Valtek Flow Boosters

Similar documents
Valtek Spring Cylinder Linear Actuators

Flowserve Spring Diaphragm Rotary Actuators

Valtek VL-HC Spring Cylinder Linear Actuators

Valtek XL Series High Performance Positioner. for Control Valves

Valtek Tek-Check Control Valves Valtek Tek-Check

USER INSTRUCTIONS. Spring Diaphragm Rotary Actuators. Installation Operation Maintenance. Experience In Motion FCD VLAIM /12

Valtek Beta Positioner. Valtek Beta Positioners. for Control Valves

Valtek MaxFlo 3 Control Valves

USER INSTRUCTIONS. Valtek Control Products Spring Cylinder Linear Actuators. Installation Operation Maintenance. Experience In Motion

Valtek Valdisk 150. Valtek Valdisk 150. Control Valves

Kämmer Series Low Flow Valve

flowserve.com Kämmer Multi-Z Kämmer Multi-Z Severe Service Valves

Valtek MaxFlo Control Valves

Kämmer Multi-Z Severe Service Valves

Experience In Motion. Flowserve Control Valve Products North American Quick Response Centers

Valtek Position Pac GENERAL INFORMATION INSTALLATION INSTRUCTIONS OPERATION. Valtek Linear Actuators

USER INSTRUCTIONS. NAF Trunnball DL Ball Valves. Installation Operation Maintenance. Experience In Motion FCD NFENIM A4 01/15

Valtek Valdisk 150. Valtek Valdisk 150. Control Valves. Flowserve Corporation, Valtek Control Products, Tel. USA

Kämmer Series Low Flow Valves

Vogt Valves The Connection Bulletin for Y Pattern Globe & Check Valves Class 1690 & Class 2680 CB 18

USER INSTRUCTIONS. Installation Operation Maintenance. NAF Setball SF Ball Sector Valves. Experience In Motion FCD NFENIM A4 09/16

Vogt Valves The Connection Bulletin for Forged Steel Globe Valves for Water-Free Chlorine Service Class 300, 600 & 800 CB 07

Kämmer Series Split Body Valves

Valtek Tek-Check. Check Valves

Solenoid Block Kit for Series 90 Modular Accessory System Installation, Operation and Maintenance Instructions

Installation Instructions

Valtek Survivor Control Valves

OpTK. Product Instruction Manual. Spring Cylinder Rotary Actuators INTRODUCTION SAFETY INFORMATION INSTALLATION. Leading Technologies For Control

Installation Instructions

Installation Instructions

Desuperheater FCD VLENTB /11. Experience In Motion

INSTRUCTION MANUAL. Anchor Darling 1878 Swing Check Valves. Installation Operation Maintenance. Sizes 1/2 through 2 FCD ADENIM

Installation Instructions

MERIDIAN, 2 or 3 PIECE, TRUNNION MOUNTED BALL VALVES

Installation Instructions

USER INSTRUCTIONS. Valtek Valdisk TX3 Triple Offset Butterfly Control Valve. Installation Operation Maintenance. Experience In Motion

Installation Instructions

NAF Duball DL Pocket Ball Valves TECHNICAL BULLETIN FCD NFENTB A4 11/17

Installation Instructions

Installation Instructions

Valtek Auxiliary Handwheels and Limit Stops

Installation, Operation and Maintenance Instructions Series 608 Ball Valve

MARPAC K SERIES. Full Bore Fire Safe Flanged Ball Valves

Series 72 Electri-SAFE On/Off Operation Including CLC Option Installation, Operation and Maintenance Instructions

RACK & PINION ACTUATORS 2R40 to 2R1750 Series Installation & Maintenance Manual

flowserve.com Limitorque LRP Limitorque Rack & Pinion Pneumatic Actuator

Flowserve Anchor Darling Isolation Valve Application

Product Specification

McCANNA Actuation Systems B

Installation Instructions

Worcester Controls Directional Ball Valves

Rotary Valve Maxflo + 60 and 80 Opening type NT

Fisher SS-263 Volume Booster

TECHNICAL BULLETIN. Audco Ball Valve. Reduced Bore Fire safe Flanged Ball Valves 51/52 Series. Experience In Motion

Figure 1 Figure 2 Double Acting Actuator Spring Return Actuator

USER INSTRUCTIONS. Limitorque TM V Series. Installation Operation Maintenance. Experience In Motion FCD LMENIM AQ 02/15

Valtek Valdisk. Valtek Valdisk Control Valves

Limitorque Accutronic MX/WTR Performance and Dimensions. Limitorque Actuation Systems

XL90 Series High-Performance Positioner

SY-SERIES S04DA75 THRU S06DA180 & S04SR75 THRU S06SR180 DOUBLE ACTING & SPRING RETURN SCOTCH YOKE ACTUATORS

Installation Instructions

Model DFR 070/156/220 Rotary Actuator

THD-SERIES S11DA280 THRU S27DA1020 & S11SR280 THRU S27SR1020 DOUBLE ACTING & SPRING RETURN SCOTCH YOKE ACTUATORS

TECHNICAL BULLETIN. NAF Trunnball DL Ball Valves. Experience in Motion FCD NFENTB A4 09/14

WORCESTER CONTROLS F519/529/819/829. Full Bore Fire Safe Flanged Ball Valves

Valtek Mark One. Valtek Mark One Control Valves

Logix 3800 Digital Positioner

Pneumatic Diaphragm On-Off Actuators

ISC Series Innovative Standard Cartridge Seals

Mark 100. Technical Bulletin F C D F C A T B

Mark 100. Installation, Operation and Maintenance Instructions F C D F C A I M

TECHNICAL BULLETIN. NAF Setball SF Ball Sector Valves. Experience In Motion. flowserve.com. NAF Setball FCD NFENTB A4 02/16

Fisher 657 Diaphragm Actuator Sizes and 87

Installation Instructions

E818/828 Series Fugitive Emissions 150# and 300# Flanged 2" - 8" Two-Piece Ball Valves Installation, Operation and Maintenance Instructions

XL90 Series High-Performance Positioner

Model DFR 026 Rotary Actuator

flowserve.com Flowserve Solenoid Valves Namur, Remote and Banjo Mounted Designs for Precision Control

TECHNICAL BULLETIN. NAF Duball DL Ball Valves. Experience in Motion FCD NFENTB A4 12/14

Fisher 2052 Diaphragm Rotary Actuator

Fisher 2625 and 2625NS Volume Boosters

Fisher 2625, 2625SST, and 2625NS Volume Boosters

Mounting: The following instructions apply to rotary actuators only. Linear applications require special mounting and coupling (consult factory).

Flow Control Division

USER INSTRUCTIONs. Installation Operation Maintenance. Valtek MaxFlo 3 Control Valves. User instructions - MaxFlo 3 - VLENIM

Spring Cylinder Rotary Actuators

Installation Instructions

Fisher VBL Volume Booster

Logix 3800 Digital Positioner

Type 2625 and 2625NS Volume Boosters

Tri-Pac E325 / E525 Ball Valve Three-Piece Bolted Body, In-Line Maintainable, Regular and Full Port. McCANNA/MARPAC Valves RO400-R4

Edward. Equiwedge Forged Gate Valvee. Experience In Motion

Standard Valves Series Globe Valves Series Angle Valves Series Way-Valves

Limitorque Actuation Systems B320 Series. Rugged and dependable bevel gear operators for manual or motorized valve control applications

Limitorque Actuation Systems PT Series Worm Gear Operator

S-17 CATALOG. Forged Steel Strainers

V-SEGMENT SERIES V-Port Segment Control Valves (VS/VV/VM) Installation & Maintenance Manual

HIGH PRESSURE CONTROL VALVE PISTON BALANCED

Product Specification

TECHNICAL BULLETIN. Valdisk TX3 Triple Offset Butterfly Control Valve. Experience In Motion FCD VLENTB A4 1/16

Transcription:

Valtek Flow Boosters GENERAL INFORMATION This bulletin is designed to assist in installing, adjusting, troubleshooting, and performing maintenance as required for the Valtek Flow Booster. Product users and maintenance personnel should thoroughly review and follow the instructions contained in this bulletin prior to the operation of the flow booster. If there are any questions concerning the procedures outlined in these instructions, contact your Valtek representative. Installation, operation, maintenance instructions on Valtek actuators and valves are contained elsewhere; reviewing those instructions is suggested before maintaining or troubleshooting a flow booster. To avoid possible injury to personnel or damage to valve parts, WARNING and CAUTION notes must be strictly adhered to. Modifying this product, substituting non-factory parts, or using maintenance procedures other than outlined could drastically affect performance, be hazardous to personnel and equipment, and may void existing warranties. Principle of Operation The Valtek booster is a pressure-balanced instrument that increases actuator stroking speeds when large input-signal changes are received. Through the adjustment of the bypass valve, sensitivity to a signal change can be increased or decreased. A small input signal to the booster will not create a pressure differential across the diaphragm assembly sufficient to cause booster actuation. Rather, the air passes through the bypass porting while the poppet valves remain tightly shut to prevent unnecessary air use. A sudden, large input-signal change will create a pressure differential across the diaphragm assembly, forcing the poppet valve down, and permitting high air flow into the control valve actuator. Rev. 11/94 Valtek No. 10076933 This high air flow continues until the pressure difference between the control valve actuator and the input signal fall within the deadband limits of the booster. Likewise, when the booster is used to exhaust a control valve actuator, the pressure imbalance across the diaphragm assembly forces it up off the upper poppet valve and the air exits the booster between the diaphragms. For on/off control valves, the bypass valve can be virtually closed to maximize the stroking speed. Installation When installing the flow booster, refer to Figure 1, and proceed as follows: WARNING: Before installing or performing any maintenance on the flow booster, shut off the air pressure to the supply line and the input signal line, and slowly release any internal pressure in the actuator and booster. High pressures not released from the booster supply lines may cause personal injury or damage to the flow booster. WARNING: Shutting off the air supply to the positioner and hence control valve can cause the valve to move to its fail position or be disabled, causing excessive pressures to build up in the system. This, in turn, may result in the system failing, causing injury to equipment or personnel. Generally the flow booster is nipple mounted on the actuator with 3 pipe. However, some systems require multiple boosters or special configurations that may require the booster to be mounted with a bracket. If special mounting is needed, contact your local Valtek representative or the factory for assistance. The supply port connection (marked SUP) and the actuator port connection (marked CYL) are both 3. The input signal port connection (marked SIGNAL) is a 1. A pipe sealant compound should be applied to all connections prior to installation 34-1

Bypass Valve O-ring (Item No. 14) Bypass Valve (Item No. 9) Bypass Valve Nut (Item No. 13) Upper Spring Cap (Item No. 18) Input Signal Port Housing Bolt (Item No. 12) Housing Cover (Item No. 2) Upper Spring (Item No. 17) Upper Diaphragm (Item No. 8) Vent Ring (Item No. 3) Poppet (Item No. 4) End Plug O-ring (Item No. 15) Output Housing (Item No. 1) Lower Diaphragm Assembly (Item No. 7) End Plug (Item No. 10) E0114 Lower Spring Cap (Item No. 21) Lower Spring (Item No. 11) Figure 1: Flow Booster NOTE: Item numbers correspond directly to the booster's bill of materials; refer to it for specific numbers. to prevent leaks. All piping and connection adapters should be rated at least as high as the maximum rated booster pressure, 150 psi (10.3 Bar). The flow booster is designed to function properly in any position. Figures 2 and 3 show possible installation configurations for two types of actuators. The supply air to the flow booster does not require regulation if the maximum rated pressure of the actuator or the flow booster, 150 psig (10.3 Bar), is not exceeded. All air flowing into the flow booster should be dry and filtered to ensure a clean and non-corrosive medium. WARNING: The exhaust ports on the flow booster exhaust air at extremely high velocities. Harm to individuals or equipment can result if positioned too closely to the exhaust ports. After the flow booster has been installed, it may need to be adjusted for optimal performance. Refer to Adjusting Flow Booster Operation section to make these adjustments correctly. Adjusting Flow Booster Operation Once the flow booster is mounted properly, the bypass valve may need to be adjusted for proper operation. This should be done prior to making any positioner calibrations. To make this adjustment, refer to Figure 1, and proceed as follows: 1. Turn the bypass valve counter-clockwise three or four turns from its closed position. 2. Calibrate the positioner according to positioner instructions. 3. Turn the bypass valve clockwise until the flow booster actuates with large positioner input changes but does not actuate with small positioner input changes. This is done by stroking the control valve and adjusting the bypass valve slightly until the desired dynamics is acheived. Turning the bypass valve clockwise increases booster action and overshoot. 34-2

CAUTION: Cycling the control valve can disrupt the process. Care must be used to ensure this disruption will not adversely affect the process. 4. Once the bypass valve has been optimally set, the bypass valve nut should be tightened down to prevent the bypass valve from turning during operation. NOTE: The flow booster is bench calibrated and may need to be re-adjusted once the valve is in the process. NOTE: When two or more flow boosters are used on one actuator, all bypass valves on one side of the actuator can usually be set the same. NOTE: If the control valve is used for only on-off operation, the bypass valve should be turned clockwise until it is nearly closed to maximize stroking speed. MAINTENANCE Although the flow booster is designed to provide a long service life, periodic maintenance is required to extend the booster's life. Some parts in the flow booster may need to be replaced periodically. These parts may include: diaphragms, poppet valve, O-rings and springs. If the lower diaphragm needs replaced, the entire lower diaphragm assembly (Item No. 7) must be ordered. WARNING: Before performing any maintenance on the flow booster, shut off the air pressure to the supply line and the input signal line and slowly release any internal pressure in the actuator and booster. High pressures not released from the booster supply lines may cause personal injury or damage to the flow booster. WARNING: Shutting off the air supply to the positioner and hence control valve can cause the valve to move to its fail position or be disabled, causing excessive pressures to build up in the system. This, in turn, may result in the system failing, causing injury to equipment or personnel. Replacing The Diaphragm Assembly To replace the diaphragms, refer to Figures 1 and 4, and proceed as follows: 1. With the flow booster in an upright position, unscrew the six cap screws. Lift the cover off the upper diaphragm. (If the cover adheres to the diaphragm, gently tap the cover loose with a rubber mallet under the bypass valve protrusion.) 2. Remove the upper diaphragm and inspect for damage or wear. If necessary, replace the upper diaphragm. 3. Remove the lower diaphragm assembly and inspect for damage or wear. Particular attention should be given to where the bottom diaphragm contacts the housing limit stops. Also, inspect the retaining rings for tightness of fit. If necessary, replace this assembly. 4. Reinstall the lower diaphragm assembly. NOTE: Clean the diaphragm mating surfaces thoroughly before replacing the diaphragms. 5. The poppet must be centered in the housing. This is ensured by pressing down on the lower diaphragm assembly slightly and then releasing pressure while holding the lower diaphragm assembly centered. This procedure may need to be repeated to center the poppet in the housing. Be certain the lower diaphragm assembly is centered on the housing and the bypass hole and diaphragm bolt holes line up with the appropriate housing holes. NOTE: The lower diaphragm assembly and housing have the same outside diameter dimension and should be flush when installed correctly. 6. Reinstall the vent ring, aligning it with the appropriate housing holes. 7. The distance between the lower poppet seat line and the upper poppet seat line is important to booster performance. To check this distance, place a straight edge across the middle of the vent ring. The aluminum seat should be on the same plane, within ±.030 inch (±762 mm), with the vent ring. If it is not, the poppet may not be centered (see step 5), or it may be worn (see Replacing the Poppet Valve section). 8. Reinstall the upper diaphragm and apply an antiseize lubricant inside the cover spring bore. 9. Place the cap and spring on the center of the diaphragm, and replace the cover on the diaphragm (be certain spring cap slides into the bore). CAUTION: To ensure proper flow booster operation, be certain the bypass hole in the diaphragms orients properly with the bypass holes in the housing, vent and cover. 10. Replace the six housing cap screws and tighten them finger tight. Be certain that the housing, vent and cover are concentric with each other before tightening the bolts with a wrench in a crisscross pattern. CAUTION: Care should be taken to not overtighten the housing cap screws. Over-tightening may damage the diaphragms, preventing the booster from operating properly. 34-3

Piston Actuator Flow Booster Flow Booster Output 2 Output 1 Positioner Signal E0115 Figure 2: Typical Flow Booster Installation Schematic on Cylinder Actuator Replacing the Poppet Valve If the urethane seat on the poppet is cut, damaged or severely indented, the poppet must be replaced. To do this, refer to Figures 1 and 4, and proceed as follows: 1. Turn the flow booster upside down and remove the end plug. Note that the poppet valve, lower spring cap and lower spring may freely drop from the booster. Check the end plug O-ring for wear or damage. Replace if necessary. 2. Remove the lower spring, lower spring cap and the poppet valve. 3. Before placing a new poppet valve in the booster housing, apply an anti-seize lubricant to the inside bore of the end plug. Re-install the lower spring and the lower spring cap. Place a new poppet into the hole of the lower spring. 4. While holding the flow booster in an upright position, carefully insert the poppet and end plug assembly into the housing. 5. Tighten the end plug. 34-4

Flow Booster Output 2 (plugged) Output 1 Positioner Diaphragm Actuator Signal E0116 Figure 3: Typical Flow Booster Installation Schematic on Diaphragm Actuator Table I: Flow Booster Specifications Input Signal Range Maximum: 150 psig (10.3 Barg) (Same as positioner output) Pressure Up to 150 psi (10.3 Bar) Ranges (check actuator rating) Nominal Deadband 5.5% of input signal span Ambient -40 to 165 O F (-40 to 74 O C) Temperature Limits Air -40 to 165 O F (-40 to 74 O C) Temperature Limits Maximum C V 5.0 Exhaust 3.0 Connections Signal 1, Output 3 Net Weight 4.9 lbs (2.2 kg) Table II: Standard Materials of Construction Component Body End Plug Diaphragm Assembly Poppet Needle Valve Springs Spring Cap Bolts, Nuts Standard Materials Anodized aluminum Nickel plated brass (electroless) Anodized aluminum and Buna-N/Nylon diaphragms Stainless steel and polyurethane Stainless steel Stainless steel Stainless steel Stainless steel 34-5

Housing Bolt (Item No. 12) Housing Cover (Item No. 2) Upper Spring (Item No. 17) Bypass Valve O-ring (Item No. 14) Bypass Valve (Item No. 9) Spring Cap (Item No. 18) Bypass Valve Nut (Item No. 13) Upper Diaphragm (Item No. 8) Vent Ring (Item No. 3) Lower Diaphragm Assembly (Item No. 7) Housing (Item No. 1) Lower Spring (Item No. 11) End Plug (Item No. 10) Poppet (Item No. 4) Lower Spring Cap (Item No. 21) End Plug O-ring (Item No. 15) Figure 4: Flow Booster Exploded View E0112 34-6

Flow Booster Troubleshooting Problem Probable Cause Corrective Action Valve overshoots 1. Bypass porting is too restrictive 1. Turn the bypass valve counterclockwise until overshoot is corrected 2. Diaphragm not aligned 2. Disassemble the flow booster and align properly over bypass porting both diaphragms over their appropriate holes 3. Obstruction in the bypass 3. Disassemble the flow booster and porting clean out the porting Valve is over-damped 1. Bypass porting is not restrictive 1. Turn the bypass valve clockwise until enough over-damping is corrected 2. Diaphragms are damaged and 2. Replace the diaphragms leaking Loss of sensitivity 1. Spring caps not sliding properly 1. Apply an anti-seize lubricant to the surface of the spring bore 2. Obstruction in the signal port 2. Remove obstruction in signal port Booster continuously 1. Bypass needle valve is closed 1. Adjust bypass valve (see Adjusting exhausting Flow Booster Operation section.) 2. Lower diaphragm is leaking air 2a. Disassemble flow booster and press down on retaining ring or replace retaining ring 2b. Replace the lower diaphragm 3. Poppet seating surfaces are 3a. Replace the poppet valve and clean damaged out obstructions that may have caused the damage 3b. Replace booster body or upper diaphram assembly if their seats are damaged 4. Positioner pressure imbalance 4. Refer to the appropriate positioner problem maintenance instructions 5. Aluminum seat/upper poppet 5a. Replace the retaining ring under the valve not sealing lower diaphragm 5b. Align the lower diaphragm with the housing bolt holes 6. Actuator is leaking air 6. Repair actuator as needed Excessive air 1. Air leakage over or under the 1a. Tighten the six capscrews evenly consumption diaphragms 1b. Clean the diaphragm surfaces 1c. Replace the diaphragm(s) 2. Air leakage past the bypass 2. Replace the O-ring on the bypass valve valve and lubricate the O-ring 3. Air leakage past the end plug 3a. Tighten the end plug 3b. Replace or straighten the O-ring 4. Air leakage at NPT connections 4a. Tighten connections 4b. Apply sealing compound/tape 34-7

Bypass Valve 3.49 (89).94 (24) 1 Input Signal Port 3.53 (90) 3 Output Actuator Port 1.38 (35) 3 Input Port 2.63 (67) 5.25 (133) Figure 5: Dimensions inches (mm) E0117 Flowserve Corporation has established industry leadership in the design and manufacture of its products. When properly selected, this Flowserve product is designed to perform its intended function safely during its useful life. However, the purchaser or user of Flowserve products should be aware that Flowserve products might be used in numerous applications under a wide variety of industrial service conditions. Although Flowserve can (and often does) provide general guidelines, it cannot provide specific data and warnings for all possible applications. The purchaser/user must therefore assume the ultimate responsibility for the proper sizing and selection, installation, operation and maintenance of Flowserve products. The purchaser/user should read and understand the Installation Operation Maintenance (IOM) instructions included with the product, and train its employees and contractors in the safe use of Flowserve products in connection with the specific application. While the information and specifications presented in this literature are believed to be accurate, they are supplied for informative purposes only and should not be considered certified or as a guarantee of satisfactory results by reliance thereon. Nothing contained herein is to be construed as a warranty or guarantee, express or implied, regarding any matter with respect to this product. Because Flowserve is continually improving and upgrading its product design, the specifications, dimensions and information contained herein are subject to change without notice. Should any question arise concerning these provisions, the purchaser/user should contact Flowserve Corporation at any of its worldwide operations or offices. For more information, contact: For more information about Flowserve and its products, contact www.flowserve.com or call USA 972 443 6500 Manufacturing Facilities 1350 N. Mt. Springs Prkwy. Springville, UT 84663 Phone 801 489 8611 Facsimile 801 489 3719 1300 Parkway View Drive Pittsburgh, PA 15205 USA Telephone 412 787 8803 Facsimile 412 787 1944 Manderscheidstr. 19 45141 Essen, Germany Telephone (49) 2 01 89 19 5 Facsimile (49) 2 01 891 9600 Alläe du Quartz 1 CH-2300 La Chaux-de-Fonds Switzerland Telephone (41) 32 925 9700 Facsimile (41) 32 926 5422 Quick Response Centers 5114 Railroad Street Deer Park, TX 77536 USA Telephone 281 479 9500 Facsimile 281 479 8511 104 Chelsea Parkway Boothwyn, PA 19061 USA Telephone 610 497 8600 Facsimile 610 497 6680 34-8 1997 Flowserve Corporation. Flowserve and Valtek-Kammer are registered trademarks of Flowserve Corporation.