SYSTIMAX 360 ipatch G2 High Density Sliding Fiber Shelf Instructions

Similar documents
ipatch Ready Upgrade Kit for SYSTIMAX 360 Fiber Shelves Instructions

SYSTIMAX 360 ipatch InstaPATCH Fiber Shelf Instructions

SYSTIMAX 360 ipatch G2 Fiber Ultra High Density (UHD) Shelf, LC InstaPATCH Distribution Panel Instructions

SYSTIMAX 360 ipatch G2 Fiber Ultra High Density (UHD) Shelf, MPO Distribution Panel Instructions

SYSTIMAX GS3 and 1100GS6 Evolve Modular Panel Instructions

SYSTIMAX SMB-4-3/4, SMB-8-1/2 Shelf-Mounted Cable Bracket Kits and 1000G2-XCPB Expanded Cable Protector Kit

SYSTIMAX G2 4U Fixed Rear Access Combination Shelf Instructions

SYSTIMAX 360 FTP Evolve Panel Instructions

UNPWM-U-Type Universal Wall Mount Patch Panel Instructions

UNP-U-Type Universal Panel Instructions

PATCHMAX GS3, GS6 and PowerSUM Modular Panels

Fiber Connector Shelf (CCS)

Pretium Wall-Mountable Housing (PWH-02P/-04P/- 06P/-12P and FZB-02P-JB)

8400 Series Fiber Distribution System

PanView iq (PViQ) Fiber Tray

INSTALLATION INSTRUCTIONS

Opticom Rack Mount Fiber Enclosures

Universal Splice Tray Installation Instructions

Environmental Distribution Center (EDC-06P-NH)

FOSC-400A4 INSTALLATION INSTRUCTION

Fiber Splice Panel Rack Mount User Manual

FL2000 Termination/Splice Panels User Manual

OFS Fitel LST1U-072/7 and LSTLW Instruction Sheet (LaserWave) Fiber Optic Comcode: Termination Shelf Installation

OFE-CLS-Type Outside Plant (OSP) Fiber Optic Closures Instructions

LPC Series Fiber Panel 12/24 Fiber Rack-Mount Enclosure Installation Instructions

CORNING. CamSplice User Guide 2. TOOLS AN MATERIALS 1. GENERAL 3. LOADING CAMSPUCE INTO TOOL

5 Removal and replacement

Installing the Switch

Instruction, EDGE8-04U Quick Start Guide

Fiber optic splice closure

IBER DISTRIBUTION FRAME (FDF) FOR EXCHANGE SIZE 900MM x 2200MM x 300 MM

UNP610-WM-12P Modular Jack Panel Installation

Instructions for Use - Opt-X 1000i Enclosure

SPEC SHEET. OmniReach FTTX Solutions. NEMA Fiber Demarcation Box (FDB) Features

Panduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF and ZDF

LSS1U-144/7 FIBER OPTIC SPLICE SHELF INSTALLATION GENERAL CUSTOMER SERVICES REFERENCES TOOLS REQUIRED

LSW Connector Module User Manual

FIBER CONNECTOR SAFETY WARNINGS

Instruction Sheet Simplex and Duplex. LightCrimp Plus LC. Fiber Optic Connector Kits Feb 2017 Rev E

OFS 400A FIBER OPTIC INTERCONNECT Instruction Sheet UNIT (FOIU) Comcode INSTALLATION

AMP NETCONNECT 19 NETWORK AND SERVER RACK SYSTEM.

Copyright 2004 Alcatel. All rights reserved.

Fiber Optic Above-Ground) Cross-Connect Enclosure (ACE) Model ACE-200DS Installation Guide)

BUDI-S-SP. Building distributor. Introduction. Seals. Kit content. Accessories. TC-957-IP Rev A, Feb Wrap around cable seals

FOSC-100 B/H FOSC-100 B2/H

<THESE INSTRUCTIONS MUST BE GIVEN TO THE END USER> B&W

Cabinet and Rack Installation

CNK200 Cable-Nook Interconnect Box

CommScope MULTILAYERED 289-TYPE INSTALLATION INSTRUCTIONS

Panduit PreConfigured ZDF48-RA Industrial Distribution Frame (IDF) Installation Instructions

Fiber Optic Splice Module

Cabinet and Rack Installation

DS1 Plug-In Digital Signal Cross-Connect (PIX-DSX-1) 19-Inch Shelf Kit Installation Instructions

OFS LSS1U-864/ Instruction Sheet Fiber Optic Comcode: Splice Shelf Installation

MODEL ELC-12/40-CVM-D BATTERY CHARGER

LC Cable Assemblies. Fiber Optic Products Catalog. Product Facts. LC Cable Assembly. Hybrid LC-SC Cable Assembly

Cabinet and Rack Installation

Z-Truck (Vertical Moving) Z-truck Flag. Y-Truck (Horizontal Moving) FIGURE 1: VIEW OF THE Z-TRUCK. Flexshaft Assembly

FIST-GMS2. FIST Generic Mixed Shelf MK2. Contents. 1 Introduction. 5 Termination of the pigtails. 2 General. 6 Splicing + fiber storage

UNPACK AND IDENTIFY THE FOLLOWING PARTS.

Mini-OTE 400. Mini-OTE 400. Content 1 General 1.1 General product information 1.2 Cable types 1.3 Symbols in this guide.

Air flow GUV-161. Box size is 8.25 high x 4.25 wide For service please call Germicidal UV-C Lamp. Furnace. 2.

Overview. Chassis Packaging

SW1 Swivel 1U Patch Panel

HP BladeSystem c7000 Carrier-Grade Options Installation Guide

Instruction Sheet 39mm Patch Panel MT RJ Jack Kits [ ], [ ], and [ ]

Ortronics. Mighty Mo. GX Cabinets. Designed to Perform, Configured to Fit

Agilent G1554A On-Column Capillary Inlet with EPC

Switch Installation. Preparing for Installation. Warnings CHAPTER

Chapter 3. Installing Equipment

icon User s manual Table of Contents section 6 icon module installation and removal

Installation Instructions For Motor Control Center (MCC) Units

SLIMRACK SLIDE-OUT MOTOR AND DRIVE BLOCK REPLACEMENT

Cabinet and Rack Installation

UNPACK AND IDENTIFY THE FOLLOWING PARTS.

SUT-450-I ASSEMBLY REQUIREMENTS

UNPACK AND IDENTIFY THE FOLLOWING PARTS.

AMP NETCONNECT 19 NETWORK AND SERVER RACK SYSTEM.

INSTALLATION & OWNER S MANUAL

WAVETRAX USER MANUAL

Installing the ONS M6 Shelf

! "! User Manual Myers Power Products CTEP/G Manual 6/2009

MODEL ELC-12/60-D BATTERY CHARGER

R O A D S M I T H TRIKE CONVERSIONS BY THE TRIKE SHOP

FiberGuide Fibre Management Systems

SW1 Swivel 3U Patch Panel

Instruction Manual. Maximum Operating Pressure 700 bar

Cisco Beacon Point Module

iphone 5s Upper Component Cable Replacement

COYOTE CLOSURE ADOBE SERIES FOR UNDERGROUND, AERIAL, AND BURIED SPLICES 6.0" x 22" 8.5" x 22" (152.4 mm x mm mm x 558.

Instructions for Use - Opt-X Ultra Enclosure Directives Enceintes Opt-X Ultra MC Instrucciones de Uso Caja Opt-X Ultra MR

Introduction. Pressed Shaft Flowmeter. Flowmeter Service Kits. Disassembly. Idler Shaft Removal

CNK200 Cable-Nook. Interconnect Box. User s Guide

TERMINATOR User Manual

USER MANUAL 6 Position Powered Rack for TD Series Modules TDR 01 AC

XChange Seat Service and Maintenance Guide

Desktop 5.5 Z Axis Retrofit

DeSoto NEMA 4X EMERGENCY LIGHTING UNIT. U.S. Versions: 6V- DM90X618 / DM90X654 12V- DM90X1254 / DM90X12100 INSTALLATION INSTRUCTIONS

SA1W: Water Detection Sensors SA1W-FN1 SA1W-FN2 SA1W-FP1 SA1W-FP2

<THESE INSTRUCTIONS MUST BE GIVEN TO THE END USER> B&W

Transcription:

Instruction Sheet 860445121 Issue 2, December 2012 SYSTIMAX Solutions SYSTIMAX 360 ipatch G2 High Density Sliding Fiber Shelf Instructions General The SYSTIMAX 360 ipatch G2 High Density Sliding Fiber Shelf is a SYSTIMAX approved product. This high density distribution shelf accommodates up to three modules that allow connection of multi-fiber trunk cables terminated with push-on (MPO) connectors. Each module provides 24 ipatch LC duplex fiber ports. Designed for use in an ipatch system, this shelf is two units high and can be mounted in a standard 19-inch (483mm) rack with a universal hole pattern. This shelf slides out for easy access. Note: The ipatch G2 High Density Sliding Fiber Shelf is compatible with Rack Manager Plus and Panel Manager units; it is not compatible with the older Rack Manager and Network Manager units. To use the ipatch G2 High Density Sliding Shelf in an existing ipatch system, the ipatch Managers must be running a software version dated April 2009 or later. The System Manager software, used to manage the system, must be Version 6.2 or later. We recommend that you upgrade the System Manager software to Version 6.2 or a later version before you install the shelf. System Manager will automatically upgrade the Network Manager and ipatch Manager software. Ordering information is listed below: Material ID Part No. Description 760093336 360-iP-HD-2U-IP-SD G2 2U high density sliding fiber shelf How to Contact Us To find out more about CommScope products, visit us on the web at http:/// For technical assistance: - Within the United States, contact your local account representative or technical support at 1-800-344-0223. Outside the United States, contact your local account representative or Authorized Business Partner. - Within the United States, report any missing/damaged parts or any other issues to CommScope Customer Claims at 1-866-539-2795. Outside the United States, contact your local account representative or Authorized Business Partner. This product is covered by one or more of the following U.S. patents or their foreign equivalents: 6,285,293 and 6,522,737. 2012 CommScope, Inc. All rights reserved For RoHS Inquiries: CommScope Inc. Corke Abbey, Bray Co. Dublin, Ireland Attn: Legal Department Page 1 of 10

860445121 Instruction Sheet Parts List Verify parts against the parts list below: Quantity Description 1 Preterminated sliding fiber tray with backplane board 1 Panel bus jumper; 2 Mounting brackets 3 Blank panels 1 Plastic shelf cover 1 Patch cord trough 4 Cable management rings 1 Hinged door for patch cord trough 4 #12-24 x 3/8 inch screws for mounting the shelf in a 19-inch or 23-inch (584mm) rack Separately Orderable Components Material ID Part No. Description 760093344 360-iP-HD-MOD-LC-LS HD 24LC LazrSPEED module 760093369 360-iP-HD-MOD-LC-TS HD 24LC TerraSPEED module 760093385 360-iP-HD-MOD-LC-OS HD 24LC OptiSPEED module 760093351 360-iP-HD-MOD-LC-LS-3 HD 24LC LazrSPEED module, 3 pack 760093377 360-iP-HD-MOD-LC-TS-3 HD 24LC TerraSPEED module, 3 pack 760093393 360-iP-HD-MOD-LC-OS-3 HD 24LC OptiSPEED module, 3 pack Various (see note) LazrSPEED 150 & 300 and TeraSPEED IPD 12-, 24-, 48-, 72-, 96-, and 144-fiber trunk cable, Plenum, MPO Note: Contact your local account representative for ordering information. Specifications Fiber Optic Interface Industry-standard LC Compatible Fiber Size Multimode with 50 µm core diameter, such as LazrSPEED Multimode with 62.5 µm core diameter, such as OptiSPEED Singlemode with 8.3 µm core diameter, such as TeraSPEED Environmental Data Temperature: -40º F to 158º F (-40º C to 70º C) (storage) Range 23º F to 122º F (-5º C to 50º C) (operational) Humidity: : 95% noncondensing Tools Required Flat blade screwdriver Page 2 of 10

860445121 Issue 2, December 2012 Important Safety Cautions To reduce the risk of fire, electric shock, and injury to persons, read, understand, and adhere to the following instructions as well as any warnings marked on the product. Remote risk of electric shock. Never install the product in wet locations or during lightning storms. Never touch uninsulated communication wires or terminals. Disconnected optical components may emit invisible optical radiation that can damage your eyes. Never look directly into an optical component that may have a laser coupled to it. Serious and permanent retinal damage is possible. If accidental exposure to laser radiation is suspected, consult a physician for an eye examination. Wear safety glasses to install the shelf. Although standard safety glasses provide no protection from potential optical radiation, they offer protection from accidental airborne hardware and cleaning solvents. Precautions ipatch high density fiber modules contain fiber optic cable and passive optical components. When removed from protective packing, they should be handled carefully and installed in appropriate racks for mechanical support and protection. ipatch high density fiber modules require virtually no maintenance to maintain their performance. They contain no user-serviceable components, and any damage to the anti-tamper label or removal of top cover or front adapter mounting panel will void the warranty. Fiber optic trunk cable and jumper performance is sensitive to bending, pulling, and crushing. Minimum bend radius must be maintained during installation per the manufacturer s specification. Appropriate pulling socks must be used during installation, and pulling forces shall not exceed manufacturer s recommendations. MPO terminated trunk cables may use ribbonized fiber optic cable, which has a preferential bend axis. Use caution to avoid kinking trunk cables. ipatch high density fiber modules are preterminated, with protective dust caps installed on all adapters. Prior to installation, clean the trunk cable and jumper connectors per the manufacturer s recommendations. All wiring that connects to this equipment must meet applicable local and national building codes and network wiring standards for communication cable. Care should be taken not to compromise the stability of the rack by installation of this equipment. ipatch high density fiber modules are for use in restricted access areas only. IMPORTANT SYSTIMAX 360 ipatch high density fiber modules use infrared sensing technology and should be installed where they are not exposed to direct sunlight or other infrared sources. Save these instructions. Page 3 of 10

860445121 Instruction Sheet Step 1 Routing the Panel Bus Jumper To route the panel bus jumper in preparation for installing the shelf: 1. Remove the tape securing the panel bus jumper to the cable support. 2. Route the panel bus jumper with protective corrugated tubing around the end of the sliding rail to the outside of the rail. 3. Snap the corrugated tubing protecting the panel bus jumper into the cable retainer on the outside of the rail as shown in Figure 1. Position the corrugated tubing so that about 1 inch (2.5cm) of the tubing extends past the end of the cable retainer. 4. Position the exposed ribbon cable of the panel bus jumper in the flat retainers on the outside of the sliding rail as shown in Figure 1. Corrugated tubing -1 in. (2.5cm) Cable retainer (See Step 3) Flat cable retainers (See Step 4) Panel bus jumper Step 2 Installing the Shelf Figure 1 Routing the Panel Bus Jumper When installing multiple shelves in a rack, install the lowest shelf first and work toward the top of the rack. To install the shelf in the rack: 1. Remove the plastic cover from the shelf. 2. Fully extend the sliding shelf to allow access to the mounting brackets. 3. Mount the shelf in the rack as shown using the four #12-24 x 3/8 inch mounting screws provided. 4. Connect the panel bus jumper to the nearest connector on the panel bus as shown in Figure 3. Note: The connector is keyed. The polarized tab on the jumper connector fits into the opening in the header connector on the panel bus. Important: Make sure that the jumper connector is fully seated in the header connector on the panel bus. Page 4 of 10

860445121 Issue 2, December 2012 Mounting screws (2) Mounting screws (2) Figure 2 Installing the Shelf in the Rack Panel bus Polarized tab Panel bus jumper Figure 3 Connecting the Panel Bus Jumper to the Panel Bus Page 5 of 10

860445121 Instruction Sheet Step 3 Installing the Trunk Cable Cable Sealing nut Cable fitting Lock nut Cable entry hole Stored cables Back of shelf Installation of cable fitting at cable entry hole To install and dress the trunk cable: Figure 4 Installing the Trunk Cable 1. Pull the trunk cable to the rack and determine the best way to route the cable to the shelf (from above or below). Note: When using a distribution frame, route and loosely secure the trunk cable to the cable retainers and cable retainer brackets. 2. Follow the manufacturer s instructions to remove the pulling sock from the trunk cable. 3. Remove the plastic plug from an appropriate cable entry hole in the back or side of the shelf. 4. Feed the MPO connectors and cables through the selected cable entry hole into the shelf. 5. Unscrew the liquid tight lock nut and feed it through the selected cable entry hole to the inside of the shelf. 6. Hold the liquid tight cable fitting so that the threaded portion is through the hole in the back of the shelf. Then tighten the locknut onto the cable fitting, securing the fitting to the back of the shelf (Figure 4). 7. Store the cables on top of the back plane board as shown. Note: If you are not going to install any high density fiber modules at this time, install the cover on the shelf and fully retract the shelf (Figure 8 on page 10). Page 6 of 10

860445121 Issue 2, December 2012 Step 4 Installing the High Density Fiber Modules Modules (ALPHA orientation) Quarter-turn latch (closed position) Blank panel Quarter-turn latch (open position) Figure 5 Installing the High Density Fiber Modules The high density fiber modules must be oriented for the proper polarity. Identical modules are used at each end of a trunk cable, but one module must be in the ALPHA orientation and the other module must be in the BETA orientation. To install the modules: 1. Fully extend the shelf. 2. If the plastic cover is installed on the shelf, remove it. 3. To remove the blank panel from the left position in the shelf, use a flat blade screw driver to turn the two quarter-turn latches to the open (horizontal) position (Figure 5). Then pull out the blank panel. 4. Rotate the module to the ALPHA or BETA orientation (Figure 6 on page 8). 5. With the module s quarter-turn latches in the open (horizontal) position, align the module with the opening in the shelf. Slide the module into the shelf so the connector on the back of the module mates with the edge connector on the back plane board. Important: Make sure no fiber cables are pinched beneath the module. 6. Use a flat blade screwdriver to turn both latches to the closed (vertical) position. 7. Repeat item 3 through item 6 to install additional modules in the center and right positions. Note: When installing only two modules in the shelf, use of the left and center positions is recommended. Important: Dust covers are installed in the ports to protect the fibers connected to the back of the ports. Do not remove the dust cover from a port until you connect a patch cord to that port. If you remove a patch cord later, replace the dust cover in the port. Page 7 of 10

860445121 Instruction Sheet ALPHA Orientation (front) BETA Orientation (front) ALPHA Orientation (back) BETA Orientation (back) Figure 6 Selecting the ALPHA or BETA Orientation for a Module Page 8 of 10

860445121 Issue 2, December 2012 Step 5 Connecting the Cable Connector Insertion Connector Removal Coupler Ribbed section Boot Figure 7 Inserting and Removing MPO Connectors 1. Remove the protective dust covers from the MPO connectors on the cable and the MPO couplers on the back of the shelf. 2. Grasp the connector by its boot, near the base of the connector (Figure 7). Insert the MPO connector into the coupler until it clicks into place as shown. Note: The MPO connection is keyed. The polarized tab on the connector fits into the opening on the coupler on the module. 3. Repeat this step to insert each of the trunk cable s MPO connectors into MPO couplers. Note: To unplug an MPO connector, grasp the ribbed sleeve section and pull the connector out of the coupler. Do not pull on the boot to unplug an MPO connector. Page 9 of 10

860445121 Instruction Sheet Step 6 Installing the Door and Cover Install the plastic cover and trough door (both provided) to shield the shelf from foreign particles. The cover, which is made of clear, flame-retardant plastic, slides on and off the shelf. The door for the patch cord trough is hinged and has touch-latches for closing and opening. To install the cover and door: 1. Slide the cover through the flanges on the shelf until the cover reaches the back wall of the shelf (Figure 8). 2. With the door at a 45 angle to the patch cord trough, position the door s hinge tabs in the corresponding slots on the trough as shown. Swing the door to the closed position, gently pressing the upper corners to latch the door. Note: To open the door, gently press both upper corners to release the latches. 3. Fully retract the shelf in the rack. Cover Installing the cover on the shelf Press both top corners to close Door Installing the door on the patch cord trough Figure 8 Installing the Cover and Door Page 10 of 10