AF24-MFT95 US Proportional Damper Actuator, Spring Return Fail-Safe, 24 V for Use with Honeywell Electronic Series 90, or a 0 to 135Ω input

Similar documents
Installation Instructions

Installation Instructions

Installation Instructions

AF Series Spring Return Direct Coupled Actuator

Dimensions [All numbers in brackets are in millimeters.] K4-2 US (supplied) 1/2" Centered (Default) 3/4" Centered (Field Selectable)

Torque min. 35 in-lb, for control of air dampers

AF Series Spring Return Direct Coupled Actuator

AM Series Direct Coupled Actuator

GM Series Direct Coupled Actuator

ZG106 or ZG 107 bracket

AFXUP-S (p. 19) AFB24-MFT. AFXUP (p. 19) AFBUP-S

LF24-ECON-R03(-R10) US Operation, Installation and Wiring

Minimum 90 in-lb Torque. Applications. NFB, NFX Series At A Glance. NFB and NFX Series Spring Return Direct Coupled Actuator

LF Series Spring Return Direct Coupled Actuator

NFB24, NFB24-S, NFX24, NFX24-S On/Off, Spring Return, 24 V

Table of Contents PAGE General Mounting Standard Reversible Clamp Linear Rotary Retrofit Brackets...275

LF Series Spring Return Direct Coupled Actuator

NMB (X) 24-MFT. Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma

LMX120-SR. Proportional Control, Non-Spring Return, Direct Coupled,100 to 240 VAC, for 2 to 10 VDC and 4 to 20 ma

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

LMCB24-SR LMCB24-SR-T. applications. Dimensions (All numbers in brackets are in millimeters.) 1/4 to 3/4 [6 to 20] 5/16 to 3/4 [8 to 26] 1.

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

NMQB24-MFT, NMQX24-MFT Quick Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

LMB24-3 (-S)(-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

Minimum 18 in-lb Torque. Applications. TF Series At A Glance. TF Series Spring Return Direct Coupled Actuator. For damper areas up to 4.

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

GMX On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 100 to 240 VAC

Mount directly to 1.05 jackshafts. AF230 US (p. 02) AF230-S US (p. 20) AF24-S US (p. 18)

ZG-JSL, ZG-JSLA Jackshaft Retrofit Linkage For AF, NF, LF, NMX and AMX Series Actuators

LF Series At A Glance

FSAF24(-S) US, FSAF120(-S) US

Versatile and Powerful

Versatile and Powerful

MS Series MS Series MS Series

Minimum 27 in-lb torque

MA40-704X Series MA41-707X Series MA41-715X Series

Minimum 27 in-lb Torque

Belimo is the Worldwide Leader in Fire and Smoke Actuation

Mounting Installation Instructions LM, NM, AM, GM

Minimum 18 in-lb Torque

MF Series MF Series MF Series

LMX24-3 (-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

Mounting Installation Instructions NKQ, GK

Actuators for heating, ventilation, air conditioning 2. LF-2 -CD. Product Information Damper actuators with spring return.

Product Cross Reference

G7150D, 3-Way, Diverting Flanged Globe Valve

Invensys Energy Solutions 1354 Clifford Avenue (Zip 61111) P.O. Box 2940 Loves Park, IL United States of America

G6125C, 2-Way, Pressure Compensated Flanged Globe Valve

MX4X-6XXX Series MX4X-7XXX Series. Selection Guide. Applications. DuraDrive Series Actuators and Accessories

MA40-704X Series, MA4X-707X Series, MA4X-715X Series DuraDrive Series Spring Return Two-Position Actuators General Instructions

MS Series MS4X-7073 Series MS4X-7153 Series

M9216 Series Electric Spring Return Actuators

Powers TM Controls EA 338 Electronic Actuator

MP-5400 Series. Application. Features. Applicable Literature. Electronic Positive Positioning Hydraulic Actuator General Instructions

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m)

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

MS Application. Features. Proportional Valve Actuator General Instructions

MA-5200 Series MA-5300 Series

MC-351, 421, 431, MC-4311

MF4E MF4E

LF24-SR US TF24-SR US TFX24 US LF24 US. B3 B Three-way Characterized Control Valve, Chrome Plated Brass Ball and Brass Stem

SAX Electronic Valve Actuator

B2/B3 Series Characterized Control Valve, Non-Spring Return Actuator

Technical Documentation Ball Valves

Commercial Actuator Selection Chart Non-Spring Return

NV Direct Coupled Globe Valve Actuator

M9208-xxx-x Series Electric Spring Return Actuators

DA-053 Series. Overview. Applications. Features & Benefits. Datasheet. 53lb-in (6 Nm), Non-Spring Return Damper Actuators

M9208-xxx-x Series Electric Spring-Return Actuators

M9208-xxx-x Series Electric Spring Return Actuators

RUS-L24-MOD Electric 24 Volt Modulating Control Damper & Louver Actuator

RUS-L24-MOD Electric 24 Volt Modulating Control Damper Actuator

SAV Electronic Valve Actuator

Accessories. Technical Data Extension Height 2" Material. Stainless Steel. Bearing TR LRB (X) ARB (X) TF LF AF. Extension Bracket CCV-EXT-Kit

MF /MS Series

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

VA-715x Electric Valve Actuator

M9203-xxx-2(Z) Series Electric Spring-Return Actuators

G6 C(S)(LCS) 2-way Pressure Compensated Flanged Globe Valve

ELECTRIC ACTUATOR HVAC/BAC ELECTRIC IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

ELECTRIC ACTUATOR 94OE IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

MP-5200 Series. Application. Features. Applicable Literature. Electronic Hydraulic Actuator General Instructions

B2 Series Characterized Control Valve, Non-Spring Return Actuator

BELIMO CONTROLS

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

M9203-xxx-2(Z) Series Electric Spring Return Actuators

Spring-Return Damper Actuator NF24(-S)

AM-676, AM , AM-690-R, AM-692, AM-693-R, AM-762, and AM-763

M100F Incremental Motor Actuator R81F Interface Board

ComfortPoint Programmable Lon, VAV/Unitary Controllers

SLC-811X Series. Single Loop Proportional Temperature Controller General Instructions APPLICATION SPECIFICATIONS

DuraDrive MF /MS Series Non-spring Return Rotary Electronic Damper Actuators 24 Vac Three-position/Modulating

M9220 Series Electric Spring-Return Actuators

Installation, Operation and Maintenance Manual

Electric Actuator Instructions

Use. Functions. OpenAir TM. Rotary version, modulating, with spring return, AC 24 V

M9208-xxx-x Series Electric Spring Return Actuators

OpenAir Electric Damper Actuators GBB/GIB Series NSR Rotary 24 Vac - Modulating Control

Transcription:

AF-MFT9 US Proportional Damper Actuator, Spring eturn Fail-Safe, V for Use with Honeywell Electronic Series 9, or a to Ω input Torque min. in-lb Control fixed, to Ω input, or Honeywell series 9 (fixed) Feedback to VDC (DEFAULT) Application For proportional modulation of dampers and control valves in HVAC systems. The AF-MFT9 US provides mechanical spring return operation for reliable fail-safe application. LISTED 9D TEMP. IND & EG. EQUIP. Technical Data AF-MFT9 US Power supply VAC ± % /6 Hz VDC ± % Power consumption running: 6 ; holding: Transformer sizing VA (class power source) Electrical connection ft, 8 GA appliance cable / conduit connector Overload protection electronic throughout to 9 rotation Operating range to Ω Honeywell electronic series (Not selectable via MFT) 9, or a to Ω input Feedback output U* to VDC,. ma max Mech. angle of rotation* 9, adjustable to 9 w/zd-af Torque in-lb [ Nm] constant Direction of rotation* spring: reversible with cw/ccw mounting motor: reversible with built-in switch Position indication visual indicator, to 9 ( is spring return position) Manual override mm hex crank (shipped w/actuator) unning time motor* seconds constant unning time spring < sec spring return fail safe position Angle of otation Off (Default) Adaptation* Override control* Min. (Min Position) = % - ZS (Mid. Position) = % - Max. (Max. Position) = % Humidity to 9% H non-condensing Ambient temperature - F to + F [- C to + C] Storage temperature Housing - F to +76 F [- C to +8 C] NEMA type / IP Housing material zinc coated metal Agency listings UL 87 listed, CE, CSA C. No. certified Noise level Servicing UL max. d (A) maintenance free Quality standard ISO 9 eight 6. lbs (.7 kg) * Variable when configured with MFT options Default/Configuration Default parameters for to Ω Input applications of the AF-MFT9 US actuator are assigned during manufacturing. If required, custom versions of the actuator can be ordered. However the control input cannot be modified via MFT PC tool software. The parameters noted in the Technical Data table are variable. These parameters can be changed by three means: Pre-set configurations from elimo Custom configurations from elimo Configurations set by the customer using the MFT PC tool software application. Operation The AF-MFT9 US actuator provides 9 of rotation and is provided with a graduated position indicator showing to 9. The actuator will synchronize the mechanical stop or the physical damper or valve mechanical stop and use this point for its zero position during normal control operations. A unique manual override allows the setting of any actuator position within its 9 of rotation with no power applied.this mechanism can be released physically by the use of a crank supplied with the actuator. hen power is applied the manual override is released and the actuator drives toward the fail-safe position. The actuator uses a brushless DC motor which is controlled by an Application Specific Integrated Circuit (ASIC) and a microprocessor. The microprocessor provides the intelligence to the ASIC to provide a constant rotation rate and to know the actuator s exact position. The ASIC monitors and controls the brushless DC motor s rotation and provides a Digital otation Sensing (DS) function to prevent damage to the actuator in a stall condition. The position feedback signal is generated without the need for mechanical feedback potentiometers using DS. The actuator may be stalled anywhere in its normal rotation without the need of mechanical end switches. The AF-MFT9 US is mounted directly to control shafts up to." diameter by means of its universal clamp and anti-rotation bracket. A crankarm and several mounting brackets are available for damper applications where the actuator cannot be direct coupled to the damper shaft. The spring return system provides minimum specified torque to the application during a power interruption. The AF-MFT9 US actuator is shipped at + ( from full fail-safe) to provide automatic compression against damper gaskets for tight shut-off. Dimensions [All numbers in brackets are in millimeters.] K- US (supplied) /" Centered (Default) /" Centered (Field Selectable)." Centered (Field Selectable) K- US (optional) /" to." Adjustable K US (optional) /8" to /" Adjustable.6" [6.].86" [98]." [8.7]." [8]." [7].9" [].9" []." [9].6" [67].97" [].7" [66].8" [8.].6" [6.].9" [9] D J7 - Subject to change. elimo Aircontrols (USA), Inc.

AF-MFT9 US Proportional Damper Actuator, Spring eturn Fail-Safe, V for Use with Honeywell Electronic Series 9, or a to Ω input Proportional Potentiometric Control J7 - Subject to change. elimo Aircontrols (USA), Inc. Switch A Switch Damper Position Damper Open Damper Closed The direction of rotation switch is set so that the fail safe position and the position of the damper is closed with no signal at wire. Override of AF-MFT9 US VAC Transformer Ω A VAC Transformer A Common, lk + Hot, ed, ht, ht 6 U Output - VDC AF-MFT9 US Common, lk + Hot, ed, ht, ht 6 U Output - VDC AF-MFT9 US Provide overload protection and disconnect as required. Actuators and controller must have separate transformers. installation information. To reverse control rotation, use the reversing switch. Series 9 VAC Transformer Series 9 low limit control Ω for to % control 8Ω for to % control Common, lk + Hot, ed, ht, ht 6 U Output - VDC AF-MFT9 US Provide overload protection and disconnect as required. Actuators and controller must have separate transformers. installation information. To reverse control rotation, use the reversing switch. AF-MFT9 US used with a Series 9 controller and a Series 9 low limit control Series 9 VAC Transformer Common, lk + Hot, ed, ht, ht 6 U Output - VDC Series 9 high limit control - 8Ω AF-MFT9 US Provide overload protection and disconnect as required. Actuators and controller must have separate transformers. installation information. To reverse control rotation, use the reversing switch. 6 7 Shunting esistor VAC Transformer Series 9 No. of actuators esistance Ω 7.Ω 7.Ω 7.Ω 6 8Ω esistor Kit No. ZG- To other actuators Common, lk + Hot, ed, ht, ht 6 U Output - VDC AF-MFT9 US Common, lk + Hot, ed, ht, ht 6 U Output - VDC AF-MFT9 US Provide overload protection and disconnect as required. Actuators and controller must have separate transformers. installation information. esistor value depends on the type of controller and the number of actuators. No resistor is used for one actuator. Honeywell resistor kits may also be used. To reverse control rotation, use the reversing switch. iring multiple actuators to a Series 9 controller. VAC Transformer Series 9 Shunting esistor H Changeover Occupied Contact S96A Minimum Position Potentiometer To other actuators Common, lk + Hot, ed, ht, ht 6 U Output - VDC AF-MFT9 US Common, lk + Hot, ed, ht, ht 6 U Output - VDC AF-MFT9 US Provide overload protection and disconnect as required. Actuators and controller must have separate transformers. installation information. esistor value depends on the type of controller and the number of actuators. No resistor is used for one actuator. Honeywell resistor kits may also be used. To reverse control rotation, use the reversing switch. 8 9 H Changeover Shunting esistor VAC Transformer Y 97, 7 No. of actuators esistance Ω 9Ω 768Ω esistor Kit No. ZG-6 Shunting esistor VAC Transformer Q9A Minimum Position Potentiometer To other actuators Honeywell Q9A Minimum Position Potentiometer To other actuators Common, lk + Hot, ed, ht, ht 6 U Output - VDC AF-MFT9 US Occupied Contact Honeywell T67A Morning armup Common, lk + Hot, ed, ht, ht 6 U Output - VDC AF-MFT9 US Used with the 97 and 7 controllers. 97, 7 T77 Honeywell T67A Morning armup Common, lk + Hot, ed, ht, ht 6 U Output - VDC AF-MFT9 US Common, lk + Hot, ed, ht, ht 6 U Output - VDC AF-MFT9 US Provide overload protection and disconnect as required. Actuators and controller must have separate transformers. installation information. esistor value depends on the type of controller and the number of actuators. No resistor is used for one actuator. Honeywell resistor kits may also be used. To reverse control rotation, use the reversing switch. AF AF-MFT9 US used with a Series 9 controller and a Series 9 high limit control iring multiple actuators to a Series 9 controller using a minimum position potentiometer. Typical wiring diagrams for multiple actuators used with the 97, 7 and T77 controllers.

Installation Instructions Quick-Mount Visual Instructions for Mechanical Installation Dimensions (All numbers in brackets are in millimeters.) min. /" [9] min. /" [] IND-AF Position Indicator (optional) emove for / to. shafts IND-AF Position Indicator (optional) J7 - Subject to change. elimo Aircontrols (USA), Inc. QUICK-MOUNT VISUAL INSTUCTIONS. otate the damper to its fail-safe position. If the shaft rotates counterclockwise, mount the CC side of the actuator out. If it rotates clockwise, mount the actuator with the C side out.. If the universal clamp is not on the correct side of the actuator, move it to the correct side. 6. Slide the actuator onto the shaft and tighten the nuts on the V-bolt with a mm wrench to 6-8 ft-lb of torque.. Slide the anti-rotation strap under the actuator so that it engages the slot at the base of the actuator. Secure the strap to the duct work with #8 self-tapping screws. NOTE: ead the Standard Mounting instructions, on the next page, for more detailed information.

Installation Instructions Mechanical Installation Determining Torque Loading and Actuator Sizing Damper torque loadings, used in selecting the correct size actuator, should be provided by the damper manufacturer. If this information is not available, the following general selection guidelines can be used. Damper Type Torque Loading Opposed blade, without edge seals, in-lb/sq. ft. for non-tight close-off applications Parallel blade, without edge seals, in-lb/sq. ft. for non-tight close-off applications Opposed blade, with edge seals, in-lb/sq. ft. for tight close-off applications Parallel blade, with edge seals, 7 in-lb/sq. ft. for tight close-off applications The above torque loadings will work for most applications under in. w.g. static pressure or FPM face velocity. For applications between this criteria and in. w.g. or FPM, the torque loading should be increased by a multiplier of.. If the application calls for higher criteria up to in. w.g. or FPM, use a multiplier of.. Damper Area (sq. ft.) 7 6 Torque Loading Chart 6 8 7 9 Torque Loading (in-lb/ sq. ft.) AF General Information elimo actuators should be mounted indoors in a dry, relatively clean environment free from corrosive fumes. If the actuator is to be mounted outdoors, a protective enclosure must be used to shield the actuator. For new construction work, order dampers with extended shafts. Instruct the installing contractor to allow space for mounting and service of the elimo actuator on the shaft. The damper shaft must extend at least /" from the duct. If the shaft extends less than -/" or if an obstruction blocks access, the shaft can be extended with the AV -8 shaft extension accessory or the actuator may be mounted in its short shaft configuration. J7 - Subject to change. elimo Aircontrols (USA), Inc. Mechanical Operation The actuator is mounted directly to a damper shaft up to. in diameter by means of its universal clamp. A crankarm and several mounting brackets are available for applications where the actuator cannot be direct coupled to the damper shaft. The AF series actuators provide true spring return operation for reliable fail-safe application and positive close-off on air tight dampers. The spring return system provides constant torque to the damper with, and without, power applied to the actuator. The AF -S versions are provided with built-in auxiliary switches. These SPDT switches are provided for safety interfacing or signaling, for example, for fan start-up. The switching function at the fail-safe position is fixed at +, the other switch function is adjustable between + to +8. Automatic Airtight Dampers/Manual Override The AF series provides 9 of rotation and is provided with a graduated position indicator showing to 9. The AF has a unique manual positioning mechanism which allows the setting of any damper position within its 9 of rotation. A pre-tensioned spring automatically tightens damper when power is applied to the actuator, compensating for damper seal deterioration. The actuator is shipped at + ( from full fail-safe) to provide automatic compression against damper gaskets for tight shut-off. hen power is applied, the manual mechanism is released and the actuator drives toward the full fail-safe position. Standard Mounting Note:The AF series actuator is shipped with the manual override adjusted for a + position at the universal clamp (not at full fail-safe, ). This allows for automatic compression of damper blade seals when the actuator is in use, providing tight shut-off. This assumes that the damper is to have tight shut-off at the fail-safe position. If tight close-off is desired at the opposite direction from fail-safe, the manual override should be released so the actuator can go to the full fail-safe position. See the manual override instructions.. Manually move the damper to the fail-safe position (usually closed). If the shaft rotated counterclockwise ( ), this is a CC installation. If the shaft rotated clockwise ( ), this is a C installation. In a CC installation, the actuator side marked CC faces out, while in a C installation, the side marked C faces out. All other steps are identical.. The actuator is usually shipped with the universal clamp mounted to the CC side of the actuator. To test for 7

Installation Instructions Mechanical Installation adequate shaft length, slide the actuator over the shaft with the side marked CC (or the C side if this is the side with the clamp). If the shaft extends at least /8 through the clamp, mount the actuator as follows. If not, go to the Short Shaft Installation section. CC CC CC CC - - CC CC Correct clamp mounting position Correct if clamp actuator mounting is at full position fail-safe. when actuator is shipped from factory (with preload) Correct pointer mounting position Correct if clamp actuator mounting is at full position fail-safe. if actuator is at full fail-safe. Correct pointer mounting position when actuator is at preload. Correct pointer mounting position if actuator is at full fail-safe. C C Fig. A Universal Clamp and IND-AF Pointer (optional) positions indicating fail-safe and pre-load settings. If the clamp is not on the correct side as determined in step #, re-mount the clamp as follows. If it is on the correct side, proceed to step #. Look at the universal clamp. If you are mounting the actuator with the CC side out, position the clamp so that the pointer section of the tab is pointing to (see Fig. C) and the spline pattern of the clamp mates with spline of the actuator. Slip the clamp over the spline. (Use the same procedure if the C side is out.) If your application requires a mechanical minimum position, read the otation Limiting, Mechanical Minimum Damper Position section. - - - C C - - C C. Lock the clamp to the actuator using the retaining clip.. Verify that the damper is still in its full fail-safe position. 6. Slide the actuator over the shaft. 7. Position the actuator in the desired location. 8. Tighten the two nuts on the clamp using a mm wrench or socket using 6-8 ft-lb of torque. 9. Slip the stud of the anti rotation strap into the slot at the base of the actuator. The stud should be positioned approximately /6 of an inch from the closed end of the slot. end the strap as needed to reach the duct. Attach the strap to the duct with #8 self tapping screws. Short Shaft Installation If the shaft extends at least / from the duct, follow these steps:. Determine the best orientation for the universal clamp on the back of the actuator. The best location would be where you have the easiest access to the V bolt nuts on the clamp.. Engage the clamp to the actuator as close as possible to the determined location.. Lock the clamp in place using the remaining retainer clip.. Verify that the damper is still in its full fail-safe position.. Slide the actuator over the shaft. 6. Position the actuator in the desired location. 7. Tighten the two nuts on the clamp using a mm wrench or socket using 6-8 ft-lb of torque. 8. Slip the stud of the anti-rotation strap into the slot at the base of the actuator. The stud should be positioned approximately /6 of an inch from the closed end of the slot. end the strap as needed to reach the duct. Attach the strap to the duct with #8 self tapping screws. 9. If damper position indication is required, use the optional IND-AF pointer. See Fig. A. Jackshaft Installation The AF series actuator is designed for use with jackshafts up to. in diameter. In most applications, the AF actuator may be mounted in the same manner as a standard damper shaft application. If more torque is required than one AF actuator can provide, a second AF actuator may be mounted to the jackshaft using the ZG- multiple actuator mounting bracket. See wiring guide for wiring details. AF actuators which may be used on one shaft: Max Quantity Model Per Shaft AF (-S) US AF (-S) US AF (-S) US AF-S US AF-MFT (-S) US Mounting: If the actuators are mounted on the opposed ends of the shaft, the actuator direction must be selected carefully. Usually, the direction of rotation is reversed. J7 - Subject to change. elimo Aircontrols (USA), Inc. 8

Installation Instructions Mechanical Installation Multiple Actuator Mounting If more torque is required than one AF actuator can provide, a second AF actuator may be mounted to the shaft using the ZG- multiple mounting bracket. Notes: The manual positioning mechanism cannot be used in multiple actuator applications. Special iring and Additional Information: See wiring guide otation Limitation The angle of rotation limiter, ZD-AF, is used in conjunction with the tab on the universal clamp or IND-AF position indicator which comes with the ZD-AF. In order to function properly, the clamp or indicator must be mounted correctly. See Fig. A. The ZD-AF may not work in certain mounting orientations using the ZG-6 or ZG-7 mounting brackets. It will not work with the ZG-8 mounting bracket. Limiting the damper rotation must be accomplished by adjusting the crankarm linkage. 6. Fasten the limiter to the actuator using the self tapping screw provided. 7. Test the damper rotation either manually with the manual crank or apply power and if required, a control signal. e-adjust if necessary. Mechanical Minimum Damper Position In order to use this procedure, the actuator must be mounted for short shaft mounting. See pages 8 &.. Position the damper to its minimum position by using the manual crank or by providing the appropriate control signal to the AF modulating type actuator.. Place the indicator on to the actuator spline in the approximate position shown in Fig. D. Fasten it with the retaining clip. Note that the mounting orientation is different than the mounting used for Damper otation Limiting. AF The ZD-AF may be used in ways to control the rotational output of the AF series actuator. One use is in the application where a damper has a designed rotation less than 9. An example would be a or 6 rotating damper. The other application would be to set a minimum damper position which can be easily set or changed without having to remove the actuator from the damper. Damper otation Limiting. Determine the amount of damper rotation required.. Locate the Angle of otation Limiter (ZD-AF) on the actuator so that its edge lines up with the degree graduation on the actuator face which corresponds with the required rotation. See Fig. C. 6 7 8 9 CC Fig. D 9 8 C 7 6 6 6 J7 - Subject to change. elimo Aircontrols (USA), Inc. Screw secured at these cross hairs Angle of rotation is now set at. Secure angle-ofrotation limiter. Find the appropriate cross-hair location through the slot of the limiter. This is the screw mounting location.. Pierce through the label material to allow easy fastening of the retaining screw.. Position the limiter back to the desired position, making sure the locating teeth on the limiter are engaged into the locating holes on the actuator. Screw Philips screwdriver Fig. C ZD-AF Securing the Angle of otation Limiter CC Fig. E C. Place the ZD-AF rotation limiter on the actuator so that it either makes contact with, or is as close as possible to, the edge of the indicator. See Fig. E. Make sure that the locating teeth are engaged into the locating holes on the actuator. If all of the mounting teeth do not align with the holes, the mounting location of the indicator to the spline may have to be moved. The limiter would then be remounted to get the best position match of both parts.. Find the cross-hair location through the slot of the limiter. This is the screw mounting location.. Pierce through the label material to allow easy fastening of the retaining screw. 6. Fasten the limiter to the actuator using the self tapping screw provided. 7. Test the damper operation either manually with the manual crank or apply power and if required, a control signal. e-adjust if necessary. 9

Installation Instructions This method should not be used for outside air damper applications. The damper will never go to the full close-off position. This may cause coils to freeze or other system problems. The AF-S (-S) US wired to either the SGA or SGF can be used for minimum position setting and still provide full close-off. Manual Override The AF series actuators can be manually positioned to ease installation or for emergency positioning. Auxiliary Switches The AF series actuators may be ordered with built-in SPDT auxiliary switches used for safety interfacing or signalling, for example, for fan start-up. The switch position near the fail-safe position is fixed at. The other is adjustable between and 8 of rotation. The crank, supplied with the actuator, or a mm allen wrench is used to adjust the switching position. Switch ating Voltage esistive Load Inductive Load VAC 7A A VAC 7A.A Two methods may be used to adjust the switching point of the adjustable switch. inding the damper actuator - insert crank handle - turn handle in direction of arrow Locking the damper actuator - rotate crank handle / turn in the direction shown by the locked icon. Unlocking the damper actuator ( options) - rotate crank handle / turn in the direction shown by the unlocked icon. - remote control by supplying power to the unit for > than sec.. The manual override will only work if no power is available to the actuator.. Insert the manual crank (shipped with the actuator) into the hexagon hole located on either side of the actuator. An illustration, located on the label, shows the location.. Turn the crank in the direction shown on the label (clockwise on the C side, counterclockwise on the CC side). It will take approximately 9 revolutions to rotate the full 9 of rotation.. To lock the actuator in the required position, rotate the crank quickly in the opposite direction, / of a revolution. The lock closed icon on the label shows the correct direction.. The manual override may be disengaged in ways. - otate the crank about a / revolution in the same direction as the initial winding. The lock open icon shows the correct direction. - Apply power to wire and. The actuator will automatically disengage the override function and will go to the on position in the case of the on-off versions. Or, in the case of the proportional versions, go to the signal position and then go to the position corresponding to the control signal. The actuator will now work normally. Testing the installation ithout Power The actuator/damper installation may be tested without power at the actuator. efer to the manual positioning section of the instructions. Move the damper to its full non-fail-safe position using the manual crank. Disengage the manual position mechanism and have the damper go to full fail-safe position. Correct any mechanical problems and retest. Method - See Fig. F The actuator must be in its fail-safe position.. Insert the crank into the hexagon shaped hole located in the center of the adjustable switch pointer.. otate the crank until the switch pointer is at the desired switch point in degrees as shown. Method - See Fig. G. Position the damper to the point at which you want the switch to activate. This may be done by using the manual override or by providing the appropriate proportional signal to AF modulating type actuator. The position of the switch pointer is not important during this step.. Insert the crank into the hexagon shaped hole located in the center of the adjustable switch pointer.. otate the switch pointer to just past the switch point indicating arrow as shown. AF series Factory setting 8 6 7 8 8 Actuator after locking 6 7 8 8 Crank Handle otate with crank handle 6 7 8 8 Crank Handle Fig. F Switch operates 6 7 8 8 Fig. G 6 set 6 7 8 8 Switch does not operate 6 7 8 8 J7 - Subject to change. elimo Aircontrols (USA), Inc.

Installation Instructions Non-direct Mounting Methods AF KH-AF Crankarm Including etaining ing. Caution: the retaining clip supplied with the clamp is not used to mount the KH-AF crankarm. The KH-AF (-) crankarm is used in non-direct coupled mounting applications. The KH-AF (-) may also be used to simultaneously direct couple to a damper shaft and provide an additional crank arm connection to a second damper. The KH-AFV V-bolt kit must be used for this non-direct application (see illustration below). Dimensions (All numbers in brackets are in millimeters.) Two sizes are available: KH-AF For round shafts up to / or square shafts up to /8 KH-AF- For jackshafts up to. KH-AFV V-bolt kit for KH-AF(-) crankarm Note: KH-AF (-) crankarms cannot be used on AF Series actuators. J7 - Subject to change. elimo Aircontrols (USA), Inc. KH-AF (-) crankarm with KH-AFV V-bolt kit KH-8 crankarm KH-AF non-direct mounting with ZG-8 mounting bracket Multiple dampers direct coupled to one actuator with linkage to operate the other damper.

Installation Instructions Electrical Operation General The AF series actuators utilize brushless DC motor technology. The AF uses this motor in conjunction with an Application Specific Integrated Circuit (ASIC). In the On-Off versions of the AF, the ASIC monitors and controls the actuator s rotation and a digital rotation sensing function to prevent damage to the actuator. The AF modulating type actuators incorporate a built in microprocessor. The microprocessor provides the intelligence to the ASIC to provide a constant rotation rate and knows the actuator s exact zero position. rushless DC Motor Operation elimo s brushless DC motor spins by reversing the poles of stationary electromagnets housed inside of a rotating permanent magnet. The electromagnetic poles are switched by a special ASIC circuit developed by elimo. Unlike the conventional DC motor, there are no brushes to wear or commutators to foul. Overload Protection The AF series actuators are protected from overload at all angles of rotation. The ASIC circuit constantly monitors the rotation of the DC motor inside the actuator and stops the pulses to the motor when it senses a stall condition. The DC motor remains energized and produces full rated torque to the load. This helps ensure that dampers are fully closed and that edge and blade seals are always properly compressed. Motor Position Detection elimo brushless DC motors eliminate the need for potentiometers for positioning in modulating type actuators. Inside the motor are three Hall Effect sensors. These sensors detect the spinning rotor and send pulses to the microprocessor which counts the pulses and calculates the position to within / of a revolution of the motor. Control Accuracy and Stability AF-S US actuators have built-in brushless DC motors which provide better accuracy and longer service life. The AF-S US actuators are designed with a unique non-symmetrical deadband. The actuator follows an increasing or decreasing control signal with a 8 mv resolution. If the signal changes in the opposite direction, the actuator will not respond until the control signal changes by mv. This allows these actuators to track even the slightest deviation very accurately, yet allowing the actuator to wait for a much larger change in control signal due to control signal instability. AF Actuator responds to a 8 mv signal when not changing direction from stop Satisfied Control Position 8 mv Minimum Control esolution AF Actuator responds to a mv signal when reversing direction from stop position. Minimum eversed Control Deadband Prior to Normal Control mv Satisfied Control Position J7 - Subject to change. elimo Aircontrols (USA), Inc. The AF-MFT US control accuracy and stability can be found in the MFT specifications, page 9.

Installation Instructions General iring J7 - Subject to change. elimo Aircontrols (USA), Inc. General iring Instructions ANING The wiring technician must be trained and experienced with electronic circuits. Disconnect power supply before attempting any wiring connections or changes. Make all connections in accordance with wiring diagrams and follow all applicable local and national codes. Provide disconnect and overload protection as required. Use copper, twisted pair, conductors only. If using electrical conduit, the attachment to the actuator must be made with flexible conduit. Always read the controller manufacturer's installation literature carefully before making any connections. Follow all instructions in this literature. If you have any questions, contact the controller manufacturer and/or elimo. Transformer(s) The AF.. actuators require a VAC class transformer and draws a maximum of VA per actuator. The actuator enclosure cannot be opened in the field, there are no parts or components to be replaced or repaired. EMC directive: 89/6/EEC Software class A: Mode of operation type Low voltage directive: 7//EEC CAUTION: It is good practice to power electronic or digital controllers from a separate power transformer than that used for actuators or other end devices. The power supply design in our actuators and other end devices use half wave rectification. Some controllers use full wave rectification. hen these two different types of power supplies are connected to the same power transformer and the DC commons are connected together, a short circuit is created across one of the diodes in the full wave power supply, damaging the controller. Only use a single power transformer to power the controller and actuator if you know the controller power supply uses half wave rectification. Multiple Actuators, One Transformer Multiple actuators may be powered from one transformer provided the following rules are followed:. The TOTAL current draw of the actuators (VA rating) is less than or equal to the rating of the transformer.. Polarity on the secondary of the transformer is strictly followed. This means that all No. wires from all actuators are connected to the common leg on the transformer and all No. wires from all actuators are connected to the hotleg. Mixing wire No. & on one leg of the transformer will result in erratic operation or failure of the actuator and/or controls. Multiple Actuators, Multiple Transformers Multiple actuators positioned by the same control signal may be powered from multiple transformers provided the following rules are followed:. The transformers are properly sized.. All No. wires from all actuators are tied together and tied to the negative leg of the control signal. See wiring diagram. ire Length for AF Actuators Keep power wire runs below the lengths listed in the Fig. H. If more than one actuator is powered from the same wire run, divide the allowable wire length by the number of actuators to determine the maximum run to any single actuator. Example: actuators, 6 Ga wire Ft Actuators = 7 Ft. Maximum wire run Maximum ire Length: ire Size Max. Feet. ire Size Max. Feet Ga 9 Ft. 8 Ga Ft. Ga Ft. Ga Ft. 6 Ga Ft. Ga 6 Ft. Fig. H ire Type and ire Installation Tips For most installations, 8 or 6 Ga. cable works well with the AF.. actuators. Use code-approved wire nuts, terminal strips or solderless connectors where wires are joined. It is good practice to run control wires unspliced from the actuator to the controller. If splices are unavoidable, make sure the splice can be reached for possible maintenance. Tape and/or wire-tie the splice to reduce the possibility of the splice being inadvertently pulled apart. The AF proportional actuators have a digital circuit that is designed to ignore most unwanted input signals (pickup). In some situations the pickup may be severe enough to cause erratic running of the actuator. For example, a large inductive load (high voltage AC wires, motors, etc.) running near the power or control wiring may cause excessive pickup. To solve this problem, make one or more of the following changes:. un the wire in metallic conduit.. e-route the wiring away from the source of pickup.. Use shielded wire (elden 876 or equal). Ground the shield to an earth ground. Do not connect it to the actuator common. Initialization of the AF-S US, and AF-MFT US hen power is initially applied, the actuator will first release its manual preload position (This assumes a manual position has been set). The actuator will then rotate to the full fail-safe position. At this point the microprocessor recognizes that the actuator is at full fail-safe and uses this position as the base for all of its position calculations. The microprocessor will retain the initialized zero during short power failures of up to seconds. The AF-MFT US will also return to its position prior to the -second-or-less power loss. For power failures greater than seconds, the actuator would naturally return to its full failsafe position prior to the microprocessor losing its memory. The actuator will also re-initialize if the manual position mechanism is used. AF

Startup and Checkout Instructions For AF-S US and AF-MFT US + P- AF-S US and AF-MFT US + P- Electrical Check-out Procedure Step Procedure Expected esponse Gives Expected esponse Go To Step Does Not Give Expected esponse Go To Step. Control signal is applied to actuator. Actuator will move to its Control Signal position. Actuator operates properly Step 7. No response at all Step. Operation is reversed Step. Does not drive toward "Control Signal Position" Step.. Check power wiring. Correct any problems. See Note. Power supply rating should be the total power requirement of the actuator(s). Minimum voltage of 9. VAC or.6 VDC. Power wiring corrected, actuator begins to drive Step. Power wiring corrected, actuator still does not drive Step.. Turn reversing switch to the correct position. Make sure the switch is turned all the way left or right. Actuator will move to its Control Signal position. Actuator operates properly Step 7. Does not drive toward Control Signal Position Step.. Make sure the control signal positive (+) is connected to ire No and control signal negative (-) is connected to wire No.. Most control problems are caused by reversing these two wires. Verify that the reversing switch is all the way CC or C. Drives to Control Signal position. Actuator operates properly Step 7. Step.. 7. 8. Note Note Check input signal with a digital volt meter (DVM). Make sure the input is within the range of the actuator. For AF-S US this is to VDC or to ma. Note: The input signal must be above the VDC or ma to have the actuator move. Check damper torque requirement. Actuator works properly. Test controller by following controller manufacturer's instructions. Input voltage or current should be ±% of what controller's adjustment or programming indicate. Torque requirement is actuator s minimum torque. output (actuator input) is correct. Input Polarity Correct Step 6. Defective Actuator. eplace Actuator - See Note. eprogram, adjust repair or replace controller as needed Step. ecalculate actuator requirement and correct installation. Check that the transformer(s) are sized properly. If a common transformer is used, make sure that polarity is observed on the secondary. This means connect all No. wires to one leg of the transformer and all No. wires to the other leg of the transformer. If multiple transformers are used with one control signal, make sure all No. wires are tied together and tied to control signal negative (-). s and actuators must have separate VAC/VDC power sources. If failure occurs within years from original installation date, notify elimo and give details of the application. J7 - Subject to change. elimo Aircontrols (USA), Inc.