Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80

Similar documents
Unit Protection System for Pumped-Storage Power Stations

KD LV Motor Protection Relay

19 A.C. Motor Protection

A21M. Introduction: Functional Overview: Key Protection & Control Functions:

Bulletin 825 SMM Smart Motor Manager

XM1 - Motor protection relay

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

3.2. Current Limiting Fuses. Contents

5. OVERCURRENT RELEASE (OCR)

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

34 th Hands-On Relay School

That s how compact transformer protection is today. The customer newsletter of Kries-Energietechnik

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

Source-Side Fuse/Load-Side Recloser Coordination

Variable speed application guidelines

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

QS20.241, QS C1

Dual Power. Protection. Protection

5. OVERCURRENT RELEASE (OCR)

APPLICATION GUIDE. Pure easiness for a wide range of applications ACS580 general purpose drives

Chapter 5 FOUNDATION. 2010, The McGraw-Hill Companies, Inc. 2010, The McGraw-Hill Companies, Inc.

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

825-P Modular Protection System for motors Specification Guide

LARSEN & TOUBRO LIMITED TYPICAL SCHEME FOR PROTECTION OF SYNCHRONOUS MOTORS

ACS motor protection circuit breakers KT 7 Introduction

Direct On Line (DOL) Motor Starter. Direct Online Motor Starter

Operating instructions Flow monitors SI5002 SI5003 SI / / 2012

MAGNETIC MOTOR STARTERS

Selective Coordination Requirements

DC-PMM/24V Power Management Modul für Positionier-Motor POSMO A Power Management Module for Positioning Motor POSMO A

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

Exercise 1-5. Current Protection Devices EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Circuit breakers

1MRB Uen Edition September Multifunction Relay Types MCX 912 and MCX 913. Operating Instructions. Home

Using an SMC-50 Solid-State Smart Motor Controller for Pump Protection

AC Motor Protection. Course No: E Credit: 3 PDH. Velimir Lackovic, Char. Eng.

PROTECTION OF THREE PHASE INDUCTION MOTOR AGAINST VARIOUS ABNORMAL CONDITIONS

New range of reclosing systems

Series Motor Protection

A problem with the motor windings. A phase loss on mains terminals L1, L2, or L3 during run mode. Parameter 2-3 Current Imbalance Delay.

Application Note. First trip test. A circuit breaker spends most of its lifetime conducting current without any

UNIVERSAL PUSHBUTTON DIMMER ETD 2 (Rail mount version)

HVW701 HVAC Drive with By-Pass

1332 TROUBLESHOOTING GUIDE. Remarks: If this function is not appropriate for the application, it can be eliminated by turning off DSWl, switch 3.

Electronic fuses to protect 24V DC load circuits

DESCRIPTION EMERGENCY POWER FUNCTION

Operating Manual (Edition 04/2004) sinamics. Braking Module / Braking Resistor SINAMICS G130

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

8 Troubleshooting and Maintenance

Technical Information

INTRODUCTION. Specifications. Operating voltage range:

Shippensburg University

Operating instructions Flow monitors SI6000 SI6100 SI /00 06/2011

Design Standards NEMA

Power Electronics. Motor brake relay GA 9031 ministop

Full Voltage Starting (Number of Starts):

Operating instructions Flow monitors SI6600 SI6700 SI /02 01/2011

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

Elbtalwerk GmbH. Universität Karlsruhe Elektrotechnisches Institut. Switched Reluctance Motor. Compact High-torque Electric Motor. Current.

Motor Protection Fundamentals. Motor Protection - Agenda

Installation Manual for DC Injection Brake Units

The behavior of the cycloconverter fed gearless drive under abnormal electrical conditions

Protective Device Coordination ETAP Star

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

Application Note CTAN #146

Electrical network protection VIP30, VIP35. User s manual 12/2008

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008

DESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN)

MX431 Generator Automatic Voltage Regulator Operation Manual

LV Capacitor Bank APC

Breaker failure relay REB 010

Chapter 3.2: Electric Motors

APPLICATION NOTE AN-ODP March 2009

ATyS d M Remotely operated Transfer Switching Equipment from 40 to 160 A

DPX moulded case circuit breakers

Application Note RESIDUAL BUS MAIN-TIE-MAIN AUTOMATIC TRANSFER SCHEME USING THREE GE 850 RELAYS

3 - Protection components Motor circuit-breakers

AP1000 European 7. Instrumentation and Controls Design Control Document

EXPERIMENT CALIBRATION OF 1PHASE ENERGY METER

Standby Power Systems

Copyright 2003 Advanced Power Technologies, Inc.

Motor Protection Application Considerations

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

Operating instructions Flow monitors SI / / 2010

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications

Application Description

2013 Grid of the Future Symposium. Utilizing Single Phase Operation Scheme on Untransposed 765kV lines for a Stability-Limited Plant

Thermal-magnetic Miniature Circuit Breaker 4230-T...

Data sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427

LED Driver Linear / area fixed output industry. Driver LCI 65W 150mA 400mA TOP INDUSTRY sl TOP series

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

Silvertel. Ag Features. Multi-Stage Charging. Battery Reversal Protection. Reduced Power Consumption. Wide DC or AC Input Voltage Range

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

Variable Frequency Drive Basics

HGM6410/6420 AUTOMATIC GENERATOR MODULE WITH J1939 INTERFACE SOFTWARE MANUAL

LED Driver Linear / area fixed output industry. Driver LCI 100W 350mA 900mA TOP INDUSTRY sl TOP series

three different ways, so it is important to be aware of how flow is to be specified

5220 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL

Transcription:

Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80 Motor settings using the SIPROTEC Compact motor protection relay 7SK80 is explained below. Information is given on how to use the motor s existing technical data to derive meaningful settings. Among other things, dynamic cold load pickup to reduce overcurrent settings during normal operation is explained. As an option, an internal RTD card or an external RTD-box can be used to directly monitor the stator and bearing temperatures via temperature sensors. Fig.1: SIPROTEC Compact 7SK80 1. SIPROTEC Compact 7SK80 The SIPROTEC Compact motor protection relay 7SK80 offers motor protection functions for mediumpower motors with the following scope: no. Protection function ANSI no. 112 Time-overcurrent protection, phase 50,51 113 Time-overcurrent protection, ground 50N,51N 116 Directional ground fault protection 67N(s),59N 117 Dynamic cold load pickup 140 Negative sequence protection 46 141 Motor starting protection 48 142 Thermal overload protection 49 143 Motor restart inhibit 66,49R 144 Load jam protection 51M 150 Undervoltage protection 27 190 Temperature monitoring 38 191 External temperature input connection type Energy Automation 08/2011 Page 1 of 11

2. Available motor data Not all data are available in our example. Unfortunately, this all too frequently reflects reality, for example when a motor has been in operation for a very long time and complete documentation is no longer available or only the data on the motor s rating plate are available. Given: Compressor motor for compressed air in an industrial plant: Size Power Rated voltage Motor rated current Max. starting current (at 100% Vn) Starting time (at 100% Vn) Heating time constant Cooling time constant at standstill Max. continuous thermal rating current Max. blocked rotor time 780kW 10kV 54A 250A 5sec 40min 140min 60A 10sec 0213 Voltage transformer connection 0204 Transformer rated current, phase primary 0205 Transformer rated current, phase secondary 0217 Transformer rated current, ground primary 0218 Transformer rated current, ground secondary 0202 Transformer rated voltage, primary 0203 Transformer rated voltage, secondary Vab, Vbc, Vn 75A 1A 60A 1A 10kV 100V 3. General power system data The current and voltage transformer data and the type of connection are entered in the unit under Power System Data 1. Current transformer 75A/1A Core-balance current transformer 60A/1A Voltage transformer 10kV/100V Isolated power system Fig.2: Connection diagram 7SK80 Energy Automation 08/2011 Page 2 of 11

4. Motor starting protection The settings for the motor starting protection require the starting current and the starting time. In our example, the blocked rotor time is not critical because it is longer than the starting time (10sec in comparison to 5sec). The associated setting for the locked rotor time is deactivated (key in a lower-case o twice for infinite). The motor starting protection can quickly respond to a blocked rotor, and external wiring with a speed monitor is dispensed with. As the guaranteed starting time (5sec) and the maximum blocked rotor time (10sec) are specified in the technical data, the protection setting must lie in between. In our specific case, the value 7sec was chosen. Taking the current transformer ratio into account, the maximum starting current is calculated as I Start = 250A/75A = 3.33. 4102 Maximum startup 3.33 current 4103 Maximum startup time 7sec 4104 Locked rotor time oo 5. Thermal overload protection Typical characteristic quantities designate the overload function, namely: maximum permissible continuous operating current, heating (heat-gain) time constant and cooling time constant at standstill. The maximum current is often not specified in the technical data. According to experience, a setting 10% above I N,Motor can be used and, in our case, I N,Motor,max = 60A is already specified. Hence the k-factor (parameter 4202) is I Motor,max / I N,CT,prim = 60A/75A = 0.8. The 40min heating time constant can be adopted directly as the setting. The overload protection function also takes cool-down behavior into account because different prerequisites for the motor (with or without fan) produce differing cooldown behavior. The value is set under parameter 4207A as a heating to cooling factor, i.e. 140min/40min = 3.5. The thermal warning stage, parameter 4204, offers an additional warning before tripping. This is why it should be set to below the 100% tripping threshold. On primary side the k factor is given by the ratio of maximum continuous thermal rating current to motor rated current (k=60a/54a=1.11). The thermal value at rated current is calculated as 1/k 2 =1/(1.11 1.11)=0.81. Therefore parameter 4204 must be set higher than the calculated value. In our specific case we select 90%. The current alarm stage ( 4205) can be set as the maximum continuous thermal rating current (60A/75=0.8A). 4208A, dropout time after emergency starting, is active only if coupling in via a binary input has been realized, so as to allow emergency starting for the overload protection function despite the presence of an overload TRIP signal. Energy Automation 08/2011 Page 3 of 11

4202 k factor 0.8 4203 Time constant 40min 4204 Thermal alarm stage 90% 4205 Current alarm stage 0.8A 4207A Kt time factor at 3.5 motor standstill 4208A Dropout time after 100sec emergency starting Under System Data 2 there is an important setting that defines the interplay of overload protection and motor starting protection (parameter 1107). The overload protection function is active up to this setting, the device detects higher current values as motor starting, the motor starting protection runs and the thermal overload model does not increase any further. It is advisable to set the value to approximately 50 % of the starting current (in our case 250A/2 = 125A, taken into account as the secondary value with the current transformer ratio of 75A/1A = 1.66A). Thus, starting at low rated voltage is detected and protection is provided against sufficiently high overloads above the maximum current (110 % of I N ). 1107 Motor starting current (blk overload) 1.66A Direct measurement of temperatures Either 5 internal RTD inputs (devices 7SK805 and 7SK806) or up to 12 RTD inputs through external RTD boxes can be applied for temperature detection. Thus, the thermal state can be monitored, in particular on motors, generators and transformers. The bearing temperatures of rotary machines are also checked to detect when limit values are exceeded. Temperatures are measured by sensors at different points on the protected object and are fed to the device. By way of example we consider an application with 5 temperature sensors (Figure 3): The ambient or coolant temperature can be fed to the overload protection function of the 7SK80. To this end, the necessary temperature sensor must be connected to sensor input 1 of 7SK805 or 7SK806. Since 50% of all motor failures are caused by overheating of the bearings, normally redundant sensors are used there. These sensors are connected to the RTD inputs 2 to 5. The stator temperature is calculated in by the current through the stator windings. Large motors might request a stator temperature measurement per phase. For this an RTD box with 12 RTD inputs can be connected either through RS485 on Port B (RTD box type 7XV5662-6AD10) or Ethernet Port A (RTD box type 7XV5662-8AD10). Figure 4 shows an alternative application of 7SK805 or 7SK806 with 5 internal RTD inputs: The stator temperature is measured by one temperature sensor per phase. Two further temperature sensors are used for the bearings. As all calculations are run with scaled quantities, the ambient temperature must also be scaled. The temperature at rated current is used as the scaling quantity. If the rated current deviates from the rated Energy Automation 08/2011 Page 4 of 11

transformer current, the temperature must be adjusted with the help of the following formula under parameter 4209, temperature at rated current. ϑ N sec ondary = ϑ N, M I I Nprim N, M 2 ϑ Nsecondary = 80 C (75/54) 2 = 154 C 4209 Temperature at rated current 154 C For example ϑ N,M =80 C (obtained by measurement), then Fig.3: Application with 5 temperature sensors for bearings and coolant Fig.4: Application with 5 temperature sensors for stator windings and bearings Energy Automation 08/2011 Page 5 of 11

Load jam protection for motors (ANSI 51M) A sudden high load may lead to deceleration or even rotor blocking that causes mechanical damages. The sudden rise in current is detected by the load jam protection function and can initiate an alarm or a trip. The thermal overload protection is too slow and therefore improper in this case. The load jam threshold value of the tripping element (parameter 4402) is usually configured below motor startup at double motor ampere rating. In our example 4402 will then be 2 54A/75=1.44A. The load jam warning element (parameter 4404) is naturally set below the tripping element, to approximately 75% of the tripping element. In our example parameter 4404 is 0.75 1.44A=1.08A. Due to the threshold setting below the motor startup current, the load jam protection must be blocked during motor startup. Through parameter 212 BkrClosed I MIN motor standstill is detected. In this condition the load jam protection is blocked. After having closed the circuit breaker, the blocking is maintained during motor startup by parameter 4406. In order to avoid malfunctioning, it is set to the double startup time. In our example we will get 2 5sec=10sec. 4402 Load Jam Tripping Threshold 4403 Load Jam Trip Delay 4404 Load Jam Alarm Threshold 4405 Load Jam Alarm Delay 4406 Load Jam Blocking after motor start 1.44A 1.00sec 1.08A 1.00sec 10.00sec 6. Motor restart Inhibit To protect the rotor a second thermal model is created in the motor restart inhibit function. The main focus is placed on the number of starts from the cold and warm states. These data are not available in our case and so three cold starts (nc) and two warm starts (nw) are assumed. The rotor temperature equalization time (parameter 4304) defines the minimum dead time between individual starts. For this parameter 1min has proven to be a good value. 4302 the quotient of starting current to rated motor current - results in 250A/54A = 4.6. The maximum permissible starting time (parameter 4303) can be taken directly from the motor data (5sec). The rated motor current is calculated as I N,Motor / I N,CT,prim = 54A/75A=0.72. If data are not available, the cooldown behavior for the motor restart inhibit function can be assumed similarly to the cool-down behavior for overload protection. In the case of overload protection, this was Energy Automation 08/2011 Page 6 of 11

140min/40min=3.5. For the motor restart inhibit function, this is entered under parameter 4308. 4309, Extension of time constant at running, takes effect when activation of the motor was successful and then the motor continues to run in rated operation. Cooling for this is clearly shorter than under parameter 4308 because rotor operation involves intrinsic cooling, and so we choose the factor 2. After three starts in brief succession, the motor restart inhibit function then blocks and issues a release signal after a calculated dead time to enable reconnection once again. The internally calculated dead time depends on the respective load and, accordingly, may differ in length. Alternatively, it is possible to consciously specify a minimum inhibit time (for example, if the customer insists on additional safety factors). This is set under parameter 4310. In our example we use the default value of 6min. 4302 I Start / l Motor 4.6 nominal 4303 Max. Permissible 5sec Starting Time 4304 Temperature 1.0min Equalization Time 4305 Rated Motor Current 0.72A 4306 Max. Number of 2 Warm Starts 4307 Number of Cold 1 Starts Minus Warm Starts 4308 Extension of Time 3.5 Constant at Stop 4309 Extension of Time 2.0 Constant at Running 4310 Min. Restart Inhibit 6.0min Time 7. Negative sequence (unbalanced-load) protection As no further information is available, recommendation-based values are used. In the case of a definite-time tripping characteristic, these are: 10% I2/IN,Motor for warning or longtime delayed tripping and approx. 40% I2/IN,Motor for short-time delayed tripping. The setting values have to be converted for the secondary side by using the transformation ratio of the current transformer (75A/1A). For parameter 4002 the lowest setting value is 0.1A. We recommend 20sec (parameter 4003) and 2sec (parameter 4005) for the corresponding delay times. Energy Automation 08/2011 Page 7 of 11

4002 Pickup Current I2> 0.1A 4003 Time Delay T I2> 20sec 4004 Pickup Current I2>> 0.29A 4005 Time Delay T I2>> 2sec we choose 1.6 (250/75)A = 5.33A. Time delay T I>> (parameter 1802) is selected at 50ms. Initially the peak value of the starting current may be even higher. With time delay T I>>, non-delayed, set at 0 ms, the I>>stage should be set to 2.5 starting current. 1.1 (250/75)A = 3.67A is calculated for the I> stage. 8. Time-overcurrent protection Only the phase time-overcurrent protection is considered; due to the isolated power system grounding, the ground function is covered by the sensitive ground-fault detection. In relation to the phase timeovercurrent protection settings, it must be noted that these must lie above the motor starting values. Due to the short-time occurring motor inrush, the I>> stage must even be set to >1.5 starting current, and so Fig.5: Coordination of protection functions (without dynamic cold load pickup) Energy Automation 08/2011 Page 8 of 11

If a short-circuit current occurs which lies at 2.5 I N,Motor, e.g. due to a contact resistance, the timeovercurrent protection will not pickup. But, as shown in Fig. 5, the motor starting protection will trip. A trip signal will be issued only after a few seconds (>7 seconds in our example), which can lead to enormous damage. It is now possible to reduce the definite-time overcurrent settings during rated motor operation, so as to be able to respond more sensitively to all manner of current faults (see Fig. 6). To this end, the Dynamic cold load pickup option is used: During the normal state, i.e. when the motor is running, lower settings are valid which may already trigger (with a short delay) in the event of faults as from 1.5 I N,Motor (depending on overload conditions). Two criteria are optionally available for detection of the deactivated system and thus changeover to high settings: The circuit-breaker position is communicated to the unit via binary inputs (parameter 1702 Start Condition = Breaker Contact). Falling below an adjustable current threshold (parameter 1702 Start Condition = No Current) is used. Dynamic cold load pickup: 1703 CB Open Time 0sec 1704 Active Time 8sec 1801 Pickup Current I>> 5.33A 1802 Time Delay T I>> 0.05sec 1803 Pickup Current I> 3.67A 1804 Time Delay T I> 0.2sec Definite time overcurrent protection: 1202 Pickup Current I>> 5.33A 1203 Time Delay T I>> 0.05sec 1204 Pickup Current I> 1.08A 1205 Time Delay T I> 1sec The active time parameter 1704 must be set above the motor starting time. The reduced value for I> (parameter 1204) results in 1.5 (54/75)A = 1.08A. Energy Automation 08/2011 Page 9 of 11

Fig.6: Reducing the time-overcurrent protection I> stage during rated operation Additional programming with PLC/CFC logic is not necessary. Changeover takes place automatically. To avoid tripping prematurely with the I> stage 1204 in the event of short-time, substantial overloads (load jumps), the tripping time is set to 1 sec. 9. Sensitive ground-fault detection Sensitive ground-fault detection includes a large number of settings, for example to exactly determine the displacement voltage or to correct transformer errors. We will consider only the essential settings for detection of a directional ground-fault. The other parameters can remain at default settings. The thresholds for the I Ns current must be determined by way of the power system data. To this end, we need the cable lengths and types to calculate the capacitive ground current I CE. Sometimes a load resistor is also connected upstream, so as to arrive at an increased ground-fault current in the event of a displacement voltage. Let us assume a capacitive ground current I CE of 20A. For a protection range of 90%, the protection should already operate at 1/10 of the full displacement voltage (parameter 3109 with 0.1 100V = 10V), where also only 1/10 of the ground-fault current results. Therefore, (20A/(60A/1A)) 0.1 0.035Α is set for parameter 3117. Because the high set element I Ns >> is not needed in our application example, we set it to the highest possible value (parameter 3113=1.6A) and the corresponding time delay to infinite (parameter 3114=oo). With regard to determining the direction, note that the ground current flows in the direction of the protected motor when parameter 3122 forward and parameter 0201 Energy Automation 08/2011 Page 10 of 11

current transformer star point in direction of line are selected and the ground CT is connected as shown in Fig. 2. 3113 Pickup Current 1.6A INs>> 3114 Time Delay T INs>> oo 3117 Pickup Current INs> 0.035A 3118 Time Delay T INs> 5.00sec 3109 VGND> measured 10V 3122 Direction INs> Forward 3125 Measurement SIN Phi Method 10. Voltage protection The motor still has to cope with up to about 80 % of the rated voltage and values below that lead to instability. 5103 Pickup Voltage V< 75V 5106 Time Delay T V< 1.5sec 5111 Pickup Voltage V<< 70V 5112 Time Delay T V<< 0.5sec 11. Summary The motor protection functions of the SIPROTEC Compact 7SK80 derived from the current and voltage inputs result in a combination that offers users effective and low-cost allround protection and which is very frequently utilized for mediumvoltage motors in industry. Steps for transferring the motor data to 7SK80 setting data were discussed and the substitute settings suitable for characteristic motor variables were proposed. Energy Automation 08/2011 Page 11 of 11