CONDUIT 27/01/2009 Technical Data Sheet Page No. 1 Applications Hospitals External Safety Critical Area Fittings IP54 SPB Fittings type A & B Characteristics Very High UV Resistance High Flexibility Medium Fatigue Life High Mechanical High Abrasion Resistance Self Extinguishing High EMI Approvals CE LVD IEC61386 Material Operating Temperature: Galvanised Steel PVC Covering Tinned Copper Braid Static: 15 C +70 C Moving: 5 C +90 C Part No. NC Size NW Pitch (B) Inside Diameter (A) Outside Diameter Dimensions Reel Length (C) Min Bend Radius Colour SPTC 6.8.0 SPTC12 13.3 14.0 SPTC16 16 13.0 17.5 30 SPTC20 20 16.9 21.5 35 SPTC 21.4 26.0 55 SPTC32 32 28.1 34.0 60 SPTC40 40 37.7 43.6 80 SPTC50 50 48.4 56.0 90 Adaptaflex, Station Road, Coleshill, B46 1HT United Kingdom Tel: +44(0)1675 468222 Fax: +44(0)1675 464930 email: sales@adaptaflex.co.uk www.adaptaflex.com
CONDUIT 27/01/2009 Technical Data Sheet Page No. 2 Mechanical Properties Method/Standards Requirements Value Crush Strength @ 23 C IEC613861 <% reduction in diameter after load N Crush Strength @ 23 C % Crush, instantaneous value 2200N Impact Strength @ 23 C IEC613861 No Cracks diameter torpedo gauged 20J (Class 5) Impact Strength @ C IEC613861 No Cracks diameter torpedo gauged 6J Tensile Strength @ 23 C IEC613861 With A Type Fittings 00N Tensile Strength @ 23 C Ultimate pullout of Atype fitting 1450N Static Bend Radius @ 23 C 45mm Dynamic Bend radius @ 5 C IEC613862.3 5000 cycles @ 50mm Pass Thermal Properties Method/Standards Requirements Value Minimum Temperature Static Permanent use 15 C Maximum Temperature Static Permanent use +70 C Minimum Temperature Dynamic IEC613862.3 5000 cycles 5 C Maximum Temperature Dynamic IEC613862.3 5000 cycles 90 C Maximum Short Term static 3000 Hours Maximum 90 C Flammability, Smoke and Toxicity (FST) Performance Method/Standard Requirement Result Unit Halogen Free No Phosphorus Free Yes Sulphur Free Yes Oxygen Index ISO 4589 % Oxygen to support combustion 28 % Glow Wire rating IEC 60695 No ignition, extinguish within 2 s 850 C Flammability UL94 Vertical (V0, V2) or Horizontal (HB) V0 Flammability IEC613861 1kW burner @ 45 Pass Pass/Fail Pre test Conditions Duration 168 (Hours) Standard EN50086/IEC61386 Temperature 23 ( 0 C) Relative Humidity 50 (%) Adaptaflex, Station Road, Coleshill, B46 1HT United Kingdom Tel: +44(0)1675 468222 Fax: +44(0)1675 464930 email: sales@adaptaflex.co.uk www.adaptaflex.com
CONDUIT 27/01/2009 Technical Data Sheet Page No. 3 EMC Screening The graph below shows the results of SPTC20 screened conduit, with its appropriate fittings, tested by ERA Technology ti IEC 600962:1993 Radio Frequency Cables Part 1 Tests measured attenuation in decibels (db) over the frequency range covered by the EMC directive. 0.1 to 00MHz. Overbraiding Details Tinned copper wire OD 0.28 0.30mm. 32 carriers, 8 wires per carrier. Minimum 90% braid coverage. EMI Screening effectiveness of SPTC conduit 1 0 90 80 Attenuation (db) 70 60 50 40 30 0.1 1 0 00 Frequency (MHz) Adaptaflex, Station Road, Coleshill, B46 1HT United Kingdom Tel: +44(0)1675 468222 Fax: +44(0)1675 464930 email: sales@adaptaflex.co.uk www.adaptaflex.com
CONDUIT 27/01/2009 Technical Data Sheet Page No. 4 Chemical Properties Astm No.1 Astm No.2 Astm No.3 Acetic Acid (%) Acetone Aluminium Chloride Aniline Benzaldehyde Benzene Carbon tetrachloride Chlorine water Chloroform Citric Acid Copper Sulphate Cresol Diesel oil Diethylamine Ethanol Ether Ethylamine Ethylene Glycol Ethyl Ethanoate Freon 32 Hydrochloric Acid (%) Hydrochloric Acid (36%) Hydrogen Peroxide (35%) Hydrogen Peroxide (87%) Lactic Acid Lubricating oil Suitable Limited Suitability Methanol Methyl Bromide MEK Nitric Acid (%) Nitric Acid (70%) Oxalic Acid Ozone (Gas) Paraffin oil Petrol Phenol Sea Water Silver Nitrate Skydrol Sodium Chloride Sodium Hydroxide (%) Sodium Hydroxide (60%) Sulphur Dioxide (Gas) Sulphuric Acid (%) Sulphuric Acid (70%) Toluene Transformer Oil 1,1,1Trichloroethane Trichloroethylene Turpentine Vegetable Oil Vinyl Acetate Water White Spirit Zinc Chloride The information above is given as a guide only and is based on published technical data and experience. The chemical resistance of the above products is dependant on factors such as chemical exposure, concentration of the chemical and temperature. The above chemicals are valid for a temperature of 23 C. Use of the above table is at the users own discretion and risk. Those using it must satisfy themselves that their application presents no health and safety risks. The end user should assess compatibility with their application and contact Adaptaflex for further information. IEC 61386 CLASSIFICATION Fitting Compression Impact Min temp Max temp Bending Electrical IP Solids IP Water Corrosion Tensile SPTC SPB 4 4 2 2 4 3 5 4 4 NonFlame Propagation 1 Suspended Load 5 Adaptaflex, Station Road, Coleshill, B46 1HT United Kingdom Tel: +44(0)1675 468222 Fax: +44(0)1675 464930 email: sales@adaptaflex.co.uk www.adaptaflex.com
CONDUIT 27/01/2009 Technical Data Sheet Page No. 5 Dimension charts for associated fittings TYPE A TYPE B Adaptaflex, Station Road, Coleshill, B46 1HT United Kingdom Tel: +44(0)1675 468222 Fax: +44(0)1675 464930 email: sales@adaptaflex.co.uk www.adaptaflex.com