Product Instruction. Door Control Board: Board 1Ø4 for PM/SSC (R3)

Similar documents
Door Operator Conversion Package: Type M to PM/SSC or HPM/SSC with Board 1Ø4

Complete Installation Manual for the ECI LCD Board

Complete Installation Manual for the ECI LCD Closed Loop Door Operator Board

NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

MDC V, 30A Brushless Controller. User s Guide L East Orangefair Lane, Anaheim, CA

Electronic Dynamo Regulator INSTRUCTION MANUAL. COPYRIGHT 2014 CLOVER SYSTEMS All Rights Reserved

DESCRIPTION OF OPERATION EcoSpace elevator with KCM831 control

ECU. Speed Switch Manual. Contents. ECU is a registered trademark of Engineering Concepts Unlimited Inc.

RCP200 Series Motor Controls. Instruction Manual Model RCP Model RCP Model RCP202-BC1 Model RCP202-BC2 Model RCP205-BC2

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Troubleshooting Bosch Proportional Valves

CN0055 & CN0055B DC to DC NEGATIVE RESISTANCE SPEED CONTROL

Electronic Dynamo Regulator INSTRUCTION MANUAL. COPYRIGHT 2014 CLOVER SYSTEMS All Rights Reserved

Coleman Air Diversion Controller Model C40

BLDPN30001 Series. 30A Brushless DC Controller. User s Guide E. Landon Drive Anaheim, CA

Trademarks All trademarks or registered product names appearing in this document are the exclusive property of the respective owners.

715B CONTROL SERIES. Instruction Manual Line Voltage DC Brushless Motor Control CONTROLS. Phone (317) Fax (317)

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

BLDC SPEED CONTROL INSTRUCTION MANUAL Line voltage Brushless DC control

BLDC SPEED CONTROL INSTRUCTION MANUAL Low voltage Brushless DC control

CURTIS TRANSISTOR MOTOR CONTROLLER

ADVR-12. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

MDC Series

MDCSL V, 30A

MDC Series

Understand how soft starters operate.

MDC VAC Input Brushless Controller. User s Guide E. Landon Drive Anaheim, CA

MDCKB VAC, 8A Brushless Controller. User s Guide E. Landon Drive Anaheim, CA

Coleman Air C440-HVM 440 Amp Diversion Controller Version 3.2

Powers TM Controls EA 338 Electronic Actuator

MODEL RMS INSTALLATION INSTRUCTIONS. CONTENTS Page A. Introduction 1. Usage 2 2. How it operates 2

MDC VAC, 15A Brushless Controller. User s Guide. 910 East Orangefair Lane, Anaheim, CA

2. AC SERVICE AND MOTOR REQUIRED 1. ENCLOSURE REQUIRED

DFC-1 STANDARD TEMPERATURE CONTROL. DFC-2 TEMPERATURE CONTROL w/ INTEGRAL 40 F-90 F SELECTOR DFTD TEMPERATURE SELECTION DIAL DFTS TEMPERATURE SENSOR

BSC Series

PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY

Stir-Guard Operation. Instructions Design III Stir-Guard Option

Features IN THIS CHAPTER

FM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

5600 Series Power Operator Installation and Instruction Manual

Boston Gear Ratiotrol DC Motor Speed Control

ASSA ABLOY Series Power Operator Installation and Instruction ASSA Manual ABLOY ASSA ABLOY

Model No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Series BFM Bulk Flow Monitor 1A FUSE RED LED RELAY. Part Number BFM-1 BFM-2 BFM-3 BFS-1

MODEL CMS INSTALLATION INSTRUCTIONS A. INTRODUCTION 1. USAGE 2 2. HOW IT OPERATES 2 B. SPECIFICATIONS 1. ELECTRICAL 3 2.

PRODUCT / TEST MANUAL 2C58K2 INSTANTANEOUS OVERCURRENT

AVR Hybrid Universal Analog Digital Voltage Regulator Operation Manual

CONTROL FEATURES AVAILABLE OPTIONS

TRAC-3 TENSION READOUT AND CONTROL

MBDC V, 10A Brush Controller. User s Guide East Landon Drive, Anaheim, CA

MODEL 422 Submersible Pump Controller

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

5001TCP SPEED CONTROLLER

CN0124 STEP MOTOR DRIVE

TM4500. Track Mounted Step Motor Driver. User s Guide. CE Certified and RoHS Compliant #L010060

INSTALLING, OPERATING AND MAINTAINING THE MODEL D1028 COMPUTER INPUT BI-DIRECTIONAL GENERATOR FIELD REGULATOR INSTRUCTION MANUAL # S-225

Electro-Mechanical Swing Operator. Table of Contents

MBD Enhanced Step Motor Driver. User s Guide #L East Orangefair Lane, Anaheim, CA

Series 20 Installation Instructions

MDC Series

ESD5500E Series Speed Control Unit

E.S.P. Embedded Sensing Probes for Motor Brushes

Installation Instructions

Graham. Vari Speed S1000 Instruction Manual. TRANSMISSIONS, Inc. Installation, Operation and Maintenance Manual

Coleman Air Diversion Controller Model C40

MDCKB VAC, 8A Brushless Controller. User s Guide E. Landon Drive Anaheim, CA

VA-715x Electric Valve Actuator

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

Mounting and operating instructions EB 5801 EN. Electric Actuators Type 5801 (Rotary Actuator) Type 5802 (Linear Actuator)

BLY34MDA Series. 50V, 30A Brushless Controller / Motor. User s Guide E Landon Drive, Anaheim, CA

DENISON HYDRAULICS Jupiter 500 Driver Card Series S

DMX-A2-DRV Integrated Advanced Step Motor Driver

DUAL SWIVEL REEL OPERATING INSTRUCTIONS

Installation Instructions

MODEL ELC-12/40-CVM-D BATTERY CHARGER

1/4HP - 7.5HP 120/240/277 VOLTS 50/60HZ

Parr Instrument Company

CBC-802 Plug-In Clutch/Brake Control with Solid State Switching

MaxPak Plus Analog DC V S Drive

DC Variable Speed Drive Panel

USER'S MANUAL MODEL DPS32PG1 DRIVER PACK

MDC Series

METROLOGIC INSTRUMENTS, INC. MX001 Industrial Control Interface Installation and User s Guide

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

User Manual. T6 Tachometer. Online: Telephone: P.O. Box St. Petersburg, Florida 33736

RP-4000 Reserve Power Control

PRODUCT/TEST MANUAL 2C58K37 INSTANTANEOUS OVERCURRENT RELAY

DPD72001, DPD Unipolar Step Motor Driver. User s Guide E. Landon Drive Anaheim, CA

EG1065X. Compatible with Barber Colman* Dyn1-1065X series * Use for reference purpose only and not a genuine Barber Colman product.

SE-3SCR-LM MANUAL MOTOR LOAD MANAGER

BLHV, BLHV-1. High Voltage Step Motor Driver. User s Guide. (714) fax: (714) website:

Euclid Full Voltage Magnet Controller

5001TCP SPEED CONTROLLER

PM300 VOLTAGE REGULATOR INSTRUCTION MANUAL

Clif Mock. CD20 (12VDC) Sampler Drive. User Manual. Manual No A

OIL FIELD ELECTRIC ACTUATOR INSTRUCTION MANUAL SPECIAL APPLICATIONS ACTUATORS Q 6.0.1

OnCommand Troubleshooting Guide Hayward Industries

ESC2301. Universal Electronic Governor Controller Operation Manual

Transcription:

Door Control Board: Board 1Ø4 for PM/SSC 61111-149 (R3) 2000-08-31

2000, 1992 KONE Inc. Unpublished work. All rights reserved. No portion of this volume may be used or reproduced in any manner without written permission from KONE Inc. One KONE Ct; Moline, IL 61265 Due to our policy of continuing improvement, we reserve the right to alter design and specification without prior notice. The right to make changes to product design and material use, without notice, is reserved. All hardware and software referenced in this publication and/or used in conjunction with equipment described herein is the exclusive property of KONE Inc. whether or not protected by U.S. and/or International Trademark, Copyright and/or Patent Laws. All rights reserved. 2 (R3) 2000-08-31

DOOR CONTROL BOARD: Board 1Ø4 for PM/SSC Equipment description 4 Features of door operators with Board 1Ø4..................... 4 Input & output terminals............................ 5 Installing door operator control Board 1Ø4 6 Adjusting door operator control Board 1Ø4 8 Measure current (optional)......................... 9 Set potentiometers............................... 9 Adjust door speeds.............................. 10 Adjust door closing force.......................... 12 Adjust nudge speed.............................. 13 Set microswitch cams............................ 14 All rights reserved. 3 (R3) 2000-08-31

Equipment description Solid state door operators with Board 1Ø4 are described as follows. Features of door operators with Board 1Ø4 Input & output terminals FEATURES OF DOOR OPERATORS WITH BOARD 1Ø4 Door operators with Board 1Ø4 control have following operations and features: 149-001 (8/2000) Door control power Current control Speed & travel limits Acceleration & deceleration Troubleshooting & switch adjusting Auxiliary piloting Other features Door control power. Door operator control uses a low voltage permanent magnet DC motor. DC motor is powered by pulse width modulated power (high speed switching - 20,000 Hz). Motor responds to average voltage of high frequency pulses, and not individual pulses. Current control. Door operator control has a current sensing circuit in both open and closed directions to supply feedback to speed control circuit. Current sensing circuit regulates door closing force, and open/stall current caused by a hooked interlock. Current sensing circuit also guarantees that door operator control relay contacts do not break or make when motor armature current is present helping to prevent damage to relay contacts. Motor direction is controlled by reversing armature connection using a conventional relay system. Speed & travel limits. Door operator control selects speed and travel limits with cam operated microswitches. These microswitches operate relays tied into speed direction circuits. Acceleration & deceleration. Door operator control has an internal soft-start circuit which regulates smooth acceleration and deceleration. Soft-start circuit allows average motor voltage to change gradually when speeds change. Board 1Ø4 Troubleshooting & adjusting switches. Door operator control has two small toggle switches mounted on common circuit board. TEST/RUN switch and O-OFF-C switch are used to signal door opening or closing from car top during troubleshooting and adjusting; and to disconnect the door open and close signals, and de-activate internal shutdown timer. Auxiliary piloting. Door operator control also has a Form C Open and a Form C Closed relay contact for auxiliary piloting. Other features. Additional items added to Solid State door control. All rights reserved. 4 (R3) 2000-08-31 Non-adjustable open current limit set at 5 amps. Non-adjustable internal shutdown timer removes power if doors do not open or close within 20 to 30 seconds after a direction signal is given. Shutdown indicated by an illuminated LED 7. F615-002 (3/97)

INPUT & OUTPUT TERMINALS The PM/SSC door operator control requires an input of single phase 115 VAC. When this power is supplied by a transformer, the transformer must have rating of at least 500 VA. Input and output terminal signals are connected to TB1 (3). 149-002 (8/2000) Input & Output Terminals L1A to L2A DO3 to L1A DO7 to L1A DO10 to L1A DO17 to L1A Required for door to operate 120VAC @ 500VA input. If one of input lines is grounded, it should be connected to L1A. Open limit signal. A relay across these terminals de-energizes when open limit microswitch is actuated. Relay is energized at all other times. Signal to close. When a relay contact across these terminals makes up, doors should close. Signal to open. When a relay contact across these terminals makes up, the doors should open. Close limit signal. A relay across these terminals de-energizes when close limit microswitch is actuated. Relay is energized at all other times. DO3 to DO10 DO7 to DO17 DO4 to DO7 Optional Auxiliary to O relay. A relay across these terminals should be energized only when doors are opening. Auxiliary to C relay. A relay across these terminals should be energized only when doors are closing. Reduced speed closing signal. When doors have a signal to close, and a relay contact across these terminals makes up, door speed is controlled by N potentiometer. F NC NO Auxiliary C relay switching contact. C Designates a Form C contact on a 1-C relay. F NC NO Auxiliary O relay switching contact. O Designates a Form C contact on 1-O relay. DSD to SS Optional - Used on some projects for load balancing or other customer requirement. F615-SI1 (3/97) All rights reserved. 5 (R3) 2000-08-31

Installing door operator control Board 1Ø4 The following describes replacing a three or four door control board with a single Door Control Board 1Ø4. Complete the following to install door operator control Board 1Ø4. When replacing a four-board system, a cable assembly (90527-022) must be used. This cable replaces the wires on the existing common board. 1. Turn OFF, lock-out, and tag mainline disconnect. 2. Disconnect the two transformer primary wires from the terminal strip on the common board. High performance operators will have two wires in each terminal. Keep twowire sets together so they can be replaced correctly on the new door control board. If the door operator is a high performance operator, the J4 jumper must be in the high performance position. 3. Unplug the molex connector. This does not apply to four-board systems. 4. Remove 45 VDC supply wires and motor wires from power board. Mark wires for correct polarity. 5. Remove wires connected to main terminal strip on common board. Label each wire to indicate which terminal the wire will be connected to later. 6. Remove common board. 7. Replace styrofoam spacer with anti-static support spacer. 8. Install new Control Board 1Ø4. 9. Connect wires previously removed from main terminal strip to new control board using labels to match each wire to correct terminal. Door Control Board 1Ø4 does not require terminals on wire leads. 10. Connect 45 VDC supply to terminals +45V and GND of TB2. Red wire is connected to +45V. Black wire is connected to GND. 11. Connect motor wires to terminal A1 and A2 of TB2. Reverse motor wires position as compared to original power board. 12. Plug molex connector into CN1. Make sure wire number 1 of board molex is plugged into pin 1 of molex connector. 13. Connect transformer primary wires L2AX and L1A terminals of TB3. Multiple terminals are furnished for connecting to HPM/SSC power supplies. 149-003 (9/2000) All rights reserved. 6 (R3) 2000-08-31

All rights reserved. 7 (R3) 2000-08-31

Adjusting door operator control Board 1Ø4 Adjust door operator control Board 1Ø4 as follows. Measure current (optional) Set potentiometers Adjust door speeds Adjust door closing force Adjust nudge speed Set microswitch cams Board 1Ø4 could be damaged if adjustment instructions are not followed carefully. If you cannot complete any of procedures as described, stop and request assistance. A604-017 (2/97) Toggle switches To adjust and service door control, use two toggle switches on door operator control Board 1Ø4 TEST-RUN switch and O-OFF-C switch. TEST-RUN. TEST-RUN switch is normally in RUN position. When TEST-RUN switch is in TEST position, it disconnects normal open and close input signals from door control, and switches the O-OFF- C toggle switch into the circuit. O-OFF-C. O-OFF-C switch is normally in OFF (center) position. OFF position does not indicate input power has been removed. It only indicates no signal to open or close when TEST-RUN switch is in TEST position. A604-SI5 (2/97) All rights reserved. 8 (R3) 2000-08-31

MEASURE CURRENT (OPTIONAL) CAUTION: Do not install an ammeter in power supply line. Current measurements are not required to adjust door operator control Board 1Ø4. If necessary, measure current as follows. SET POTENTIOMETERS Make sure all potentiometers are set to ZERO, except P8. Do not set potentiometer P8. It is factoryset and sealed. These multi-turn potentiometers require 25 turns to traverse their complete range. A604-019 (3/97) 1. Connect a voltmeter to resistor R2 (.1 Ohm 5 watt resistor) located between heat sinks Q2 and D2. Viewing from TB1 side of control board, right side of resistor R2 is (-) and left side of resistor R2 is (+). 2. Set voltmeter to a low range 1 volt or 2.5 volt. 3. Read measurement with following in mind. 1 volt on meter indicates 10 amps of current..5 volt on meter indicates 5 amps of current. A604-018 (2/97) All rights reserved. 9 (R3) 2000-08-31

ADJUST DOOR SPEEDS 1. Disconnect and tag-out power. 2. Remove door operator cover and close doors. 3. Set switches and potentiometer in following positions. All speed control potentiometers - fully counter-clockwise. C.C.L. potentiometer - Fully clockwise. TEST-RUN switch - TEST position. O-OFF-C switch - OFF (center) position. Two position jumper J4 - just to right, and slightly above, R01 relay. (Standard position if one pair of wires is present at TB3. High Performance if two pairs of wires are present at TB3.) 4. Apply power. Toggle O-OFF-C switch to O position. LED6 next to PL potentiometer illuminates, indicating doors are in PL zone. 5. Turn PL potentiometer clockwise until doors begin to open. When PL microswitch drops, LED next to PL potentiometer goes out, and LED next to OF potentiometer illuminates. 6. Turn OF potentiometer clockwise, just enough to move doors through OF speed zone. When OSDL microswitch drops, LED next to OF potentiometer goes out, and LED next to OS potentiometer illuminates. 7. Turn OS potentiometer, just enough to move door through OS speed zone. When OL cam activates OL microswitch, LED next to OS potentiometer goes out. Doors should be fully open. 8. Toggle O-OFF-C switch to C position. LED next to CF potentiometer comes on. 9. Turn CF potentiometer clockwise until doors begin to move. When CSDL microswitch is dropped by its cam, LED next to CF potentiometer goes out and LED next to CS potentiometer illuminates. 10. Turn CS potentiometer clockwise until CL microswitch is actuated by its CAM. LED next to CS potentiometer goes out. Doors should open and close at slow speed. If doors do not fully open or close within 20 to 30 seconds, internal timer removes motor power and LED 7 is lit. If board senses over 5 amps, power shuts down and LED 7 is lit. 11. Using speed zone potentiometer and CAM settings, adjust door speeds for desired performance. Green LED s indicate which speed control potentiometer is controlling door speed. Increase door speed turn potentiometer clockwise Decrease door speed turn potentiometer counterclockwise Do not set potentiometer P8. It is factory-set and sealed. A604-020 (4/97) TIP: If doors do not operate smoothly, particularly on slower moving doors, it may help to remove jumper J3. This eliminates dynamic braking, and allows a smoother transition between speeds. A604-SI6 (2/97) All rights reserved. 10 (R3) 2000-08-31

Board 1Ø4 All rights reserved. 11 (R3) 2000-08-31

ADJUST DOOR CLOSING FORCE 1. Toggle TEST-RUN switch to TEST position. 2. Stop doors at mid-point in closing direction by toggling O-OFF-C switch to OFF position. 3. Turn CCL (close current limit) potentiometer fully counter-clockwise until doors stall. 4. Turn CCL potentiometer clockwise until desired door close operation is achieved. Door closing force should be less than 30 pound maximum allowed by Code. 5. To check door pressure, physically stall door at midpoint in closing direction. 6. Place rubber end of a pressure gauge (1) on edge of power-driven car door (3). Read pounds of force (2) on gauge and record results. 7. Open and close doors with O-OFF-C switch several times. 8. Physically stall doors again in closing direction and re-check door closing force with pressure gauge. If door closing force CANNOT be kept under 30 pounds, contact the door factory. A604-021 (9/2000) All rights reserved. 12 (R3) 2000-08-31

ADJUST NUDGE SPEED 1. Simulate a nudge signal by placing a jumper on terminal strip TB-1 between L1A and DO4. 2. Set the TEST-RUN switch to TEST position. 3. Set O-OFF-C switch to C position. Doors should close at nudge speed. 4. Turn the N potentiometer clockwise to desired nudging speed. 5. Remove jumper between L1A and DO4 before returning the TEST-RUN switch to RUN. F615-010 (2/97) When all adjustments are complete, place O-OFF-C switch in OFF position, and TEST-RUN switch in RUN position. Replace door operator cover. A604-SI7 (2/97) All rights reserved. 13 (R3) 2000-08-31

SET MICROSWITCH CAMS PM/SSC door operator microswitch cams determine where changes in door speed occur. Factory settings are approximate. Set microswitch cams, if necessary, per individual job requirements. CL PL OSDL CAM actuates CL microswitch when doors are in their desired fully closed position. Initial opening CAM drops microswitch when car door clutch has just engaged both hoistway door rollers, but should not drop microswitch if door interlock hangs up. CAM drops OSDL microswitch when doors are approximately half open. CSDL OL DSD CAM drops CSDL microswitch when doors are approximately 4 inches [10.2 mm] from their fully closed position. CAM actuates OL microswitch when doors are in fully open position. (optional) CAM actuates DSD microswitch when doors are approximately 4 to 6 inches [10.2 to 15.2 mm] from fully closed position when used with load balancing. CAM can also be set for other customer requirements. F615-009 (2/97) All rights reserved. 14 (R3) 2000-08-31

Door in closed position Door in open position All rights reserved. 15 (R3) 2000-08-31

NOTES All rights reserved. 16 (R3) 2000-08-31