MIQ MINERAL INSULATED HEATING CABLE INSTALLATION INSTRUCTIONS

Similar documents
FLX TM Self-Regulating Winterization/Freeze Protection INSTALLATION PROCEDURES

Electric Heat Tracing INSTALLATION PROCEDURES

TubeTrace Tubing Bundles

Electric Heat Tracing INSTALLATION PROCEDURES

Pipe Freeze Protection Design/Install Guide

Installation Instructions Mineral Insulated (M.I.)

Heating Cable. Construction

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

Power-Limiting Cables

PRO-Tect Pipe Freeze Protection Self-Regulating Heating Cable Install Manual (PT-Series)

Heating Cable. Construction

C Power Connection Kit

Installation Instructions CONSTANT WATT (CW) AND SELF-REGULATING (SR) PIPE TRACING CABLES

Introduction to Heat Trace Cable Systems

Nuheat WEATHER-READY HEAT TRACE PIPE FREEZE PROTECTION SYSTEM. Self-Regulating Heating Cable Installation Guide. UV Resistant Polyolefin Outer Jacket

3M Self Regulating Heating Cables

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

Specification for Heated Instrument Tubing in Process Applications* (March 29, 2007)

Power Connection Kit installation instructions

FLEXTRACE. FSG - FSG/T - FSG/TP - FSG/TF Self-regulating cables for refrigeration. Applications. Characteristics

The Use of Conduction Tracers Vs Bare Tracers Metric Version

MI Heating Cable. HDPE jacketed, copper sheathed MI cable. For surface snow melting in concrete, asphalt, and pavers. MI Heating Cable Configuration

WarmTrace TM HSX Hot Water Temperature Maintenance INSTALLATION PROCEDURES

Ecoflex potable PEX plus pre-insulated pipe system Installation guide

Kompensator External Low Voltage Heating Cable System

Instruction Manual. for Heating Cables and Cold Leads Type and Catalogue no and Hemstedt GmbH.

INDUSTRIAL HEAT TRACE

Heating Cable. Cut to Length in Field. Description

XMI-L STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES

STACKPAK INSTRUCTIONS

Terminator. DP Power Connection Kit INSTALLATION PROCEDURES

Pictorial Index... A-14 Introduction to Heat Trace Cable Systems Installation Examples Engineering Guide Heat Loss Tables...

MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE. For commercial and industrial applications. Heating cable construction

FAK-7HTS High Temperature Tubing Bundle End Seal Kit INSTALLATION PROCEDURES

STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES

Installation Instructions

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

Cold Shrink QS T Trifurcating Transition Splice Kit

155 CARTRIDGE SINGLE SEAL

MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE. For heat loss replacement, floor heating and radiant space heating

Uniflex-stow remote valve operating systems

Frost protection for pipes. 16 Technical handbook. Thermostat with line or ambient temperature sensor

Selection Guide. Freeze Protection Heating Cable. Thermwire - Wrap. Thermwire - Wrap Pre-Assembled. Thermwire - Comp. Thermwire - Melt.

FREEZSTOP MICRO SYSTEM

Self-regulating cables

Self-Regulating Freeze Protection Heating Cable

Mineral-Insulated RTD Temperature Probe According to DIN EN 60751

QUICKTERM TERMINATION KIT

Self-Regulating Cables

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

CLARKSON URETHANE KNIFE GATE VALVES FIGURE SU10R

TracePlus. PCA Power Connection Kit INSTALLATION PROCEDURES. PCA-H for BSX, HTSX, KSX, HPT, FP PCA-V for RSX, TSX, VSX

Armor Rods. Armor Rods NOMENCLATURE GENERAL RECOMMENDATIONS

QAA 132 Operating Manual for Heat Tracing System ELSR-MA and ELSR-WA

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

3M Cold Shrink Splice Kit QS-III 5536A

SELF-REGULATING CABLES

Heating Cable. Description

INSTRUCTION SHEET PRL-97X04 AC AND DC VOLTAGES

FREEZSTOP MICRO SYSTEM. Freeze Protection of Pipework

Terminator DP/FAK-2 and FAK-2L. Elbow Splice Kit for Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES

DESIGN GUIDE FOR STEAM TRACING APPLICATIONS. THERMON The Heat Tracing Specialists

HTP PTP/ PTJ Power Connection Kit for Pipes

PIPINGSOLUTIONS, INC.

CONTENTS. This Product is Certified by CANADIAN STANDARDS ASSOCIATION and Bears the Mark:

XL-Trace System. Installation and Operation manual for pipe freeze protection and flow maintenance

Specified Conventional Tube Tracers Suggested TraceBOOST Tracers

NAMSR SELF-REGULATING FREEZE PROTECTION HEATING CABLE SELECTION

CAT-1 Series 3. Installation Guide. The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877

Signet 2517 Brass Paddlewheel Flow Sensor * *

Product Overview. Application

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

Terminator DP/FAK-4 and FAK-4L for In-Line Splice of Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES

COYOTE CLOSURE ADOBE SERIES FOR UNDERGROUND, AERIAL, AND BURIED SPLICES 6.0" x 22" 8.5" x 22" (152.4 mm x mm mm x 558.

HTSB system System overview

TESCO THE EASTERN SPECIALTY COMPANY Date: 05/04/15 Canal Street and Jefferson Avenue Bristol, PA 19007

Type LT Self-Regulating Heater Cable For use in Ordinary (Unclassified) and Hazardous (Classified) Locations

Terminator DP/FAK-5 and FAK-5L

Heating Cable. Description

Segurança. Segurança. PSB Heating System Cold applied connection technology. Compulsório. Compulsório. Operation Manual and Installation Instructions

AMENDMENT ELECTRIC SERVICE MANUAL 2014

PIPE FREEZE PROTECTION AND FLOW MAINTENANCE XL-TRACE SYSTEM

Power Connection Kit Installation Instructions. Terminator DP-M for use with TEK and HTEK series constant watt heating cables

THIS MATERIAL IS MEANT TO BE USED ALONG WITH OUR CATALOG IT IS NOT A SUBSTITUTE FOR THE CATALOG

Pipe fi ttings MUST be installed by a certifi ed welder only. Signet will not assume liability of any kind for improper fi tting installations.

Safety - Installation and Operation:

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

Installation Instructions

TracePlus. VIL-6 End of Circuit Light Kit INSTALLATION PROCEDURES. VIL-6-H for BSX, HTSX, KSX, HPT, FP VIL-6-V for RSX, TSX, VSX

OWNERS GUIDE TO INSTALLATION AND OPERATION OF 1/2-5 HP, 5, 7, 10, 15, 19 & 27 GPM 4 SUBMERSIBLE PUMPS

Pipe fi ttings MUST be installed by a certifi ed welder only. Signet will not assume liability of any kind for improper fi tting installations.

CONTROLS RESILIENT SEATED BUTTERFLY VALVES 20/21, 22/23, 30/31, 3A/3AH, 31H, 31U, 32/33, 35/36, 36H. The High Performance Company

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

LCD Annunciator Installation Instructions

Terminator TM DL Lighted Power Connection/End Termination Kit INSTALLATION PROCEDURES. For Power Connection or End Termination Applications

WarmlyYours ET-SR Series Heating Cable Installation Manual for Roof & Gutter Deicing

3M Cold Shrink QT-III Silicone Rubber Termination

EPLX and D2LX lighting panelboards Installation & maintenance information IF 1813 APPLICATION D2LX/EPLX IF SHEET TABLE OF CONTENTS WEIGHTS

IOM Manual. IOM Manual. Series 76/77.

Installation handbook

Transcription:

MIQ INSTALLATION INSTRUCTIONS MIQ CATALOGUE REF. NO. Example: D / MIQ-50E3H-2S / 200 / 1404 / 120 / 4 / 12 / 6 Design (A,B,D,E) Cable Reference Length (Feet or Meters) Watts Volts Cold Lead Length (Feet or Meters) Cold Lead AWG Cold Lead Voltage Rating 1 1 1. If the unit of measurement is omitted, the imperial measurement of feet will be assumed. Metric lengths are followed by the letter "m". HEATER SET TYPES A B D E FORM 5001-01C REV. D SHEET 1

INSTALLATION PROCEDURE FOR MIQ HEATING CABLE I. UPON RECEIVING HEATING CABLE: A. Check the cable set to make sure the proper type has been received. ONE (1) CONDUCTOR MIQ-20E1H-1S MIQ-16E1H-1S MIQ-13E1H-1S MIQ-10E1H-1S MIQ-5E2H-1S MIQ-70E2H-1S MIQ-50E2H-1S MIQ-3E2H-1S MIQ-30E2H-1S MIQ-25E2H-1S MIQ-20E2H-1S MIQ-17E2H-1S MIQ-15E2H-1S MIQ-10E2H-1S MIQ-0E3H-1S MIQ-70E3H-1S MIQ-60E3H-1S MIQ-40E3H-1S MIQ-30E3H-1S MIQ-20E3H-1S MIQ-10E3H-1S MIQ-65E4H-1S MIQ-25E4H-1S HEATING CABLE IDENTIFICATION CHART CAUTION: DO NOT connect power to heating cable while it is in shipping carton or coiled off pipe. B. Visually inspect cable for any damage incurred during shipment. Perform insulation resistance test as described in installation note 2. Measure DC resistance and compare to value on fab sheet provided with set. C. Store in dry area. SOLID CONDUCTOR 600V RATED CABLE Ohms/ft. TWO (2) Ohms/ft. @20 C CONDUCTOR @20 C 2.00 1.60 1.30 1.00 0.5 0.70 0.50 0.3 0.30 0.25 0.20 0.17 0.15 0.10 0.00 0.070 0.060 0.040 0.030 0.020 0.010 0.00651 MIQ-40E4H-1S 0.00409 0.0025 MIQ-16E4H-1S 0.00162 MIQ-11E0H-2S MIQ-90E1H-2S MIQ-60E1H-2S MIQ-40E1H-2S MIQ-20E1H-2S MIQ-10E1H-2S MIQ-70E2H-2S MIQ-50E2H-2S MIQ-30E2H-2S MIQ-20E2H-2S MIQ-15E2H-2S MIQ-10E2H-2S MIQ-70E3H-2S MIQ-50E3H-2S MIQ-40E3H-2S MIQ-30E3H-2S 11.00 9.00 6.00 4.00 2.00 1.00 0.70 0.50 0.30 0.20 0.15 0.10 0.07 0.05 0.04 0.03 MIQ-20E3H-2S 0.020 MIQ-16E3H-2S MIQ-13E3H-2S MIQ-10E3H-2S 0.016 0.013 0.0104 300V RATED CABLE TWO (2) CONDUCTOR MIQ-11E0L-2S MIQ-90E1L-2S MIQ-75E1L-2S MIQ-60E1H-2S MIQ-50E1L-2S MIQ-40E1L-2S MIQ-32E1L-2S MIQ-27E1L-2S MIQ-25E1L-2S MIQ-20E1L-2S MIQ-17E1L-2S MIQ-14E1L-2S MIQ-10E1L-2S MIQ-70E2L-2S MIQ-50E2L-2S MIQ-30E2L-2S MIQ-25E2L-2S MIQ-20E2L-2S MIQ-15E2L-2S MIQ-10E2L-2S MIQ-70E3L-2S MIQ-50E3L-2S Ohms/ft. @20 C 11.00 9.00 7.50 6.00 5.00 4.00 3.20 2.70 2.50 2.00 1.70 1.40 1.00 0.70 0.50 0.30 0.25 0.20 0.15 0.10 0.070 0.050 SOLID CONDUCTORS SEAMLESS ALLOY 25 SHEATH MAGNESIUM OXIDE INSULATION MAGNESIUM OXIDE INSULATION FORM 5001-02C REV. C SHEET 2

II. BEFORE INSTALLING HEATING CABLE: A. Make sure all piping and equipment to be traced is completely installed and tested in accordance with applicable codes. B. Pipes and equipment surface should be reasonably clean. Any loose scale, oil, or rust should be removed. C. Pipe heating cable must be installed in accordance with the Canadian Electric Code. Installation shall also be in accordance with the standards as outlined in IEEE Standard 515. Review these documents as well as any applicable local codes and standards prior to beginning the installation. D. Refer to the heat tracing isometric for power point location, equipment allowances, etc. Confirm if any sets are to be connected in series. III. INSTALLATION HEATING CABLE: TYPICAL INSTALLATION LENGTH FROM VALVE ALLOWANCE CHART LENGTH VALVE MIQ HEATING CABLE END HEAT TRACING CIRCUIT TEMPERATURE SENSOR COILED COLD LEAD 3" MIN. (76mm) PIPE SUPPORT 3" MIN. (76mm) STAINLESS STEEL BANDS OR WIRE AT 12" (305mm) INTERVALS HEATING CABLE LOOP TO CROSS UNDER VALVE HEATING SET TAG RECOMMENDED ORIENTATION HEAT TRACING ( WHEN 3 OR MORE HEATING CABLES ARE INSTALLED EQUALLY SPACE AROUND PIPE.) 12 AWG COLD TAIL WIRES PIPE TEMPERATURE SENSOR 90 1/2" N.P.T. FITTING M.I. COLD LEAD 30 MIN. 30 MIN. HEATING CABLE FORM 5001-03C REV. D SHEET 3

III.INSTALLATION HEATING CABLE (cont'd) A. Permanently install heating cable on pipe, valves and equipment by starting with the cold lead section (power end) and working towards the end section (hot end). B. Install cable with slight "wave" as shown in step 3. Heating cable minimum bend radius is 6x cable O.D. D. For extreme temperature exposure see detail on sheet #. E. Route MI cable set cold lead(s) into junction box hub(s). Slowly tighten gland connector with set of wrenches until ferrule begins to make positive contact with cold lead sleeve and cold lead cannot be moved by hand. Then tighten fitting 1/ additional turn. C. Secure the heating cable to the pipe using tie wire or stainless steel banding straps at 12" (305 mm) intervals. Use only thermon approved banding materials. Do not overtighten banding or tie wire. TYPICAL ARANGEMENT F. Any excess cable must be distributed evenly along pipe and equipment. STEP 1 LAY HEATING CABLE ALONG SIDE PIPE AND FIX HOT TO COLD JUNCTION. BAND JUNCTION AT 6"(152mm) DISTANCE ON BOTH SIDES. 6" 6" WIRE HOT TO COLD JUNCTION HOT END TIE COLD LEAD IN LOOP FOR CONVENIENCE UP TO 10' SPACING (TEMPORARY ONLY) STEP 2 TEMPORARILY TIE CABLE TO PIPE LEAVING MEASURED ALLOWANCES FOR HEAT SINKS. STEP 3 ADJUST CABLE WHERE NECCESSARY AND START TO SECURE WITH S AND FORM CABLE AROUND HEAT SINKS. SPACING 12" 12" END TERMINATION 6" STEP 4 COMPLETE SECURING CABLE WITH WIRES TO END PIPE. FORM 5001-06C REV. C SHEET 4

III. INSTALLATION HEATING CABLE (cont'd) HEATING CABLE ALLOWANCE FOR VALVES/FLANGES NOMINAL PIPE SIZE (INCH) 1/2" 3/4" 1" 1 1/2" 2" 2 1/2" 3" 4" 6" " 10" 12" 14" 16" 1" 20" 24" 30" SCREWED OR WELDED VALVE 6" 9" 1'-0" 1'-6" 2'-0" 4'-0" 7'-0" 9'-6" 1 15'-0" 1'-0" 21'-6" 25'-6" 34'-0" 40'-0" FLANGED VALVE 1'-0" 1'-6" 2'-0" 3'-0" 3'-6" 5'-0" '-0" 11'-0" 14'-0" 16'-6" 19'-6" 23'-0" 27'-0" 30'-0" 36'-0" 42'-0" BUTTERFLY VALVE 0" 0" 1'-0" 1'-6" 2'-0" 3'-0" FLANGES 4" 4' 4" 5" 5" 5" 5" 6" 6" 6" 7" " 9" 10" 10" 11" 1'-0" 1'-7" 3'-6" 4'-0" 4'-0" 5'-0" 5'-6" 6'-0" 6'-6" 7'-0" '-0" 10'-0" NOMINAL PIPE SIZE (MM) 10 15 20 25 30 40 50 65 0 100 125 150 200 250 300 350 400 450 500 600 700 00 SCREWED OR WELDED VALVE 0.15 0.20 0.30 0.35 0.40 0.50 0.60 0.75 0.95 1.2 1.6 2.0 2. 3.7 4.6 5.5 6.5 7.5.5 10.2 11.6 12.6 FLANGED VALVE 0.35 0.40 0.45 0.55 0.65 0.75 0.5 1.05 1.25 1.6 1.9 2.3 3.2 4.1 5.0 6.0 7.0.0 9.0 10. 12.2 13.3 BUTTERFLY VALVE 0 0 0.25 0.30 0.35 0.45 0.50 0.60 0.70 0.0 0.95 1.05 1.2 1.4 1.6 1. 2.0 2.2 2.4 2.6 2.9 3.2 FLANGES 0.22 0.24 0.25 0.2 0.36 0.4 0.5 0.64 0.71 0.6 1.0 1.2 1.3 1.5 1.6 1.75 2.0 ALL ALLOWANCES IN METERS NOTES: (1) SCREWED, WELDED AND FLANGED VALVES INCLUDE WEDGE PLUG, GLOBE DIAPHRAGM GATE, MULTIPORT CONTROL AND GLAND. (2) IF MULTIPLE TRACERS ARE USED, VALVE ALLOWANCE IS FOR ONE TRACER IF SPACE ALLOWS. VALVE ALLOWANCE TO BE ALTERNATED AMOUNG TRACERS FOR MULTIPLE VALVES IN A HEAT TRACE CIRCUIT. (3) ABOVE ALLOWANCES FOR 150 POUND VALVES. MORE CABLE IS REQUIRED FOR HIGHER RATINGS. (4) REFER TO HEAT TRACE ISOMETRIC DRAWING FOR ACTUAL ALLOWANCES. (1) PASS ACROSS THE VALVE LENGTH FROM VALVE ALLOWANCE CHART TAPE MEASURE MARK THIS POINT ON HEATING CABLE THEN MEASURE F THE LENGTH CABLE FROM THE VALVE ALLOWANCE CHART FORM 5001-05C REV. C SHEET 5

III. INSTALLATION HEATING CABLE (cont'd) ELBOWS VALVES CABLE TO SWEEP AROUND OUTSIDE DIAMETER PIPE WIRE OR BANDING 4" (100mm) OR BANDING FLANGES WIRE OR BANDING NOTE: FOR SMALL VALVES (ie: LESS THAN 2") IT MAY IMPRACTICAL TO INSTALL THE CORRECT CABLE ALLOWANCE ON THE VALVE BODY ITSELF. IT CAN BE INSTALLED IN A UNIFORM MANNER ACROSS MANNER ACROSS THE VALVE AND EITHER SIDE THE PIPE AS SHOWN BELOW. AVOID BOLTS HEATING CABLE NOTE: ON SMALL FLANGES AND JOINTS, TO AVOID THE RISK THE CABLE BECOMING EMBEDDED IN IN INSULATION, ONE THREE METHODS CAN BE ADOPTED. (A) WRAP CABLE AND FLANGE WITH ALUMINIUM FOIL TAPE AND SECURE WITH. (B) USE THIN, NON RUSTING METAL BRIDGING PIECES ACROSS FLANGE TO SUPPORT CABLE. (C) USE THERMON HEAT TRANSFER CEMENT TO FILL GAP BETWEEN CABLE AND FLANGE. HEATING CABLE METAL BRIDGING PIECE OR CEMENT (SEE NOTE ABOVE) HEATING CABLE WIRE OR BANDING S OR BANDING FORM 5001-07C REV. D SHEET 6

III. INSTALLATION HEATING CABLE (Cont'd) PUMPS SHOES WIRES OR BANDING END TERMINATION 3"(76mm) PIPE WIRE 3"(76mm) HEATER CABLE PIPE SUPPORT (NON-INSULLATED) EXTREME TEMPERATURE EXPOSURE INSTALLATION HANGER HOT END TERMINATION FITTING (LIFTED F PIPE AND INTO THE INSULATION & SUPPORTED WITH A BLOCK RIGID INSULATION). HOT-COLD LEAD TERMINATION FITTING (LIFTED F PIPE AND INTO THE INSULATION & SUPPORTED WITH A BLOCK RIGID INSULATION). WIRES OR BANDING WIRES OR BANDING INSULATION FORM 5001-09C REV. C SHEET 7

III. INSTALLATION HEATING CABLE (cont'd) INSTALLATION NOTES 1. Heating cable shall not touch, cross over, or overlap itself. 2. Test insulation resistance of heating cable set when received, when installed with pipe uninsulated, and after thermal insulation has been installed. Using a 500 Vdc megohmmeter, the minimum acceptable reading is 5 megohms between conductor and metallic sheath. Use of a 1000 Vdc megohmeter is recommended. Perform test with set de-energized and all circuit neutrals isolated from ground. Record readings. 3. Metal structures or materials used for the support of or on which cables or sets are installed, are to be grounded in accordance with CSA standard C221.1, Section 10. 4. Minimum installation temperature is -30 C. 5. Do not alter heating cable set length. 6. Do not remove metal tags from heating cable set. 7. Thermostat or solid state temperature control device must be used.. Heating cable must not be embedded in the thermal insulation. 9. Heating cable set shall be spaced at least 13 mm (1/2") from any combustible surface. 10. MI Cable Set cold lead ends must be kept dry before, during and after installation. 11. Do not damage cable by repeatedly bending and straightening at same location. 12. Do not bend cable less than 6" away from hot-to-cold joint, splice, or end termination. 13. Minimum spacing between cables is 1" when installing multiple passes or loops. 14. The metal covering shall not be used as the bonding-to-ground means. Alternate means of protection shall be provided per C.E. Code Part I. The metal covering on this set and metal structures or materials used for the support of this set shall be grounded. 15. Provisions must be made to protect MIQ cable from welding slag, grinders, etc. 16. Keep lids on all power and splice junction boxes. 17. Refer to Thermon Form TMP0006-0901 for information on electrical safety precautions for electrical heat tracing. 1. At a tee branch in a pipeline, particularly if the branch pipe is smaller than the main pipe, double tracing the smaller pipe with the main heating unit may cause unbalanced pipe temperature. Use caution, check schedules to see if permissible. Determine Heat Loss There are several ways to determine the heat loss for pipes under a given set of design conditions: - Heat loss calculations such as those detailed in IEEE Std.515-1997 (IEEE Standard for the Testing, Design, Installation, and Maintenance of Electrical Resistance Heat Tracing for Industrial Applications). - Computer-aided design programs that allow the user to input detailed information specific to an application. (Thermon's CompuTrace design and selection program provides this and more based on the formulas presented in IEEE Std. 515-1997). - Heat loss charts based on selected pipe diameters, temperature differentials and insulation materials. - Please contact Thermon for additional information on pipe heat loss. FORM 5001-011C REV. C SHEET

TYPICAL POWER JUNCTION BOX INSTALLATION TYPICAL IN LINE SPLICE TYPICAL INSTALLATION FOR MODULE TRANSPORTATION 333 2 STREET N.E. (403)273 555 FAX. (403)273 5695 FORM 5001 09C REV. A SHEET 1 1