www. ElectricalPartManuals. com Digitrip RMS Trip Units Used with Type SPB Systems Pow-R Breakers Page

Similar documents
Master Connection Diagram Series C R-Frame Circuit Breaker with DIGITRIP RMS Trip Units

www. ElectricalPartManuals. com Instructions for Digitrip RMS 600 Trip Unit I.L A

www. ElectricalPartManuals. com Instructions for Digitrip RMS 500 Trip Unit I.L A Page

Digitrip RMS and Digitrip OPTIM Trip Units Used with R-Frame Circuit Breakers

www. ElectricalPartManuals. com Instructions for Digitrip RMS 700 Trip Unit

Instructions for The Digitrip RMS Pole and 4-Pole Trip Unit Installation and Operation with K-Frame Series C Circuit Breakers

Eaton Digitrip RMS and Digitrip OPTIM Trip Units with Types DSII and DSLII Low Voltage Power Circuit Breakers

Instructions for Field Testing of Systems Pow-R Breakers. l.l File www. ElectricalPartManuals. com. Effective June, 1979

Instructions for Digitrip RMS 510 Trip Unit. Page. 1.1 Protection Information UL Listed Devices Test Procedure...

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Individual breakers in separate enclosures can be applied in low voltage distribution systems through 600 volts Ac, 50/60 Hertz.

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

Modular Metering - Trip Unit for >1200A Mains DEH41187 Application Guide

Advanced Test Equipment Rentals ATEC (2832)

Instructions for Digitrip Models 220, 520, 520i, 520M, and 520Mi Trip Units for use only in Cutler-Hammer Magnum and Magnum DS Circuit Breakers

Q and M-Frame Circuit Breaker Instruction Leaflet for Installation and Operation for Thermal Magnetic Trip Units

INSTRUCTIONS. seconds. the tween the end of the bearing screw and the. top of the shaft. The moving contact is a small silver hemisphere

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

SIEMENS. Microprocessor-Based Tripping System. Static lrip III. www. ElectricalPartManuals. com

www. ElectricalPartManuals. com Instructions for Ground Fault Protection Systems INTRODUCTION SENSOR Fig. 1 Cu"ent Monitor

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

www. ElectricalPartManuals. com ltciil Cutler-Hammer A WARNING

www. ElectricalPartManuals. com INSTRUCTIONS PNEUMATIC TIMING RELAYS DESCRIPTION MAINTENANCE OPERATION Type AM With or without Auxiliary Switch Units

www. ElectricalPartManuals. com Master Connection Diagram for the Systems Pow-R Breaker All Frame Ratings Westinghouse Electric COrporation Beaver, PA

ELECTRIC SERVICE REQUIREMENTS FOR MEDIUM-SIZED COMMERCIAL INTERCONNECTED DISTRIBUTED GENERATION SOURCES

Magnum IEC Air Circuit Breakers and Drawout Cassette Engineering Data

A. Submit manufacturer's literature and technical data before starting work.

POWER BREAK Circuit Breakers

Instructions for Digitrip Models 1150 and 1150i Trip Units for use only in Cutler-Hammer Magnum and Magnum DS Circuit Breakers

www. ElectricalPartManuals. com !tell Cutler-Hammer I.L A WARNING Instructions for Digitrip RMS 510 Trip Unit

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units

White Paper. Ground Fault Application Guide. WL Low Voltage Power Circuit Breakers

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

Electropneumatic Timing Relays Series 7000 Industrial

I.L. 29C184A File WARNING

I.L. 29C121A WARNING 1. INTRODUCTION. Maximum Freq. Maximum Dielectric Voltage Current Withstand (V) (A) Voltage (V)

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

Electrical devices may only be mounted and connected by electrically skilled persons.

Critical Power Switchboards. Selection and Application Guide

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

Cutler-Hammer. Installation Instructions for the ND OPTIM 550 PowerNet and/or Zone Interlock Accessories (ICK 550N, ZGK550N, ZGPK550N) I.L.

SpaceStation TM. Installation Instructions SpaceStation Occupancy Lighting Control System. Please Save These Instructions

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

www. ElectricalPartManuals. com Systems Pow-R Breaker Transfer Switches Technical Data Page 1

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Instructions for A200, A210, A250 size 6, two- or three-pole non-reversing or reversing motor controllers

Moulded case circuit breakers

SURE TRIP RETRO KITS

IN2 Enclosed Switches and Circuit Breakers

Guide for Primary Injection Testing WL Circuit Breakers. Document No. : 11-C

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

Instructions for Digitrip Models 520V and 520MCV for use only in Cutler-Hammer Type VCP-T, VCP-TR and T-VAC, T-VACR Circuit Breakers

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

Type SOQ Negative Sequence Time Overcurrent Relay

AP/UP, AP/MIL Series Magnetic Circuit Protectors

Table of Contents. For latest version, visit:

Single Pole Circuit Protectors 55. Multi-Pole Circuit Protectors 56. Configurations 58. Operating Characteristics 59.

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

www. ElectricalPartManuals. com INSTRUCTIONS TYPE CO CONTACT MAKING AMMETER INSTALLATION OPERATION MAINTENANCE I.. L APPLICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

1.15 Instrument Cluster (IC) Contents

a WARNING Allen-Bradley Parts K-Frame Circuit Breaker Instruction Leaflet for Alarm Switch and Alarm /Auxiliary Switch Combination Bul.

N-frame Circuit Breaker

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII

Installation Instructions for NW, HNW, and NWC Circuit Breakers and N-frame Series C Molded Case Switches

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

General Description. Construction

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

SURE-TRIP OEM RELACEMENT TRIP UNIT

Instruction Bulletin. Enclosed ALTISTART 46 Controller Supplemental Instruction Bulletin Class 8638 and 8639 INTRODUCTION

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

Q and M-Frame Circuit Breakers Instruciton Leaflet for Alarm Switch and Auxiliary Switch Combinaiton

Low Voltage Power Circuit Breakers

Horizontal Circuit Switchers

GENSET CONTROL MODULE A121A / A241A

Cutler-Hammer. Installation Instructions for Undervoltage Release Mechanism (Handle Reset) with LED for E 2 L and E 2 LM Mining Circuit Breakers

www. ElectricalPartManuals. com Operator's Manual Onon OT III Transfer Switch 40 to 10iOO Ampere's Ut.i I ity-to-uliuty

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

MAGNETIC MOTOR STARTERS

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

with Electronic Trip Units

File E47705 Vol. 7 Sec. 9 Page 1 Issued: and Report Revised:

2.2. Molded Case Circuit Breakers. Contents. NG-Frame ( Amperes) Series G

GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM. Special logic to re-establish cranking following a false start.

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

INSTRUCTION MANUAL HIGH-VOLTAGE VACUUM CONTACTORS MOTOR& TRANSFORMER APPLICATION. May, 2001 TOSHIBA CORPORATION SOCIAL INFRASTRUCTURE SYSTEM COMPANY

molded case circuit breakers A www. ElectricalPartManuals. com mastering electrical power MERLIN GERIN

Cutler-Hammer I.L. 29C160G WARNING NOTICE 1-0 INTRODUCTION. General Information

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

SIEMENS-ALLIS. Medium Voltage. Metalclad Switchgear. www. ElectricalPartManuals. com

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

Transcription:

Digitrip RMS Trip Units Used with Type SPB Systems Pow-R Breakers Table of Contents. 2. 3. 4. 4. 4.2 4.3 4.4 4.5 5. 5. 5.2 5.3 5.4 5.4. 5.4.2 5.4.3 5.4.4 5.4.5 5.5 5.6 5.6. 5.6.2 5.6.3 5. 5. 6....2.3 Supplementary nformation........... Digitrip RMS Trip Units...................... Rating Plugs................ Digitrip RMS Model Considerations............ Digitrip RMS 5................. Digitrip RMS 6....................... Digitrip RMS............... Digitrip RMS.................. Reset Operation..................... Principle of Operation....... General........................ Digitrip RMS Trip Assembly......... Low Energy Shunt Trip............ Ground Fault Protection................. General.............. Residual Sensing.......................... Ground Return Sensing............ Zero Sequence Sensing.................. Ground Fault Settings........... Current Sensors.................. Digitrip RMS Accessories............. Power/Relay Module.......... Potential Transformer Module...... Dielectric Testing........... Connection Diagram.................. Trip Unit Settings Protection...... Time Current Curves.......... References............. Type SPB Systems Pow-R Breakers........ Digitrip RMS Trip Units........... Miscellaneous.......... WARNNG DO NOT ATTEMPT TO NSTALL OR PERFORM MAN TENANCE ON EQUPMENT WHLE T S ENERGZED. DEATH OR SEVERE PERSONAL NJURY CAN RESULT FROM CONTACT WTH ENERGZED EQUPMENT. ALWAYS VERFY THAT NO VOLTAGE S PRESENT BEFORE PROCEEDNG WTH THE TASK, AND ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY PROCEDURES. THE WESTNGHOUSE ELECTRC CORPORATON S NOT LABLE FOR THE MSAPPLCATON OR MSN STALLATON OF TS PRODUCTS. Page The user is cautioned to observe all recommendations, wa rnings and cautions relating to the safety of personnel and equipment, as well as all general and local health and safety laws, codes, and procedures. The recommendations and information contained herein are based on Westinghouse experience and judgement, but should not be considered to be all inclusive or covering every application or circumstance which may arise. f any questions arise, contact Westinghouse Electric Corporation for further information or instructions. 2 2 2 3 3 4 5 5 5 6 6 4 4 4 4 Effective October, Supersedes.L. 2-55 dated May, Rating Plug Fig. View of SPB Circuit Breaker Shown with Digitrip RMS BOO Trip Unit nstalled. Supplementary nformation.l. 2-55-A The instructions contained in this book supplement the instructions for type SPB Systems Pow-R Breakers covered in.l. 2- (.B. 52). 2. Digitrip RMS Trip Units This instruction book specifically covers the application of Digitrip RMS Trip Units installed in type SPB Systems Pow-R Breakers as illustrated in Fig.. Digitrip RMS Trip Units are AC devices that employ microprocessor based technology that provides true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. The primary function of the Digitrip RMS Trip Unit is circuit protection. This is achieved by analyzing the secondary current signals received from the circuit breaker current sensors and initiating trip signals to the circuit breaker shunt trip when pre-set current levels and time delay settings are exceeded. n addition to the basic protection function, all Digitrip RMS Trip Unit models provide mode of trip information and integra l test provisions.

2 --'-;::====t---- Digitrip RMS 6 Protection.C...--- Function Panel Fig. 2 View of the Four Basic Models of the Digitrip RMS Trip Unit The protection section of the Digitrip RMS Trip Unit can be equipped with a maximum of five phase and two ground (time current) curve shaping adjustments. The exact selection of the available protection function adjustments is optional to satisfy the protection needs of any specific installation. The short delay and ground fault pick-up adjustments can be set for either flat or l't response. A pictorial representation of the applicable time-current curve for the selected protection functions is provided on the face of the trip unit for user reference. Red LEOs that are placed in the Time-Current curves depicted on the face of the trip unit provide mode of trip indication for ground fault, overload and short circuit trip operations. All Digitrip RMS Trip Units that are not equipped with an adjustable instantaneous trip element (LS and LSG) are provided with a making current release which is referred to as a discriminator. n addition, a high-level instantaneous override circuit is provided to insure rapid circuit clearing under abnormal fault current conditions. Digitrip RMS Trip Units are available in four basic models, as illustrated in Fig. 2, 5, 6, and. Separate instruction leaflets referenced in Section.2 cover the basic functions and features of each model. This instruction book is arranged to describe the unique features of each type as they relate to their application in Type SPB, Systems Pow-R Breakers. Table illustrates the available functions and features of each of the four trip unit models. 3. Rating Plugs Rating Plugs, as illustrated in Fig. 3, determine the continuous current rating of the circuit breaker. All protection function settings on the face of the trip unit are expressed in per unit multiples of the plug ampere rating (l n l Available rating plugs are shown in Table 2. Plugs must be selected to match the desired continuous current rating of the RMS Sensing with Current Display ---Rating Plug circuit breaker as well as the frame rating and the system frequency, i.e., 5 or 6 Hz. Rating plugs are equipped with a back-up battery, as illustrated in Fig. 3, to maintain the mode of trip operation following a circuit breaker tripping operation when external control power is not available. The battery is a long-life lithium type, that is replaceable from the front of the trip unit, when required, without removing the rating plug. Replacement types and instructions are provided in the Digitrip RMS Trip Unit instruction leaflet referred to in Section.2 of this book. Following a trip operation and with no supplementary control power available, the battery will maintain the mode of trip LED for approximately 6 hours. Note: The rating plug must be securely tightened in the trip unit before operating the circuit breaker. 4. Digitrip RMS Model Considerations 4. Digitrip RMS 5 The Digitrip RMS 5 Trip Assembly consists of a Digitrip RMS 5 Trip Unit as described in.l. 2-5, 3 or 4 auxiliary current transformers and a stab-in trip unit terminal block as shown in Figs. 4 and 5. The fourth auxiliary current transformer is supplied when the optional ground fault protection function is selected in the trip unit. Also, a side mounted 4-point terminal block is provided to pre-wire the mode of ground fault sensing used, i.e., residual, source ground or zero sequence. The trip unit contains a receptacle for use with an optional Auxiliary Power module (Cat. No. PRTAAPM). When this module is in place on the trip unit and connected to a 2 V. 5/6 Hz supply, the circuit breaker can be bench tested using the integral test panel. With the circuit breaker in the closed posiwww. ElectricalPartManuals. com

Fig. 3. View with Hinged Cover Closed Hinged Cover Fig. 3 Typical Rating Plug Fig. 3.2 View with Hinged Cover Open and Battery nstalled Circuit Breaker Type dentification Plug dentification----+ Battery Check Pushbutton ---i--tllli Battery ----...J Check LED Battery tion, it can be "tripped" when the test selector switch is in either the "6T" or "GFT' positions. CAUTON TESTNG OF A CRCUT BREAKER BY NTATNG A TRP OPERATON WHLE N THE CELL "CO N NECTED" POSTON BY THE NTEGRAL TEST PRO VSONS N THE DGTRP RMS TRP UNT S NOT RECOMMENDED. THE TRPPNG OPERATON OF THE CRCUT BREAKER WLL CAUSE DSRUPTON OF SERVCE AND POS SBLY PERSONAL NJU RY RESULTNG FROM UNNECESSARY SWTCHNG OF CONNECTED EQUPMENT. TESTNG OF A CRCUT BREAKER SHOULD BE DONE ONLY N THE "TEST", "DSCON NECTED" OR "WTH DRAWN" CELL POSTONS. 4.2 Digitrip RMS 6 The Digitrip RMS 6 Trip Assembly consists of a Digitrip RMS 6 Trip Unit as described in.l. 2-52, 3 or 4 auxiliary current transformers, a stab-in trip unit terminal block and a Power/ Relay module mounted as illustrated in Figs. 4 and 5. The Digitrip RMS 6 Trip Unit is similar to a Digitrip RMS 5 Trip Unit with the addition of a four-digit display, three phase O A, s. lc) and one ground current ( G ) green pointer LEOs along with a stepping pushbutton, a red High Load LED as illustrated in Table. Signal contacts are provided for hard wiring three..,:.. Battery Removal Tab -- Retention Screw -- Variable Settings Fig. 3.3 View with Hinged Cover Open and Battery Removed Polarity Marks remote mode of trip indicators (long delay, short circuit, ground fault) and a High-Load remote alarm. The ground current pointer LED and ground fault mode of trip signal contact are supplied only when the ground fault protection function is provided in the trip unit. A 2 V, 5/6 Hz 6 VA Power/Relay module is standard for operating the display and internally mounted signal relays. The relay contacts are each rated 2 V,. A. A 23 V 5/6 Hz 6 VA power relay module is also available. The Power/Relay module will maintain the cause of trip LEOs history and trip history as long as the control power supply is available. With loss of the control power supply, only the cause of trip LEOs will be maintained by the back-up battery located in the rating plug. The High-Load LED and remote alarm switch are pre-set at 5% of the value of the long delay setting. The High-Load relay operates and the LED turns "ON" when the 5% level is exceeded only after an approximate 4 second delay to ride through momentary High-Load conditions. 4.3 Digitrip RMS The Digitrip RMS Trip Assembly consists of a Digitrip RMS Trip Unit as described in.l. 2-53, 3 or 4 auxiliary current transformers, a stab-in trip unit terminal block, a Power/Relay module and a Potential Transformer module with a disconnect plug for dielectric testing of the circuit breaker mounted as partially illustrated in Figs. 4 and 5. The Digitrip RMS Trip Unit is similar to a Digitrip RMS 5 Trip Unit with the addition 3

4 Table - Digitrip RMS Trip Unit Characteristics Digitrip RMS Type 5 6 nstruction Leaflet No..L. 2-5.L. 2-52.L. 2-53.L. 2-54 Long Delay Setting X X X X Long Delay Time X X X X Long Time Memory X X X X Short Delay Pick-up OPT. OPT. OPT. OPT. c Short Delay Time OPT. OPT. OPT. OPT. FlatJ2T Response X X X X "B Zone nterlocking Q) GJ GJ GJ GJ nstantaneous Pick up OPT. OPT. OPT. OPT. : Ground Fault Pick-up OPT. OPT. OPT. OPT. Ground Fault Time OPT. OPT. OPT. OPT. Flatii2T Response X X X X Ground Time Memory X X X X Zone nterlocking GJ GJ GJ GJ nterchangeable Rating Plug X X X X c.c Mode of Trip LED's X X X X ;:: t-.;::; Battery- for Mode of Trip - "' "' u LEDS X X X X Battery Status LED 3 Battery Test Pushbutton X X X X X X X X ntegral Test Provisions X X X X "' >-- Trip Unit Status ndication Q) LED X X X X Auxiliary Power Module OPT. OPT. OPT. OPT. Power/Relay Module X X X 4 Digit Display - X X A Current LED X X :5 B Current LED X X 6.- C Current LED X X ro Gnd. Current LED u c Display Stepping.3o Pushbutton X X High Load LED X X Remote Signal Contacts:.s "' Long Delay Trip X X X E c Short Circuit Trip X X X Q).Q' Ground Fault Trip O::<Jl High Load Alarm X X X Potential Transformer Module X X PTM Disconnect Plug for "' c: Dielectric Testing of Circuit >' Breaker X X C). Energy Monitoring: c: Q) Parameters.j::; Peak Demand @ X Peak Demand Reset PB @ X Present Demand @ X Energy Consumption @ X N COM X X c,. E (ntegrated c 3 - Communications) NCOM Address Register X X Transmittable Parameters: ndividual Phase Currents @ Ground Currents Energy @ @ Breaker Status: Open/Closed/Tripped @ (j) Mode of Trip: Override @ nstantaneous @ "' Discriminator @ Short Delay @ Q) Ground Fault @ : Long Delay @ "' "' Long Delay Pick-up @ nformation: External Trip Command c: "' (Over NCOM) @ @.= Data Memory Test Failure (RAM @ Program Memory Test Failure (ROM) @ Missing or Defective Rating Plug @ @ Reverse Power Flow @ @ Response to Depressing Test Pushbutton @ @ Communication Failure g c: u Breaker Command (Via NCOM: Trip X X @ Close OPT.<lJ OPT.()) OPT = Optonal CD Use of zone interlocking is optional with breaker wiring modification. Remote location only unless optional AEM local monitor is used. @ Local (on face of trip unit) or remote via N COM. @J Remote only. On AEM denoted by absence of response from addressed breaker. Supplied only when trip unit is equipped with ground fault protection option. (D Requires spring release or electrical operator option. of an NCOM module along with an adjustable NCOM address register. Signal contacts are provided for hard-wiring three remote mode of trip indicators (long delay, short delay, ground fault) and a High-Load remote alarm. The ground fault mode of trip signal contact is supplied only when the ground fault protection function is provided in the trip unit. These additions, along with the transmittable data possibilities, are illustrated in Table. Only the mode of trip LED indicators provide data on the face of the trip unit. However, with the addition of a locally mounted Assemblies Electronic Monitor (AEM), as described in.l -26, the data in Table referenced by Note 2 can also be viewed. The Assemblies Electronic Monitor (AEM) is a microprocessorbased, self-contained, door-mounted device designed to monitor circuit breakers equipped with Digitrip RMS or Digitrip RMS Trip Units. Network interconnections for the NCOM circuit must be connected as shown in.l. 2S-53, Figs, SA, S, and SC using twisted pair (shielding preferred), No. AWG conductors. The three-digit NCOM address must be set on each trip unit per instructions given in.l 2S-53. To insure that each circuit breaker in an assembly is properly located after the address is set, the breaker should be identified with its proper cell location and that reference along with the breaker NCOM address should be marked on the face of the trip unit in the spaces provided. n addition to the communication of breaker data, the NCOM module allows for remote tripping (via the low energy shunt trip) and closing of the circuit breaker. 4,4 Digitrip RMS The Digitrip RMS Trip Assembly is similar to the Digitrip RMS Trip Assembly with the addition of a four-digit display, three phase (l A,, lc) and one ground current ( G ) green pointer LEDs along with a stepping pushbutton, a red High Load LED, peak demand, present demand and energy consumed green pointer LEDs along with a peak demand reset pushbutton as illustrated in Table. The Digitrip RMS Trip Unit is described in.l 2S-54. The Trip Assembly provides for both local displays on the face of the trip unit and remote communications via an NCOM communication network signal link as illustrated in Table. n addition, if desired, an Assemblies Electronic Monitor (AEM) as described in.l -26, may also be installed to show the parameters in Table covered under Note 2. nterconnections for the NCOM circuit must be connected as shown in.l 2S-54, Figs, SA, S and SC using twisted pair (shielding preferred) No, AWG conductors. The three-digit NCOM address must be set on each trip unit per instructions given in.l 2S-54. To insure that each circuit breaker in an assembly is properly located after the address is set, the breaker should be identified with its proper cell location and that reference along with the breaker NCOM address marked on the face of the trip unit in the spaces provided. n addition to the communication of the breaker data, the NCOM module allows for remote tripping (via the low energy shunt trip) and closing of the circuit breaker,

Terminal ---!: Block DGTRP RMS --- Trip Unit GFP Terminal -- Block.---- Fixed Mounted 3 A SPB ---Manual Charging Handle ---Operating Mechanism ---- Low Energy Shunt Trip ---Auxiliary Current Transformers ---- Ground Fault Auxiliary Current Transformer Fig. 4 View of 3 A Circuit Breaker with Front Cover Removed to Expose Digitrip RMS Trip Unit WARNNG CARELESSLY PLANNED AUTOMATC CRCUT BREAKER CLOSNG OPERATONS NTATED BY NCOM COMMUNCATON SGNALS DURNG MAN TENANCE PERODS COULD CAUSE SEVERE PER SONAL NJURY OR DEATH. NSTALL APPROPRATE PERMSSVE CONTROL MEANS AS LLUSTRATED N CONNECTON DA GRAM.S. 5545 (SHEETS 4,4 AND 42) TO AVOD UNDESRED REMOTE CLOSNG OPERATONS DUR NG MANTENANCE PERODS. ALSO, PROVDE ADE QUATE EQUPMENT WARNNGS FOR NORMAL OPERATON PERODS. 4.5 Reset Operation Following a overload, short circuit or ground fault tripping event, the Digitrip's "Trip Reset" push button must be depressed before the circuit breaker can be reclosed. 5. Principle of Operation 5. General The circuit breaker is tripped automatically on fault current conditions by the combined action of three components:. The sensors which determine the current level. 2. The Digitrip RMS Trip Unit, which provides a tripping signal to the Low Energy Shunt Trip when current and time delay settings are exceeded. 3. The low energy shunt trip which actually trips the circuit breaker. Schematically, this may be represented as illustrated in Fig. 6 for a 3A. Pow-R Breaker. This arrangement provides a very flexible system covering a wide range of tripping characteristics as illustrated by the Time-Current curves appearing in Sections 6., 6.2 and 6.3 of this instruction book. Not only is the Digitrip RMS Trip Unit adjustable, but selection of rating plugs provides a wide range of continuous current ratings. The automatic overload and short circuit tripping characteristics for a specific circuit breaker are determined by the ratings of the installed current sensors, rating plugs and the selected functional protection settings. Specific setting instructions are provided in the applicable trip unit instruction leaflet referenced in Section.2 of this instruction book. When the functional protection settings are exceeded, the Digitrip RMS Trip Unit supplies a trip signal to the low energy shunt trip. Thus all tripping operations initiated by the protection functions of the Digitrip RMS Trip Unit are performed by secondary control circuitry, with no mechanical or direct magnetic action between the primary current and the mechanical tripping parts of the breaker and with no external control power required. 5

6 Stab-n Trip Unit ---t-'"-:: Terminal Block Power/Relay ---+' Module Used with DGTRP RMS Models 6, and Fig. 5 View of 3 A Circuit Breaker with Front Cover and Digitrip RMS Trip Unit Removed to Expose Power/Relay Module and Stab-n Terminal Block 5.2 Digitrip RMS Trip Assembly The basic Digitrip RMS Trip Assembly, as illustrated in Figs., 2 and 4, includes the following which could vary slightly depending upon the exact model of the Digitrip RMS Trip Unit installed:. Digitrip RMS Trip Unit 2. Rating Plug 3. Auxiliary Current Transformers - 3 or 4 depending upon whether or not ground fault protection is included. Not required on 4-2 C. 4. Stab-in Terminal Block for Trip Unit 5. Power/Relay module (Digitrip RMS Trip Unit Models 6, and only) 6. Potential Transformer module with Dielectric Test Disconnect Plug (Digitrip RMS Trip Unit Models and only) As shown in Figs. and 4, the Digitrip RMS Trip Unit assembly mounts in the left hand pole of a Systems Pow-R Breaker. The Systems Pow-R Breaker is factory wired in accordance with the applicable pages of connection diagram.s. 5545. Any field installation or modification must be made in accordance with the applicable pages of this same document...---fixed Mounted 3 A SPB -- Manual Charging Handle '!---Operating Mechanism -!---Lclw Energy Shunt Trip ---Auxiliary Current Transformers '---- Ground Fault Auxiliary Current Transformer CAUTON MPROPER POLARTY CONNECTONS ON THE LOW ENERGY SHU NT TRP COL WLL VOD OVERLOAD AND SHORT CRCUT PROTECTON WHCH COULD RESULT N PERSONAL NJURY. OBSERVE POLARTY MARKNGS ON THE SHU NT TRP LEADS AND CONNECT PROPERLY WTH NSTRUC TONS PROVDED SHOULD ANY CHANGES BE MADE. 5.3 Low Energy Shunt Trip The mechanical force required to initiate the tripping action of a type SPB Systems Pow-R Breaker is provided by a special low energy shunt trip. t is mounted, as shown in Fig. 4, on the underneath side of the mechanism housing. t contains a permanent magnet assembly, moving and stationary core assemblies along with a spring and coil. The circuit breaker mechanism assembly contains a mechanism actuated reset lever and a rotating trip lever to actuate the tripping action of the circuit breaker. When the Low Energy Shunt Trip is reset by the operating mechanism, the moving core assembly is held in readiness against the force of the compressed spring by the permanent magnet. When a tripping action is initiated, the Low Energy Shunt Trip coil receives a tripping pulse from the Digitrip RMS

Trip Unit. This pulse overcomes the holding effect of the permanent magnet, and the moving core is released to trigger the tripping operation via the rotating trip lever. 5.4 Ground Fault Protection 5.4. General When the Digitrip RMS Trip Assembly includes ground fault protection, the distribution system characteristics, i.e., system grounding, number of sources, number and location of ground points, etc. must be considered as well as the manner and location in which the circuit breaker is applied to the system. Three modes of sensing ground fault currents are generally used: residual, source ground and zero sequence. Systems Pow-R Breakers are internally prewired to accommodate all three types. A side mounted 4-point terminal block, as shown in Fig. 4, is provided to revise connections required to accommodate each method. A nameplate is provided on the side of the circuit breaker that illustrates the required connections. Applicable connection variations are illustrated in Figs. and. f the system neutral is grounded, but no phase to neutral loads are used, the Digitrip RMS Trip Assembly includes all of the components necessary for ground fault protection. 5.4.2 Residual Sensing The standard mode of ground fault sensing in Systems Pow-R Breakers is Residual Sensing. This mode utilizes one current sensor on each phase conductor and one on the neutral. This mode of sensing vectorially sums the outputs of the four individual current sensors. As long as the vectorial sum is zero, then no ground fault exists. The neutral sensor must have characteristics which are identical to the three internally mounted phase current sensors. Available types of neutral sensors are illustrated in Figs. 2, 3 and 4. Residual ground fault sensing means are adaptable to main and feeder breaker applications. Available ground fault pick-up settings employing Residual Sensing means are given in Table 3. 5.4.3 Ground Return Sensing Depending upon the installation requirements, alternate ground fault sensing schemes may be dictated. The ground return method is most applicable where ground fault protection is desired only on the main circuit breaker in a simple radial system. This method is also applicable on double-ended systems where a mid-point grounding electrode is employed. For this mode of sensing, a single current sensor mounted on the equipment bonding jumper measures directly the total ground current flowing in the grounding electrode conductor and all other equipment grounding conductors. The values shown in Table 3 will apply when the neutral sensors shown in Figs. 2, 3 and 4 are employed in a ground return sensing scheme provided the neutral sensor is the same as the frame rating. Note: Regardless of the mode of sensing employed, the polarity of the sensor connections is critical. Always observe the polarity markings on the installation drawings. To insure correct ground fault equipment performance, conduct field tests to comply with National Electrical Code requirements under Article 23-5(C). Table 2 - Catalog Numbers of Available Rating Plugs Rated Current (Amps l n l Frame Rating (Amps) 2 4 25 3 4 4 6 6 2 2 6 2 6 2C 2 6 2 6 2 2 6 25 2 25 6 3 2 25 3 2 4 25 3 32 4 3 5 32 4 5 CD Actual plug ratmg 63A. Actual plug rating 25A. Catalog Catalog Number Number 6 Hz 5 Hz PD6S4A2 PD6S4A25 PD6S4A3 PD6S4A4 PD6SA4 PD6SA6 PD6SA PD6S 2A6 PD6S 2A PD6S2A PD6S 2A2 PD6S 6A PD6S 6A PD6S 6A2 PD6S 6A6 PD6S2 A PD6S2A2 PD6S2A6 PD6S2A2 PD6S2A6 PD6S2A2 PD6S25A6 PD6S25A2 PD6S25A25 PD6S3A6 PD6S3A2 PD6S3A25 PD6S3A3 PD6S4A2 PD6S4A25 PD6S4A3 PD6S4A32 PD6S4A4 PD6S5A3 PD6S5A32 PD6S5A4 PD6S5A5 Table 3 - Ground Fault Current Pick-up Settings Using Residual Sensing Mode PD5S4A2 PD5S4A25 PD5S4A3 PD5S4A4 PD5SA4 PD5SA63CD PD5SA PD5S 2A63 CD PD5S 2A PD5S2A PD5S2A25 PD5S 6A PD5S6A PD5S6A25 PD5S6A6 PD5S2A PD5S2A25 PD5S2A6 PD5S2A2 PD5S2A6 PD5S2A2 PD5S25A6 PD5S25A2 PD5S25A25 PD5S3A6 PD5S3A2 PD5S3A25 PD5S3A3 PD5S4A2 PD5S4A25 PD5S4A3 PD5S4A32 PD5S4A4 PD5S5A3 PD5S5A32 PD5S5A4 PD5S5A5 nstalled Pick-up (Dial) Setting Rating Amperes@ Plug Amperes A@ @ C @ E F H K On l 2 5 6 2 5 2 25 63 5 25 5 25 3 5 5 2 5 225 3 4 2 4 6 2 24 3 4 6 5 2 24 3 36 45 6 2 24 2 32 4 4 6 25 3 35 4 5 6 5 2 3 36 42 4 6 2 2 6 4 4 56 64 6 t-;too 2 2 5 6 '"""2iio 2 2 25 625 5 5 2 2 2 2 3 5 5 2 2 2 2 2 32 6 2 2 2 2 2 2 4 2 2 2 2 2 2 2 5 2 2 2 2 2 2 2 2 @J Except as noted, tolerances on pck-up levels are ± % of values shown in chart. @ Ground fault pick-up levels shown are nominal values when tested with external control power present. Without external control power, such as is the case with the Digitrip RMS 5, ground pickup levels may exceed these values and be as high as the value shown for the "E" setting of that particular rating plug.

AUXLARY CURRENT TRANSFORMERS POLARTY MARKS BOT END LOW ENERGY SHUNT TRP -----------------W H _ TE -5- -< r L---------------------B-LACK ---------------------:E - -- o- : 4 :J/x 2 :.la_.--------- -- -- -- --------------:-:-< OVERRDE JY ZENER 'T -- f--------------------------- Digitrip +----+-CURRENT SENSORS Fig. 6 Partial nternal Connections of a 3 A Systems Pow-R Breaker 5.4.4 Zero Sequence Sensing Zero Sequence Sensing (also referred to as vectorial summation) is applicable to mains, feeders and special schemes involving zone protection. Since most ground fault sensing requirements can be resolved by using either the residual, the ground return or a combination of the two, the Zero Sequence mode of sensing is seldom used. For specific applications requiring this mode of sensing, contact Westinghouse. 5.4.5 Ground Fault Settings The adjustment of the ground fault functional settings is illustrated in the applicable Digitrip RMS Trip Unit instruction leaflet referenced in Section.2 of this instruction book. Either flat response or l't response settings may be selected. The effect of these settings is illustrated in the ground fault Time-Current curve included in Section 6 of this instruction book. Applicable residual ground fault pick-up settings and current values are given in Table 3 as well as on the "G" Time-Current curve. 5.5 Current Sensors The three primary current sensors installed in the circuit breaker are located internally on the lower conductors which are normally on the load side of the main contacts. The physical location is shown in Fig.. n the larger frame ratings, 2A. through 5A., the auxiliary current transformers are mounted as shown in Fig. 4. The ground fault auxiliary current transformer is supplied only when the ground fault protection function is supplied in the Digitrip RMS Trip Unit. A partial internal schematic is shown in Fig. 6 as well as in the residual diagram shown in Fig... RMS L- j GROUND FAULT AUXLARY CURRENT TRANSFORMER NOT SHOWN n the smaller frame ratings, 4A. through 2A. (compact 6 inch high frame), the auxiliary current transformer supplied is a 5-winding transformer as shown in the residual diagram in Fig.. The physical location is shown in Fig.. The primary current sensors produce an output proportional to the load current and furnish the Digitrip RMS Trip Assembly with the intelligence and energy to trip the circuit breaker when functional protection settings are exceeded. 5.6 Digitrip RMS Accessories 5.6. Power/Relay Module The Power/Relay Module which is supplied with Digitrip RMS Trip Unit models 6, and is mounted in the left pole of the Systems Pow-R Breaker as shown in Figs. 5 and. This module provides control power for operating the 4-digit display and internally mounted signal relays. 5.6.2 Potential Transformer Module The Potential Transformer Module is supplied with Digitrip RMS Trip Unit models and. t is mounted in the left pole of the Systems Pow-R Breaker as shown in Fig.. This module provides voltage for computing the energy monitoring parameters. The potential disconnect plug (not shown) is mounted on the left side of the Systems Pow-R Breaker just above the 4-point GFP terminal block as shown in Figs. 4 and 5. This plug must be removed prior to any dielectric testing of the circuit breaker.

SPB POW-R ---<,_. Breaker 2A, Maximum with Front Cover Removed Primary ---lf,l+-' Current Sensors Fig. Side View of 2 A Maximum Pow-R Breaker 5.6.3 Dielectric Testing DELECTRC TESTNG OF THE CRCUT BREAKER WTH THE DELECTRC DSCONNECT PLUG NSTALLED WLL DAMAGE THE POTENTAL TRANS FORMER MODULE AND DGTRP RMS OR TRP UNT. REMOVE THE DSCONNECT PLUG PROR TO DONG ANY DELECTRC TESTNG OF THE CRCUT BREAKER. REPLACE THE PLUG AFTER ALL DELECTRC TEST NG S COMPLETED AND PROR TO CLOSNG THE CRCUT BREAKER PER THE ESTABLSHED OPER ATNG PROCEDURES. 5. Connection Diagram A complete master connection diagram for the Systems Pow-R Breaker employing a Digitrip RMS Trip Unit is given in.s. 5545. Each circuit breaker shipped from the factory includes a copy of the pages from this document that are applicable to the equipment included in the breaker. 5. Trip Unit Settings Protection To insure the non-tampering of selected protection settings, a sealable plexi-glass cover as shown in Fig. 5 is provided. The cover is held in place by four cover screws. The non-tamperability is insured by the insertion of a standard meter seal through the holes in two of the cover retention screws.,...--- Potential Transformer Module (Used with Digitrip RMS,, Only) -ttt--"'tiit--- Power/Relay Module (Used with Digitrip 6,, Only) '----f---- 5 Winding Auxiliary Current Transformer GF Breakers Only 6. Time-Current Curves The following Time-Current curves illustrate the adjustability and configuration of the resultant Time-Current characteristic curves of the Digitrip RMS Trip Unit family. All protection function time-current settings should be made following the recommendations of the specifying engineer in charge of the installation. NOTCE THE PROVSON FOR ZONE NTERLOCKNG S STANDARD ON ALL SYSTEM POW-R BREAKERS WTH DGTRP RMS HAVNG ETHER SHORT TME OR GROUND FAULT FUNCTON. APPROPRATE JUMPERS MUST BE ADDED ON BREAKER F ZONE NTERLOCKNG S NOT DESRED OR F FELD TEST NG S DESRED (REF..S. 5545 SHEET 3).

::::j... 6. Long Time/nstantaneous Time-Current Curve SC-423-5.2.3.4.5 - ADJUSTABLE i- LONG DELAY 6 - SETTNG - r+.5,.6,.,.,.5,.,.5, 5 \ 4 3 2 6 5 4 3 2 6 5 4 3 2 6 5 4 3 6 5......4. 3. 2..5. VARABLE SEmNGS MARKED ON PLUG M M 2.2 \ \\ \\ CURRENT N MULTPLES OF PLUG RATNG n MAXMUM TOTAL \ v CLEARNG \ \ TME \ \ MNMUM (/ \ TOTAL CLEARNG TME ADJUSTABLE NSTANTANEOUS PCKUP 2, 2.5, 3, 4, 5, 6,M.M 2, n SPB 4-3A FRAMES B.3.4. 5 SPB 4 5A FRAMES 3.5 4.5 \\ \\ \ \ \\ \ \ \ \[\ l\ \ ' l\\ f\ \ \ '4 ' \ f\ \,\ \ \. \ l\ \\ \ \ \X " : 2 =l_ 3 F Rs \) [:J 2 4 6... 2- -.. "' :-:- J..... \ r'\. 4.5 Mi s;:j DGTRP RMS 5/6// Typical Time-Current Characteristic Curve (L) for Type SPB Systems Pow-R Breakers g SPB Systems POW-R Breakers Frame Breaker Short nterrupting Capacity Amperes Type Time AMS Symmetrical KA SPB- Rating 24v 4V 6V 6 KA 5 M 2 4/BOO 5 25 65 5 42 25 5 5 25 2 5 2 65 35 B5 65 42 5 5 35 2 5 35 6/2C 65 35 B5 65 5 35 B5 5 5 2 5 2253 35 B5 5 5 2 5 4/5 65 5 5 5 2 5 Available DGTRP RMS Rating Plugs Frame Amps Plug rating n Amps () 4 2, 25, 3, 4 BOO 4, 6, BOO 2 6, BOO,, 2 6 BOO,, 2, 6 2C, 2, 6, 2 2 6, 2 25 6, 2, 25 3 6, 2, 25, 3 4 2, 25, 3, 32, 4 5 3, 32, 4, 5 ADJUSTABLE t-(-- NOTE: LONG DELAY TME t-(-- SPECFC RATNG PLUG REQURED FOR SHOWN t-t- 5 OR 6 HZ APPLCATONS. @ 6n 2, 4,,, 2, 6, 2, 24 t-(-- 2 CURVES APPLY FROM -2"C TO + 55"C AMBENT '\. CURRENT N MULTPLES OF PLUG RATNG n TOLERANCES LOS = TRP RANGE 5% TO 3% OF SmiNG LOT = +, -33%, DAL - SHOWN @ 6 n NST = ± % DAL APPL CATON DETERMNES END OF CURVE l l 4 3 2 6 5 4 3 2 6 5 4.3.2

6.2 Long Time/Short Time Time-Current Curve SC-424- "' c z c u w "' >= OS 4 5 :J:::J : r- ADJUSTABLE '-- LONG DELAY SETNG 6 -.5. 6,.,.,.5,.,.5..., n \ -,--+..::.f-lf'-:oh--',... "--------l--+-+-+-+++-!------f--f- soo-rrr-4-4+hh, --+-+++++---+--r 4 f-++-h+--t--lr---t----ht-t\\.-----+--+---+-+-r++++----+ ---+ \\ MAXMUM loo ---+---+--+--.+-----+++---+-- \ TME 6 5 4 3 - - - -. =. -. -.6 -.5 -.4 f--.3 t-. -...,..,..6 -.5,..4 -.3 -. -. -.5 _l'tsho{t DELAY TME SETNGS - '\ \ \ \ \ \\ \ ). \ \ \\ \ \ VARABLE SETNGS MARKED ON PLUG s, \ \ \ UM 'f-v++t-\--\-'\'r\--\-f-\-lim\<+-+++--++---+ 4 5 '\ '\ '\ \ \ \ \ \ \ \\ \ '\24 \\'"'.\\ \ M N M TOTA L CLEARNG \ TE l [\ \\ J.5* @ @.l*r:: SPB 4-3A FRAMES DGTRP RMS 5/6// Typical Time-Current Characteristic Curve (LS) for Type SPB Systems Pow-R Breakers ADJUSTABLE LONG DELAY TME \ \ \ S 2 SHOWN -t+t--'lr+-''"""-;p.:.,.jdftt @ 6 n -+++----l-' -':-ll 'vh2. 4,.. t2. \ l \ \t.. 6. 2,24 \\'r.\' Frame Amperes 4/ 2 6/2C SPB SYSTEMS POW R BREAKERS Breaker Short Time nterrupting Capacity rfs 5 5 65 5 65 5 2/25/3 5 4/5 5 e ing : s: etrlcal 25 25 25 35 35 35 35 35 5 35 5 65 5 65 5 2 t5 5 65 2 t5 5 65 2 5 2 tso too 2 5 Available Dlgltrlp RMS Rating Pluga<D Frame Amps -.w-- t2 6 2C 2 25 3 4 5 Plug Rating in Amps {) 2, 25, 3, 4 4, 6, 6,,, 2,, 2, 6, 2. 6, 2 6. 2 6, 2, 25 6, 2, 25, 3 2, 25, 3, 32, 4 3. 32. 4, 5 NOTES <D SPECFC RAnNG PLUG REQURED FOR ETHER 5 HZ OR 6HZ. APPUCATONS. CURVES APPLY FROM -2" TO +55 C AMBENT @ WTH ZONE NTERLOCKNG ON SHORT DELAY unuzed AND NO RESTRANNG SGNAL. THE MNMUM nme BAND (SDM WLL BE N EFFECT - REGARDLESS OF SETnNG. TOLERANCES (PREUMNARY LDS = TRP RANGE 5'o TO 3'o OF SffiiNG LOT = +, - 33'/o, DAL- SHOWN @ 6 SDPU = "' % DAL \) T C \ \ NOMNAL i;aj 3 ):=JS ltrt ADJUSTABLE»:t= = DELAy -++Ht:_2_,2_.5_.,3.r4_.5_._sr, NSTANTANEOust::t::l=t::l:l KA soov 42 5 42 5 5 5 too 5 5 5 OVERRDE s. _ s f2 i=ti=== P ; C:K-t P s J rsl T 3] ADJUSTABLE APPLCATON DETEAMNES l- END OF SHOAT TME DELAY FLAT RESPONSE.'.2,.3,.4,.5 -+++---+--+--+---H!--++-H-'\----'\--+-----' ;:lng t-t+i---t- H--H-t+---t---,., r- --r--r- -----T---t--f-,_, CfUiAV+E--;-,_--.-t4-Tf 2 CURRENT N MULTPLES OF PLUG RATNG n CURRENT N (SEE MULTPLES CHART OF ABOVE) SHORT TME RATNG 6 5 4 3 6 5 4 3 2 3 3 :::! ;:: m z n z "'

.. 2 6.3 Ground Fault Protection Time-Current Curve SC-422-6 5 4 3 2 BO 6 5 4 3 2 B 6..6..6 5.4.3.2..OB.6.5.4.3.2 5.5..2 -.2 A t--.4 5.6 K 4-- ' ""- CURRENT N MULTPLES OF PLUG RATNG llnl 5 6 ADJUSTABLE GROUND FAULT PCKUP TYPCAL FOR EXACT VALUES AND TOLERANCES OF GFPU LETTER CODE SEE CHART \.5 \ ) G_] ' ' -j r-... '\. " ". DGTRP RMS 5/6// Typical Time-Current Characteristic Curve {G) for Type SPB Systems Pow-R Breakers - -..3.4.5.6..B. B GROUND PCKUP LEVELS AMPERES<D@ A. B C D E 5 6 BO 2 5 25 63 BB 25 5 BB 25 3 5 5 2 5 lbo 5 3 4 4 6 4 3 4 6 5 lbo 2 4 3 36 45 6 5 BOO 2 24 2BO 3 4 4 6 BOO 5 :roo 35 4 5 6 5 2 :roo 36 42 4 6 2 2 6 4 4 56 64 BOO 6 2 2 5 6 BOO 2 2 2 25 625 5 B5 2 2 2 3 5 5 2 2 2 2 2 4 2 2 2 2 2 2 2 5 2 2 2 2 2 2 2 l't RESPONSE ON GROUND TME DAL NDCATED BY*.4 GROUND FAULT DELAY.3 ADJUSTMENTS FLAT RESPONSE.3.4.5.6..B. 5 6 B.2 CURRENT N MULTPLES OF PLUG RATNG llnl.3.4.5.6..b..* BOO 6 5 4 3 2 BO 6 5 4 3 Notes <D Except as noted tolerances on pickup levels are ± % of values shown in chart. Ground Fault Pickup levels shown are nominal values when tested with external power present such is the case in Digitrip 6, and models. Without external power, such as is the case with the Digitrip 5, Ground Pickup lavals may exceed these values and be as high as the value shown for the "E" setting of that particular rating plug. B Specific rating plug required for 5 HZ or 6 HZ, applications. @ All tabulated values are based on the use of a residual sensing scheme with the same rated current sensor in all phase and neutral... conductors. Curves apply from - ZOOC to + ssoc ambient. With zone interlocking on ground fauh utilized and no restraining z signal, the minimum time band (GDM) will be in effect - regardless of setting. n z en 2. B..6.5.2.....6.5.4.3.2.Q 5 6

RESDUAL SENSNG SOURCE GROUND SOURCE N A B c! t! 5/.2 LOW ENERGY SHUNT TRP D6 GFT 4 22 :2 : :: : ::: : ::=::::=:::=):=3r-*:)(: 3---< : ) N A B c LOAD 5/.2 (J) ;2'UJ o:s:! o.. > - UJ O:CJ!:::: o.. )-- (.') - -: Cli- D CONNECT D5 TO 6 AND TO DB ON 4 PONT GFP TERMNAL BLOCK FOR RESDUAL SENSNG. SEE ALSO FG.. CONNECT D5 TO D ON 4 PONT GFP TERMNAL BLOCK FOR SOURCE GROUND AND ZERO SEQUENCE SENSNG. Fig. SPB Master Connection Diagram Typical Current Sensor Connections for 2 A and Greater Frame Ratings 3

4 POLARTY MARKS PRMARY CURRENT SENSORS CD TOP END \ \ \ 2 L---- v v v BOT. END L ' - - ---- - - 4 f---: 3 :EUTRAL,------ SENSOR L _j EXTERNAL SHORTNG STRAPS MUST BE N PLACE DURNG TEST NG AND OPERATNG CONDTONS PER NSTRUCTON N.P. ON SDE OF BREAKER. CONNECT NEUTRAL SENSOR SO THAT POLARTY RELATONSHP TOWARDS SOURCE S DENTCAL FOR PHASE AND NEUTRAL SENSORS. NO. 4 OR NO. 2 COPPER WRE S REQURED PER UL 53 FOR SEC ONDARY WRNG OF NEUTRAL SENSORS....J FRAME AM PS/. '-tl----4._..-' Fig. SPB Master Connection Diagram Ground Fault External Connection 3PH, 4W., Residual, 4/ 2 62 A Breakers (2 A in Compact, 6 in. High Frame). References. Type SPB Systems Pow-R Breakers.L. 2-.S. 5545 Type SPB Systems Pow-R Breakers Master Connection Diagram for Type SPB Systems Pow-R Breakers.2 Digitrip RMS Trip Units.L. 2-5.L. 2-52.L. 2-53.L. 2-54.3 Miscellaneous.L. -26 nstructions for Digitrip RMS 5 Trip Unit nstructions for Digitrip RMS 6 Trip Unit nstructions for Digitrip RMS Trip Unit nstructions for Digitrip RMS Trip Unit Assemblies Electronic Monitor (AEM)

RESDUAL SENSNG SOURCE GROUND N A B c t t t ) ) SOURCE LOW ENERGY SHUNT TRP FLUX TRP DEVCE 5 WNDNG TRANSFORMER D D 4 't--+-+-+--+-+-e--..je-,:-----<( LOAD 2./.2 D2 D2 3 AUX. C.T. ( BLACK (ST-) CONNECT D5 TO D AND D6 TO D2 ON 4 PONT GFP TERMNAL BLOCK FOR RESDUAL SENSNG. CONNECT D5 TO D6 ON 4 PONT GFP TERMNAL BLOCK FOR SOURCE GROUND AND ZERO SEQUENCE SENSNG. 5 4 4 3,--- - -r,,--f, -- - _, RMS OVERRDE ZENER Fig. SPB Master Connection Diagram Typical Current Sensor Connections for 2 A (Compact) and Less Frame Ratings 5

6 EXTERNAL SHORTNG STRAPS 4 PONT GFP T.B. PRMARY CURRENT SENSORS TOP END A A A v v v BOT. END D - -- '-----"!'-''----'-- - -- - -- ----, 5; 2 BASC BREAKER NTERNAL CONNECTONS (PARTAL ONLY) 4 --<,---, : ' _ DGTRP RMS _ j _j NEUTRAL SENSOR f.\ EXTERNAL SHORTNG STRAPS MUST BE N PLACE DURNG TEST NG AND OPERATNG CONDTONS \:..) PER NSTRUCTON N.P. ON SDE OF BREAKER. f?\ CONNECT NEUTRAL SENSOR SO THAT POLARTY RELATONSHP TOWARDS SOURCE S DENTCAL FOR \J PHASE AND NEUTRAL SENSORS. Fig. SPB Master Connection Diagram Ground Fault External Connections 3PH., 4W., Residual, 225345 A Breakers (2 A in 22 in. High Frame)

POLARTY MARKNGS -+--- 4.3 ----.. +---- 5. ---+ _ J..,- L.. L- Sensor Rating Amperes 4 BOO 2 6 2C * _Jr -- TO, ' J...J Style No. 26D25G 26D25G3 26D25G4 26D25G2 26D25G5 * "C" denotes 2 amp in 6 inch frame. Fig. 2 Neutral Current Sensor (4-2C A).-32 THD. 2 TERMNALS.25.5

.. r 2.4-3 TH D. 4 HOLES.5 "\ \,, ' + #" Lf l ).2 DA 4 HOLES -/ -.4.. J // ''\ (,;... "' Sensor Rating Amperes *3... --- POLARTY MARKNGS / "'>'{ r.?"...\ \ ''\ r )-{ "'' {,! /:. t\ T '--' // \, 2.2 2.2 6.35 \ ---- - -- - - - --- Style Number 26D26G3 : - -..L - L - * Used also in 25A and 2A (22 inches High) Frames Fig. 3 Neutral Current Sensor (3, 25, 2 A) - 3.35 'T' 3.5 5. _t 5 2.625.-32 THO. 2 TERMNALS r-''" t. l l_ h-h.35 t \. 3. -t,.,- H-r- Jl / 4.2

.4-b-.3 3. 6.!.2 DA. 4 HOLES J..6 } 5 4. 2.3 t r """ 3.5! J r;.2 \!:: Fig. 4 Neutral Current Sensor (4, 5 A) POLARTY MARKS 4..4 ---- ---- ----- ----- = 3. l--.25-.4 6.6 2.25.3 Sensor Rating Amperes Style Number 4 36D6G 5 36D6G2 ---"

2 DGTRP RMS Trip Unit Retention Screws (4) Plastic Cover. -- Meter Seal Fig. 5 View of nstalled Digitrip RMS Trip Unit with Sealed Cover Westinghouse Electric Corporation Distribution and Control Business Unit Electrical Components Division Pittsburgh, PA 522 Style No. 232CH