Compact Emergency Light Fittings Series C-LUX 6108 / 6508

Similar documents
Compact Emergency Light Fittings Series C-LUX 6108 / 6508

7 Lighting Technology

Zone 1 and Zone 2. Lighting Technology. Compact Emergency Light Fittings Series C-LUX 6108

Emergency Light Fittings for Fluorescent Lamps Series ECOLUX 6608

Compact Sheet-Steel Light Fittings Series 6114

Sheet Steel Emergency Light Fitting Series 6018

7 Lighting Technology

Emergency Light Fitting for Fluorescent Lamps Series EXLUX 6008 / 6408

Zone 1 and Zone 2. Lighting Technology. Emergency Light Fittings Series EXLUX 6008

Emergency Light Fitting for Fluorescent Lamps Series ECOLUX 6608 Economy

7 Lighting Technology

Light Fitting for Fluorescent Lamps Series ECOLUX 6600

Emergency Light Fitting for Fluorescent Lamps Series 6009

Compact Sheet-steel Emergency Light Fitting Series 6118/1

7 Lighting Technology

Linear Luminaire for Fluorescent Lamps Series EXLUX 6401

Linear Luminaire for Fluorescent Lamps Series ECOLUX 6600

Light Fitting for Fluorescent Lamps Series ECOLUX 6600

Light Fittings for Fluorescent Lamps Series EXLUX 6000 / 6400

Sheet-Steel Light Fittings Series 6014 / 6414

Linear Luminaire for Fluorescent Lamps Series ECOLUX METAL 6010/1

Compact Sheet-Steel Light Fittings Series 6114/1

Linear Luminaire for Fluorescent Lamps Series EXLUX 6001

Linear luminaire with LED Series EXLUX 6002

Linear Luminaire with LED Series EXLUX 6402/2

LED Linear Luminaire Series EXLUX 6402

Linear Luminaire with LED Series EXLUX 6002

Emergency Luminaire with LED Series EXLUX 6009/1 Version IIC

Emergency Luminaire with LED Series EXLUX 6409/1

Linear Luminaire with LED Series EXLUX 6002/2 Version IIC

Portable Lamps Series HS6145, HSL145

Plugs and Sockets SolConeX & CES Series 7570, 7571, 7575, 7579, 7581

Plug and Socket Devices SolConeX 16 A Series 8570

Ex UPS standard Series 8265

Plugs and Sockets SolConeX & CES Series 8570, 8571, 8575, 8581

Terminal Boxes Series 8125

Plugs and Sockets SolConeX & CES Series 8570, 8571, 8575, 8581

Safety Switches Series 8537

Plugs and Sockets SolConeX & CES Series 8570, 8571, 8575, 8581

Terminal Boxes Series 8125

Floodlight LED Series 6525

Floodlight LED Series 6125

Tank Inspection Lights Series 6122

Plugs and Sockets SolConeX & CES Series 8570, 8571, 8575, 8579, 8581

Floodlight LED Series 6525

Easy and safe installation

2.4. Ex-Emergency light fittings with a self-contained battery system for fluorescent lamps

Load disconnect switch Series 8146/5-V11

10 Load and Motor Switchgear

Lighting: Fluorescent Lighting RE Series: Recessed Fluorescent Lighting Fixtures, Standard and Emergency Back-Up Increased Safety

Control Equipment. ATHEX bvba Tel: +32 (0) Fax: +32 (0) Alpenroosbaan 2, 2900 Schoten, België

Floodlight Series 6521/4

7 Lighting Technology

Floodlight Series 6121

ATX FE Series Nonmetallic Fluorescent Luminaires Standard and Emergency Battery Back-Up. Increased Safety

EX-REPAIR AND MAINTENANCE RECEPTACLES

Battery Boxes Series 8316

110/127 V - 220/240 V BI-PIN HEAVY DUTY LUMINAIRES FOR ARMOURED OR NON-ARMOURED CABLE Fluo 2 x 36 W

FE Series Nonmetallic Fluorescent Luminaires Standard and Emergency Battery Back-Up. Increased Safety

Control Buttons / Switches for Panel Mounting Series 8003

Linear fittings EVS fluorescent fitting with easy disconnect - zones 1, 2, 21 & 22

Load and Motor Switches, Load-Break Switches Series 8544

Position Switches Series 8074/2

AVN. - Zone 2, 21, 22 - Lower maintenance costs - Easy to install - Suited to ambient temperatures of up to +55 C. Ex n. Stainless steel clips

J: Emergency lighting (optional) L: pole type X: ceiling type Mounting

Tubular fittings Tubular fluorescent fitting with automatic switch off XFP - Zones 1, 2 & 21, 22

Leading the way in hazardous areas Features EATON

Wellglass fittings EVH, EVX Wellglass fitting all zones - zones 1, 2, 21 & 22

Load and Motor Switches, Load-Break Switches Series 8544

Schaltgeräte GmbH GmbH Geschäftsbereich Leuchten

Control switch/load disconnect switch Series 8008

Fluorescent Lighting FE Series: Nonmetallic Fluorescent Lighting Fixtures, Standard and Emergency Battery Back-Up Increased Safety

1/122 Sales: Malux Finland Oy, P.O.Box 69, FI Porvoo, Phone , Fax ,

Position Switches Series 8060/2

ATX FN Series Heavy Duty Nonmetallic Fluorescent Luminaires Standard and Emergency Back-Up. Zone 2-21 and 22

Emergency Light Fittings

2.15. Ex-Linear luminaires for T5 HE fluorescent lamps. nllk W - 35 W (Zone 2 and 22)

FE Series Nonmetallic Fluorescent Luminaires Standard and Emergency Battery Back-Up. Increased Safety

Position Switches Series 8070/2

Linear Luminaire for Fluorescent Lamps

E II 3 (1) G Ex na [ia Ga] IIC/IIB T4 Gc

Linear fluorescent luminaire LED V-CG-S

Control Device System NEC Series ConSig 8040

4.6. Ex-Floodlights for high-pressure discharge lamps, series FZD 04 / FZD EN. (Zone 1, 2, 21, 22)

Linear fittings Fluorescent fitting EVN - Zones 2 & 22

Load and Motor Switches, Load-Break Switches Series 8549

Tubular fittings Tubular fluorescent fitting XFF - Zones 1, 2 & 21, 22

2.2. Ex-Linear LED light fittings. ellk/m 92 LED 400/800 / ellk/m 92 LED 400/800 V-CG-S / NE / NIB-HT / NIB-CSA (Zone 1, 2, 21, 22)

L: pole type. X: ceiling type. Lamp number Lamp wattage(w) Explosion-proof light fittings for fluorescent lamp BAY51-18 x 1L

Installation Accessories

9 Control Equipment. Control Unit System Series ConSig 8040

EXENC-L. - Zone 2, Zone Low installation costs - Locking system operated by hexagonal-head tool - High quality electrical components

CEAG Products Main Catalogue Part 1 Chapter 3. Emergency and safety light fittings. EATON 1.3.1

I Ex-safety switches I

Control Buttons Series 8082

Operating Instructions

International approvals.

4.7. Ex-Floodlights for high-pressure discharge lamps, series FZD 04 (Zone 1, 2, 21, 22)

Linear fittings EVN Fluorescent fitting - zones 2 & 22

2.2. Ex-Linear LED light fittings. ellk/m 92 LED 400/800 / ellk/m 92 LED 400/800 V-CG-S / NE / NE-HT / NIB-HT / NIB-CSA (Zone 1, 2, 21, 22)

Transcription:

> Operating modes non-maintained operation non-maintained operation with switchable emergency light blocking > With continous operating test > For fluorescent lamps 8 W, d 16 mm, for two-pin holder G5 > Suitable for wall and ceiling mounting > Can be fitted to order with emergency exit signs > Central locking www.stahl.de 01907E00 Series C-LUX 6108 and 6508 compact emergency lighting fitting can be used for safety illumination, but also as information or emergency exit sign lights. ATEX Zone 0 1 2 20 21 22 6108: For use in x x x x 6508: For use in x x x WebCode 6108A Lighting /1

Selection Table Version Lamps Emergency light duration test C-LUX 6108 for Zones 1, 2, 21, 22 C-LUX 6508 for Zones 2, 21, 22 Battery capacity Emergency light operation time Order number Weight Ah h kg 1 x 8 W with 2.5 1.5 6108/1081-8017-74-00 3.700 1 x 8 W with 2.5 1.5 6508/1081-8017-74-00 3.900 Order Number Supplement Cable entries Standard: 1 x Cable gland M25 x 1.5 2 x Plugs M25 x 1.5 Special: Specify non-standard entries in writing needed only when used as information lights or escape sign lights; With adhesive symbols positioned as follows: Mounting position Standard 6108/...-..1.-..-.. 6108/...-..9.-..-.. Special please specify other positions in writing Please specify emergency exit sign number (see below) Symbol complying with VGB 125, DIN 4844, DIN 5035; recognition distance e = 30 m; size 150 x 355 mm 08481E00 6108/...-...-..-60 08483E00 6108/...-...-..-61 08482E00 6108/...-...-..-62 08484E00 6108/...-...-..-87 03018E00 6108/...-...-..-91 08485E00 6108/...-...-..-71 03206E00 6108/...-...-..-81 12617E00 /2 Lighting

Order Number Supplement 6108/...-...-..-92 08486E00 09020E00 6108/...-...-..-72 6108/...-...-..-82 12618E00 6108/...-...-..-90 08487E00 6108/...-...-..-70 03203E00 12616E00 6108/...-...-..-80 08488E00 6108/...-...-..-93 6108/...-...-..-73 12615E00 6108/...-...-..-83 Note 12619E00 The light fittings are supplied without tubes and mounting material. These accessories must be orde separately. Explosion Protection Marking Version 6108 (Zones 1, 2, 21, 22) 6508 (Zones 2, 21, 22) Europe (ATEX) Gas E II 2 G EEx edm IIC T4 E II 3 G Ex na II T4 (Zone 2) explosion protection Dust explosion E II 2 D IP66 T75 C E II 2 D IP66 T75 C protection Certificates Version 6108 (Zones 1, 2, 21, 22) 6508 (Zones 2, 21, 22) Europe (ATEX) Gas PTB 97 ATEX 2161 ASEV 99.1 10381.01 explosion protection Dust explosion LCIE 02 ATEX 6239 SEV 05 ATEX 0125 protection Other certificates Kazakhstan (JSC) Marking C 0158 C 0158 Lighting /3

Technical Data Electrical data Version 6108 (Zones 1, 2, 21, 22) 6508 (Zones 2, 21, 22) Nominal voltage AC: 220... 254 V, 50... 60 Hz AC: 110... 127 V, 50... 60 Hz possible on request AC: 220... 254 V, 50... 60 Hz AC: 110... 127 V, 50... 60 Hz possible on request Rated current 0.15 A 0.15 A Ballast Electronic ballast, single channel with integral Electronic ballast, single channel with integral emergency light electronics emergency light electronics Disconnection of light fitting on opening Faulty lamp Light technical data Lamps Light guides Operating modes Central locking device with safety interlock; switch 8080 with N/C contacts; when central lock is opened, voltage to ballast is disconnected on both poles; a safety interlock in switching mechanism prevents fitting from being reconnected while cover and central lock are open. If lamp is faulty power supply is automatically switched off by electronic ballast No switching-off when opening light fitting If lamp is faulty power supply is automatically switched off by electronic ballast 1 x 8 W; two-pin fluorescent lamps, 8 W, d 16 mm, for G5 holder Reflector painted ; Cover with prism structure, providing directed light from the fitting Mains operation for general lighting or as information lights; Emergency operation: fed from battery-set built into emergency lighting fitting when used for escape route illumination or as emergency exit sign lighting. Ambient conditions Charging - 5... + 50 C Normal mode - 20... + 50 C Mechanical data Degree of protection IP66 (IP64 with Breathing gland 8162) Protection class I (with internal PE connection terminal) Material Enclosure glass fibre reinforced polyester resin; colour:, similar to RAL 9010 Cover Polycarbonate Sealing gasket Polyurethane; foamed into cover Cover options Central locking using socket spanner M8 / SW 13; cover hinged for access central lock cover hinge Assembly / Installation Cable entry Standard Grafik 1 cable entry 8161 in plastic M25 x 1.5 and 2 plugs 8290 in plastic, M25 x 1.5 (enclosed) 08478E02 Special Connection Terminal block Marking Terminal size Installation notes Looping through of cables Other entries in moulded plastic or metal are available to order, details available on request in Polyamide with terminal cover L, L, N, PE 2 x 4 mm 2 for solid cores 2 x 2.5 mm 2 for flexible cores 2 leads can be connected to each terminal on the input side, making fittings suitable for looped connection. 08479E02 Mounting Can be wall- or ceiling-mounted 08480E00 /4 Lighting

Technical Data Emergency light electronics Construction Incorporated in one housing with electronic ballast unit Operating options Emergency lighting electronics are available: with automatic emergency light duration test; in maintained operation or maintained operation with switchable emergency lighting blocking. Self-test function The emergency light fitting is available with self-test function. The built-in self-test functions are activated as soon as light is connected to mains and automatically repeated after pre-set time has elapsed. Operating test Weekly test of emergency light function; battery and lamp faults are recognized and indicated via LED. Emergency light duration test Testing of battery capacity at intervalls of 6 months; operating of fitting in emergency light mode for 2.3rd of rated operating time. If the fitting is switches off by the discharge protection before time has elapsed. Battery cannot be used longer for emergency operation. Fault is indicated via LED. Function indicators 1 LED and 1 LED, incorporated in reflector; can be seen from outside throught cover LED Indication Function Green On Light fitting okay; charging current is supplied Blinking Light fitting okay; function test or continous on test is running Red On Battery error; not connection to the battery or battery completely discharged Blinking Battery error; battery has not enough capacity Flashing 1:10 Lamp error; lamp is out of order or lamp is end of life Green / Blinking Emergency light function is jam by external Red switch Blinking 1 s ON 1 s OFF Flashing 0.25 s ON 1.75 s OFF Battery charging intelligent battery management system, microprocessor-based (on-load time of max. 14 h) deep-discharging protection to the avoidance of cell pol reversal Emergency light duration Battery capacity 2.5 Ah Emergency light operation time 1.5 h Operation modes On delivery light fitting is wi for maintained operation; by removing the jumper between terminals 9 and 10 and connecting external switch F, the fitting is converted to maintained operation with switchable emergency lighting. Terminals emergency lighting electronics Jumper Maintained operation 08711E02 External switch F Terminals emergency lighting electronics Maintained operation with switchable emergency lighting 08712E02 Functions Maintained operation On failure of supply to general lighting, fitting is supplied from the battery, irrespective of the light switch position Maintained operation with switchable emergency lighting On failure of power supply to general lighting, fitting switches to emergency lighting operation only if external switch F is closed. To switch emergency lighting centrally to Ready or Not ready, e. g. depending on plant operation times. The external switch has a potential-free NO contact. Changeover voltage Light power during emergency light operation Battery set Type Operating voltage Capacity Charging battery set Note: - line wiring max. 30 emergency light fittings for 1 external switch; - point to point wiring 50 emergency light fittings for 1 external switch - length of cable max. 500 m with wire 1.5 mm 2 from mains to battery operation at U < 0.74 x U N from battery to mains operation at U > 0.80 x U N 1.5 h / 70 % 3.0 h / 30 % NICd battery, gas tight, built into light fitting 6 V 2.5 Ah When the central lock is opened the battery set is de-energized; it can be removed from the housing by unplugging its removable contact. Lighting /5

Technical Data s Use Material Recognition distance Mounting Options for information and escape sign fittings Foil, self-adhesive, printed with various pictograms in different colours e = 30 m Foil is stuck to cover externally The various types of adhesive foil which can be supplied are detailed in table "Accessories and Spare Parts" Accessories and Spare Parts Designation Illustration Description Order number Weight kg Fluorescent lamps 8 W, d 16 mm, for two-pin G5 holder 04936E00 Colour of Light flux light cool 450 Im 10 pcs 119045 0.415 Socket spanner M8 / SW 13; to operate central locking 140486 0.126 Adapter plate 05321E00 for use with metal cable glands which are integrated into the earthing system via the stainless steel adapter plates 2 x M20 x 1.5 1 pc 115826 0.060 05755E00 2 x M25 x 1.5 1 pc 1 pc 115828 0.060 113182 0.015 08483E00 1 pc 113183 0.015 08482E00 1 pc 113184 0.015 08484E00 1 pc 113206 0.015 03018E00 1 pc 113210 0.015 08485E00 1 pc 113193 0.015 03206E00 1 pc 113200 0.015 12617E00 1 pc 113211 0.015 08486E00 1 pc 113194 0.015 09020E00 1 pc 113201 0.015 12618E00 1 pc 113209 0.015 08487E00 /6 Lighting

Accessories and Spare Parts Designation Illustration Description Order number Weight kg 1 pc 113192 0.015 03203E00 12616E00 1 pc 1 pc 113199 0.015 113212 0.015 08488E00 1 pc 113195 0.015 12615E00 1 pc 113202 0.015 Diffuser 12619E00 for light fitting 8 W 119044 0.250 05704E00 Dimensional Drawings (All Dimensions in mm) - Subject to Alterations 181 a 4 9 R3,5 425 11 445 7 Additional dimensions for cable entries 8161 and plugs 8290 a (mm) 8161 M25 x 1.5 32 8290 M25 x 1.5 6 119 150 355 04293E00 We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be conside binding. 04295E00 Lighting /7