ENGINEERING PROJECTS INDIA LIMITED HAL PROJECT, NASIK BOQ FOR ELECTRICAL WORKS IN PACKAGE II

Similar documents
INDIAN INSTITUTE OF TECHNOLOGY KANPUR

SCHEDULE OF QUANTITY

INDIAN INSTITUTE OF TECHNOLOGY KANPUR

Total Cost Abstract. Project Name : - RDPL, Jaipur. Grand Total

BOQ FOR ELECTRICAL WORK OF CANARA BANK RENGALI BRANCH

Tender Schedule for Electrical Works at Varagani Branch. Sl. No. Particulars Quantity Unit Rate Amount

ESTIMATE FOR ELECTRICAL WORKS AT CHINCHOLI BRANCH

Tender Schedule. Sl. No. Particulars Quantity Unit Rate `

B.O.Q FOR ELECTRICAL WORK (Including Fitting & Fixtures) OF STAFF QUARTERS AT BUUBANESWAR FOR UNITED INDIA INSURANCE CO. LTD

Estimate For The Electrical Works At Pittakayagulla Branch Sl.N Particulars Quantity Unit Rate Amount

Name of work : Electrification of PG Block Second Floor in V.P.S.V Ayurveda college Kottakkal.

BILL OF QUANTITY (BOQ) FOR ELECTRICAL WORKS BOGAPURAM BRANCH

Estimate For Electrical Works PROPOSED RUDSET INSTITUTE AT BERHAMPUR

Bills of Quantities and Schedule for the Electrical Works at M/s.Bank of India, Madurai CPC Branch, East Aavani Moola Street, Tamil Nadu.

B.O.Q's FOR ELECTRICAL WORKS FOR BANK OF INDIA, COLLEGE ROAD, DHAKA BRANCH

B.O.Q ELECTRICAL WORK OF CANARA BANK, BUDHARAJA BRANCH

SCHEDULE OF QUANTITIES FOR THE ELECTRIFICATION STRUCTURED / DATA CABLING WORKS FOR THE FEDERAL BANK'S

FINANCIAL BID NAME OF WORK : ELECTRIFICATION WORK AT THE NEW OFFICE PREMISES OF SBI EXCLUSIF KOZHIKODE BRANCH

TENDER DOCUMENT PART-II

Amount (Rs) 1.5 sq. mm ISI marked, FR

INDIAN INSTITUTE OF TECHNOLOGY KANPUR

SCHEDULE OF QUANTITIES ITEM DESCRIPTION

Corrigendum-I. Bill of Quantity

PART B: FINANCIAL BID

PART A: FINANCIAL BID

TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID

S P E C I F I C A T I O NS

ESTIMATE PROPOSED ELECTRICAL & ALLIED WORKS FO INDIA ONE AVIGHNA PARK, CURREY ROAD BRANCH AT C MUMBAI

TENDER DOCUMENTS SUPPLY OF ELECTRICAL EQUIPMENT FOR BHADRAK MUNICIPALITY FOR THE YEAR LAST DATE OF RECEIVED OF TENDER DOCUMENTS :

TENDER DOCUMENT. (TENDER No: NRO/CON/696/660) FOR

AN ISO 9001 & COMPANY TENDER DOCUMENT. TENDER No: DLI/CON/696/411 FOR

sl. No Description Unit Qty Rate (Rs) Amount (Rs)

Set /

to UPS outgoing DB. c With 2 nos. 6 Sq.mm + 1 no. 2.5 Sq.mm. PVC insulated copper wire from UPS outgoing DB to CDB / Main panel to LDB /


STATE BANK OF INDIA BOQ FOR THE ELECTRICAL 74 JANPATH BRANCH. S.No. DESCRIPTION OF WORKS UNIT QTY RATE AMOUNT

FORMAT-III B - ANNEXURE-III

STATE BANK OF INDIA ADMINISTRATIVE OFFICE -7 : HUBBALLI KUDRIGE BRANCH - REGION 5, KARNATAKA. ELECTRICAL WORKS : SCHEDULE OF ITEMS(BOQ)

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

FORMAT B (Annexure-III)

Bill of Quantity for Electrical & Computer wiring works for Shifting of SMECC Jamshedpur to Jamshedpur Branch Premises

GUJARAT ENERGY TRANSMISSION CORPORATION LIMITED SARDAR PATEL VIDYUT BHAVAN RACE COURSE, VADODARA TENDER FOR

Rate (Rs.) in figure. Rate (Rs.) in words. VAT (%) Amount (Rs.) & all other taxes.

BILL OF QUANTITIES - ABSTRACT

SBI INFRA MANAGEMENT SOLUTIONS PVT.LTD. PART B: FINANCIAL BID. Proposed Electrical Work For SBI Ramdaspeth Branch, Nagpur. S. NANDEDKAR & ASSOCIATES


Estimate of Under Ground Electrification Work

FORMAT-III B - ANNEXURE-IV

M. C. B. / D. B./MCCB : MDS/Schneider/Siemens/havells

STATE BANK OF INDIA ESTIMATE FOR THE ELECTRICAL

STANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011

Electrical BOQ for P Block Connaught Place Branch S.No. DESCRIPTION OF WORKS UNIT QTY RATE AMOUNT

LIST OF EDD DESCRIPTION/ SPECIFICATION AS 19 TH OCTOBER 2016

SCHEDULE OF QUANTITIES OF ELECTRICAL WORKS FOR BOI, ZO, JODHPUR. PART - II

SBI INFRA MANAGEMENT SOLUTIONS PVT.LTD. CIRCLE OFFICE, AHMEDABAD STATE BANK OF INDIA, RBO-II, C.N. VIDYALAYA CAMPUS, AMBAWADI, AHMEDABAD

PROPOSED COST SCHEDULE OF MATERIALS FOR CONSUMER JOB AND OTHER JOBS

List of materials for 1Km. Of L.T line 1-Ph., 2-Wire AB cable (1 X 25+1X16) sq.mm using 8M X 200 KG. PSC Pole

3.6 Kwp Solar system Supply, Installation, Commissioning & Maintenance of Solar Systems to YEMAC office in HADDA street, Sana a city

MOTHER DAIRY A UNIT OF GUJARAT CO-OPERATIVE MILK MARKETING FEDERATION LIMITED PURCHASE ENQUIRY

Rate. Sl No. Description of item Unit Qty

TENDER DOCUMENT TENDER No.: NRO / CON / 592 / 537 FOR SUPPLY & INSTALLATION. DG Sets & Sychronising Panel

MOTHER DAIRY A UNIT OF GUJARAT CO-OPERATIVE MILK MARKETING FEDERATION LIMITED PURCHASE ENQUIRY

STATE BANK OF INDIA INFRA MANAGEMENT SOLUTION (P) LTD BOQ- ELECTRICAL WORKS OF KATKOL BRANCH, RBO-2, AO-7

MAIN INCOMER -1 (500 KVA TRF.)

S P E C I F I C A T I O N

: Material Description Quantity UOM

PUNE EAST ZONE - BANK OF MAHARASHTRA Kesari Wada, Narayan Peth, Pune

SNO DESCRIPTION QTY UNIT RATE AMOUNT MAIN PUMP 1

Technical Specifications

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

T. No 03/ /Eldb

Total Ex. Tax/VAT. (Rs.) (if any) in Rs. (Bought out/direct) length 587M 226M

ANNEXURE-I : LIST OF ITEMS H.O. PURCHASE ITEM LIST:

West Bengal State Electricity Distribution Co. Ltd.

LOT Kwp Solar PV Power Solution with Battery Backup

1 SITC of Surge protector OBO BETTERMAN V25-B+C/3+NPE with manufacturer's enclosure, 3 phase 415 V. no 1. No 1

GEMSCAB has been associated with marketing and manufacturing of Electric Cables

SBI, DHROLL BRANCH, DIST. JAMNAGAR - ELE. INST. WORK - OCT. 2018

Item Code Description Unit Qty Total

ESTIMATE: ELECTRICAL AND DATA CABLING WORK SBI Panchanan Bhawan Bhopal (M.P)

NEPAL ELECTRICITY AUTHORITY (An Undertaking of Government of Nepal) Project Management Directorate

KERALAM MUSEUM OF HISTORY & HERITAGE


(C)- ABSTRACT OF COST AR&M-

AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

PONDICHERRY UNIVERSITY ELECTRICAL WING Schedule

TENDER SPECIFICATION. Rayalaseema Thermal Power Project (Muddanur) V.V.Reddy Nagar, Kalamalla Post,Cuddapah Dt, AP

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

Design specifications

Price List "NATIONAL" PVC FLEXIBLE CABLES COPPER CONDUCTOR 1.1 KV CONFORMING TO IS:694/2010. Size Twin Two Three Four

QUOTING SHEET BIDDER'S PRICE % QUOTE ABOVE / AT PAR / BELOW In figures

POLYCAB WIRES PVT. LTD.

INDIAN INSTITUTE OF TECHNOLOGY GUWAHATI Guwahati Phone : (0361) , Fax : (0361)

NEPAL ELECTRICITY AUTHORITY (An Undertaking of Government of Nepal) Project Management Directorate

Annexure- II (Price Bid) SCHEDULE B LIST OF ELECTRICAL ITEMS TO BE SUPPLIED

PRICE BID - PART: I I

TGK Prefabricated Substation Technical Data

KENYA POWER-MOMBASA BRANCH REPLACEMENT OF AIR-CONDITIONING AND ASSOCIATED WORKS BILLS OF QUANTITIES FOR ELECTRICAL INSTALLATIONS BILL NO

Schedules 1 to 4, Lot B: Extension of the Lessos Substation

Key features. DESIGNS: - Conservator type - Hermetically sealed

Transcription:

ENGINEERING PROJECTS INDIA LIMITED HAL PROJECT, NASIK BOQ FOR ELECTRICAL WORKS IN PACKAGE II 1 Installation of 11kV 7 Module Indoor Type VCB Panel in Substation Installation only of 11kV, 7 Module of VCB, Indoor Type Vacuum Circuit Breaker Panel with Two nos 1250 A VCB as incomers for the Ring Main System and Five nos of 800A VCB as outgoings to transformers in Substation. The rate should be quoted only for installation of VCB's Panels including angle iron frame work and fixing accessories such as grip bolts/grouting/ welding to steel structures etc as well as civil work required for installation of the VCB's Panels complete in the substation. The technical specification for installation of of the VCB's Panels are mentioned in the Technical specification book separately. te : The VCB's Panels will be procured separately by HAL and shall be provided free of charge to contractor for installation by the contractor. Only labour charges to be quoted for installation.. 1.00 2 Installation of Indoor Transformers in Substation Erection(Installation) only of 1600 kva, 11kV/380V, Dyn11, Oil Cooled ONAN type double copper wound, delta star connected Indoor Distribution Transformer with OLTC, RTCC Panel,AVR Panel, Marshaling Box, Oil Temperature Indicator, Winding Temperature Indicator, Buccholz Relay, Bidirectional rollers, cable boxes on both LT & HT side, Pressure Relief Valve, etc., including transformer foundation (level concrete plinth) and angle iron frame work and fixing accessories such as grip bolts/grouting/ welding to steel structures etc including civil work required for installation of transformer 2.01 and its accessories in Substation.The rate should be quoted only for installation of transformer with including transformer foundation ( level concrete plinth), angle iron frame work and fixing accessories such as grip bolts/grouting/ welding to steel structures etc as well as civil work required for installation of the Transformer, OLTC, RTCC Panel, AVR Panel, Marshaling Box, Oil Temperature Indicator, Winding Temperature Indicator, Buccholz Relay, Bidirectional rollers, cable boxes on both LT & HT side,. 2.00 Pressure Relief Valve, etc. complete in the Substation. Refer technical specification book for details of installation of Transformer, OLTC, RTCC Panel etc. te : The 1600 kva, 11kV/380V, Dyn11, Oil Cooled ONAN type, Indoor Transformer will be procured separately by HAL and shall be provided free of charge to contractor for installation by the contractor. Only labour charges to be quoted for installation.

2.02 Erection(Installation ) only of 2000 kva, 11kV/433V, Dyn11, Oil Cooled ONAN type double copper wound, delta star connected indoor Distribution Transformer with OLTC, RTCC Panel, Marshaling Box, Oil Temperature Indicator, Winding Temperature Indicator, Buccholz Relay, Bidirectional rollers, cable boxes on both LT & HT side, Pressure Relief Valve, etc., including the transformer foundation (level concrete plinth) and angle iron frame work and fixing accessories such as grip bolts/grouting/ welding to steel structures etc including civil work required for installation of transformer in Substation. The rate should be quoted only for installation of transformer and its associated accessories with including transformer foundation (level concrete plinth), angle iron frame work and fixing accessories such as grip bolts/grouting/ welding to steel structures etc as well as civil work required for installation of the OLTC, RTCC Panel,AVR Panel, Marshaling Box, Oil Temperature Indicator, Winding Temperature Indicator, Buccholz Relay, Bidirectional rollers, 2.00 cable boxes on both LT & HT side, Pressure Relief Valve, etc. complete in the Substation. Refer technical specification book for details of installation of Transformer, OLTC, RTCC Panel, AVR panel, etc. te : The 2000 kva, 11kV/433V, Dyn11, Oil Cooled ONAN type, Indoor Transformer will be procured separately by HAL and shall be provided free of charge to contractor for installation by the contractor. Only labour charges to be quoted for installation. 3 HT Cable : Laying, Testing and Commissioning of the above 3 core 300 sq.mm HT 11kV(E) XLPE insulated, aluminium amoured cable in full round hume pipe / in already built up cable trench as per the IS -1255 : 1983. Refer Technical specifications in the technical 3.02 specification book of procedure for laying of the HT cable as per IS Standards. The technical specification for laying of the 11kV HT cable is mentioned in the Technical specification book separately. 4 H.T. Cable End Termination : Supply, Installation,Testing and Commissioning of HT cable end termination for indoor with Heat shrinkable end termination kit suitable for the above XLPE, 11 kvht cable with all sundry material required for termination of XLPE, 11 kv HT cable etc complete. 3-Core x 300 Sqmm indoor End Termination kit. The technical specification for H.T. Cable End Termination is mentioned in the Technical specification book separately. 5 Miscellaneous Works at Substation Supply and Installation of 2 nos of red color painted Fire buckets round bottom of 9 5.01 Ltrs capacity filled with dry sand with including suitable angle iron support red color painted Mtrs 200.00. 8.00 5.00

5.02 5.03 5.04 5.05 5.06 5.07 Supplying & Erection of Danger notice plate of l.6mm thick mild steel vitreous enameled white with letters, figures and conventional skull and bones in signal red colour and fixed with M. S.clamps, bolts and nuts of approved size for LT 20 x 15 cm size and same size for HT 20 x 15 cm. The danger notice plate shall comply with IS : 2551-1982. 6.00 Supplying & Installation of PVC insulating Mats of 15 KV grade mats of 2.5 mm thickness and 1 mtr width as required by the Electrical Standards and confirming to IS Mtr 80.00 15652. Supply and Installation of 5kg capacity ABC type fire extinguishers complete with mounting brackets, spray nozzles, connecting pipes, "OPEN / CLOSE" valves with all 22.00 other necessary accessories complete as required. Supply and Installation of Shock Treatment Chart with teak wood frame and glass cover as approved by Electrical Inspector. 9.00 Prepartion and Installation of Electrical Single Line Diagrams(SLD) of the substation mentioning equiptment details, earthing scheme details. on suitable size acrylic display board. Also suitable stickers to be put on the panels for identification of incomong and 6.00 outgoing supplies as per site requirement. Supply and Providing of 11 kv grade hand glouse with chalk powder including suitable weather proof transparent box with lock and key. 6.00 5.08 Supply and Providing of First Aid Box as per IS Standard. 6.00 6 Battery and Battery Charger Supply & Installation & Testing & Commissioning of 24 V DC 110AH sealed maintenance free battery, battery charger with control & relay protection, complete with all accessories like insulators, clamps, bimetal connectors, M.S.support rack etc. battery charger should have main input 230V +/- 20%,50 Hz single phase.the 1.00 technical specification for Battery and Battery Charger is mentioned in the Technical specification book separately. 8 L.T Sandwich Bus Duct Design, manufacturer, supply, installation, testing and commissioning of busduct in sandwich construction of Aluminium bus bars, non-ventilation, fabricated out of extruded CRCA sheet painted with necessary supports with approved paint shade as per specification including 2 s. of 50x6 mm Alumimium earthing conductor through out the length of the bus duct and 90 deg bends, Adaptor boxes and flange Ends. (Phase sequence should matched). The technical specification for L.T Sandwich Bus Duct is mentioned in the Technical specification book separately. 8.01 8.02 2500A 415V, TPN+E, Sandwitch type LT Bus duct suitable for indoor type application with external double earthing. 2500A 415V, TPN+E 90 Deg Bend of LHS (or) RHS or Vertical or Horizontal suitable for indoor type application. Mtr 20.00 8.00

8.03 8.04 8.05 8.06 8.07 8.08 2500A, 415V, TPN+E Flange end box with terminal bars adopter chamber, for connecting the bus duct to Transformer, (or) Panel with all neccessory accessories as required for Indoor type. 4.00 Supply and Providing the 2500A TPN +E laminated bimetallic copper flexible mimimum 400mm with necessary all fixing electrolyte grade hardware's as required. 2.00 4000A 415V, TPN+E, Sandwitch type LT Bus duct suitable for indoor type application with external double earthing. Mtr 60.00 4000A 415V, TPN+E 90 Deg Bend of LHS (or) RHS or Vertical or Horizontal suitable for indoor type application. 12.00 4000A, 415V, TPN+E Flange end box with terminal bars adopter chamber, for connecting the bus duct to Transformer, (or) Panel with all neccessory accessories as 6.00 required for Indoor type. Supply and Providing the 4000A TPN +E laminated bimetallic copper flexible mimimum 400mm with necessary all fixing electrolyte grade hardware's as required. 3.00 9 Preparation of Detailed Drawings of the Substation and complete electrification of Package II and Test commissioning, Final Commissioning after obtaining Approval from Central Electricity Authority Preparation of detailed drawing of the substation and complete electrification scheme fully complied with relevant standards of Indian Electricity Act. This includes : 1) Preparation of proposed drawings as per electrical standards 2) Test Commissioning of the System 3) Final Commissioning. This work is inclusive of : a) Liasioning with Central electricity Authority (CEA) for obtaining their permission /approval for energisation of electrical installation for final commissioning LS ( Rs / KVA ) 9700.00 b) Filing all relevant applicatiions as per Procedure of CEA c) Furnishing technical information as required by CEA d) Payment of all applicable fees as required for obtaining approval. All incidental costs(if any) must be borne by the contractor and he shall not seek clients assistance for obtaining relevant documents 11 Distribution Boards

Supply Installation Testing and Commissioning of Power Distribution Boards, Light Distribution Boards, Switch - Socket Distribution Boards and SPN / TPN / VTPN Double Door Distribution boards of dust and vermin protected and rated for 230 / 415V, Single phase / Three Phase AC supply, 50 Hz operation either surface / recess mounted as per drawings including incoming and out going MCBs / ELCB as per specifications and required capacity including Neutral Bus Bar and Earth terminal complete as required. MCB's shall be D-curve for LDB'S, and for PDB, conform to IS : 8828 and ELCB /RCCB shall conform to IS : 12640 and MCCB shall conform to IS: 13947(Part 3) -1993. The technical specification for distribution boards is mentioned in the Technical specification book separately. 11.01 11.02 11.03 11.04 12 Way VTPN DB suitable to install 125A 4P MCCB -1 (25KA ) as Incomer with Metal Double Door protection IP 43 (PDB) 8 Way VTPN DB suitable to install 125A 4P MCCB -1 (25KA ) as Incomer with Metal Double Door protection IP 43 (PDB) 8 Way TPN Phase Segregated MCB 7-Segment DB suitable to install 63A TPN MCB -1 as Incomer With Metal Door protection IP 42 6Way TPN Phase Segregated MCB 7-Segment DB suitable to install 63A TPN MCB -1 as Incomer With Metal Door protection IP 42 8.00 8.00 11.00 15.00 13 Laying of LT Cables Laying of following sizes of LT cables in excavated, built up cable trench, through RCC full round hume pipes, cleated on walls and on cable trays(indoor/outdoor) with all materials, accessoreis required for installtion of LT cables as required.the work of underground cables shall be carried out as specified in IS:1255-1983. The technical specification for laying of the LT cables is mentioned in the Technical specification book separately.the cable shall conform to IS : 7098(PART I) 1985 or Ammended for XLPE insulated cables and IS 1554(Part I)-1988 or ammended for PVC insulated cables. te : The empty dable drums should be to be handed to HAL and stored at HAL as directed by the HAL Engineer In Charge. 13.01 3.5 Core x 240 Sqmm XLPE Aluminium armoured Cable Mtr 10200.00 13.02 3.5 Core x 185 Sqmm XLPE Aluminium armoured Cable Mtr 2100.00 13.03 3.5 Core x 150 Sqmm XLPE Aluminium armoured Cable Mtr 750.00 13.04 3.5 Core x 95 Sqmm XLPE Aluminium armoured Cable Mtr 3650.00 13.05 3.5 Core x 50 Sqmm XLPE Aluminium armoured Cable Mtr 3600.00 13.06 4.0 Core x 25 Sqmm XLPE Aluminium armoured Cable Mtr 5500.00 13.07 4 Core x 16 Sqmm XLPE Aluminium armoured Cable Mtr 5250.00 13.08 4 Core x 6 Sqmm PVC Aluminium armoured Cable Mtr 2300.00 13.09 4 Core x 2.5 Sqmm PVC Copper armoured Cable Mtr 625.00 13.10 3 Core x 2.5 Sqmm PVC Copper armoured Cable Mtr 100.00

13.11 3 Core x 240 Sqmm XLPE Copper armoured Cable Mtr 310.00 13.12 3 Core x 95 Sqmm XLPE Copper armoured Cable Mtr 100.00 13.13 3 Core x 50 Sqmm XLPE Copper armoured Cable Mtr 3250.00 13.14 24 Core x 2.5 Sqmm XLPE Copper armoured Cable Mtr 250.00 14 Cable End Terminations : Supply and Termination of LT cables with double compression type brass gland, heavy duty copper and aluminium lugs, insulation tape, identification tags etc., including earthing of gland etc. The technical specification for cable end termination is mentioned in the Technical specification book separately. 14.01 3.5 Core x 240 Sqmm XLPE Aluminium armoured Cable 214.00 14.02 3.5 Core x 185 Sqmm XLPE Aluminium armoured Cable 30.00 14.03 3.5 Core x 150 Sqmm XLPE Aluminium armoured Cable 40.00 14.04 3.5 Core x 95 Sqmm XLPE Aluminium armoured Cable 98.00 14.05 3.5 Core x 50 Sqmm XLPEAluminium armoured Cable 114.00 14.06 4.0 Core x 25 Sqmm XLPE Aluminium armoured Cable 164.00 14.07 4 Core x 16 Sqmm XLPE Aluminium armoured Cable 136.00 14.08 4 Core x 6 Sqmm PVC Aluminium armoured Cable 120.00 14.09 4 Core x 2.5 Sqmm PVC Copper armoured Cable 50.00 14.10 3 Core x 2.5 Sqmm PVC Copper armoured Cable 2.00 14.11 3 Core x 95 Sqmm XLPE Copper armoured Cable 2.00 14.12 3 Core x 50 Sqmm XLPE Copper armoured Cable 90.00 14.13 3 Core x 240 Sqmm XLPE Copper armoured Cable 12.00 14.14 24 Core x 2.5 Sqmm XLPE Copper armoured Cable 10.00 15 FLP Cable End Terminations : Supply and Termination of LT cables with FLP double compression type brass gland, heavy duty copper and aluminium lugs, insulation tape, identification tags etc., including earthing of gland etc. The technical specification for FLP cable end termination is mentioned in the Technical specification book separately. 15.05 3.5 Core x 50 Sqmm XLPE Aluminium armoured Cable 16.00 15.06 4.0 Core x 25 Sqmm XLPE Aluminium armoured Cable 2.00 15.07 4 Core x 16 Sqmm XLPE Aluminium armoured Cable 2.00 15.08 4 Core x 6 Sqmm PVC Aluminium armoured Cable 2.00 15.09 4 Core x 2.5 Sqmm PVC Copper armoured Cable 2.00 15.10 3 Core x 2.5 Sqmm PVC Copper armoured Cable 2.00 16 Power Point Wiring

Supply, Installation Testing and Commissioning of Power Points of modular switches/sockets mounted on suitable size metal boxes covered by Wraparound plus white color front plate fixed flush/surface on the wall with all fixing, wiring accessories, earthing etc including supply, wiring, testing and commissioning of the specified size 1100V grade FRLS PVC insulated multi strand copper conductor wires in and including 25 mm size heavy duty ERW MS conduits laid on wall. The wiring conforming shall confirm to IS 732-1989. The rate shall include supply, installation of all materials required like elbow bends, clamps, saddles and all other fixing accessories with necessary end termination with suitable copper lugs and ferrules identification etc.the technical specification for point wiring is mentioned in the Technical specification book separately. 16.01 16.02 Prewired 10M horizontal plate assembled with 3 intel sockets controlled by 16 A indicator switch with surface box(wraparound) with 2 Runs of 2.5 sqmm wire & 1Run of 1.5 sqmm earth with 25mm heavy duty ERW MS Conduit from PDB to First Socket complete and will be measured as one Point. Prewired 10M horizontal plate assembled with 3 intel sockets controlled by 16 A indicator switch with surface box(wraparound) with 2 Runs of 2.5 sqmm wire & 1Run of 1.5 sqmm earth with 25mm MS Conduit from Socket to Socket complete and will be measured as one Point. ( Max 4 socket sets in One Circuit will be the criteria ) 30.00 s 79.00 16.03 16.04 1 of 6/16 Amps, 6-pin (250 Volts, ) Single Phase universal socket (Combination of Multipin) with 16 Amps single pole switch with 3-Module surface box(wraparound) and 3-Module face plate with 2 Run of 4 Sqmm Wire & 1Run 2.5 sqmm earth with 25mm MS Conduit from PDB to First Socket complete amd will be measured as one Point 1 of 6/16 Amps, 6-pin (250 Volts), Single Phase universal socket (combination of Multipin) with 16 Amps single pole switch with 3-Module surface box and 3-Module face plate with 2 Runs of 4 Sqmm Wire & 1Run of 2.5 Sqmm earth with 25mm MS Conduit from First Socket to Next Socket complete and will be measured as one Point. ( Max 2 socket in One Circuit will be the criteria) 76.00 75.00 16.05 1 of 6/16 Amps, 3-pin (250 Volts), Single Phase universal socket with box and 16 Amps single pole switch with 2- Module surface box and 2 -Module face plate(geyser POWER POINT) with 2 Runs of 4 Sqmm Wire & 1Run 2.5Sqmm Earth with 25mm MS Conduit from PDB to Switch and Switch to Socket complete and will be measured as one Point. 18.00

16.06 16.07 16.08 16.09 20 Amps, 3-pin single phase metal clad industrial Metal Clad socket with plug top, controlled by 20 Amps SP MCB enclosed in powder coated MS box with 2 Runs of 4 Sqmm wire & 1Run of 2.5 sqmm earth with 25mm MS Conduit from PDB to First socket complete and will be measured as one Point. ( PDB TO SOCKET). The plug top should be handed to HAL Supply and Installation of 25mm heavy duty MS ERW conduit on wall. The rate shall include supply, installation of all materials required like elbow bends, clamps, saddles and all other fixing accessories etc required for the conduit. Supply and laying of 2 runs of 2.5 sqmm FRLS PVC insulated multi strand copper conductor wires with 1 run of 1.5 sqmm FRLS PVC insulated multi strand Copper conductor earth wire through the existing 25 mm dia conduit. Supply and laying of 2 runs of 4 sq.mm FRLS PVC insulated multi strand copper conductor wires with 1 run of 2.5 sqmm FRLS PVC insulated multi strand copper conductor earth wire through the existing 25mm dia ERW MS conduit. 96.00 Mtr. 150.00 Mtr. 100.00 Mtr. 100.00 17 Load Break Switches/Sockets for rmal Area Supply, Erection,Installation Testing and Commissioning of factory made Metal Clad Plug Socket and Top totally enclosed with metal housing with industrial socket/interlocked combined. All MCB/MCCB/SFU & Sockets should be be housed in MS coated boxes. The erection rate shall include supply of angle iron frame work and fixing accessories such as grip bolts/grouting/ welding to steel structures etc. The technical specification for Load Break Switches/Sockets is mentioned in the Technical specification book separately. The plug top shoukd be handed to HAL. 17.01 17.02 17.03 17.04 17.05 17.06 32 Amps, 440V, 50 Hz, 3 Phase and Earth industrial Metal Clad socket with plug top, controlled by 32A 3P, MCB. 125 Amps, Single Phase, 690V, Switch Fuse Disconnector Unit with Din Type fuses totally enclosed in SS Housing along with cable termination boxes on incoming and outgoing side. 32 Amps, TPN, 690V, Switch Fuse Disconnector Unit with Din Type fuses totally enclosed in SS Housing along with cable termination boxes on incoming and outgoing side. 63 Amps, TPN, 690V, Switch Fuse Disconnector Unit with Din Type fuses totally enclosed in SS Housing along with cable termination boxes on incoming and outgoing side 125 Amps, TPN, 690V, Switch Fuse Disconnector Unit with Din Type fuses totally enclosed with SS Housing along with cable termination boxes on incoming and outgoing side. 160 Amps, TPN (690V), Switch Fuse Disconnector Unit with Din Type fuses totally enclosed in SS Housing along with cable termination boxes on incoming and outgoing side. 17.00 11.00 68.00 17.00 4.00 5.00

17.07 250 Amps, TPN, 690 V, Switch Fuse Disconnector Unit with Din Type fuses totally enclosed in SS Housing along with cable termination boxes on incoming and outgoing side. 8.00 400 Amps, TPN, 690V, Switch Fuse Disconnector Unit with Din Type fuses 17.08 Totally Enclosed with Metal Housing along with cable termination boxes on incoming 3.00 and outgoing side. 17.09 630 Amps, TPN, 690V, Switch Fuse Disconnector Unit with Din Type fuses Totally Enclosed with Metal Housing along with cable termination boxes on incoming and outgoing side. 2.00 630 Amps, DP, 550 V, Switch Fuse Disconnector Unit with Din Type fuses totally 17.1 enclosed in SS Housing along with cable termination boxes on incoming and 1.00 outgoing side. 18 Load Break Switches/Sockets for Flameproof Area Supply, Erection, Installation Testing and Commissioning of FLP Switch Fuse Units/ Combined Switch and Sockets on angle iron frame work. The SFU/Sockets shall be with Cast Aluminium alloy enclosure finished with epoxy grey stove enamelled and conform to IS 2148 and certified by CMRI Dhanbad. The erection rate shall include supply of angle iron frame work and fixing accessories such as grip bolts/grouting/ welding to steel structures etc. The technical specification for Load Break Switches/Sockets for flameproof area is mentioned in the Technical specification book separately.the plug top should be handed to HAL 25 Amps, SPN & Earth, 230V, industrial socket with plug top,controlled by 20Amps, SP MCB in LM6 enclosure 19 GI Cable Trays and Raceways : Supply & Erection & Installation of the following sizes hot dip Galvanised G.I ladder and perforated type cable tray and Raceways made of 2mm thick with cover. The Quoted price of cable tray items shall inclusive of elbows,cross,tee, bend,coupler plate with necessary grip bolts, grid plates and all other mounting & fixing accessories complete as required. The technical specification for cable tray and raceways is mentioned in the Technical specification book separately. The plug top The steel items required for supporting the cable tray shall be covered separately under "Steel Items" 5.00 19.01 1000 mm wide x 75 mm depth Ladder Type Mtr 1770.00 19.02 600 mm wide x 75 mm depth Ladder Type Mtr 1000.00 19.03 450 mm wide x 50 mm depth Ladder Type Mtr 150.00 19.04 300mm wide x 50 mm depth Preforated type Mtr 500.00 19.05 100mm wide x 50 mm depth sectioned GI Raceways with cover. Mtr 300.00 19.06 50mm wide x 50 mm depth sectioned GI Raceways with cover. Mtr 200.00 20 STEEL ITEMS

Supply, Fabrication, Erection, Painting of all type of Steel items (ISMC,ISMB,ISA,etc.., )as required as per specification complete. Generally Steel items are for cable trays, BBT's supporting arrangements, checkers plates above trenches and any other steel work. The quoted rate should inclusive of painting the steel items with two coats of red oxide primer and two coats of synthetic enamel paint of approved shade. The Structural Steel E205 shall conform to IS 2062-2006. MT 18.00 21 Excavation Works for Outdoor Cable Laying : Preparation of Outdoor cable trenches at a depth as specified for laying of LT cable, telephone cables, street light cables below the ground level including excavation of any type of soil, cement surface as per site conditions with sand layer cushioning for the LT cable, providng brick layer above and the sides of the LT cables and backfilling of the excavated part and making good surface as required.the excavation work shall conform to IS : 3764-1992. 21.01 Trench of width 750mm & depth 1000mm for LT cables m3 75.00 21.02 Trench of width 450mm & depth 750mm for Telephone and Street Light cables m3 1687.50 22 Earthing : Installation of safe earth electrode of 3 mts long 80mm dia with 2 nos bag back fill compound, construction of brick trough, providing meshed funnel, 450 X 450 CI heavy duty cover, brick work of 1 cubic mtr and other civil engineering works, 22.01 spreading a back fill compound mixture of fixing of copper bolt nut etc, completely as 37.00 required as per IS 3043-1987 or latest revision. The technical specification for earthing is mentioned in the Technical specification book separately 22.02 Installation Copper Plate Earth station, with 600 X 600 X 6.3 mm thick Copper plate terminated with 2 runs of 32 x6 mm copper strip of 3 M long with 40 mm dia G.I pipe with including construction of brick pedestal, providing meshed funnel, 450 X 450 CI heavy duty cover, brick work of 1.5 cubic mtr and other civil engineering works, spreading a homogenous mixture of 50 kg of salt and 25 kg of charcoal around the plate, 25 kg of bentonite powder, copper bolt nut etc, completely as per IS 3043, 1987 36.00 or latest revision.the technical specification for earthing is mentioned in the Technical specification book separately 23 Earthing Tapes/ Wires: laying of following size Copper and GI strip including all fixing accessories for laid inside the building with all necessary interconnections with earth station and equipments completely as per IS 3043, 1987 or latest revision.the technical specification for earthing is mentioned in the Technical specification book separately The cost shall also include the supply & installation of earthing tapes with end terminated with suitable copper lugs,copper fixing hardware's etc. 23.01 50 x 6 mm Copper Tape Mtr 200.00 23.02 25 x 3 mm Copper Tape Mtr 100.00

23.03 50 x 6 mm Hot Dip Galvanized GI strip Mtr 2400.00 23.04 25 x 6 mm Hot Dip Galvanized GI strip Mtr 200.00 23.05 25 x 3 mm Hot Dip Galvanized GI strip Mtr 3980.00 23.06 8 SWG copper wire ( DB Earthing) Mtr 500.00 23.07 Erection & Installation of 25 x 3 mm GI tape with DMC Insulator at every 0.6 mtrs interval for supports of the down conductors as per specification and drawings used for Lightning Arrester. Mtr 3070.00 23.08 Supply & Erection & Installation of 25 x 3 mm Copper tape covered with heat shrinkable PVC colored sleeves with DMC Insulator at every 0.6 mtrs interval for supports of the down conductors as per specification and drawings used for special earthing.the cost shall also include the supply & installation of heat shrinkable PVC colored sleeves. end terminated with suitable copper lugs,copper fixing hardware's etc. Mtr 250.00 25 Point Wiring Supply, Wiring, Testing and Commissioning of Point Wiring for Light/ ceiling Fan/ exhaust fan & 6A independent socket with 2 runs of 2.5 Sqmm + 1 run of 1.5 Sqmm FRLS PVC insulated 1100V grade multistrand copper conductor wires up to first point and 1.5 sq.mm foer subsequent points in cases of light points run in and including 25 mm dia,2mm thick MS Heavy Duty ERW conduits on wall / ceiling including all accessories such as junction boxes, conduit bends elbows and ceiling rose, with metal boxes, modular switch/socket and the box etc covered with wraparound plus front plate along with all necessary fixing accessories like mounting screws etc.the Wiring conforming shall confirm to IS 732:1982. The technical specification for point wiring is mentioned in the Technical specification book separately NOTE: The point wiring under this item shall be measured from the switch box to the light / fan / socket only in utility areas other than those with MCB controlled lights.maximum four light points should be controlled by one switch will be the criteria. 25.01 25.02 25.03 25.04 Single light / Ceiling fan / Exhaust fan / point controlled by a 6A SP Switch with surface box,, face plate, ceiling rose, with 2.5 sqmm wire & 1.5 sq.mm wire for earth & 25 mm heavy duty ERW MS Conduit. Added light point controlled by a existing light point with 1.5 sqmm wire & heavy duty ERW MS Conduit. Two way light point controlled by a 6A TW switch with surface box,, face plate, ceiling rose2.5 sqmm wire & & 1.5 sq.mm wire for earth & 25 mm heavy duty ERW MS Conduit. Wall fan point with wall mounted 5A, 5 pin socket near to wall fan location and 6A single pole controlling switch located independently. 437.00 782.00 38.00 182.00

25.05 25.06 25.07 LDB to Switch Board or Switch Board to Switch Board Point Wiring With with surface box,, face plate, 2.5 Sqmm Wire & 1.5 sq.mm wire for earth & 25 mm heavy duty ERW MS Conduit. 270.00 1.6 Amps, 5-pin (250 Volts) socket with 6 Amps single pole switch with box and front plate, Metal box with Lighting Switch Board including looping of 2.5 sqmm wire. 270.00 Single light point cabling with 3C x 2.5 sqmm copper armoured cable including cable termination with double compression gland. LDB to First Light point 168.00 Added light point cabling with 3C x 2.5 sqmm copper armoured cable including cable 25.08 termination with double compression gland. Light point to Light point. 25.09 FLP Point Wiring FLP light / Fan point cabling with 3C x 2.5 sqmm copper armoured cable including FLP cable termination with gland.this will from LDB to Control Gear and from Control Gear to Lamp 26 n FLP Lighting Fixtures with Lamps Supply, Receive, Store, Installation, Testing & Commissioning of the following types of light fixture complete with ballast choke, starters,control gear, connecting wire with lamps, PF improvement capacitors for CFL Lamps etc as required. The rates includes the installation of the following types of light fixtures with all other fixing steel support accessories etc as required.the technical specification for n FLP Lighting Fixtures with Lamps is mentioned in the Technical specification book separately 336.00 118.00 26.01 26.02 26.03 26.04 26.05 NOTE: All fittings shall be with energy efficient copper ballast. All the CFL fixtures shall be provided with PF improvement condenser compulsorily. Tubes shall be of color 84 (cool day light). Also the rates quoted shall include the cost of ball & sockets as per requirements. 1X400Watts, MH, High bay Luminaries with 400 W MH lamp, Control Gear and all other fixing steel support accessories as required including 3C x 2.5 sqmm copper flexible cable from junction box to light fixture with PVC gland. 1X250 Watts, MH, High bay Luminaries with 250 W MH lamp, Control Gear and all other fixing steel support accessories as required including 3C x 2.5 sqmm copper flexible cable from junction box to light fixture with PVC gland. 1X 150 Watts, MH, High bay Luminaries with 150 W MH lamp, Control Gear and all other fixing steel support accessories as required including 3C x 2.5 sqmm copper flexible cable from Junction Box to light fixture with PVC gland. Supply, Fixing, Testing & Commissioning of the cable junction box with copper loop in loop out terminal box with IP 55 protection with necessary fixing arrangements on truss / wall / roof / supporting structure etc. 3 x 36 Watts, PL-L, Recess Mounted (2' X 2') Mirror Optic, Clean room, Luminaries with Electronic Ballast, with PL-L lamps, bottom opening, push fit type lamp holder, connector and all other fixing accessories as required 16.00 214.00 274.00 504.00 80.00

26.06 26.07 26.08 26.09 26.1 2x28 W, T5, fluorescent surface mounted fitting along with all accessories such as control gear, Reflector, power factor improvement capacitor, with T-5 lamps etc as required with all fixing accessories. 2X36W,CFL,Recess Mounted (2' X 2') Mirror Optic fitting along with all accessories such as control gear, power factor improvement capacitor, with CFL lamps etc as required with all fixing accessories. 1 x 28 W,T5, fluorescent surface mounted light fitting along with all accessories such as control gear, power factor improvement capacitor, with T5 lamps etc as required with all fixing accessories. 3X36W,CFL,Recess Mounted (2' X 2') Mirror Optic fitting along with all accessories such as control gear, power factor improvement capacitor, with CFL lamps etc as required with all fixing accessories. 1 x 11 Watts PL-5, Luminaries with lamps and all other fixing accessories as required 1 x 10 Watts, CFL Bulkhead luminaries with Lamp, Lamp holders, connectors and all 26.11 other fixing accessories as required 1 x 28 W,T5, fluorescent surface mounted light fitting along with all accessories such 26.12 as control gear, power factor improvement capacitor, with T5 lamps etc as required with all fixing accessories to be operated from Solar system LDB 27 Ceiling Fans, Wall Mounted, Pedestal Fans Supply, Erection, Testing and Commissioning of 5 Star rated ceiling fan with 300mm length down rod,double ball bearings, accessories, connecting wire and other standard accessories as required including regulator and heavy duty wall mounted air circulators fans with all necessary bracket for installation on wall, steel structure etc 209.00 292.00 110.00 302.00 39.00 12.00 114.00 27.01 1200mm Sweep, 3 blade Ceiling fan with 2 module 5 Step electronic regulator 155.00 27.02 300 mm Sweep, Wall Mounted fan. 44.00 27.03 750mm, 1 phase, 1440rpm Wall Mounted Air Circulators Fans. 96.00 27.04 750mm, 1 phase, 1440rpm Pedastal Mounted Air Circulators Fans. 28.00 28 Exhaust Fans Supply Installation, Testing and Commissioning of Exhaust fans with sheet metal blades, necessary brackets, anti corrosive epoxy painting, rubber cushions etc to be installed. 225 mm dia, 900 RPM Industrial Exhaust fan for tiolets 25.00 29 FLP Indoor Lighting Fixtures with Lamps

Supply, Installation, Testing and Commissioning of FLP Well Glass fixtures suitable for the following MH lamps, made out of Cast Aluminium alloy, toughened clear glass cemented into a blaze ring which is bolted to the body, and lamp holder with insulator mounted on a bush plate and secured with screws. The body shall be finished with epoxy Grey stove enamelled outside and white inside. The fixture shall be inclusive of all accessories including lamp and separate control gear. The fixture shall conform to IS 2148 & IS 2206 and shall be certified by CMRI Dhanbad for ZONE I / GROUP IIB.The technical specification for FLP Lighting Fixtures with Lamps is mentioned in the Technical specification book separately Supply, Installation, Testing and Commissioning of Flame Proof 250 W, MH, n- Integral High Bay Luminaries in LM6 material with toughned clear well glass along with 29.01 250 W MH lamp,separate control gear box, M.S FAN hook box and other fixing accessories including all accessories etc. Supply, Installation, Testing and Commissioning of flame proof 150 W, MH, Low bay, n integral luminaries in LM6 material with toughned clear well glass along with 29.02 150 W MH lamp, separate control gear box, M.S FAN hook box and other fixing accessories including all accessories etc. Supply, Installation, Testing and Commissioning of 2x 28 W, T-5, flame proof surface mounted type fluroscent fitting along with all accessories such as control gear,t-5 29.03 lamps, power factor improvement capacitor etc as required with all fixing accessories in LM 6 materials. Supply, Installation, Testing and Commissioning of 1x 28 W, T-5, flame proof surface mounted type fluroscent fitting along with all accessories such as control gear, T-5 29.04 lamp, power factor improvement capacitor etc as required with all fixing accessories in LM 6 materials. 30 FLP Wall Mounted Fans Supply and Fixing of 457mm sweep FLP Wall mounting fan with all other fixing accessories as required for installation of the fan. 31 Street Lighting Supply, Erection, Installation, Testing and Commissioning of hot dip Galvanized GI Single Section Octagonal poles of 9 mtr. long, earthing studs, TPN loop-in and loopout smart pack juction box with MCB & Stand terminals as per specifications with one 31.01 10A(10kA) SP MCB and 20A TPN terminals.this includes supply and erection of RCC Civil foundation & "U" Bolts & Nuts as per Civil drg. The technical specification for Street Lighting is mentioned in the Technical specification book separately 28.00 50.00 10.00 13.00 17.00 53.00 31.02 31.03 Supply, Erection, Installation, Testing and Commissioning 1.5 mtrs Single cross Arm bracket suitable to the above pole Supply, Erection, Installation, Testing and Commissioning 1.5 mtrs Double cross Arm bracket suitable to the above pole 53.00 8.00

31.04 Supply, Erection, Installation, Testing and Commissioning 150 W MH Fitting suitable for the street light with MH Lamp, Control Gear and all other fixing steel support accessories as required including 3C x 2.5 Sqmm copper flexible cable from Junction 61.00 Box to Light Fixture with PVC gland. 31.05 Supply, Erection, Installation, Testing and Commissioning 1X250 Watts, MH, integral floodlight Luminaries with 250 W MH lamp, Control Gear and all other fixing steel support accessories as required including 3C x 2.5 Sqmm copper flexible cable from 3.00 Junction Box to Light Fixture with PVC gland. 32 Telephone Cables / Jelly Filled Cables laying, Testing and Commissioning of of telephone cables armoured annealed tinned copper conductor and petroleum jelly filled with polythene outer jackets conforming to P&T specification. The method of Telephone cables shall be run in a separate trench at least 600 mm away from other power cables.this rate shall include cable end terminations using kits cable glands, cable lugs etc as required complete. The technical specification for Telephone and LAN system is mentioned in the Technical specification book separately 32.01 10 Pair Armoured annealed tinned copper conductor cable and petroleum jelly filled 0.63 mm Mtr 90.00 32.02 20 Pair Armoured annealed tinned copper conductor cable and petroleum jelly filled 0.63 mm Mtr 120.00 32.03 50 Pair Armoured annealed tinned copper conductor cable and petroleum jelly filled 0.63 mm Mtr 700.00 32.04 100 Pair Armoured annealed tinned copper conductor cable and petroleum jelly filled 0.63 mm Mtr 3000.00 32.05 Supply, Installation, Testing and Commissioning Joint Kit For the 100 pair Telephone cable weather proof type suitable to jelley filled armooured annealed tinned copper 6.00 conductor cable with minimum 1.5 km in one piece 33 Krone Connector Terminal Box 33.01 Supply and Installation of 10 pair krone connectors ordinary terminal box with including krone connectors, locking arrangements etc. 1.00 33.02 Supply and Installation of 50 pair krone connectors ordinary terminal box with including krone connectors,locking arrangements etc. 4.00 33.03 Supply and installation of 100 pair krone connectors ordinary terminal box with including krone connectors,locking arrangements etc 2.00 33.04 Supply and installation of 300 pair krone connectors MDF ordinary terminal box with including krone connectors,locking arrangements etc 1.00 34 Telephone / LAN Sockets Point Wiring : TELEPHONE Socket with Wiring :- Supply,Termination and Fixing of Information 34.02 outlet Telephone outlet (RJ11) modular type jack with including Synergy Face Plate, with level holders Including Metal box with 2Px 0.5 sqmm wire in 25mm MS Conduit 94.00 upto Krone JB. 36 Lighting Protection System :

36.01 Installation,Testing and Commissioning of Vertical Air termination with Lightning protection system 1 mtr long copper rod air terminal with base. Air Termination shall be manufactured as per NFC 17-102 and IEC-62305 Standards with including flash tester should be available for maintenance purpose. Performances of the airtermination should have been tested in High Voltage Laboratory completely as per IS 2309-1989 or latest revision The technical specification for Lighting Protection System is mentioned in the Technical specification book separately 54.00 36.02 Supply, Installation,Testing and Commissioning of bolts and other material. Earth link with suitable size of nut 40.00