Frequency Control of Isolated Network with Wind and Diesel Generators by Using Frequency Regulator

Similar documents
Possibilities of Distributed Generation Simulations Using by MATLAB

COMPARISON BETWEEN ISOLATED AND GRID CONNECTED DFIG WIND TURBINE

Workshop on Grid Integration of Variable Renewable Energy: Part 1

Statcom Operation for Wind Power Generator with Improved Transient Stability

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz Fall 2011

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

A Variable Speed Wind Generation System Based on Doubly Fed Induction Generator

ANALYSIS OF WIND AND PV SYSTEMS 4.1 Wind Energy Conversion Systems (WECS)

Performance Analysis of 3-Ø Self-Excited Induction Generator with Rectifier Load

Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

Comparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults

Performance of Low Power Wind-Driven Wound Rotor Induction Generators using Matlab

Control Scheme for Grid Connected WECS Using SEIG

Design and Modelling of Induction Generator Wind power Systems by using MATLAB/SIMULINK

Effect of prime mover speed on power factor of Grid Connected low capacity Induction Generator (GCIG)

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz

Design and Control of Lab-Scale Variable Speed Wind Turbine Simulator using DFIG. Seung-Ho Song, Ji-Hoon Im, Hyeong-Jin Choi, Tae-Hyeong Kim

Matlab Modeling and Simulation of Grid Connected Wind Power Generation Using Doubly Fed Induction Generator

Wind Farm Evaluation and Control

Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1

Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment

Abstract. Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application

APPLICATION OF STATCOM FOR STABILITY ENHANCEMENT OF FSIG BASED GRID CONNECTED WIND FARM

Dynamic Behaviour of Asynchronous Generator In Stand-Alone Mode Under Load Perturbation Using MATLAB/SIMULINK

CHAPTER 5 ACTIVE AND REACTIVE POWER CONTROL OF DOUBLY FED INDUCTION GENERATOR WITH BACK TO BACK CONVERTER USING DIRECT POWER CONTROL

Effect of crowbar resistance on fault ride through capability of doubly fed induction generator

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

ELG4125: Flexible AC Transmission Systems (FACTS)

APPLICATION OF VARIABLE FREQUENCY TRANSFORMER (VFT) FOR INTEGRATION OF WIND ENERGY SYSTEM

Intensification of Transient Stability in Grid Connected Squirrel Cage Induction Generator Using Plugging Mode Operation

LECTURE 19 WIND POWER SYSTEMS. ECE 371 Sustainable Energy Systems

Published by: PIONEER RESEARCH & DEVELOPMENT GROUP ( 201

Neural network based control of Doubly Fed Induction Generator in wind power generation.

CHAPTER 4 MODELING OF PERMANENT MAGNET SYNCHRONOUS GENERATOR BASED WIND ENERGY CONVERSION SYSTEM

Analysis of Low Voltage Ride through Capability of FSIG Based Wind Farm Using STATCOM

STUDY ON MAXIMUM POWER EXTRACTION CONTROL FOR PMSG BASED WIND ENERGY CONVERSION SYSTEM

Combined Input Voltage and Slip Power Control of low power Wind-Driven WoundRotor Induction Generators

Modelling and Simulation of DFIG based wind energy system

Advance Electronic Load Controller for Micro Hydro Power Plant

ENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG

POWER QUALITY IMPROVEMENT BASED UPQC FOR WIND POWER GENERATION

International Journal of Scientific & Engineering Research, Volume 6, Issue 10, October ISSN

Induction Generator: Excitation & Voltage Regulation

Laboratory Tests, Modeling and the Study of a Small Doubly-Fed Induction Generator (DFIG) in Autonomous and Grid-Connected Scenarios

Power Conditioning of Microgrids and Co-Generation Systems

Wind Generation and its Grid Conection

CONTROL AND PERFORMANCE OF A DOUBLY-FED INDUCTION MACHINE FOR WIND TURBINE SYSTEMS

Modelling of Wind Turbine System by Means of Permanent Magnet Synchronous Generator Manjeet Kumar 1, Gurdit Singh Bala 2

Principles of Doubly-Fed Induction Generators (DFIG)

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

Module 3: Types of Wind Energy Systems

Experimental Resultsofa Wind Energy Conversion Systemwith STATCOM Using Fuzzy Logic Controller

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC

ASSESSING BEHAVOIR OF THE OUTER CROWBAR PROTECTION WITH THE DFIG DURING GRID FAULT

International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering. (An ISO 3297: 2007 Certified Organization)

THE IMPORTANCE OF INTEGRATING SYNCHRONOUS COMPENSATOR STATCOM IN WIND POWER PLANT CONNECTED INTO THE MEDIUM VOLTAGE GRID

Squirrel cage induction generator based wind farm connected with a single power converter to a HVDC grid. Lluís Trilla PhD student

VECTOR CONTROL AND DIRECT POWER CONTROL METHODS OF DFIG UNDER DISTORTED GRID VOLTAGE CONDITIONS

ENHANCEMENT OF TRANSIENT STABILITY OF SMART GRID

OPTIMIZATION IN GENERATION FROM A HORIZONTAL AXIS WIND TURBINE VIA BLADE PITCH CONTROL AND STRUCTURE MORPHING

CHAPTER 6 DESIGN AND DEVELOPMENT OF DOUBLE WINDING INDUCTION GENERATOR

Model Predictive Control of Back-to-Back Converter in PMSG Based Wind Energy System

Modelling and Simulation of DFIG with Fault Rid Through Protection

Performance of FACTS Devices for Power System Stability

Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line

CHAPTER 5 ROTOR RESISTANCE CONTROL OF WIND TURBINE GENERATORS

CONTROL OF DOUBLY FED INDUCTION GENERATOR BASED WIND ENERGY CONVERSION SYSTEM

Simulation and Analysis of a DFIG Wind Energy Conversion System with Genetic Fuzzy Controller

Simulation Modeling and Control of Hybrid Ac/Dc Microgrid

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM

Modeling of doubly fed induction generator (DFIG) equipped wind turbine for dynamic studies

PERFORMANCE ANALYSIS OF SQUIRREL CAGE INDUCTION GENERATOR USING STATCOM

Using energy storage for modeling a stand-alone wind turbine system

Study of DFIG based Wind Turbine for Reactive Power Generation Capability

Implementation of Distributed Fuzzy Load Control to an Autonomous Wind Diesel System

Grid Stability Analysis for High Penetration Solar Photovoltaics

Anupam *1, Prof. S.U Kulkarni 2 1 ABSTRACT I. INTRODUCTION II. MODELLING OF WIND SPEED

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

VIII. Three-phase Induction Machines (Asynchronous Machines) Induction Machines

J.-J.Simond*, A.Sapin**, B.Kawkabani*, D.Schafer***, M.Tu Xuan*, B.Willy***

EPE97 OPTIMIZED DESIGN OF VARIABLE-SPEED DRIVES BASED ON NUMERICAL SIMULATION

Integration of Large Wind Farms into Electric Grids

Facility Employing Standard Converters for Testing DFIG Wind Generators up to 30kW

The Modeling and Simulation of Wind Energy Based Power System using MATLAB

Modeling, Simulation & Control of Induction Generators Used in Wind Energy Conversion

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System

Performance Analysis of DFIG Based Wind Power Generation under Unbalanced Conditions

Use of STATCOM for Improving Dynamic Performance of Wind Farms Connected in Power Grid

COMPARISON OF PID AND FUZZY CONTROLLED DUAL INVERTER-BASED SUPER CAPACITOR FOR WIND ENERGY CONVERSION SYSTEMS

Dynamic Reactive Power Control for Wind Power Plants

Increasing the Battery Life of the PMSG Wind Turbine by Improving Performance of the Hybrid Energy Storage System

e t Electronics Based Dump Load Controller (DLC) for an Grid Isolated Asynchronous Generator (GIAG)

Studies regarding the modeling of a wind turbine with energy storage

Control of Grid Voltage and Power of Doubly Fed Induction Generator wind turbines during grid faults

Review on Grid-Connected Hybrid DFIG Based Wind and PV System

A Transient Free Novel Control Technique for Reactive Power Compensation using Thyristor Switched Capacitor

Asian Journal on Energy and Environment ISSN Available online at

Doubly fed electric machine

Fault Rid Through Protection of DFIG Based Wind Generation System

Transcription:

Frequency Control of Isolated Network with Wind and Diesel Generators by Using Frequency Regulator Dr.Meenakshi mataray,ap Department of Electrical Engineering Inderprastha Engineering college (IPEC) Abstract Due to the recent expansion of renewable energy applications, wind energy conversion is receiving much interest all over the world. However, output fluctuations of wind generators cause network frequency variations in power systems. This can decrease the power quality and then cause a restriction of wind farm installation, especially in an isolated network, for example, electrical power system in a small island. Therefore the problem of output fluctuation needs to be solved for Expanding further the wind energy conversion. This paper presents a new application frequency regulator to an isolated network with a high penetration no storage wind diesel system for improving the network frequency quality. The validity of the proposed controller is evaluated by computer simulation analysis using Matlab/Simulink. Index Terms wind turbine, isolated network, network frequency, high penetration no storage wind diesel (HPNSWD) system. I.Introduction As a result of conventional energy sources consumption and increasing environmental concern, efforts have been made to generate electricity from renewable sources, such as wind energy sources. Institutional support on wind energy sources, together with the wind energy potential and improvement of wind energy conversion technology, has led to a fast development of wind power generation in recent years. However, the frequency variation of power Ms. Shamsha Keshwani Department of Electrical Engineering Inderprastha Engineering college (IPEC) system due to wind generator output fluctuations is a serious problem. If installations of wind farms continue to increase, frequency control of power system by the main sources, that is, hydraulic and thermal power stations will be difficult in the near future, especially in an isolated network like a small island which has weak capability of power regulation. In such a case, the installation may be restricted even though it is a small wind farm. Though there is such a difficulty, an introduction of the wind energy utilization is much effective in an isolated power system, because main power plant in a small island is mostly a diesel engine driven generating plant and it has no good effect on the environment. Moreover, the price of diesel fuel is continuously increasing. On the other hand, the wind energy is a clean and inexhaustible energy source but due to great variation in wind speed which occurs from season to season, it can not be used as an autonomous source of generation. Hence, it is necessary to explore possibilities of combining a wind generator with the diesel generators in order to reduce the running cost per kwh and to increase the reliability of power supply. Research teams in many countries are now working to store the wind diesel energy. However, owing to the high cost of most forms of energy storage, the complexity of suitable storage devices and conversion again to AC electricity, only limited storage capacity will be aviable. The main problem of high penetration no storage wind diesel (HPNSWD) system is the complexity of the control technique. The wind speed variations, ISSN: 2249-2615 http://www.ijpttjournal.org Page 30

dependency of output turbine power on the cube of wind speed, and the configuration of the loads make the control tasks not easy to be achieved. In a distributed control system based on the controller area network is implemented in hybrid wind diesel systems with high wind penetration. II.Wind turbine Wind turbines can be classified by their mechanical power control, and further divided by their speed control. All turbine blades convert the motion of air across the airfoils to torque, and then regulate that torque in an attempt to capture as much energy as possible, yet prevent damage. At the top level turbines can be classified as either stall regulated or pitch regulated. Stall regulation is achieved by shaping the turbine blades such that the airfoil generates less aerodynamic force at high wind speed, eventually stalling, thus reducing the turbine s torque this is a simple, inexpensive and robust mechanical system. Pitch regulation, on the other hand, is achieved through the use of pitching devices in the turbine hub, which twist the blades around their own axes. As the wind speed changes, the blade quickly pitches to the optimum angle to control torque in order to capture the maximum energy or self-protect, as needed. Some turbines now are able to pitch each blade independently to achieve more balanced torques on the rotor shaft given wind speed differences at the top and bottom of the blade arcs. Beyond mechanical power regulation, turbines are further divided into fixed speed (Type 1), limited variable speed (Type 2), variable speed with either partial power electronic conversion. (Type 3) or full power electronic conversion. (Type 4) The above speed control types are implemented via different rotating AC machines and with the use of power electronics. Another machine type which is called Type 5 in which a mechanical torque converter between the rotor s low-speed shaft and the generator s high-speed shaft controls the generator speed to the electrical synchronous speed. The Type 1 WTG is implemented with a squirrel-cage induction generator (SCIG) and is connected to the step-up transformer directly. See Figure below. The turbine speed is fixed (or nearly fixed) to the electrical grid s frequency, and generates real power (P) when the turbine shaft rotates faster than the electrical grid frequency creating a negative slip (positive slip and power is motoring convention). Fig1: Configuration of Type1 WTG In Type 2 turbines, wound rotor induction generators are connected directly to the WTG step-up transformer in a fashion similar to Type 1 with regards to the machines stator circuit, but also include a variable resistor in the rotor circuit. This can be accomplished with a set of resistors and power electronics external to the rotor with currents flowing between the resistors and rotor via slip rings. Alternately, the resistors and electronics can ISSN: 2249-2615 http://www.ijpttjournal.org Page 31

be mounted on the rotor, eliminating the slip rings. The variable resistors are connected into the rotor circuit softly and can control the rotor currents quite rapidly so as to keep constant power even during gusting conditions, and can influence the machine s dynamic response during grid disturbances. For an added rotor resistance the turbine would have to spin faster to create the same output power. This allows some ability to control the speed, with the blades pitching mechanisms and move the turbines operation to a tip speed ratio (ration of tip speed to the ambient wind speed) to achieve the best energy capture. It is typical that speed variations of up to 10% are possible, allowing for some degree of freedom in energy capture and self protective torque control. The Type 3 turbine, known commonly as the Doubly Fed Induction Generator (DFIG) or Doubly Fed Asynchronous Generator (DFAG), takes the Type 2 design to the next level, by adding variable frequency ac excitation (instead of simply resistance) to the rotor circuit. The additional rotor excitation is supplied via slip rings by a current regulated, voltage-source converter, which can adjust the rotor currents magnitude and phase nearly instantaneously. This rotor-side converter is connected backto-back with a grid side converter, which exchanges power directly with the grid. Fig3: Configuration of Type3 WTG The Type 4 turbine (Figure 4) offers a great deal of flexibility in design and operation as the output of the rotating machine is sent to the grid through a full-scale backto-back frequency converter. The turbine is allowed to rotate at its optimal aerodynamic speed, resulting in a wild AC output from the machine. In addition, the gearbox may be eliminated, such that the machine spins at the slow turbine speed and generates an electrical frequency well below that of the grid. This is no problem for a Type 4 turbine, as the inverters convert the power, and offer the possibility of reactive power supply to the grid, much like a STATCOM. Fig2: Configuration of Type2 WTG Fig4: Configuration of Type4 WTG Type 5 turbines (Figure 5) consist of a typical WTG variable-speed drive train connected to a torque/speed converter coupled with a synchronous generator. The torque/speed converter changes the variable speed of the rotor shaft to a constant output shaft speed. The closely coupled synchronous generator, operating at a fixed speed (corresponding to grid frequency), can then be directly connected to the grid through a synchronizing circuit breaker. The synchronous generator can be designed ISSN: 2249-2615 http://www.ijpttjournal.org Page 32

appropriately for any desired speed (typically 6 pole or 4 pole) and voltage (typically medium voltage for higher capacities). This approach requires speed and torque control of the torque/speed converter along with the typical voltage regulator (AVR), synchronizing system, and generator protection system inherent with a gridconnected synchronous generator. Type 5 turbines (Figure 5) consist of a typical WTG variable-speed drive train connected to a torque/speed converter coupled with a synchronous generator. The torque/speed converter changes the variable speed of the rotor shaft to a constant output shaft speed. The closely coupled synchronous generator, operating at a fixed speed (corresponding to grid frequency), can then be directly connected to the grid through a synchronizing circuit breaker. The synchronous generator can be designed appropriately for any desired speed (typically 6 pole or 4 pole) and voltage (typically medium voltage for higher capacities). Fig5: Configuration of Type5 WTG This approach requires speed and torque control of the torque/speed converter along with the typical voltage regulator (AVR), synchronizing system, and generator protection system inherent with a gridconnected synchronous generator. component of the rotor current (this is the component of the current that is in-line with the stator flux). In a Type 4 WTG voltage control is achieved by varying the quadrature (reactive) component of current at the gridside converter. To allow voltage control capability, the gridside converter must be rated above the rated MW of the machine. Since a synchronous generator is used in a Type 5 WTG, an automatic voltage regulator (AVR) is typically needed. Modern AVRs can be programmed to control reactive power, power factor and voltage. The voltage control capabilities of individual WTGs are typically used to control the voltage at the collector bus or on the high side of the main power transformer. Usually a centralized wind farm controller will manage the control of the voltage through communication with the individual WTGs. The reactive power capabilities of modern WTGs are significant as most grid codes require the WPP to have reactive power capability at the point of interconnect over a specified power factor range, for example 0.95 leading (inductive) to 0.95 lagging (capacitive). Type 1 and Type 2 WTGs typically use PFCCs to maintain the power factor or reactive power of the machine to a specified setpoint. The PFCCs may be sized to maintain a slightly leading (inductive) power factor of around 0.98 at rated power output. III.SYNCHRONOUS CONDENSER A Synchronous Condenser (sometimes synchronous capacitor or synchronous compensator) is a device identical to synchronous motor,whose shaft is not connected to anything but spins freely. Its purpose is not to convert electrical power to mechanical power or vice -versa, but to adjust conditions on the electrical power transmission grid. Its field is controlled by a voltage regulator to either generate or absorb reactive power as needed to adjust the grid's voltage, or to improve power factor. Unlike a capacitor bank, the value of reactive power from a synchronous condenser can be continuously adjusted. ISSN: 2249-2615 http://www.ijpttjournal.org Page 33

In an industrial plant, synchronous motors can be used to supply some of the reactive power required by induction motors. This improves the plant power factor and reduces supply current. The system produces no switching transients and is not affected by system electrical harmonics (some harmonics can even be absorbed by synchronous condensers). The reactive power produced by a capacitor bank is in direct proportion to the square of its terminal voltage, and can be adjusted to compensate for falling terminal voltage. This reactive power improves voltage regulation in situations such as starting large motors, or where power must travel long distances from where it is generated to where it is used. IV.Asynchronous Generator An induction generator or asynchronous generator is a type of AC electrical generator that uses the principles of induction motors to produce power. Induction generators operate by mechanically turning their rotor in generator mode, giving negative slip. An asynchronous generator is really only an induction motor used as a generator. It will only supply 1/3 of a facilities power requirements because it still needs to be tied to the grid for excitation currents. The only time it will produce power is when the frequency of the rotor is greater than the frequency of the grid. This is what makes it asynchronous (out of synch). This is also the reason it can't be used to produce 100% of a facilities power generation. V.The Control Strategies The Frequency Regulator The frequency is controlled by the frequency controller block. This controller uses a standard three-phase phase locked loop (PLL) system to measure the system frequency. The measured frequency is compared to the reference frequency (60 Hz) to obtain the frequency error. This error is the input of a PID controller. The output signal of the controller is converted to an 8-bit digital signal controlling switching of the eight three-phase secondary loads. In order to minimize the voltage disturbances, switching is performed at zero crossing of voltage. VI.An Isolated Power System Model The turbine power characteristics are illustrated as shown below Fig6: wind Turbine characterstics These characteristics are plotted at pitch angle =0 (deg). The wind speed is 10 m/s such that the wind turbine produces enough power to supply the load. Here, the diesel generator is used as a synchronous condenser and its excitation system controls the grid voltage at its nominal value. The dynamic performance of the frequency control system is illustrated when an additional 25 KW customer load is switched on. For the IG mode, its speed is slightly above the synchronous speed (1.011 p.u). According to the turbine characteristics, for a 10 m/s wind speed, the turbine ISSN: 2249-2615 http://www.ijpttjournal.org Page 34

output power is 0.75 p.u (206 KW). Because of the IG losses, the IG produces 200 KW. As the main load is 50 KW, the secondary load absorbs 150 KW to maintain a constant 60 Hz frequency. At t=0.2 s, the additional load of 25 KW is switched on. The frequency momentarily drops and the frequency controller reacts to reduce the power absorbed by the secondary load in order to bring the frequency back to 60 Hz. The voltage stays at the rated value without any fluctuations. Here, the HPNSWD system presented uses a 480 V, 300 KVA synchronous machine as diesel power plant, a wind turbine driving a 480 V, 275 KVA induction generator, a 50 KW customer load and a variable secondary load (0-446.25 KW). The data of wind turbine, IG, and the diesel power plant are illustrated in Appendix. At low wind speeds both the induction generator and the diesel driven synchronous generator are required to feed the load. When the wind power exceeds the load demand, it is possible to shut down the diesel generator. A secondary load bank is used to regulate the system frequency by absorbing the wind power exceeding consumer demand. The secondary load block consists of eight sets of three phase resistors connected in series with GTO thyristors switches. The control signal m(t) is converted to 8-bit digital signal to control the thyristors VII.Simulation Results: Fig7: voltage waveform Fig8: current frequency and asm speed waveform Fig9: Waveform for power across turbine,secondary load, main load Fig10: waveform for power across synchronous condenser ISSN: 2249-2615 http://www.ijpttjournal.org Page 35

VIII. Conclusion This paper has proposed a new method of network frequency control by using the frequency regulator for an isolated power system including a high penetration no storage wind diesel (HPNSWD) system. The validity of the proposed method has been evaluated by computer simulations. This method can contribute to expand wind energy utilization into isolated power systems like in small island. IX. Appendix a) Induction Generator Data TABLE 1. Induction Generator Data The apparent power 275 KVA frequency (fref) 60 Hz Stator Resistance 0.016 p.u Rotor Resistance 0.015 p.u The stator inductance 0.06 p.u The Rotor inductance 0.06 p.u Line to line voltage 480v Number of pole pairs 2 The inertia constant 2s The friction factor 0 b) Wind Turbine Data TABLE 2. Wind Turbine Data mechanical power 275kw wind speed 10m/s c) Power Plant Data TABLE 3. Synchronous Condencer Data The apparent power 300KVA Line to Line voltage Friction Factor 0 Pole Pairs 2 480V X. References 1.T. Ahmed, K. Nishida and M. Nakaoka,Static Var compensator based voltage regulation implementation of 1- phase self excited asynchronous generator in IEEE proc. Gen., Trans. and Dist., vol. 152, no.2, pp.145-156, March 2005. 2. Atul S. Kini, and Udaykumar R. Y, Modeling and performance analysis of a wind/diesel hybrid power system, in Proc. IEEE 41th IAS Industry Applications Annual Meeting Conference, vol. 3, pp. 1215-1221, 2006. 3. R. Gagnon, B. Saulnier, G. Sybille, P. Giroux; "Modeling of a Generic High- Penetration No-Storage Wind- Diesel System Using Matlab/Power System Blockset" 2002 Global Windpower Conference, April 2002, Paris, France 4. L. Mott (NPS), B. Saulnier (IREQ) " Commercial Wind-Diesel Project, St. Paul Island, Alaska" 14th Prime Power Diesel Inter-Utility Conference, May 28- June 2, Winnipeg, Manitoba, Canada 5. O. Ojo, O. Omozusi and Adiso A. Jimoh, The operation of an inverter assisted single phase asynchronous generator, IEEE, Trans, on Industrial Electronics, vol. 47, no. 3, pp 632-640, June 2000. ISSN: 2249-2615 http://www.ijpttjournal.org Page 36