Oil/Air Cooler Units. Standard series OK-P type. Test procedure certified following EN

Similar documents
Oil/Air Cooler Units. Compact application with AC Motor OK-ELC Type. Test procedure certified following EN 1048

Oil/Air Cooler Units. Mobile series with DC motor OK-ELD Type. Test procedure certified following EN 1048

Oil/Air Cooler Units. Standard series EL Type. Test procedure certified following EN 1048

Oil/Air Cooler Units. Compact application with AC Motor OK-ELC Type

Oil/Air Cooler Units. Mobile application and Hydraulic motor OK ELH Type. Test procedure certified following EN 1048

Oil/Air Cooler Units

Air Cooler Industry AC-LN 8-14 / ACA-LN 8-11 / ACAF-LN 8-11

Cooling Systems FLKS - 3S/1.0/W... FLKS - 3L/1.0/W DESCRIPTION

Coolers. OK Series. Air Cooled Oil Coolers Hydraulic Symbol OK 1-11 OKF Cooling Systems Catalog. Applications

Air Cooler Mobile OK-ELD 0-6 with DC motor

Air Cooler Mobile AC-LNH 8-14 with hydraulic motor

Oil/air cooler BLK. Fluidcontrol

Cooling Systems Air Cooled / Liquid Cooled

Oil/Air Cooler Units Standard series - Accessories

Oil/air cooler BLK. Fluidcontrol

Coolers. Air Cooled / Liquid Cooled

GMP-Type. Key Features: Integrated Motor-Pump Units

ELD Series - DC Motor Drive

Off-line filter / cooler unit FGSL

ELD Series - DC Motor Drive

Oil/air cooler BLK ATEX-3GD

ELH Series - Hydraulic Fan Drive

HEAT EXCHANGERS AIR/OIL TYPE LAC. - ATEX Version. Approved for applications where there may be an explosive environment above ground.

Oil / air cooler Series BLK-DC

Feed Pumps VP / VPB / VPBM

Oil/air coolers. Table of contents. Features. Possible applications. RE 50111/12.06 Replaces: Types KOL and KOLP

Hydraulic primary unit Type ABPAG

HYDAC nitrogen charging units facilitate fast and cost effective filling or topping up of the required gas pre charge pressure in bladder, diaphragm

BYPASS SERIES GLOBAL STANDARD COOLER

MINI POWER PACKS WITH SUBMERSED MOTOR AND PUMP

Feed Pumps Direct Drive Series 1.1.

Feed Pumps Direct Drive Series 1.1.

A-L O C COOLING SYSTEM OLAER COOLERS. Olaer A-LOC with integrated circulation pump for industrial hydraulic systems

OFFLINE SERIES GLOBAL STANDARD COOLER

HYDAC KineSys The energy-efficient drive system

Proportional Pressure Reducing Valve PDM08130

A-L A C AIR OIL COOLER LUFT/ÖL-KÜHLER OLAER COOLERS. Olaer A-LAC with A.C. motors for industrial hydraulic systems

GLOBAL STANDARD COOLER

Industrial Diesel Generator Set KD1650-E 50 Hz - Emission Optimized EPA Tier 2 Compliant

Clamping and drive module

Industrial Diesel Generator Set KD2500-F 50 Hz Fuel Consumption Optimized

Industrial Diesel Generator Set KD1100-F 50 Hz Fuel Consumption Optimized

IGP /117 ED INTERNAL GEAR PUMPS SERIES 10 OPERATING PRINCIPLE TECHNICAL SPECIFICATIONS HYDRAULIC SYMBOL

Backflushing Filter AutoFilt RF3

UD and UC Gear pump unit

Circulation pumps BFP-ATEX-T3/T4

Pressure Relief Valve DB12 CE

Vane pumps, direct controlled Type PV7...A

PUMP SIZE Flow rate at 1500 rpm lt/min Operating pressures bar

Series VENTS KSK. Centrifugal kitchen fan in sound-insulated casing with air flow up to 8138 m 3 /h

Pressure Compensated Flow Control Valves SRVR/SRVRP

Off-line filter / cooler unit BKF

GLOBAL STANDARD COOLER

Heat Exchangers. Evaporator Catalogue

Change-Over Inline Filter AFLD to API 614

Drive module. Table of contents. Features. Applications. RE 51145/06.12 Replaces: Type UPE 5

@Perkins. Technical Data Series 1104C-44TAG1. Diesel Engine ElectropaK. 79, rev/min 88, rev/min. Basic technical data

Backflushing Filter AutoFilt RF4

VARIABLE SPEED WATER BOOSTER SETS WITH MULTISTAGE VERTICAL ELECTRIC PUMPS FLOW RATES UP TO 400 m 3 /h. 50 Hz GHV30 GHV40 SERIES

GLOBAL STANDARD COOLER

Centrifugal pumps. Main catalogue.

Technical data 50 & 60 Hz. Vertical centrifugal pumps Series: DPLHS

09GDV and 09LDV. Air Cooled Dry coolers and Condensers

GLOBAL STANDARD COOLER

Change-Over Inline Filter RFLD Welded Version

Inline Filters NF. Flow rates up to 3,500 l/min Pressure range 25 bar Material: Aluminium / Aluminium-Cast Iron

LKI LKI-HYD COOLING. Series. advanced quality customized designs made in europe. Oil/Air heat exchangers. Low noise level. High performance.

Off-Line Filter BNF. FluidControl

DIESEL GENERATOR SET MTU 18V2000 DS1400

GLOBAL STANDARD COOLER

Operating voltage 120, 230 V AC Air volume 24 m³/h (14.1 CFM) Rated power 13 W Size 1

Change-Over Pressure Filter DFDK

DIESEL GENERATOR SET MTU 12V4000 DS1650

Multi directional heating. Air heaters Model NOZ

Industrial Diesel Generator Set KD2250-F 50 Hz Fuel Consumption Optimized

ABB component drives ACS150, 0.5 to 5 Hp

Variable Vane Pump, Direct Controlled PV7...A Series 1X / 2X

Industrial Diesel Generator Set KD1750-UF 60 Hz Fuel Consumption Optimized

Gerotor pump, fixed displacement volume

Return Line Filter RFM with 4-Hole Mounting

Return line and Suction Boost Filter RKM

Industrial Diesel Generator Set KD1100-F 50 Hz Fuel Consumption Optimized

Process Multi-Rheo Filter PMRF

Resolair 64 and 68. Comfort air conditioning unit with highly efficient regenerative heat storage packages. AIR VOLUME FLOW: 3,900 23,100 m³/h

3.3 VARIABLE DISPLACEMENT MECHANICAL COMPENSATION

Cooling Systems CC Series TT rail 20/30lpm

@Perkins. Technical Data Series 1104C-44TAG2. Diesel Engine ElectropaK. 99, rev/min 112, rev/min Performance

Industrial Diesel Generator Set KD3500-F 50 Hz Fuel Consumption Optimized

DIESEL GENERATOR SET MTU 16V2000 DS1100

Oil Filter Module Pi 8300

Motor-pump group. Features. Table of contents RE 51171/ Type ABAPG and ABHPG

Sectional Directional Control Valve RS 220

PRODUCT SPECIFICATION File: EA-250U1C-10 Date: May, 25, 2005

HYDAC (Three-Phase Current) Compact Power Units CO1

1 AIR HANDLING UNIT TYPE AIR ACCESS 75

GLOBAL STANDARD COOLER

DIESEL GENERATOR SET MTU 16V2000 DS KVA

2.3 MEDIUM HEAVY DUTY SERIES

DIESEL GENERATOR SET MTU 16V2000 DS1000

KVAR POWERHOUSE RANGE 140 KVA 200 KVA

Transcription:

COMPLETE OIL / AIR COOLER WITH AXIAL FAN FOR INDUSTRIAL APPLICATIONS. Application These high performance coolers with axial fans are suitable for hydraulic cooling applications. Typical applications include: industrial power units, lubrication systems (i.e. gearboxes) and hydraulic presses. Oil/Air Cooler Units Standard series OK-P type OK-P Product Features 5 Sizes, 12 models 16 Bar Dynamic Pressure Rating OK-P coolers use high efficiency axial fans and strong cooling elements to achieve maximum performance. These units have been designed for standard applications where maximum performance is needed at the best price. There are two or three fan speeds available for each model so that you can choose the best combination of performance and noise level to suit the application. The P-Series is a full industrial quality cooler designed to meet the demands of most applications, at the best price performance level available today by using the latest technology in design. Both 50 Hz and 60Hz models are available. Test procedure certified following EN 1048

OIL/AIR COOLER DESCRIPTION GENERAL In hydraulic systems energy is transformed and transmitted. During this transformation and transmission losses occur, i.e. mechanical and hydraulic energy is converted into heat. It is the function of the cooler to dissipate this heat. OK-P 8-12 www.comoso.com OK-P 8-12 ADVANTAGES OF THE OIL/AIR COOLERS: Environmentally friendly: exchange between air and oil not possible For commissioning only electrical energy is required Low operating costs, no additional cooling circuit necessary for the cooling medium, i.e. air CONSTRUCTION FOR OK-P 8-12 Oil/air cooler units consists of the (1) heat exchanger, (2) metal housing, (3) feet, (4) axial fan, (5) protection grid, (6) motor. The oil connections are external. 2

COOLER SELECTION Designation: = Power loss [kw] = Specific cooling capacity [kw/ C] V = Tank contents [l] ρ oil = Density of the oil [kg/l] for mineral oil: 0.915 kg/l C oil = Specific heat capacity [kj/kgk] for mineral oil 1.88 kj/kgk T = Temperature increase in the system [ C] t = Operating time [min] T 1 = Desired oil temperature [ C] T 3 = Ambient temperature [ C] Example 1: Measurement of the power loss on existing units and machinery. For this method the temperature increase of the oil is measured over a certain period. The power loss can be calculated from the temperature increase. Parameters: The oil temperature increases from 20 C to 60 C over 16 minutes. The tank contains 400 l. Heat to be dissipated: = T c ρ V oil oil [kw] t 60 = 40 1.88 0.915 400 = 28.7 [kw] 16 60 Cooler selection: Desired oil temperature: 60 C Ambient temperature air: 30 C = T 1 - T 3 [kw/ C] = 28.7 = 0.96 [kw/ C] 60-30 A 10% safety margin is recommended to allow for element contamination, and therefore the specific power is: 1.1 = 1.06 kw/ C. The power loss 1.06 kw/ C must be dissipated by an oil cooler. Suggestion: Cooler OK-P 9L, = 1.12 kw/ C at 180 l/min Example 2: The power loss can also be estimated. With unrestricted flow approx. 15 to 20% of the drive power. With restricted flow up to 30% of the drive power. 1. TECHNICAL DETAILS 1.1. TABLE OF TECHNICAL SPECIFICATIONS Type of cooler www.comoso.com N of poles[-]/size[-] Motor capacity [kw] at 50Hz Noise level [db(a)] (at 1m distance) at 50Hz OK-P8L 6/90 1.1 75 16 130 2000 78 A OK-P8S 4/100 3.0 87 16 130 2000 83 B or C OK-P9LL 8/90 0.55 70 16 130 2000 84 A OK-P9L 6/90 1.1 77 16 130 2000 84 A OK-P9S 4/100 3.0 89 16 130 2000 89 B or C OK-P10LL 8/100 1.1 73 16 130 2000 103 A OK-P10L 6/100 1.5 78 16 130 2000 103 B or C OK-P10S 4/112 5.5 90 16 130 2000 110 B or C OK-P11LL 8/100 1.1 77 16 130 2000 126 A OK-P11L 6/112 2.2 83 16 130 2000 132 B or C OK-P12LL 8/132 3.0 83 16 130 2000 205 B or C OK-P12L 6/132 5.5 90 16 130 2000 215 B or C For direction of fan rotation, see arrow on cooler housing. Electric vent drive: axial drive with forward flow through cooler element (sucking). Cooling fluid: mineral oil to DIN 51524; for other fluids, please contact our sales/ technical department Three-phase motors IP55, conforming to CE norm The noise levels are only a guide as acoustic properties vary and depend on the characteristics of the room, connections, viscosity and resonance. Fan protection grid to EN 294 Warning! When operating a cooler in situations where the difference in temperature between ambient air and inlet oil exceed 50 Deg. Celsius, care must be taken to avoid cycling of the fan at full speed/air flow as this can cause rapid change in material temperature of element and may result in significant reduction in lifetime or direct damage to the element through thermal stress. Please contact your Hydac Branch or distributor for speed control solutions. Max. operating pressure [bar] Max. oil temperature [ C] Max. Viscosity [mm²/s] Weight [kg] Motor voltages available (see par.3) 3

1.2. PERFORMANCES 1.2.1 Cooling capacity depending on oil flow and the temperature differential T between the oil inlet and air inlet. For calculations with low T values (i.e. below 10 C), please contact our technical support staff. Tolerance: ± 5% 130 Heat dissipation at T = 40 C [kw] 120 110 100 90 80 70 60 50 40 30 20 10 P8S P9S P9L P9LL P8L 0 0 0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 Oil flow [l/min] *: Values measured at T = 40 C, may vary at lower T values P12L P12LL P10S P11L P11LL P10L P10LL 3.25 3 2.75 2.5 2.25 2 1.75 1.5 1.25 1 0.75 0.5 0.25 Specific heat dissipation [kw/ C] * 1.2.2 Pressure differential p measured at 30 mm²/s using mineral oil Tolerance: ± 5% 2.0 1.8 1.6 P8 P9 P12 P10 P11 Pressure drop at 30 mm²/s [bar] 1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0 0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 For other viscosities the result must be multiplied by K Oil flow [l/min] Viscosity (mm 2 /s) 10 15 22 30 46 68 100 150 Factor K 0.35 0.5 0.75 1 1.4 1.9 2.5 3.5 4

2. MODEL TYPE (also order example) OK-P 10L / 1.0 / M / A / 1 / IBP Type of cooler Size / motor speed LL = 8 poles (750 rpm) L = 6 poles (1000 rpm) S = 4 poles (1500 rpm) Type code and modification number For the latest version of each cooler, please see the table in our internet site Fluids M = Mineral oil to DIN 51524 Other fluids on request Motor voltage A = Standard voltages and frequencies for three-phase motor at 50 Hz / 60 Hz 50Hz : 380-420 V (Y) / 220-240 V ( ) 60Hz : 440-480 V (Y) / 254-277 V ( ) Except for OK-P 12 and OK-P10S, for which the standard voltages are: 50Hz : 660-720V (Y) / 380-420V ( ) 60Hz : 760-830V (Y) / 440-480V ( ) B = Standard voltages and frequencies for three-phase motor at 50 Hz 50Hz : 380-420 V (Y) / 220-240 V ( ) Except for OK-P 12, for which the standard voltages are: 50Hz : 660-720V (Y) / 380-420V ( ) C = Standard voltages and frequencies for three-phase motor at 60 Hz 60Hz : 440-480 V (Y) / 254-277 V ( ) Except for OK-P 12, for which the standard voltages are: 60Hz : 760-830V (Y) / 440-480V ( ) S = Other special voltages and frequencies on request and clearly written Paint 1 = RAL 9005 No other paint available Accessories AITF48 = Thermostat (fixed) IBP = Heat exchanger with integrated bypass valve IBT = Heat exchanger with integrated thermo-bypass valve HF = Horizontal fixing 5

3. DIMENSIONS PLUG A1 B C2 C1 E1 E2 Z1 D2 W1 W2 ±10 ±20 ±10 ±10 ±5 ±5 ±5 min.* min.* OK-P8L 880 670 760 602 600 178 G1 ¼" 549 1900 700 OK-P8S 880 680 760 602 600 178 G1 ¼" 549 1900 700 OK-P9LL 944 670 841 695 630 192 G1 ¼" 606 2100 800 OK-P9L 944 670 841 695 630 192 G1 ¼" 606 2100 800 OK-P9S 944 680 841 695 630 192 G1 ¼" 606 2100 800 OK-P10LL 1027 680 955 786 760 167 G1 ½" 686 2500 900 OK-P10L 1027 680 955 786 760 167 G1 ½" 686 2500 900 OK-P10S 1027 695 955 786 760 167 G1 ½" 686 2500 900 OK-P11LL 1196 695 1155 910 910 163 G1 ½" 828 2800 900 OK-P11L 1196 695 1155 910 910 163 G1 ½" 828 2800 900 OK-P12LL 1349 798 1335 1016 1060 151 G1 ½" 955 3000 1000 OK-P12L 1349 798 1335 1016 1060 151 G1 ½" 955 3000 1000 *: for smaller distances please contact our technical office 4. CERTIFICATION FOLLOWING EN 1048 Hydac SA design and manufacture high quality coolers that are tested and certified to give reliable and repeatable high performance. To ensure the performance is accurate, testing in compliance with a recognised international test standard is the best solution. For air/liquid coolers this is EN 1048. Hydac SA test procedure complies with the requirements of EN 1048 and both the procedure and test equipment are independently inspected and certified by TÜV SÜDDEUTSCHLAND. The cooler performance details in this brochure have been tested following EN 1048. 5. NOTE The information in this brochure relates to the operating conditions and applications described. For applications or operating conditions not described, please contact the relevant technical department. Subject to technical modifications. 6

NOTES www.comoso.com 7