrants, hydrant valves and hydrant tools.

SECTION VALVES PART 1 -GENERAL

The full WeatherTRAK Flow3 Installation and Maintenance Manual is available online at

Contents Project: Model: Chk d: Date:

Industrial Electric Monitors. Industrial

Peerless Pump FIRE PUMPS. Horizontal Split-Case, Vertical Turbine, In-Line and End Suction. Sterling Fluid Systems (USA), Inc.

FIRE HYDRANTS. Wet Barrel Fire Hydrants

Approved. Size L H. 3" (76mm) 9-1/2" (241mm) 5-51/64" (147mm) 46. 4" (102mm) 11-1/2" (292mm) 6-45/64" (170mm) 81

PIUSI BOX PRO 12V y 24V

Bennett Pump Company

NC State University Design and Construction Guidelines Division 23 Hydronic Pumps

8L SERIES THREE SCREW PUMPS

DELUGE VALVE DATA SHEET

1100 Series Multi-Stage Vertical Turbine Pumps

Cash Valve. A Series. Pressure Regulators. Flow Control. Issued - January 2001 CAVMC-0508-US-0609 ISO 9001 Certified

ADMIRAL HYDRANT. clowvalve.com

VALVES & CONTROLS KEYSTONE BUTTERFLY VALVES RESILIENT SEATED SERIES 61, 14" TO 24" 61W - Wafer style and 61L - Lugged style FEATURES

mh-valve.com 129 HYDRANT AWWA C502 NSF 61/372 CERTIFIED UL LISTED FM APPROVED 250 PSI WORKING PRESSURE 10-YEAR LIMITED WARRANTY

THIS WARRANTY IS IN LIEU

Transcription:

Features APPLICATIONS: The Hersey Meters FM 3 fire service meter is designed for combined fire service and domestic water where a single supply line supports both fire and domestic or process needs. The meter may be utilized in automatic sprinkler systems and fire service, as a master meter for an entire water system, as a master meter for zoned systems, and for domestic or processed water where accuracy across a broad range of flows is critical. The FM 3 meter eliminates the need for secondary service lines, saving time and reducing installation expenses and is compliant for all UL, FM, NSF -61 fire service meter applications. CONSTRUCTION: Every Hersey FM 3 meter is manufactured with epoxy coated ductile iron construction which eliminates additional gaskets and fasteners, reducing ongoing maintenance costs. The unique, Hersey strainer design protects the horizontal turbine meter measuring element in a unibody construction that reduces meter vault and installation costs due to its compact size and reduced weight while providing four times the inlet pipe diameter of strainer surface area. The unitized horizontal turbine measuring element is easily accessed through the top case of the meter and o-ring seals simplify field service. A Hersey EDCIV detector check provides proven backflow protection with a spring loaded clapper assembly that is mounted to the top case of the check valve for ease of service. Bypasses consist of an appropriately sized positive displacement or residential fire line meter for low flow accuracy. Dual ball valves permit isolation of the meter and a swing check prevents backflow through the bypass. Stainless steel and bronze fasteners are used throughout the meter where required. REGISTER: Separate mainline and bypass registers provide visibility of performance and field testing opportunity. The permanently sealed registers use proven magnetic drive design and the exclusive Hersey triple seal provides clarity and error free meter reading. Internal gears are self lubricating, molded plastic for minimal friction and a long service life. visual read and electronic Translator registers offer odometer wheels with a totalizing display, 3 degree test circle with center sweep hand and a low flow indicator. All Hersey FM 3 models are available with electronic meter reading system components to meet any utility AMR/AMI requirement and all registers are protected by the unique Hersey locking pin which requires no special removal tools for field service. OPERATION: During normal low flow operation, all water flows through the sensitive bypass meter for accurate registration. As flow and pressure loss through the bypass increases, the mainline clapper assembly automatically opens, permitting water to flow through the horizontal turbine measuring element and the bypass meter for accurate combined registration of all flows. The element employs Hersey s unique Retro-Thrust feature to divide wear across multiple points, increasing accuracy, reducing friction and extending the life of the measuring element. Integral flow straightening vanes on the inlet and outlet sides of the measuring element contribute to the long term accuracy of the meter. As flow and pressure loss through the bypass meter decrease, the clapper assembly once again closes, redirecting all water through the bypass. Higher demand instances include master meter supply applications and fire suppression requirements. INSTALLATION: Hersey FM 3 meters are designed for horizontal installation with a minimum of five times the inlet pipe diameter of straight pipe prior to the meter and a minimum of three times the pipe diameter after the meter. MAINTENANCE: All service components for the FM 3 are unitized for easy replacement. Access to components is accomplished through the top side of the meter for full in-line service. Drop In Measuring Elements (DIMES) are available in pre-tested configurations which include a new measuring element, top case, register and o-ring for utilities that require quick field replacement. A calibration vane permits field adjustments to ensure accurate registration and extend the service life of the measuring element. The calibration vane is protected by the register and the locking pin for added security. For additional information regarding Hersey s unitized replacement options, please contact the Mueller Systems Sales and Technical Support Group at 0-323-84. 4" x 1" FM 3 with Residential Fire Meter Materials and Specifications MODEL FM 3 Fire Service Meter SIZES 3" x 3/4" FM 3 with Residential 3" Fire with Meter 3/4" RFM bypass meter 4" with 1" RFM bypass meter 6" with 2" PD bypass meter 8" with 2" PD bypass meter 10" with 2" PD bypass meter STANDARDS Manufactured and tested to meet or exceed all applicable parts of C3, NSF -61 compliant INSTALLATION Horizontal only with 5X pipe diameter of straight pipe (same size as meter) on inlet and 3X on outlet side of meter OPERATING FLOW RANGE See Chart on the following page ACCURACY See Chart on the following page PRESSURE LOSS See Chart on the following page MAXIMUM WORKING PRESSURE 1 PSI WATER TEMPERATURE RANGE 33ºF to ºF MEASURING ELEMENT Mainline: Horizontal Turbine Element on all sizes Bypass: RFM...Vertical Turbine Residential Fire Meter on 3" and 4" sizes Bypass: PD...High Pressure Nutating Disc Meter on 6", 8" and 10" sizes METER CONNECTIONS ANSI class 125 standard end flanges OPTIONS All AMR/AMI Reading Systems

Meter Registration Meter Initial Dial* Capacity Initial Dial* Capacity Size 3" Gallons Million 10 Cubic Feet 10 Million 4" Gallons Million 10 Cubic Feet 10 Million 6" 0 Gallons 1 Billion Cubic Feet Million 8" 0 Gallons 1 Billion Cubic Feet Million 10" 0 Gallons 1 Billion Cubic Feet Million *Registration equal to one full revolution of the sweep hand. Flow Characteristics Meter Size Typical Low Flow (% Min) Typical Operating Range (% ± 1.5%) Maximum Continuous Operation Maximum Intermittent Flow 3" 1/2 GPM 6 to 0 GPM 0 GPM 7 GPM 4" 3/4 GPM 8 to 0 GPM 0 GPM 12 GPM 6" 2 GPM 15 to 2000 GPM 2000 GPM 20 GPM 8" 2 GPM 30 to 30 GPM 30 GPM 4400 GPM 10" 2 GPM 40 to 00 GPM 00 GPM 00 GPM Dimensions and Weights E A Meter Size 3x3/4 4x1 6x2 8x2 10x2 Dimension A 33" 35" 45" 53" 68" B 23-5/8" 23-5/8" 33-11/32" 33" 39-17/32" C 16" 19" 24-1/4" 25-15/16" 31-7/16" D 6-3/8" 9-3/8" 11-1/2" 11-9/16" 14" E 15-5/8" 15-5/8" 22-11/32" 19-7/8" 22-29/32" Weight 220 2 5 8 10 NOTE: Weights are in pounds and are approximate. D B C

Head Loss 3" with 3/4" RFM Bypass 1 1 1 Head Loss 4" with 1" RFM Bypass 1 1 1 0 200 300 400 0 0 0 0 200 400 0 0 0 1200 3" with 3/4" RFM Bypass 4" with 1" RFM Bypass 0 1 200 2 300 3 400 4 0 0 0 6 0 7 0 200 300 400 0 0 0 0 0 0 1 1200 Head Loss 6" with 2" PD Bypass Head Loss 8" with 2" PD Bypass 1 1 1 1 1 1 0 0 0 10 2000 20 0 0 0 10 2000 20 3000 30 4000 40

6" with 2" PD Bypass 8" with 2" PD Bypass 0 200 400 0 0 0 1200 1400 10 10 2000 2200 2400 20 0 0 0 10 2000 20 3000 30 4000 40 Head Loss 10 with 2" PD Bypass Meter 10" with 2" PD Bypass Meter 1 1 1 0 0 2000 3000 4000 00 00 00 0 0 0 10 2000 20 3000 30 4000 40 00 00 00 60 00

FM3 FM3 with Bypass FM3 WITH BYPASS EXPLODED ASSEMBLY (See parts listing, next page) D E D E D E D E D E

3" - 10" FM3 WITH BYPASS PARTS LIST (See exploded assembly diagram for reference) Mueller Systems 12/21/2010 FM 3