Galaxy VM 160kVA 1+1 Module UPS with Modular Battery Cabinets Solution Drawing Guide Sheet No. Component /Detail Description 1 Draw ing Guide Galaxy VM 160kVA 1+1 Module UPS w ith Modular Battery Cabinet Solution Draw ing Guide 2-3 Solution Isometric & Runtime Chart Galaxy VM 160kVA 1+1 Module UPS w ith Modular Battery Cabinets Solution Isometric & Runtime Chart 4 Solution General Arrangement Galaxy VM 160kVA 1+1 Module UPS w ith Modular Battery Cabinets Solution General Arrangement 5 Solution Rear View Galaxy VM 160kVA 1+1 Module UPS w ith Modular Battery Cabinets Solution Rear View 6 Solution Top & Bottom View s Galaxy VM 160kVA 1+1 Module UPS w ith Modular Battery Cabinets Solution Top & Bottom View s 7 Solution Anchoring Details Galaxy VM 160kVA 1+1 Module UPS w ith Modular Battery Cabinets Solution Anchoring Details 8-10 UPS (Single) Internal view s & Details Galaxy VM 160kVA 1+1 Module UPS w ith Modular Battery Cabinets Solution-Single UPS Internal View s & Details 11-13 UPS (Parallel) Internal view s & Details Galaxy VM 160kVA 1+1 Module UPS w ith Modular Battery Cabinets Solution-Parallel UPS Internal View s & Details 14-15 UPS Communication boards Galaxy VM 160kVA 1+1 Module UPS w ith Modular Battery Cabinets Solution -Single/Parallel UPS Communication Boards 16-17 Modular Battery Cabinet (Wide) Galaxy VM 160kVA 1+1 Module UPS w ith Modular Battery Cabinets Solution-Modular Battery Cabinet Details (Wide) 18-19 Modular Battery Cabinet (Narrow ) Galaxy VM 160kVA 1+1 Module UPS w ith Modular Battery Cabinets Solution-Modular Battery Cabinet Details (Narrow ) 20-21 System One Line Diagrams Galaxy VM 160kVA 1+1 Module UPS w ith Modular Battery Cabinets Solution System One Line Diagrams 22 Electrical Specifications Galaxy VM 160kVA 1+1 Module UPS w ith Modular Battery Cabinets Solution System Electrical Specifications
Runtime in Minutes Number of Battery Catridges (GVMMBTU) Quantity and Type of Cabinet 6.7min 10 1W 7.8min 11 1W 8.8min 12 1W 9.9min 13 1W+1N 11min 14 1W+1N 12min 15 1W+1N 13min 16 1W+1N 14.5min 17 1W+1N 15.5min 18 1W+1N 22.5min 24 2W 30min 30 2W+1N 38min 36 3W 46min 42 3W+1N 54min 48 4W 62.5min 54 4W+1N 71min 60 5W 79.5min 66 5W+1N 88.5min 72 6W 97.5min 78 6W+1N 105min 84 7W 115min 90 7W+1N 125min 96 8W LEGEND 1N = 1 Narrow Battery Cabinet : SKU no. GVMMODBCNS 1W = 1 Wide Battery Cabinet : SKU no. GVMMODBCWS
Floor Loading Data SKU # Dimensions HxWxD in mm [Inches] Weight in Floor Loading kg [lb] in kg/m 2 [lb/ft 2 ] 0G-GVMPB160K180D (Power Cabinet-1/2) 1970x600x854 [77.56x23.62x33.62] 469 [1032] 917 [188] 0G-GVMI200KH (I/O Cabinet-1) 1970x450x854 [77.56x17.71x33.62] 230 [506] 598 [122] GVMSB160KHS (UPS-1) 1970x1052x854 [77.56x41.42x33.62] 699 [1538] 778 [159] 0G-GVMIP200KH (I/O Cabinet-2) 1970x450x854 [77.56x17.71x33.62] 230 [506] 598 [122] GVMPB160KHS (UPS-2) 1970x1052x854 [77.56x41.42x33.62] 699 [1538] 778 [159] GVMMODBCW (Wide Battery Cabinet-without Batteries) 1970x700x854 [77.56x27.56x33.62] 210 [462] 355 [73] GVMMODBCN (Narrow Battery Cabinet-without Batteries) 1970x370x854 [77.56x14.57x33.62] 139 [306] 443 [91] GVMMODBCWS+12 GVMMBTU 1970x700x854 [77.56x27.56x33.62] 1650 [3630] 2755[564] GVMMODBCNS+2 GVMMBTU 1970x370x854 [77.56x14.57x33.62] 379 [834] 1199 [245] CENTER OF GRAVITY Cabinet Center of Gravity in mm [Inches] X-Distance Y-Distance Z-Distance Power Cabinet 300 [11.81] 950 [37.40] 379 [14.92] I/O Cabinet 200 [7.87] 800 [31.49] 300 [11.81] Battery Cabinet(Wide) 350 [13.78] 1000 [39.37] 400 [15.75] Battery Cabinet(Narrow) 185 [7.28] 1000 [39.37] 400 [15.75]
UPS RATING / POWER FACTOR INPUT VOLTAGE / BYPASS VOLTAGE 380V 400V 415V OUTPUT VOLTAGE 380V 400V 415V INPUT FREQUENCY / WIRING BYPASS FREQUENCY / WIRING UPS INPUT NOMINAL INPUT CURRENT (A) 230 219 211 MAXIMUM INPUT CURRENT (A) 278 262 253 INPUT CURRENT LIMITATION (A) 278 UPS BYPASS NOMINAL CURRENT (A) 243 231 223 OUTPUT FREQUENCY / WIRING ELECTRICAL DATA SHEET-DUAL MAINS 160kVA / 0.9 40-70HZ / WIRING : 3 PH, 3 WIRE -3PH+PE 50/60HZ / WIRING : 3 PH, 3 WIRE -3PH+PE, 4WIRE- 3PH+N+PE 50/60HZ / WIRING : 3 PH, 3 WIRE -3PH+PE, 4WIRE- 3PH+N+PE UPS RATING / POWER FACTOR INPUT VOLTAGE 380V 400V 415V OUTPUT VOLTAGE 380V 400V 415V INPUT FREQUENCY / WIRING UPS INPUT NOMINAL INPUT CURRENT (A) 230 219 211 MAXIMUM INPUT CURRENT (A) 278 262 253 INPUT CURRENT LIMITATION (A) OUTPUT FREQUENCY / WIRING NOMINAL OUTPUT CURRENT (FULL LOAD) (A) 243 231 223 NOMINAL BATTERY VOLTAGE (VDC) ELECTRICAL DATA SHEET-SINGLE MAINS 160kVA / 0.9 40-70HZ / WIRING : 3 PH, 3 WIRE -3PH+PE 4WIRE- 3PH+N+PE 278 50/60HZ / WIRING : 3PH, 3 WIRE -3PH+PE, 4WIRE- 3PH+N+PE 480 NOMINAL OUTPUT CURRENT (FULL LOAD) (A) 243 231 223 NOMINAL BATTERY VOLTAGE (VDC) END OF DISCHARGE VOLTAGE (FULL LOAD) (VDC) 480 384 BATTERY CURRENT AT FULL LOAD AND NOMINAL BATTERY VOLTAGE (A) BATTERY CURRENT AT FULL LOAD AND MINIMUM BATTERY VOLTAGE (A) THDI THDV MAXIMUM SHORT CIRCUIT WITHSTAND REQUIRED UPSTREAM INPUT BREAKER/RATING/SETTING REQUIRED UPSTREAM BYPASS BREAKERS/RATING/SETTING RECOMMENDED INPUT CABLE SIZE FOR INSTALLATION METHODS B1 / B2 / C -Sqmm RECOMMENDED BYPASS CABLE SIZE FOR INSTALLATION METHODS B1 / B2 / C -Sqmm RECOMMENDED OUTPUT CABLE SIZE FOR INSTALLATION METHODS B1 / B2 / C -Sqmm HEAT DISSIPATION -NORMAL OPERATION in kw [BTU/hr] HEAT DISSIPATION -ECO MODE in kw [BTU/hr] 314 393 < 3%@ 100% LOAD, <4% @ 50% LOAD, <6% @ 25% LOAD < 2%@ 100% LINEAR LOAD, < 3%@ 100% NON-LINEAR LOAD 65kA @ REQUIRED BREAKER SIZE NSX400H Mic2.3 / 400A / Io-280A, Ir(X lo)-1, Isd(X lr)-1.5-10 NSX400H Mic2.3 / 400A / Io-250A, Ir(X lo)-1, Isd(X lr)-8 (2) 70 / (2) 95 / (2) 50 (2) 70 / (2) 70 / (1) 95 (2) 70 / (2) 70 / (1) 95 5.76 [19650] 1.44 [4910] END OF DISCHARGE VOLTAGE (FULL LOAD) (VDC) BATTERY CURRENT AT FULL LOAD AND NOMINAL BATTERY VOLTAGE (A) BATTERY CURRENT AT FULL LOAD AND MINIMUM BATTERY VOLTAGE (A) THDI THDV MAXIMUM SHORT CIRCUIT WITHSTAND REQUIRED UPSTREAM INPUT BREAKER/RATING/SETTING RECOMMENDED INPUT CABLE SIZE FOR INSTALLATION METHODS B1 / B2 / C -Sqmm RECOMMENDED OUTPUT CABLE SIZE FOR INSTALLATION METHODS B1 / B2 / C -Sqmm HEAT DISSIPATION-NORMAL OPERATION in kw [BTU/hr] HEAT DISSIPATION-ECO MODE in kw [BTU/hr] 384 314 393 < 3%@ 100% LOAD, <4% @ 50% LOAD, <6% @ 25% LOAD < 2%@ 100% LINEAR LOAD, < 3%@ 100% NON-LINEAR LOAD 65kA @ REQUIRED BREAKER SIZE NSX400H Mic2.3 / 400A / Io-280A, Ir(X lo)-1, Isd(X lr)-7 (2) 70 / (2) 95 / (2) 50 (2) 70 / (2) 70 / (1) 95 5.76 [19650] 1.44 [4910]