Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Similar documents
Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Two-way cable interlock kit for Magnum drawout circuit breakers

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

Two-way cable interlock kit for Magnum fixed circuit breakers

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

3-way multi-family drawout cable interlock kit - type 32 - RF

Factory Authorized Mechanism Enhancement (FAME)

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

Effective November 2016 Supersedes September 1998 (S )

Instruction Booklet IB E. Contents

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

CM52 Network Protector with Arc Flash Reduction Module

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

Digitrip Retrofit System for BBC LKD 8 Breakers

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

O & M Manual for the EATON Generator Ready Loadcenter

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

CCP2-FLR1-21_ flange-rod operating mechanism

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

Digitrip Retrofit System for Allis-Chalmers G-25 Breakers

Effective June 2016 New Issue

Magnum Breaker Remote Racking Device (MRR1000)

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

Effective March 2015 Supersedes S August 2012

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2

Digitrip Retrofit System for the General Electric AKR 6D/7D-30/50 and AKRT 6D/7D-50 Series Breakers

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

Type NR oil switch installation and operation instructions

TVSS Installation for RLCM/CHGENLC, RLCU, and CHGEN ATSs

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

Flush Mount AIN ALPHA Meters. General. Hardware Kit

Effective May 2017 Supersedes December 2004 (S )

Advanced Test Equipment Rentals ATEC (2832)

Effective May 2017 Supersedes January 2003 (S )

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear rated up to 15kV, 25 and 40kA UPPER TERMINAL SET VERSION

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

High-voltage primary bushings installation instructions

www. ElectricalPartManuals. com Digitrip Retrofit System for the Westinghouse DA-50 IL 33-DAC-2 WARNING

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

COOPER POWER SERIES. KA146W5 single pole-mounting hanger; KA146W2 tank lifting windlass assembly and installation instructions. Reclosers MN280039EN

Magnum breaker remote racking device (MRR1000)

38 kv Type VCPW-HD Simple Electrical Ground & Test Device (SEG&TD) lower terminal instruction booklet

Effective November 2016 Supersedes February 2012 (S )

COOPER POWER SERIES. Types D and DV recloser installation instructions. Reclosers MN280030EN

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

Instructions for installation, operation, and maintenance of medium voltage VC-W MR2 (integral racking)

www. ElectricalPartManuals. com Digitrip Retrofit System for Allis-Chalmers LA-4000 F Fused Breakers IL 33-A1K-1 WARNING

Type DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

DANGER. See Wiring Diagrams on page 7 for illustrations of both internal and connection wiring diagrams. WARNING

Installation Instructions for R-Frame Circuit Breakers and Molded Case Switches

Installation Instructions for Series C F-Frame 310+ Electronic Circuit Breaker Types FDE, HFDE, FDCE

! WARNING I.L D WARNING GENERAL INFORMATION

Installation Instructions For Motor Control Center (MCC) Units

RotoTract Remote Racking Operating Manual

IL 33-DRC-1 Retrofit System for Westinghouse and Cutler-Hammer DS Power Circuit Breakers. Table of Contents

Freedom FlashGard Aftermarket Kit Installation Manual

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION

COOPER POWER SERIES. Metal-enclosed capacitor banks installation instructions. Power Capacitors MN230010EN

O & M Manual for the EGSU Automatic Transfer Switch with RTC-100 Control and Integral Loadcenter-100 Amp

Installation Instructions for Series C F-Frame 310+ Electronic Circuit Breaker Types FDE, HFDE, FDCE

The Ultimate Smart Grid Solution INSTRUCTION MANUAL

The Ultimate Smart Grid Solution INSTRUCTION MANUAL

PowerWorx Power Distribution Products Select Series Circuit Breaker for ±24 or ±48 Vdc User Manual

COOPER POWER SERIES. Metal-enclosed, pad-mounted capacitor banks installation instructions. Power Capacitors MN230009EN

SPX9000 FR10 FR12 Adjustable Frequency Drives

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

50 / 75 / 150 DHP [Cable or Hard Bus Application] Ground and Test Device

Installation Power Management Unit Battery Cables and Battery Harness

Users Guide for Ac-sync

Transcription:

Instruction Leaflet IL2A12995H02 effective March 2012 Trip Indicator with Remote Reset for Magnum WARNING (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT. (2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A CIRCUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK LOCATION. (3) DRAWOUT CIRCUIT BREAKERS SHOULD BE LEVERED (RACKED) OUT TO THE DISCONNECT POSITION. (4) ALL CIRCUIT BREAKERS SHOULD BE SWITCHED TO THE OFF POSITION AND MECHANISM SPRINGS DISCHARGED. FAILURE TO FOLLOW THESE STEPS FOR ALL PROCEDURES DESCRIBED IN THIS INSTRUCTION LEAFLET COULD RESULT IN DEATH, BODILY INJURY, OR PROPERTY DAMAGE. WARNING THE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT LABELS HAVE TO BE FOLLOWED. OBSERVE THE FIVE SAFETY RULES: DISCONNECTING ENSURE THAT DEVICES CANNOT BE ACCIDENTALLY RESTARTED VERIFY ISOLATION FROM THE SUPPLY EARTHING AND SHORT-CIRCUITING COVERING OR PROVIDING BARRIERS TO ADJACENT LIVE PARTS DISCONNECT THE EQUIPMENT FROM THE SUPPLY. USE ONLY AUTHORIZED SPARE PARTS IN THE REPAIR OF THE EQUIPMENT. THE SPECIFIED MAINTENANCE INTERVALS AS WELL AS THE INSTRUCTIONS FOR REPAIR AND EXCHANGE MUST BE STRICTLY ADHERED TO PREVENT INJURY TO PERSONNEL AND DAMAGE TO THE SWITCHBOARD.

Instructional Leaflet IL2A12995H02 Section 1: General information A red, pop out mechanical trip indicator is an optional feature located above the trip unit on the breaker s front faceplate. In the event the trip unit trips the breaker on an overcurrent condition, the red trip flag releases and pops out to provide local visual indication. This trip indication is always in addition to any LED trip indication provided by the trip unit. The remote reset trip indicator comes equipped with mechanical interlocking features. These features mechanically lock the breaker after it has tripped and prevent the breaker from being re-closed until the trip indicator has been reset. The remote reset trip indicator can be reset by applying a control voltage to the electromagnetic coil enclosed in the accessory device. After allowing sufficient time to reset the TI, the control voltage is cutoff by a timing board also enclosed in the accessory device. The control voltage cannot, however, be continuously applied to the device to allow the board to reset and be ready for the next event. It is recommended that the control voltage not be applied to the secondary terminals any longer than 5 seconds. NNote: The proper control voltage of the device is located on the accessory device. Required Tools ¼ (10mm) Socket Drive (with torque measuring capabilities) 10mm Socket Phillips Head Screwdriver (#2 recommended) Dremmel Saw (or similar device used for removing front cover prongs) NNote: This is only required when retrofitting this accessory into a Magnum breaker produced prior to August 2011. Wire Cutters (for removal of any necessary wire ties) Kit Parts Identification Refer to Figure 1 for visual identification of the parts listed below: A. Trip Indicator (1) B. Trip Indicator Push Rod (1) C. Trip Unit Mounting Plate (1) D. M3.5 x 13 Hi-Lo Screw (2) E. M3.5 Flat Washer (2) F. Accessory Kit Labels (1) G. Wire Ties (2) (C) (A) Figure 1. Contents of Kit 2C15799 Section 2: Installation of Remote Reset Trip Indicator Kit Proceed with the following 9 steps: Step 1e: Remove the front cover by unscrewing the hex head captive bolts (4 for 3-pole, 6 for 4-pole) that join the cover to the breaker housing using a 10mm ¼ inch drive socket. Then hold the charge handle down approximately 45 degrees to pull off the cover. Step 2e: Place the trip indicator option label (F) on the front cover nameplate space located under Accessories. Using a Dremmel saw (or similar tool), remove the two notches in the top right corner of the front cover as shown in the figure. NNote: The notches must be removed in order to replace the front cover with the remote reset trip indicator installed. (F) (B) (D) (F) 2

Instructional Leaflet IL2A12995H02 Notches Being Removed Upper Hook End Connected Trip Indicator (A) Push Rod (B) Partial Rear View of Cover Shown with Notches Removed Label Bolt Bottom Hook End to Rear Figure 2. Steps 1 and 2 Step 3e: To simplify the installation and avoid inadvertent damage to the trip indicator push rod (B), the push rod should be installed in the breaker first by inserting one hooked-end of the push rod through the hole in the lever on the mechanism. The open end of the hook should be toward the rear as shown. Push Rod (B) Figure 4. Step 4 Step 5e: If the installed trip unit is a Model 520 trip unit, skip this step and proceed directly to step 6. If the installed trip unit is a Model 1150 trip unit, complete this step as outlined below and then proceed to step 7. Remove the trip unit retaining spring from the upper left hand corner of the trip unit mounting deck. Mount the completed trip indicator assembly from step 4 to the top two posts of the trip unit s mounting deck directly above the Model 1150 trip unit using the supplied hardware (two M3.5 x 13 Hi-Lo Screws (D), two M3.5 Flat Washers (E) as shown. Torque 0 18-22 in-lbs. (2.0-2.5 N-m). Connect the trip indicator assembly wires to the corresponding marked secondary terminal (Wire A4 should connect to secondary block A, position 4, labeled OTS2 MAKE. Wire A5 should connect to secondary block A, position 5, labeled OTS2 COM.). Figure 3. Step 3 Bottom Hook End to Rear Model 1150 Trip Unit Step 4e: Connect the trip indicator (A) to the already attached push rod (B) from step 3 by carefully rotating the trip indicator onto the upper hook end of the push rod as shown. Keep in mind that the lower hook end of the push rod must ultimately point to the rear. Figure 5. Step 5 3

Instructional Leaflet IL2A12995H02 Mounted Trip Indicator Assembly Shown Trip Indicator (A) Trip Unit Mounting Plate (C) Figure 6. Step 5 Step 6e: If the installed trip unit is a Model 520 trip unit and a metal plate is already mounted to the two top posts of the trip unit s mounting deck, remove the plate completely. Position the completed trip indicator assembly from step 4 to the top two mounting posts of the deck. Replace the trip unit mounting plate with the supplied trip unit mounting plate (C) and secure the trip indicator between the posts and the plate using the removed mounting screws (There are extra screws supplied in the kit). Torque to 18-22 in-lbs. (2.0-2.5 N-m). Connect the trip indicator assembly wires to the corresponding marked secondary terminal (Wire A4 should connect to secondary block A, position 4, labeled OTS2 MAKE. Wire A5 should connect to secondary block A, position 5, labeled OTS2 COM.). Keep in mind that the trip indicator (A) is shown here without the push rod (B) attached for mounting orientation reasons only. Figure 7. Step 6 Step 7e: After installation, verify that the trip indicator assembly remains latched when the breaker is operated with the push buttons. Verify that the trip indicator assembly opens the breaker with the trip actuator. Verify the breaker cannot be reclosed with the trip indicator in the tripped (popped out) position. Finally, verify that the trip indicator assembly resets when the proper control voltage is applied to the secondary terminals. Step 8e: Static trip actuator test: As the trip latch rotates slowly, the trip actuator must not trip before the breaker trips. The indicator may not trip during this test but the breaker must trip. Step 9e: Optional Overcurrent Trip Switch (Bell Alarm) wiring installation: If the indicator assembly was supplied with an overcurrent trip switch (bell alarm) wiring option, wire to the secondary wiring block illustration as shown. A1 wires into OTS1 MAKE A2 wires into OTS1 COM A3 wires into OTS1 BREAK Figure 8. Step 9 4

Instructional Leaflet IL2A12995H02 5

Instructional Leaflet IL2A12995H02 Disclaimer of warranties and limitation of liability The information, recommendations, descriptions, and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment, and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability, or otherwise for any special, indirect, incidental, or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations, and descriptions contained herein. The information contained in this manual is subject to change without notice. Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township, PA 15108 United States 877-ETN-CARE (877-386-2273) Eaton.com 2011 Eaton Corporation All Rights Reserved Printed in USA Publication No. IL2A12995H02 March 2012 Power Chain Management is a registered Trademark of Eaton Corporation All other Trademarks are property of their respective owners. 6